Plan Review Details - Permit 08010504
Plan Review Stops For Permit 08010504
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-09-04 Cont ID  
Sent By mjacobs Date 2008-09-04 Time 13:25 Rev Time 0.00
Received By mjacobs Date 2008-09-04 Time 11:32 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-28 Cont ID  
Sent By mjacobs Date 2008-07-28 Time 14:50 Rev Time 0.00
Received By mjacobs Date 2008-07-28 Time 13:15 Sent To PC
Notes
2008-07-28 14:50:05 
  
  
  
  
  
  
  
  
  
  
  
  
 BUILDING PLAN REVIEW 3RD
 PERMIT: 08010504
 ADD: 3501 ELECTRONICS WAY
 CONT: UNITED GENERAL CONTRACTORS
 TEL: (561)422-0755
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD 7-28-08
 ACTION: DENIED
  
 1A)OK
 1B)OK
  
 2)DUE TO THE FACT THAT THE CERTIFICATE OF OCCUPANCY
 IS NOT ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE
 REVIEWED AND BY THE DESIGN TEAM OF THE BASE BUILDING.
 EACH SHEET OF THE PLANS SHALL CONTAIN AN APPROVED
 REVIEW STAMP BY THE DESIGNERS OF THE BASE BUILDING.
 NEW: THE PLANS CONTAIN SEVERAL DIFFERENT SIGNATURES FOR
 THE SAME PERSON GARY K. MUNKELT. FOR MORE INFORMATION
 REGUARDING THIS COMMENT SEE ELECTRICAL NOTES #1 #2 AND
 #3.
 3)OK
 4)OK
 5)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-03 Cont ID  
Sent By mjacobs Date 2008-05-03 Time 11:17 Rev Time 0.00
Received By mjacobs Date 2008-05-03 Time 09:44 Sent To  
Notes
2008-05-03 11:17:35BUILDING PLAN REVIEW 2ND
 PERMIT: 08010504
 ADD: 3501 ELECTRONICS WAY
 CONT: UNITED GENERAL CONTRACTORS
 TEL: (561)422-0755
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND5-3-08
 ACTION: DENIED
  
 1A)OK
 1B)OK
  
 2)DUE TO THE FACT THAT THE CERTIFICATE OF OCCUPANCY
 IS NOT ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE
 REVIEWED AND BY THE DESIGN TEAM OF THE BASE BUILDING.
 THE PLANS SHALL CONTAIN AN APPROVED REVIEW STAMP BY THE
 DESIGNERS OF THE BASE BUILDING.
  
 3)OK
 4)OK
 5)OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-25 Cont ID  
Sent By mjacobs Date 2008-02-25 Time 12:51 Rev Time 0.00
Received By mjacobs Date 2008-02-23 Time 14:04 Sent To  
Notes
2008-02-25 12:51:31BUILDING PLAN REVIEW
 PERMIT: 08010504
 ADD: 3501 ELECTRONICS WAY
 CONT: UNITED GENERAL CONTRACTORS
 TEL: (561)422-0755
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 2-25-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)DUE TO THE FACT THAT THE MASTER PERMIT IS NOT
 ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE REVIEWED
 AND BY THE DESIGN TEAM OF THE BASE BUILDING. THE PLANS
 SHALL CONTAIN AN APPROVED REVIEW STAMP BY THE DESIGNERS
 OF THE BASE BUILDING.
  
 3)PROVIDE THE LIFE SAFETY PLAN WHICH SHALL INCLUDE
 EXIT ACCESS / EXIT / EXIT DISCHARGE / HORIZONTAL EXITS
 / EXIT PASSAGEWAYS.
  
 4)FBC 1004.1.1 THE DESIGN OCCUPANT LOAD SHALL BE
 INDICATED ON THE DRAWINGS IN DETERMINING MEANS OF
 EGRESS REQUIREMENTS. THE NUMBER OF OCCUPANTS FOR WHOM
 MEANS OF EGRESS FACILITIES SHALL BE PROVIDED SHALL BE
 ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN
 ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3.
  
 5)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE
 DRAWN TO A MINIMUM 1/8 INCH SCALE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-10-02 Cont ID  
Sent By dpalmer Date 2008-10-02 Time 09:26 Rev Time 0.00
Received By dpalmer Date 2008-10-02 Time 09:26 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 5 Status F Date 2008-09-22 Cont ID  
Sent By dpalmer Date 2008-09-22 Time 16:29 Rev Time 0.00
Received By dpalmer Date 2008-09-22 Time 16:29 Sent To PC
Notes
2008-09-22 16:29:30 
 ** DENIED 5TH REVIEW **
  
  
 1) NOTE: PLEASE SEE THE PLANS AS SUBMITTED. THE SHEETS
 NOW CONTAIN A RUBBER STAMP FOR THE ENGINEER OF RECORD
 MR. PETER BONNES. THIS IS REQUIRED BY FS 471.025 AND
 FAC 61G15-23.002 TO CONTAIN AN ORIGINAL RAISED SEAL.
 THE PLANS DO CONTAIN AN ORIGINAL SIGNATURE AND DATE.
 ** ONE SET OF ELECTRICAL ARE RETAINED BY THIS OFFICE.
  
 2) NOTE: ON ALL PREVIOUS REVIEWS AS THE BASE BUILDING
 DOES NOT HAVE A CERTIFICATE OF OCCUPANCY THE BASE
 BUILDING ENGINEER RESPONSIBLE IS TO PLACE A *SHOP
 DRAWING* REVIEW STAMP ON PLANS AND SIGN EACH SHEET. IN
 SEVERAL PHONE CONVERSATIONS WITH MANY INDIVIDUALS IT
 HAS BEEN STATED: THE BASE BUILDING ELECTRICAL ENGINEER
 WILL ONLY STAMP THE SHOP DRAWING REVIEW STAMP ON EACH
 SHEET AND SIGN. HE IS NOT PERMITTED UNDER FLORIDA
 STATUTES TO PLACE HIS RAISED SEAL ON PLANS. THIS IS IN
 VIOLATION OF FS 471.025.
 ** ONE SET OF PLANS ARE RETAINED BY THIS OFFICE.
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-09-04 Cont ID  
Sent By dpalmer Date 2008-09-04 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2008-09-04 Time 08:29 Sent To  
Notes
2008-09-04 08:30:07 
  
  
  
  
 ** DENIED 4TH TIME REVIEW **
  
 ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS
 REVIEW WHICH ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE
 SIGNATURE OF THE ENGINEER OF RECORD. AS THIS OFFICE HAS
 SEEN MORE THAN ONE SIGNATURE AND THE ENGINEER HAS
 STATED THAT SOME PREVIOUS PLANS WERE SIGNED BY HIS
 SECRETARY THE PREVIOUS REVIEW STATED THAT A SIGNATURE
 VERIFICATION LETTER IS REQUIRED. AT THIS TIME THIS
 OFFICE DOES KNOW WHICH SIGNATURE IS CORRECT. PLEASE
 SUBMIT THE LETTER, PLEASE BE SURE THE LETTER IS
 ORIGINAL, SIGNED, DATED WITH RAISED SEAL AND CORRECTLY
 NOTARIZED.
 FS 471.025
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE
 BASE BUILDING DESIGNERS OF RECORD WERE REQUIRED TO
 *STAMP* PLANS AS SHOP DRAWING REVIEW AND SIGN EACH
 SHEET. THE ELECTRICAL SHEETS ARE NOT SIGNED BY THE
 *ENGINEER* OF RECORD FOR THIS PROJECT.
 FS 471.025
  
 ** BASE/SHELL BUILDING DESIGNERS ARE RESPONSIBLE FOR
 ALL WORK IN THIS BUILDING UNTIL C OF O OR C OF C.
  
 3) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS
 TABLE PROVIDED ONLY NOW FOR THE FIRST REVIEW IS STATING
 THE 2007 FLORIDA BUILDING CODE. PLEASE SEE FS 553.73 AS
 THE 2007 FBC HAS NOT BEEN ADOPTED BY THE STATE OF
 FLORIDA. THE CODE IN EFFECT ON ANY PROJECT IS BASED ON
 PERMIT APPLICATION DATE. THE 2007 FBC ADOPTION HAS BEEN
 PUSHED BACK UNTIL AT LEAST DECEMBER 31ST, 2008. AS
 PERMIT APPLICATION WAS MADE IN JANUARY OF 2008 THE CODE
 IN EFFECT AT TIME OF PERMIT APPLICATION IS 2004 FBC W/
 2007 REVISIONS. PLEASE CORRECT PLANS.
  
 4) NOTE: PLEASE EXPLAIN WHY THE NORMAL LEVELS OF
 PHOTO-METRICS ARE NOT COMPLETE FOR STAIRS ON ALL
 LEVELS. IN FACT SOME LEVELS ARE MISSING THE STAIRS
 COMPLETELY AND SOME ARE MISSING ONE STAIR BUT NOT THE
 OTHER.
 THE LEVELS OF LIGHTING ARE REQUIRED ON THE SLOPE, NOT
 ONLY WHAT WOULD BE A FLAT SURFACE.
 NFPA-7.8.1.3
  
 5) NOTE: PLEASE PROVIDE THE LIGHTING FIXTURE PRODUCT
 DATA SHEET WHICH PROVIDES THE BALLAST POWER FACTOR.
 13-415.2, 13-415.2.ABC.1.1, .1.2.
 NEC 110.3
 FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION.
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-07-17 Cont ID  
Sent By dpalmer Date 2008-07-17 Time 10:42 Rev Time 0.00
Received By dpalmer Date 2008-07-17 Time 10:42 Sent To  
Notes
2008-07-17 10:43:01** DENIEDRE-SUB **
  
 ** MOST OF THE SAME COMMENTS FROM PREVIOUS TWO REVIEWS
 ARE STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE:PLEASE SEE PLANS CONTAIN A SIGNATURE WHICH IS
 COMPLETELY DIFFERENT THAN PREVIOUS SUBMITTED PLANS BY
 THE SAME ENGINEER. PLANS ARE NOW BEING RETAINED FOR
 POSSIBLE REVIEW BY THE FLORIDA BOARD OF ENGINEERS.
 PLEASE SEE FS 471.025 AS THE ENGINEER MAY BE THE ONLY
 PERSON TO SIGN, DATE AND SEAL PLANS. FAC61G15-23.002.
 AT THIS TIME THIS OFFICE HAS MULTIPLE RECORDS OF THE
 SAME PERSON. NEED TO SUBMIT A SIGNATURE VERIFICATION
 LETTER ALONG WITH PHOTO ID OR THE ENGINEER OF RECORD
 MAY APPEAR IN PERSON WITH ID TO SIGN, DATE AND SEAL
 PLANS.
 IF A LETTER IS SUBMITTED, THIS MUST STATE THE LEGAL
 SIGNATURE, BE SIGNED, DATED, SEALED AND BE PROPERLY
 NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARY
 REQUIREMENTS.
  
 2) NOTE: PLEASE SEE PREVIOUS COMMENTS AS THE PLANS ARE
 REQUIRED TO GO BACK TO THE BASE BUILDING DESIGNER OF
 RECORD FOR *SHOP DRAWING REVIEW* AND STAMPING. THE
 ENGINEER OF RECORD IS NOT SIGNED OR STAMPED ON PLANS.
 THE BASE BUILDING DESIGNER STILL NEEDS TO STAMP PLANS.
 THIS PERSON IS RESPONSIBLE FOR THIS BUILDING UNTIL THAT
 SCOPE OF WORK IS COMPLETED.
 THIS IS REQUIRED ON EACH SHEET IN ALL SETS.
  
 3) NOTE:PLEASE KNOW THIS CONSTRUCTION WORK BEING
 APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE
 SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A
 SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF
 UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER
 MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF
 UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE
 SAME AREAS ETC.
 IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE
 BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT
 BE REQUIRED.
  
 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER
 THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE
 AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE
 BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE
 BUILDING MUST ALSO BE INCLUDED.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 AND .1.3.
 PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER
 RIDES.
  
 6) NOTE: PLEASE PLACE NOTES ON PLANS PER
 13-413.1.ABC.2.1 AND .2.2.
  
 7) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY
 REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING
 LEVELS IN THE LIFE SAFETY CODE.
 PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM
 LEVELS.
 PLEASE ALSO SEE FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION WITH PLANS.
  
 8) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET
 E-6 SHOWS A NEW PANEL WHICH IS NOW SHOWN AS HB HOWEVER
 THE INCREASED LOAD CALCULATIONS ON PANELS AND SERVICE
 WAS NOT SUBMITTED AS PREVIOUSLY REQUESTED.
 PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE
 WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16
 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 9) NOTE: PREVIOUS REVIEW GAVE NOTICE TO FLORIDA
 STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS
 FOR CODE COMPLIANCE.THIS IS THE THIRD REVIEW IN WHICH
 SEVERAL ITEMS ARE REPEATED FOR MINIMUM CODE COMPLIANCE
 ONCE AGAIN. THE FEE HAS NOW BEEN ASSESSED AND IS DUE
 BEFORE PLANS MAY BE RESUBMITTED.
 THE FEE OF $5,619.00 IS NOW DUE BEFORE PLANS MAY BE
 SUBMITTED BACK FOR THE FORTH REVIEW. TWO SETS OF
 ELECTRICAL PLANS HAVE NOW BEEN RETAINED BY THIS OFFICE
 FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD OF
 ENGINEERS.
 THE PREVIOUS REVIEW STATED IF THERE WERE QUESTIONS TO
 PLEASE CALL. TO DATE NO CONTACT HAS BEEN MADE TO THIS
 REVIEWER.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-04-24 Cont ID  
Sent By dpalmer Date 2008-04-24 Time 10:15 Rev Time 0.00
Received By dpalmer Date 2008-04-23 Time 17:25 Sent To  
Notes
2008-04-24 10:15:48** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME OF THE EXACT SAME NOTES ARE IN NEED
 OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES DUE TO
 THIS BEING THE SECOND REVIEW AND PROJECT WHICH IS NOT
 ISSUED FOR PERMIT AND NOT FINALE.
  
 1) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE ELECTRICAL
 PAGES ARE STILL MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER. THIS IS A FLORIDA STATUTE AS
 GIVEN ON PREVIOUS REVIEW WHICH REQUIRES THE FIRM TO BE
 LICENSED IN THE STATE OF FLORIDA AND THE FLORIDA
 ADMINISTRATIVE CODE REQUIRES THAT LICENSE NUMBER TO BE
 ON THE TITLE BLOCKS ON EACH SHEET FOR SAID FIRM. PLEASE
 SEE FS 471.023 AND FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE THE SEAL NOW ON SAID PLANS IS NOT
 CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE BE SURE
 ALL INFORMATION ON RAISED SEAL IS CLEAR AND VISIBLE. FS
 471.025
  
 3) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE
 BUILDING HAS NOT YET BEEN ISSUED THIS PERMIT MAY NOT
 YET BE ISSUED. PLEASE ALSO KNOW THE BASE BUILDING IS
 ALREADY UNDER A RESPONSIBLE ENGINEERING FIRM. ANY WORK
 WHICH IS BEING PERFORMED IN THE BUILDING BEFORE THE
 BASE BUILDING HAS OBTAINED A CERTIFICATE OF OCCUPANCY
 IS STILL UNDER THE RESPONSIBILITY OF THE BASE BUILDING
 DESIGNER(S).
 PLEASE BE SURE THE PLANS CONTAIN STAMPS BY THE BASE
 BUILDING RESPONSIBLE DESIGN TEAM SUCH AS A *SHOP
 DRAWING* REVIEW STAMP.
 IF THIS SCOPE OF WORK IS NOT GOING TO BE PERMITTED
 UNTIL AFTER C OF O OF THE BASE BUILDING THEN THIS WILL
 NOT BE REQUIRED. IF THERE ARE ANY QUESTIONS ON THIS
 PLEASE CALL.
  
 4) NOTE: PLEASE KNOW THIS CONSTRUCTION WORK BEING
 APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE
 SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A
 SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF
 UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER
 MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF
 UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE
 SAME AREAS ETC.
 IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE
 BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT
 BE REQUIRED.
  
 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2.
 PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER
 THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE
 AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE
 BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE
 BUILDING MUST ALSO BE INCLUDED.
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO
 REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO
 LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2,
 AND .1.3.
 PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER
 RIDES.
  
 7) NOTE: PLEASE PLACE NOTES ON PLANS PER
 13-413.1.ABC.2.1 AND .2.2.
  
 8) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY
 REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING
 LEVELS IN THE LIFE SAFETY CODE.
 PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM
 LEVELS.
 PLEASE ALSO SEE FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION WITH PLANS.
  
 9) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET
 E-6 SHOWS A NEW PANEL LP, HOWEVER THISPANEL IS NOT ON
 THE BASE BUILDING PLANS. IF THIS IS GOING TO BE A NEW
 PANEL THEN PLEASE SUBMIT LOAD CALCULATIONS, RISER
 DIAGRAM ON HOW AND WHERE THIS PANEL IS BEING FED ETC.
 PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE
 WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16
 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 10) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH
 RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE
 KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. PLEASE
 ALSO KNOW THIS OFFICE IS NOW RETAINING PLANS DUE TO
 REPEAT COMMENTS.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-04-23 17:25:402008-04-23 17:25:40
  
 PLAN REVIEW WILL BE IN A FAILED STATUS, NOTES TO
 FOLLOW.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-31 Cont ID  
Sent By dpalmer Date 2008-01-31 Time 13:01 Rev Time 0.00
Received By dpalmer Date 2008-01-30 Time 20:05 Sent To  
Notes
2008-01-31 13:01:46** DENIED REVIEW **
  
 1) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING
 FIRM IS MISSING THE REQUIRED CERTIFICATE OF
 AUTHORIZATION NUMBER.
 PLEASE SEE FAC 61G15-23.002, FS 471.023
  
 2) NOTE: PLEASE BE SURE WHEN SEALING PLANS THE ENTIRE
 SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID
 SEAL. FS 471.025
  
 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE
 CALCULATIONS PER FBC CHAPTER 13, 13-415.2.
 PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH A
 FIXTURE LEGEND TO BE SUBMITTED.
  
 4) NOTE: PLEASE SUBMIT TIMES ON SCHEDULING OF LIGHTING
 CONTROL PANEL AND MAXIMUM TIMES OF OVER RIDE DEVICES
 PER 13-415.1.ABC.1.1, .1.2.
  
 5) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER
 13-413.1.ABC.2.1, AND .2.2.
  
 6) NOTE: PLEASE PROVIDE VOLTAGE DROP INFORMATION PER
 13-413.1ABC.1
  
 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR MINIMUM
 LIGHTING LEVELS UNDER NORMAL CONDITIONS AS WELL AS
 MINIMUM LEVELS UNDER EMERGENCY CONDITIONS PER LS 7.8
 AND 7.9. PLEASE SEE SPECIFIC AREAS SUCH AS STAIRS ARE
 UNDER 7.8.1.3 AND 7.9.2.2.
 FAC 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 8) NOTE: PLEASE SEE SHEET E-6.0 SHOWS A NEW PANEL LP ,
 YET DOES NOT SHOW ANY INFORMATION WHERE THIS PANEL IS
 BEING FED FROM, LOAD CALCULATIONS ON EXISTING EQUIPMENT
 WHICH FEEDS THIS PANEL ETC.
 FEEDERS, GROUNDING, LOADS, OVER CURRENT PROTECTION
 ETC.
 PLEASE SEE 210, 220, 230, 215.5, 240.4, 310.16 ETC FBC
 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR ADDITIONAL
 INFORMATION.
  
 ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET
 SUBMITTED FOR REVIEW A COMPLETE REVIEW CAN NOT BE DONE
 AT THIS TIME.
 PLEASE ALSO KNOW THERE MAY VERY WELL BE NEW COMMENTS ON
 THE FOLLOWING REVIEW BASED ON INFORMATION WHICH WILL BE
 IN REVIEW FOR THE FIRST TIME.
  
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-01-30 20:05:44IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-08-29 Cont ID  
Sent By mwennerg Date 2008-08-29 Time 15:33 Rev Time 0.00
Received By mwennerg Date 2008-08-29 Time 15:33 Sent To  
Notes
2008-08-29 15:33:54STAMPED LS AND FP SHEETS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 14:11 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 14:11 Sent To  
Notes
2008-07-21 14:26:54***DENIED***
  
  
 1) PLANS APPEAR CODE COMPLIANT HOWEVER PLEASE SEE
 ELECTRICAL REVIEW COMMENTS REGARDING RESPONSIBILTY FOR
 SIGNING, DATING AND SEALING OF PLANS. WHEN PLANS ARE
 RE-SUBMITTED WITH CORRECTIONS, PLANS WILL BE STAMPED AT
 THAT TIME.
  
 2) PLEASE LIMIT SUBMITTAL OF FIRE PROTECTION SHEETS TO
 NOT MORE THAN THREE (3) COPIES.
  
 3) AS PREVIOUSLY STATED, SEPARATE SHOP DRAWINGS AND
 PERMIT REQUIRED FOR FIRE SPRINKLER REMODEL. SUBMITTAL
 OF CALCULATION SHEETS AND MANUFACTURER SPECIFICATION
 SHEETS WILL BE REQUIRED AT THE TIME OF FIRE SPRINKLER
 PERMIT APPLICATION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By mwennerg Date 2008-05-14 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2008-05-14 Time 10:01 Sent To  
Notes
2008-05-14 10:07:56***DENIED***
  
 1) MOST COMMENTS HAVE BEEN ADDRESSED AND PLANS APPEAR
 CODE COMPLIANT. RESPONSE REFERENCES LIFE SAFETY. EXIT
 AND EMERGENCY LIGHTS ARE ILLUSTRATED ON ELECTRICAL
 SHEETS. LIFE SAFETY SHEETS WOULD INDICATE MEANS OF
 EGRESS OCCUPANT LOADS AND MAXIMUN TRAVEL DISTANCE
 INFORMATION.
  
 2) PLEASE SEE OTHER REVIEW COMMENTS REGARDING
 INFORMATION THAT IS REQUIRED FOR DRAWINGS.
  
  
 PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS TO
 OTHER REVIEW COMMENTS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 10:38 Rev Time 0.00
Received By mwennerg Date 2008-02-27 Time 10:38 Sent To  
Notes
2008-02-27 11:07:01***DENIED***
  
 1) THE FLOW TEST DATE OF 12/5/06 IS NOT COMPLIANT WITH
 THE ONE YEAR DATA REQUIREMENT. IF FLOW DATE HAS BEEN
 UPDATED, PLEASE INCLUDE INFORMATION.
  
 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR
 INSTALLATION OR REMODEL OF FIRE SPRINKLER SYSTEM.
  
 3) PLANS ILLUSTRATE A NEW CHAIN LINK FENCE AND GATE.
 FIRE PROTECTION EQUIPMENT INCLUDING THE FIRE DEPARTMENT
 CONNECTION SHALL NOT BE OBSTRUCTED AND MAINTAIN PROPER
 CLEARANCES. PLEASE SHOW HOW FDC WILL BE ACCESSED BY
 FIRE APPARATUS.
  
 4) SHEET FP-1 SHOWS BOTH FDC BREAK OFF CAPS AND KNOX
 LOCKING CAPS. NEW INSTALLATIONS ARE REQUIRED TO BE
 SECURED WITH KNOX LOCKING CAPS. AN APPLICATION CAN BE
 OBTAINED FROM BUREAU OF FIRE PREVENTION. (561)
 804-4724
  
 5) PLANS SHOW PHASING OF PROJECT ON ELECTRICAL SHEETS.
 PLEASE INDICATE ALL REQUIRED MEANS OF EGRESS.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 7) NEW FIRE HYDRANTS TO BE FULLY OPERATIONAL PRIOR TO,
 DURING AND AFTER CONSTRUCTION.
  
 8) APPLICATION INDICATES IN-RACK FIRE SPRINKLER SYSTEM.
 PLANS SEEM TO SHOW A NEW FIRE SPRINKLER SYSTEM FOR
 BUILDING. PLEASE CLARIFY AND AS A NOTE, MONITORING OF
 NEW FIRE SPRINKLER SYSTEMS SHALL BE UL CERTIFIED FOR
 CENTRAL STATION SERVICE PRIOR TO FINAL INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-29 Cont ID  
Sent By adarroug Date 2008-09-29 Time 11:21 Rev Time 0.00
Received By adarroug Date 2008-09-29 Time 11:21 Sent To E
Notes
2008-09-29 11:22:10TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-09-17 Cont ID  
Sent By adarroug Date 2008-09-17 Time 12:05 Rev Time 0.00
Received By adarroug Date 2008-09-17 Time 12:05 Sent To E
Notes
2008-09-17 12:06:13TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-21 Cont ID  
Sent By adarroug Date 2008-08-21 Time 14:57 Rev Time 0.00
Received By adarroug Date 2008-08-21 Time 14:57 Sent To  
Notes
2008-08-21 14:58:08TO "COMM" BD#60

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-20 Cont ID  
Sent By adarroug Date 2008-06-20 Time 08:48 Rev Time 0.00
Received By adarroug Date 2008-06-20 Time 08:48 Sent To  
Notes
2008-06-20 16:55:14TO "COMM" BD#56
2008-06-20 08:49:20WAITING FOR "COMM" BD

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 16:39 Sent To  
Notes
2008-06-03 16:41:35TO "COMM" BD#41/PLANS ON RACK/LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-16 Cont ID  
Sent By adarroug Date 2008-04-16 Time 10:51 Rev Time 0.00
Received By adarroug Date 2008-04-16 Time 10:51 Sent To  
Notes
2008-04-16 10:55:03TO "COMM" BD#39

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-27 Cont ID  
Sent By mwennerg Date 2008-02-27 Time 11:11 Rev Time 0.00
Received By mwennerg Date 2008-01-23 Time 09:42 Sent To  
Notes
2008-01-23 09:42:27TO "COMM" BD#60


Account Summary | Usage Policy | Privacy Policy