| Plan Review Stops For Permit 08010504 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-09-04 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-09-04 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-09-04 |
Time |
11:32 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-07-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-07-28 |
Time |
14:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-07-28 |
Time |
13:15 |
Sent To |
PC |
|
| Notes |
| 2008-07-28 14:50:05 | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | BUILDING PLAN REVIEW 3RD | | | PERMIT: 08010504 | | | ADD: 3501 ELECTRONICS WAY | | | CONT: UNITED GENERAL CONTRACTORS | | | TEL: (561)422-0755 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD 7-28-08 | | | ACTION: DENIED | | | | | | 1A)OK | | | 1B)OK | | | | | | 2)DUE TO THE FACT THAT THE CERTIFICATE OF OCCUPANCY | | | IS NOT ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE | | | REVIEWED AND BY THE DESIGN TEAM OF THE BASE BUILDING. | | | EACH SHEET OF THE PLANS SHALL CONTAIN AN APPROVED | | | REVIEW STAMP BY THE DESIGNERS OF THE BASE BUILDING. | | | NEW: THE PLANS CONTAIN SEVERAL DIFFERENT SIGNATURES FOR | | | THE SAME PERSON GARY K. MUNKELT. FOR MORE INFORMATION | | | REGUARDING THIS COMMENT SEE ELECTRICAL NOTES #1 #2 AND | | | #3. | | | 3)OK | | | 4)OK | | | 5)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-03 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-03 |
Time |
11:17 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-03 |
Time |
09:44 |
Sent To |
|
|
| Notes |
| 2008-05-03 11:17:35 | BUILDING PLAN REVIEW 2ND | | | PERMIT: 08010504 | | | ADD: 3501 ELECTRONICS WAY | | | CONT: UNITED GENERAL CONTRACTORS | | | TEL: (561)422-0755 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND5-3-08 | | | ACTION: DENIED | | | | | | 1A)OK | | | 1B)OK | | | | | | 2)DUE TO THE FACT THAT THE CERTIFICATE OF OCCUPANCY | | | IS NOT ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE | | | REVIEWED AND BY THE DESIGN TEAM OF THE BASE BUILDING. | | | THE PLANS SHALL CONTAIN AN APPROVED REVIEW STAMP BY THE | | | DESIGNERS OF THE BASE BUILDING. | | | | | | 3)OK | | | 4)OK | | | 5)OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-25 |
Time |
12:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-23 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2008-02-25 12:51:31 | BUILDING PLAN REVIEW | | | PERMIT: 08010504 | | | ADD: 3501 ELECTRONICS WAY | | | CONT: UNITED GENERAL CONTRACTORS | | | TEL: (561)422-0755 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST 2-25-08 | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 2)DUE TO THE FACT THAT THE MASTER PERMIT IS NOT | | | ISSUED AT THIS TIME, THESE DRAWINGS SHALL BE REVIEWED | | | AND BY THE DESIGN TEAM OF THE BASE BUILDING. THE PLANS | | | SHALL CONTAIN AN APPROVED REVIEW STAMP BY THE DESIGNERS | | | OF THE BASE BUILDING. | | | | | | 3)PROVIDE THE LIFE SAFETY PLAN WHICH SHALL INCLUDE | | | EXIT ACCESS / EXIT / EXIT DISCHARGE / HORIZONTAL EXITS | | | / EXIT PASSAGEWAYS. | | | | | | 4)FBC 1004.1.1 THE DESIGN OCCUPANT LOAD SHALL BE | | | INDICATED ON THE DRAWINGS IN DETERMINING MEANS OF | | | EGRESS REQUIREMENTS. THE NUMBER OF OCCUPANTS FOR WHOM | | | MEANS OF EGRESS FACILITIES SHALL BE PROVIDED SHALL BE | | | ESTABLISHED BY THE LARGEST NUMBER COMPUTED IN | | | ACCORDANCE WITH SECTIONS 1004.1.1 THROUGH 1004.1.3. | | | | | | 5)WPB AMENDMENTS 106.1.3 BUILDING PLANS SHALL BE | | | DRAWN TO A MINIMUM 1/8 INCH SCALE. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-10-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-10-02 |
Time |
09:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-10-02 |
Time |
09:26 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
F |
Date |
2008-09-22 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-22 |
Time |
16:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-22 |
Time |
16:29 |
Sent To |
PC |
|
| Notes |
| 2008-09-22 16:29:30 | | | | ** DENIED 5TH REVIEW ** | | | | | | | | | 1) NOTE: PLEASE SEE THE PLANS AS SUBMITTED. THE SHEETS | | | NOW CONTAIN A RUBBER STAMP FOR THE ENGINEER OF RECORD | | | MR. PETER BONNES. THIS IS REQUIRED BY FS 471.025 AND | | | FAC 61G15-23.002 TO CONTAIN AN ORIGINAL RAISED SEAL. | | | THE PLANS DO CONTAIN AN ORIGINAL SIGNATURE AND DATE. | | | ** ONE SET OF ELECTRICAL ARE RETAINED BY THIS OFFICE. | | | | | | 2) NOTE: ON ALL PREVIOUS REVIEWS AS THE BASE BUILDING | | | DOES NOT HAVE A CERTIFICATE OF OCCUPANCY THE BASE | | | BUILDING ENGINEER RESPONSIBLE IS TO PLACE A *SHOP | | | DRAWING* REVIEW STAMP ON PLANS AND SIGN EACH SHEET. IN | | | SEVERAL PHONE CONVERSATIONS WITH MANY INDIVIDUALS IT | | | HAS BEEN STATED: THE BASE BUILDING ELECTRICAL ENGINEER | | | WILL ONLY STAMP THE SHOP DRAWING REVIEW STAMP ON EACH | | | SHEET AND SIGN. HE IS NOT PERMITTED UNDER FLORIDA | | | STATUTES TO PLACE HIS RAISED SEAL ON PLANS. THIS IS IN | | | VIOLATION OF FS 471.025. | | | ** ONE SET OF PLANS ARE RETAINED BY THIS OFFICE. | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-09-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-04 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-04 |
Time |
08:29 |
Sent To |
|
|
| Notes |
| 2008-09-04 08:30:07 | | | | | | | | | | | | | | | | ** DENIED 4TH TIME REVIEW ** | | | | | | ** PLEASE SEE THERE ARE COMMENTS FROM THE PREVIOUS | | | REVIEW WHICH ARE STILL IN NEED OF ADDRESSING. | | | | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WITH RESPECT TO THE | | | SIGNATURE OF THE ENGINEER OF RECORD. AS THIS OFFICE HAS | | | SEEN MORE THAN ONE SIGNATURE AND THE ENGINEER HAS | | | STATED THAT SOME PREVIOUS PLANS WERE SIGNED BY HIS | | | SECRETARY THE PREVIOUS REVIEW STATED THAT A SIGNATURE | | | VERIFICATION LETTER IS REQUIRED. AT THIS TIME THIS | | | OFFICE DOES KNOW WHICH SIGNATURE IS CORRECT. PLEASE | | | SUBMIT THE LETTER, PLEASE BE SURE THE LETTER IS | | | ORIGINAL, SIGNED, DATED WITH RAISED SEAL AND CORRECTLY | | | NOTARIZED. | | | FS 471.025 | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH STATED THE | | | BASE BUILDING DESIGNERS OF RECORD WERE REQUIRED TO | | | *STAMP* PLANS AS SHOP DRAWING REVIEW AND SIGN EACH | | | SHEET. THE ELECTRICAL SHEETS ARE NOT SIGNED BY THE | | | *ENGINEER* OF RECORD FOR THIS PROJECT. | | | FS 471.025 | | | | | | ** BASE/SHELL BUILDING DESIGNERS ARE RESPONSIBLE FOR | | | ALL WORK IN THIS BUILDING UNTIL C OF O OR C OF C. | | | | | | 3) NOTE: PLEASE SEE LIGHTING PERFORMANCE CALCULATIONS | | | TABLE PROVIDED ONLY NOW FOR THE FIRST REVIEW IS STATING | | | THE 2007 FLORIDA BUILDING CODE. PLEASE SEE FS 553.73 AS | | | THE 2007 FBC HAS NOT BEEN ADOPTED BY THE STATE OF | | | FLORIDA. THE CODE IN EFFECT ON ANY PROJECT IS BASED ON | | | PERMIT APPLICATION DATE. THE 2007 FBC ADOPTION HAS BEEN | | | PUSHED BACK UNTIL AT LEAST DECEMBER 31ST, 2008. AS | | | PERMIT APPLICATION WAS MADE IN JANUARY OF 2008 THE CODE | | | IN EFFECT AT TIME OF PERMIT APPLICATION IS 2004 FBC W/ | | | 2007 REVISIONS. PLEASE CORRECT PLANS. | | | | | | 4) NOTE: PLEASE EXPLAIN WHY THE NORMAL LEVELS OF | | | PHOTO-METRICS ARE NOT COMPLETE FOR STAIRS ON ALL | | | LEVELS. IN FACT SOME LEVELS ARE MISSING THE STAIRS | | | COMPLETELY AND SOME ARE MISSING ONE STAIR BUT NOT THE | | | OTHER. | | | THE LEVELS OF LIGHTING ARE REQUIRED ON THE SLOPE, NOT | | | ONLY WHAT WOULD BE A FLAT SURFACE. | | | NFPA-7.8.1.3 | | | | | | 5) NOTE: PLEASE PROVIDE THE LIGHTING FIXTURE PRODUCT | | | DATA SHEET WHICH PROVIDES THE BALLAST POWER FACTOR. | | | 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | NEC 110.3 | | | FBC 106.1.1, 106.1.2 FOR ADDITIONAL INFORMATION. | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-17 |
Time |
10:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-17 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2008-07-17 10:43:01 | ** DENIEDRE-SUB ** | | | | | | ** MOST OF THE SAME COMMENTS FROM PREVIOUS TWO REVIEWS | | | ARE STILL IN NEED OF ADDRESSING. | | | | | | | | | 1) NOTE:PLEASE SEE PLANS CONTAIN A SIGNATURE WHICH IS | | | COMPLETELY DIFFERENT THAN PREVIOUS SUBMITTED PLANS BY | | | THE SAME ENGINEER. PLANS ARE NOW BEING RETAINED FOR | | | POSSIBLE REVIEW BY THE FLORIDA BOARD OF ENGINEERS. | | | PLEASE SEE FS 471.025 AS THE ENGINEER MAY BE THE ONLY | | | PERSON TO SIGN, DATE AND SEAL PLANS. FAC61G15-23.002. | | | AT THIS TIME THIS OFFICE HAS MULTIPLE RECORDS OF THE | | | SAME PERSON. NEED TO SUBMIT A SIGNATURE VERIFICATION | | | LETTER ALONG WITH PHOTO ID OR THE ENGINEER OF RECORD | | | MAY APPEAR IN PERSON WITH ID TO SIGN, DATE AND SEAL | | | PLANS. | | | IF A LETTER IS SUBMITTED, THIS MUST STATE THE LEGAL | | | SIGNATURE, BE SIGNED, DATED, SEALED AND BE PROPERLY | | | NOTARIZED. PLEASE SEE FS 117.05 FOR NOTARY | | | REQUIREMENTS. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS COMMENTS AS THE PLANS ARE | | | REQUIRED TO GO BACK TO THE BASE BUILDING DESIGNER OF | | | RECORD FOR *SHOP DRAWING REVIEW* AND STAMPING. THE | | | ENGINEER OF RECORD IS NOT SIGNED OR STAMPED ON PLANS. | | | THE BASE BUILDING DESIGNER STILL NEEDS TO STAMP PLANS. | | | THIS PERSON IS RESPONSIBLE FOR THIS BUILDING UNTIL THAT | | | SCOPE OF WORK IS COMPLETED. | | | THIS IS REQUIRED ON EACH SHEET IN ALL SETS. | | | | | | 3) NOTE:PLEASE KNOW THIS CONSTRUCTION WORK BEING | | | APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE | | | SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A | | | SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF | | | UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER | | | MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF | | | UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE | | | SAME AREAS ETC. | | | IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE | | | BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT | | | BE REQUIRED. | | | | | | 4) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER | | | THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE | | | AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE | | | BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE | | | BUILDING MUST ALSO BE INCLUDED. | | | | | | 5) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO | | | REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO | | | LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2, | | | AND .1.3. | | | PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER | | | RIDES. | | | | | | 6) NOTE: PLEASE PLACE NOTES ON PLANS PER | | | 13-413.1.ABC.2.1 AND .2.2. | | | | | | 7) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY | | | REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING | | | LEVELS IN THE LIFE SAFETY CODE. | | | PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM | | | LEVELS. | | | PLEASE ALSO SEE FAC 61G15-33.004 | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION WITH PLANS. | | | | | | 8) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET | | | E-6 SHOWS A NEW PANEL WHICH IS NOW SHOWN AS HB HOWEVER | | | THE INCREASED LOAD CALCULATIONS ON PANELS AND SERVICE | | | WAS NOT SUBMITTED AS PREVIOUSLY REQUESTED. | | | PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE | | | WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16 | | | ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 9) NOTE: PREVIOUS REVIEW GAVE NOTICE TO FLORIDA | | | STATUTES 553.80(2)(B) WITH RESPECT TO REPEAT COMMENTS | | | FOR CODE COMPLIANCE.THIS IS THE THIRD REVIEW IN WHICH | | | SEVERAL ITEMS ARE REPEATED FOR MINIMUM CODE COMPLIANCE | | | ONCE AGAIN. THE FEE HAS NOW BEEN ASSESSED AND IS DUE | | | BEFORE PLANS MAY BE RESUBMITTED. | | | THE FEE OF $5,619.00 IS NOW DUE BEFORE PLANS MAY BE | | | SUBMITTED BACK FOR THE FORTH REVIEW. TWO SETS OF | | | ELECTRICAL PLANS HAVE NOW BEEN RETAINED BY THIS OFFICE | | | FOR POSSIBLE SUBMISSION TO THE FLORIDA BOARD OF | | | ENGINEERS. | | | THE PREVIOUS REVIEW STATED IF THERE WERE QUESTIONS TO | | | PLEASE CALL. TO DATE NO CONTACT HAS BEEN MADE TO THIS | | | REVIEWER. | | | | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-04-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-04-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-04-23 |
Time |
17:25 |
Sent To |
|
|
| Notes |
| 2008-04-24 10:15:48 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME OF THE EXACT SAME NOTES ARE IN NEED | | | OF ADDRESSING. PLEASE ALSO SEE SOME NEW NOTES DUE TO | | | THIS BEING THE SECOND REVIEW AND PROJECT WHICH IS NOT | | | ISSUED FOR PERMIT AND NOT FINALE. | | | | | | 1) NOTE: PLEASE SEE THE TITLE BLOCKS FOR THE ELECTRICAL | | | PAGES ARE STILL MISSING THE REQUIRED CERTIFICATE OF | | | AUTHORIZATION NUMBER. THIS IS A FLORIDA STATUTE AS | | | GIVEN ON PREVIOUS REVIEW WHICH REQUIRES THE FIRM TO BE | | | LICENSED IN THE STATE OF FLORIDA AND THE FLORIDA | | | ADMINISTRATIVE CODE REQUIRES THAT LICENSE NUMBER TO BE | | | ON THE TITLE BLOCKS ON EACH SHEET FOR SAID FIRM. PLEASE | | | SEE FS 471.023 AND FAC 61G15-23.002 | | | | | | 2) NOTE: PLEASE SEE THE SEAL NOW ON SAID PLANS IS NOT | | | CLEAR AND VISIBLE WITH ALL INFORMATION. PLEASE BE SURE | | | ALL INFORMATION ON RAISED SEAL IS CLEAR AND VISIBLE. FS | | | 471.025 | | | | | | 3) NOTE: PLEASE KNOW AS THE PERMIT FOR THE BASE | | | BUILDING HAS NOT YET BEEN ISSUED THIS PERMIT MAY NOT | | | YET BE ISSUED. PLEASE ALSO KNOW THE BASE BUILDING IS | | | ALREADY UNDER A RESPONSIBLE ENGINEERING FIRM. ANY WORK | | | WHICH IS BEING PERFORMED IN THE BUILDING BEFORE THE | | | BASE BUILDING HAS OBTAINED A CERTIFICATE OF OCCUPANCY | | | IS STILL UNDER THE RESPONSIBILITY OF THE BASE BUILDING | | | DESIGNER(S). | | | PLEASE BE SURE THE PLANS CONTAIN STAMPS BY THE BASE | | | BUILDING RESPONSIBLE DESIGN TEAM SUCH AS A *SHOP | | | DRAWING* REVIEW STAMP. | | | IF THIS SCOPE OF WORK IS NOT GOING TO BE PERMITTED | | | UNTIL AFTER C OF O OF THE BASE BUILDING THEN THIS WILL | | | NOT BE REQUIRED. IF THERE ARE ANY QUESTIONS ON THIS | | | PLEASE CALL. | | | | | | 4) NOTE: PLEASE KNOW THIS CONSTRUCTION WORK BEING | | | APPLIED FOR IN THE BASE BUILDING IS BEING DONE AT THE | | | SAME TIME THE BASE BUILDING IS BEING CONSTRUCTED BY A | | | SEPARATE CONTRACTOR. THERE MUST BE A LETTER OF | | | UNDERSTANDING BETWEEN THE TWO CONTRACTORS. THIS LETTER | | | MUST BE ORIGINAL AND NOTARIZED WITH THE WORDING OF | | | UNDERSTANDING FOR INSPECTIONS, WORK BEING DONE IN THE | | | SAME AREAS ETC. | | | IF THIS SCOPE OF WORK IS NOT ISSUED UNTIL AFTER THE | | | BASE BUILDING OBTAINS C OF O/ FINAL THEN THIS WILL NOT | | | BE REQUIRED. | | | | | | 5) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS PER FBC 13-415.2, 13-415.2.ABC.1.1, .1.2. | | | PLEASE SEE THE PREVIOUS REVIEW REQUESTED THIS HOWEVER | | | THE PLANS DO NOT SHOW ANY OF THE INFORMATION. PLEASE BE | | | AWARE OF LIGHTING WHICH IS ALREADY IN PLACE UNDER THE | | | BASE BUILDING. THIS LIGHTING WHICH IS PART OF THE BASE | | | BUILDING MUST ALSO BE INCLUDED. | | | | | | 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH ALSO | | | REQUESTED COMPLIANCE FOR FBC CHAPTER 13 WITH RESPECT TO | | | LIGHTING CONTROLS REQUIRED PER 13-415.1.ABC.1.1, .1.2, | | | AND .1.3. | | | PLEASE SUBMIT SCHEDULING AND ALL MAXIMUM TIMES ON OVER | | | RIDES. | | | | | | 7) NOTE: PLEASE PLACE NOTES ON PLANS PER | | | 13-413.1.ABC.2.1 AND .2.2. | | | | | | 8) NOTE: PLEASE SUBMIT THE PHOTO-METRICS AS PREVIOUSLY | | | REQUESTED IN ORDER TO COMPLY WITH THE MINIMUM LIGHTING | | | LEVELS IN THE LIFE SAFETY CODE. | | | PLEASE SEE 7.8, 7.9 AND 7.8.1.3, 7.9.2.2 FOR MINIMUM | | | LEVELS. | | | PLEASE ALSO SEE FAC 61G15-33.004 | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND | | | COORDINATION WITH PLANS. | | | | | | 9) NOTE: PLEASE SEE AS STATED ON PREVIOUS REVIEW SHEET | | | E-6 SHOWS A NEW PANEL LP, HOWEVER THISPANEL IS NOT ON | | | THE BASE BUILDING PLANS. IF THIS IS GOING TO BE A NEW | | | PANEL THEN PLEASE SUBMIT LOAD CALCULATIONS, RISER | | | DIAGRAM ON HOW AND WHERE THIS PANEL IS BEING FED ETC. | | | PLEASEBE SURE ALL ITEMS TO BE SUBMITTED COORDINATE | | | WITH THE 2005 NFPA-70 210,220,230,215.5,240.4,310.16 | | | ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 10) NOTE: PLEASE SEE FLORIDA STATUTES 553.80(2)(B) WITH | | | RESPECT TO REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE | | | KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. PLEASE | | | ALSO KNOW THIS OFFICE IS NOW RETAINING PLANS DUE TO | | | REPEAT COMMENTS. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2008-04-23 17:25:40 | 2008-04-23 17:25:40 | | | | | | PLAN REVIEW WILL BE IN A FAILED STATUS, NOTES TO | | | FOLLOW. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-31 |
Time |
13:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-30 |
Time |
20:05 |
Sent To |
|
|
| Notes |
| 2008-01-31 13:01:46 | ** DENIED REVIEW ** | | | | | | 1) NOTE: PLEASE SEE THE TITLE BLOCK FOR THE ENGINEERING | | | FIRM IS MISSING THE REQUIRED CERTIFICATE OF | | | AUTHORIZATION NUMBER. | | | PLEASE SEE FAC 61G15-23.002, FS 471.023 | | | | | | 2) NOTE: PLEASE BE SURE WHEN SEALING PLANS THE ENTIRE | | | SEAL IS CLEAR AND VISIBLE WITH ALL INFORMATION ON SAID | | | SEAL. FS 471.025 | | | | | | 3) NOTE: PLEASE SUBMIT LIGHTING PERFORMANCE | | | CALCULATIONS PER FBC CHAPTER 13, 13-415.2. | | | PLEASE BE SURE ALL FIXTURES ON PLANS COORDINATE WITH A | | | FIXTURE LEGEND TO BE SUBMITTED. | | | | | | 4) NOTE: PLEASE SUBMIT TIMES ON SCHEDULING OF LIGHTING | | | CONTROL PANEL AND MAXIMUM TIMES OF OVER RIDE DEVICES | | | PER 13-415.1.ABC.1.1, .1.2. | | | | | | 5) NOTE: PLEASE PLACE NOTES ON PLANS AS REQUIRED PER | | | 13-413.1.ABC.2.1, AND .2.2. | | | | | | 6) NOTE: PLEASE PROVIDE VOLTAGE DROP INFORMATION PER | | | 13-413.1ABC.1 | | | | | | 7) NOTE: PLEASE SUBMIT PHOTO-METRICS FOR MINIMUM | | | LIGHTING LEVELS UNDER NORMAL CONDITIONS AS WELL AS | | | MINIMUM LEVELS UNDER EMERGENCY CONDITIONS PER LS 7.8 | | | AND 7.9. PLEASE SEE SPECIFIC AREAS SUCH AS STAIRS ARE | | | UNDER 7.8.1.3 AND 7.9.2.2. | | | FAC 61G15-33.004 | | | FBC 106.1.2, 106.3.5.1.2 ADMIN SECTION FOR ADDITIONAL | | | INFORMATION. | | | | | | 8) NOTE: PLEASE SEE SHEET E-6.0 SHOWS A NEW PANEL LP , | | | YET DOES NOT SHOW ANY INFORMATION WHERE THIS PANEL IS | | | BEING FED FROM, LOAD CALCULATIONS ON EXISTING EQUIPMENT | | | WHICH FEEDS THIS PANEL ETC. | | | FEEDERS, GROUNDING, LOADS, OVER CURRENT PROTECTION | | | ETC. | | | PLEASE SEE 210, 220, 230, 215.5, 240.4, 310.16 ETC FBC | | | 106.3.5.1.2, 106.1.2 ADMIN SECTION FOR ADDITIONAL | | | INFORMATION. | | | | | | ** PLEASE KNOW AS THERE ARE SEVERAL ITEMS NOT YET | | | SUBMITTED FOR REVIEW A COMPLETE REVIEW CAN NOT BE DONE | | | AT THIS TIME. | | | PLEASE ALSO KNOW THERE MAY VERY WELL BE NEW COMMENTS ON | | | THE FOLLOWING REVIEW BASED ON INFORMATION WHICH WILL BE | | | IN REVIEW FOR THE FIRST TIME. | | | | | | | | | ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY | | | QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR | | | NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN | | | CONTACTING THIS REVIEWER. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2008-01-30 20:05:44 | IN ELEC FOR REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-08-29 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-08-29 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2008-08-29 15:33:54 | STAMPED LS AND FP SHEETS. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-07-21 |
Time |
14:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-07-21 |
Time |
14:11 |
Sent To |
|
|
| Notes |
| 2008-07-21 14:26:54 | ***DENIED*** | | | | | | | | | 1) PLANS APPEAR CODE COMPLIANT HOWEVER PLEASE SEE | | | ELECTRICAL REVIEW COMMENTS REGARDING RESPONSIBILTY FOR | | | SIGNING, DATING AND SEALING OF PLANS. WHEN PLANS ARE | | | RE-SUBMITTED WITH CORRECTIONS, PLANS WILL BE STAMPED AT | | | THAT TIME. | | | | | | 2) PLEASE LIMIT SUBMITTAL OF FIRE PROTECTION SHEETS TO | | | NOT MORE THAN THREE (3) COPIES. | | | | | | 3) AS PREVIOUSLY STATED, SEPARATE SHOP DRAWINGS AND | | | PERMIT REQUIRED FOR FIRE SPRINKLER REMODEL. SUBMITTAL | | | OF CALCULATION SHEETS AND MANUFACTURER SPECIFICATION | | | SHEETS WILL BE REQUIRED AT THE TIME OF FIRE SPRINKLER | | | PERMIT APPLICATION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-05-14 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-05-14 |
Time |
10:01 |
Sent To |
|
|
| Notes |
| 2008-05-14 10:07:56 | ***DENIED*** | | | | | | 1) MOST COMMENTS HAVE BEEN ADDRESSED AND PLANS APPEAR | | | CODE COMPLIANT. RESPONSE REFERENCES LIFE SAFETY. EXIT | | | AND EMERGENCY LIGHTS ARE ILLUSTRATED ON ELECTRICAL | | | SHEETS. LIFE SAFETY SHEETS WOULD INDICATE MEANS OF | | | EGRESS OCCUPANT LOADS AND MAXIMUN TRAVEL DISTANCE | | | INFORMATION. | | | | | | 2) PLEASE SEE OTHER REVIEW COMMENTS REGARDING | | | INFORMATION THAT IS REQUIRED FOR DRAWINGS. | | | | | | | | | PLANS WILL BE STAMPED WHEN RETURNED WITH CORRECTIONS TO | | | OTHER REVIEW COMMENTS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-02-27 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-02-27 |
Time |
10:38 |
Sent To |
|
|
| Notes |
| 2008-02-27 11:07:01 | ***DENIED*** | | | | | | 1) THE FLOW TEST DATE OF 12/5/06 IS NOT COMPLIANT WITH | | | THE ONE YEAR DATA REQUIREMENT. IF FLOW DATE HAS BEEN | | | UPDATED, PLEASE INCLUDE INFORMATION. | | | | | | 2) SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR | | | INSTALLATION OR REMODEL OF FIRE SPRINKLER SYSTEM. | | | | | | 3) PLANS ILLUSTRATE A NEW CHAIN LINK FENCE AND GATE. | | | FIRE PROTECTION EQUIPMENT INCLUDING THE FIRE DEPARTMENT | | | CONNECTION SHALL NOT BE OBSTRUCTED AND MAINTAIN PROPER | | | CLEARANCES. PLEASE SHOW HOW FDC WILL BE ACCESSED BY | | | FIRE APPARATUS. | | | | | | 4) SHEET FP-1 SHOWS BOTH FDC BREAK OFF CAPS AND KNOX | | | LOCKING CAPS. NEW INSTALLATIONS ARE REQUIRED TO BE | | | SECURED WITH KNOX LOCKING CAPS. AN APPLICATION CAN BE | | | OBTAINED FROM BUREAU OF FIRE PREVENTION. (561) | | | 804-4724 | | | | | | 5) PLANS SHOW PHASING OF PROJECT ON ELECTRICAL SHEETS. | | | PLEASE INDICATE ALL REQUIRED MEANS OF EGRESS. | | | | | | 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 7) NEW FIRE HYDRANTS TO BE FULLY OPERATIONAL PRIOR TO, | | | DURING AND AFTER CONSTRUCTION. | | | | | | 8) APPLICATION INDICATES IN-RACK FIRE SPRINKLER SYSTEM. | | | PLANS SEEM TO SHOW A NEW FIRE SPRINKLER SYSTEM FOR | | | BUILDING. PLEASE CLARIFY AND AS A NOTE, MONITORING OF | | | NEW FIRE SPRINKLER SYSTEMS SHALL BE UL CERTIFIED FOR | | | CENTRAL STATION SERVICE PRIOR TO FINAL INSPECTION. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-09-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-29 |
Time |
11:21 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-29 |
Time |
11:21 |
Sent To |
E |
|
| Notes |
| 2008-09-29 11:22:10 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-09-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-17 |
Time |
12:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-17 |
Time |
12:05 |
Sent To |
E |
|
| Notes |
| 2008-09-17 12:06:13 | TO "DPALMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-08-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-21 |
Time |
14:57 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-21 |
Time |
14:57 |
Sent To |
|
|
| Notes |
| 2008-08-21 14:58:08 | TO "COMM" BD#60 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-06-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-20 |
Time |
08:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-20 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2008-06-20 16:55:14 | TO "COMM" BD#56 | | 2008-06-20 08:49:20 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-03 |
Time |
16:39 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-03 |
Time |
16:39 |
Sent To |
|
|
| Notes |
| 2008-06-03 16:41:35 | TO "COMM" BD#41/PLANS ON RACK/LARGE FOLDED PLANS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-04-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-16 |
Time |
10:51 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-16 |
Time |
10:51 |
Sent To |
|
|
| Notes |
| 2008-04-16 10:55:03 | TO "COMM" BD#39 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-02-27 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-23 |
Time |
09:42 |
Sent To |
|
|
| Notes |
| 2008-01-23 09:42:27 | TO "COMM" BD#60 |
|
|