Plan Review Details - Permit 08010437
Plan Review Stops For Permit 08010437
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-10-02 Cont ID  
Sent By jwitmer Date 2008-10-02 Time 07:55 Rev Time 0.77
Received By jwitmer Date 2008-10-02 Time 07:55 Sent To  
Notes
2008-10-02 07:56:27REVIEWED:
 D-101,D-102, M-701 & M-702

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-04 Cont ID  
Sent By jwitmer Date 2008-06-04 Time 07:25 Rev Time 2.22
Received By jwitmer Date 2008-06-04 Time 07:25 Sent To  
Notes
2008-06-04 07:35:16BUILDING PLAN REVIEW
 PERMIT: 08010437
 ADD: 1041 45TH ST
 CONT: ** PLAN REVIEW**
 TEL: (561)718-4140 JON VANDERBERG
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW"PLAN REVIEW"
 ACTION: DENIED
  
 1A-C) COMPLIED
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) COMPLIED.
  
 2)COMPLIED.
  
 3) COMPLIED, NOTED.T
  
 4)2ND REQUEST, PLANS DO NOT INDICATE THE CORRIDOR
 WALLS AS THE REQUIRED SMOKE PARTITIONS (407.3). THE
 PLANS WILL ALSO NEED TO INDICATE THE SMOKE BARRIER
 WALLS THAT ARE REQUIRED IN 407.3 AND ALSO INDICATE
 COMPLIANCE WITH 407.4.1 REFUGE AREA PER PATIENT WITHIN
 THE AGGREGATE AREA OF CORRIDORS, PATENIT ROOMS
 TREATMENT ROOMS LOUNGE OR DINING ROOMS AND OTHER LOW
 HAZARD AREAS ON EACH SIDE OF EACH SMOKE BARRIER.
  
 ON VARIOUS SHEETS WHERE THE DUCTS CROSS SMOKE BARRIERS
 FROM ONE CHAMBER TO ANOTHER THE DUCTS ARE MISSING SMOKE
 DAMPERS. PLEASE ILLUSTRATE CODE COMPLIANCE WITH 716.1.1
 AND OR 712.3. AND 712.3.4.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-27 Cont ID  
Sent By jwitmer Date 2008-01-27 Time 20:10 Rev Time 2.22
Received By jwitmer Date 2008-01-27 Time 20:10 Sent To  
Notes
2008-01-27 21:03:47BUILDING PLAN REVIEW
 PERMIT: 08010437
 ADD: 1041 45TH ST
 CONT: ** PLAN REVIEW**
 TEL: (561)###-####
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW"PLAN REVIEW"
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2)) 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION
 THAT IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE
 OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.UPDATE THE CODE COMPLIANCE TO INCLUDE THE 2007
 SUPPLEMENTS.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. COMPLIED.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601. TAGLE 601 CONSTRUCTION TYPE IIIA OR IIIB? D)
 THE OCCUPANT LOAD, SEE 1004.COMPLIED.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED? F)
 WHETHER THE SPRINKLER SYSTEM IS REQUIRED? (AREA
 INCREASES)
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .H) NUMBER OF FLOORS
 THE ABOVE MENTIONED REQUIREMENTS ARE NEEDED TO DO AN
 ACCURATE REVIEW UNDER THE CURRENT CODES.
  
 3) THE TECHNICAL SPECIFICATIONS INDICATE THE PRESENCE
 OF ASBESTOS. PLEASE SEE WPB ADMINISTRATIVE CODE
 105.3.6* ,553.79 FL SS & 455.302 FL SSFOR ASBESTOS
 REMOVAL. THIS ABATEMENTOF ASBESTOS MUST BE BY STATE
 LAW MUST BE ACCOMPLISHED BYLICENSED CONTRACTORS.
 BFORE ABATEMENT OF ASBESTOS
 REQUIREMENTS INCLUDE - ASBESTOS SURVEY AND SUBMISSION
 OF WRITTEN NOTIFICATION TO THE FLORIDA DEPARTMENT OF
 ENVIROMENTAL PROTECTION PRIOR TO MOST RENOVATION
 ACTIVITIES IN REGULATED STRUCTURES WHERE ASBESTOS IS
 DISTURBED OR REMOVED. FOR FURTHER INFORMATION IN PALM
 BEACH COUNTY, CONTACT THE DIVISION OF ENVIROMENTAL
 HEALTH & ENGINEERING HRS/ PALM BEACH COUNTY HEALTH
 UNIT.
 HAS THE WRITTEN PERMISSION FOR REMOVAL OF ASBESTOS BEEN
 OBTAINED FOR THE PB COUNTY HEALTH DEPARTMENT?
  
 4) ON VARIOUS SHEETS WHERE THE DUCTS CROSS SMOKE
 BARRIERS FROM ONE CHAMBER TO ANOTHER THE DUCTS ARE
 MISSING SMOKE DAMPERS. PLEASE ILLUSTRATE CODE
 COMPLIANCE WITH 716.1.1 AND OR 712.3. AND 712.3.4.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-10-03 Cont ID  
Sent By dpalmer Date 2008-10-03 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2008-10-03 Time 14:13 Sent To  
Notes
2008-10-03 14:13:32** DENIED **
  
 1) NOTE: PERMIT APPLICATION HAS YET TO BE MADE. THE
 FINAL STAMPING OF ELECTRICAL PLANS WILL TAKE PLACE ONCE
 PERMIT IS APPLIED FOR. REVIEW OF LICENSING ETC WILL
 TAKE PLACE AT THAT TIME.
  
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANOR PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-02 Cont ID  
Sent By dpalmer Date 2008-06-02 Time 17:25 Rev Time 0.00
Received By dpalmer Date 2008-06-02 Time 17:25 Sent To  
Notes
2008-06-02 17:25:52** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME COMMENTS FROM PREVIOUS REVIEWS ARE
 STILL IN NEED OF ADDRESSING.
  
  
 1) NOTE: PLEASE SEE ONCE AGAIN PLANS ARE SUBMITTED
 WITHOUT BEING SUBMITTED BY A CONTRACTOR FOR PERMIT
 APPLICATION. PLEASE KNOW EVEN ONCE ALL CODE COMMENTS
 ARE ADDRESSED PLANS WILL STILL REMAIN IN A FAILED
 STATUS UNTIL PERMIT APPLICATION IS MADE. THERE ARE MANY
 ITEMS REVIEWED AND VERIFIED ONCE APPLICATION IS MADE
 AND NEED TO BE DONE AT THAT TIME.
  
 2) NOTE: PLEASE SEE ONCE AGAIN TITLE BLOCKS AND
 LICENSING INFORMATION HAS NOT BEEN CORRECTED. PLEASE
 SEE TITLE BLOCKS STILL SHOW *AR* INSTEAD OF AN *AA* OR
 *AAC* FOR ARCHITECTURAL BUSINESS. PLEASE SEE ONCE AGAIN
 THE LICENSING ON SOME SHEETS FOR MORSE ASSOCIATES IS
 NOT THE SAME ON ALL SHEETS. PLEASE KNOW THE LICENSING
 SHOWN ON ELECTRICAL SHEETS DOES NOT COME UP AS VALID
 WITH THE DEPARTMENT OF BUSINESS AND PROFESSIONAL
 REGULATION.
 PLEASE SUPPLY INFORMATION ON WHICH ENGINEERS WORK FOR
 WHICH FIRM. AS DYANKI SHOWN ON TITLE BLOCKS IS THE ONLY
 FIRM LISTED WITH AN ENGINEERING BUSINESS LICENSE NUMBER
 IT IS UNCLEAR OF THE ARCHITECTURAL FIRM BEING LISTED.
 IT IS ALSO NOT CLEAR WHY THERE ARE STILL TWO SEPARATE
 LICENSE NUMBERS.
 LICENSING FOR NAME AND FIRMS LISTED HAS BEEN NOTED ON
 NUMEROUS REVIEWS BY THIS OFFICE ON MULTIPLE PROJECTS TO
 BE COORDINATED AND FINALIZED YET THIS STILL COMES BACK
 AS AN ISSUE.
 PLEASE SEE FLORIDA STATUTES 481.219, 471.023 AND
 FLORIDA ADMINISTRATIVE CODE 61G1-16.004, 61G15-23.002
 FOR INFORMATION NEEDED AND REQUIRED.
  
 3) NOTE: PLEASE SEE ONCE AGAIN INCOMPLETE METHOD *A*
 CALCULATIONS ARE STILL BEING SUBMITTED. MAY NOT USE OR
 SUBMIT METHOD *A* CALCULATIONS UNLESS COMPLYING WITH
 THE CODE FOR WHOLE BUILDING AS VERSION STATES.
 PLEASE ALSO KNOW PER 13-400.A.3 VERSION 3.0 IS NOT
 ADOPTED BY THE STATE OF FLORIDA OR THE FLORIDA BUILDING
 CODE.
 CALCULATIONS SUBMITTED ARE NOT REVIEWED FOR ANY
 ELECTRICAL CODE COMPLIANCE. IF SCOPE OF WORK IS TO
 INCLUDE ALL ELECTRICAL AS INDICATED, THEN PLANS WILL BE
 REQUIRED TO MEET CHAPTER 13 UNDER THE 2004 W/2007
 REVISIONS.
  
 4) NOTE: PLEASE SEE THE REVISED ELECTRICAL RISER WHICH
 APPEARS TO NOW BE SHOWING THE EXISTING MAIN LUG ONLY
 ENCLOSURE BEING CONVERTED TO A JUNCTION BOX HOWEVER
 THIS COULD NOT BE DONE AS SHOW.
 THE PLANS STILL SHOW THE PANEL SCHEDULE FOR THE SWB
 WHICH WOULD ACTUALLY NO LONGER EXISTS.
 THIS WOULD NOW CONTAIN PROTECTED AND UN-PROTECTED (LINE
 AND LOAD) CONDUCTORS IN THE SAME ENCLOSURE WHICH IS NOT
 PERMITTED.
 PLEASE SEE THAT NO MORE THAN 8FT OF UNPROTECTED
 CONDUCTORS ARE PERMITTED INSIDE THE BUILDING.
 PLEASE SEE NEW PROPOSED MSD ALSO DOES NOT CONTAIN ANY
 MAIN YET THERE ARE MORE THAN 6 SPACES WHICH ARE NOT
 PERMITTED.
 PLEASE SEE THAT ONCE A MAIN IS INSTALLED GF PROTECTION
 WILL BE REQUIRED.
 NOTE # 2 TO GENERAL NOTES ON RISER MENTIONS THE
 ALTERNATIVE FOR SERVICE INTO VAULT. THIS WOULD NEED TO
 BE SHOWN AT THIS TIME.
  
 230.70, 230.71, 230.72, 240.13, 230.95.300.3B ETC
  
 ** AS NOTED ON PREVIOUS REVIEW AS SOME ITEMS ARE NOT
 CLEAR YET AND SOME INFORMATION IS NOT YET SHOWN PLEASE
 KNOW THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW
 WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By dpalmer Date 2008-01-29 Time 17:27 Rev Time 0.00
Received By dpalmer Date 2008-01-29 Time 17:27 Sent To  
Notes
2008-01-29 17:27:12** DENIED REVIEW **
  
  
 1) NOTE: PLANS ONLY SUBMITTED FOR PLAN REVIEW AND NOT
 FOR PERMIT. PLEASE BE AWARE WHEN PLANS ARE CODE
 COMPLIANT AND READY FOR ISSUANCE THE REVIEW WILL REMAIN
 IN FAILED STATUS UNTIL SUCH TIME PERMIT APPLICATION HAS
 BEEN MADE.
  
 2) NOTE: PLEASE VERIFY LICENSING OF FIRM AS LISTED ON
 SPECIFICATION BOOKS AND PLANS. PLEASE SEE FOR EXAMPLE:
 BOOKS CONTAIN *MORSE, ZEHNTER ASSOCIATES* HOWEVER PLANS
 CONTAIN MORSE AND ASSOCIATES.
 PLEASE ALSO SEE THE PLANS STATE A FIRM LICENSE NUMBER
 OF AR001209. PLEASE KNOW THE AR IS FOR REGISTERED
 ARCHITECT AND THE LICENSE NUMBER AS LISTED ABOVE IS NOT
 THAT AS LISTED ON THE STATE OF FLORIDA DEPARTMENT OF
 BUSINESS AND PROFESSIONAL REGULATION WEBSITE. PLEASE
 SEE ATTACHED PRINT OUT FROM DPBR WHICH SHOWS THE
 CURRENT NAME AND LICENSURE INFORMATION.
 PLEASE SEE FAC 61G1-16.004, AND FS 481.219 FOR
 INFORMATION REQUIRED TO COORDINATE.
 ** THIS IS REQUIRED WHETHER OR NOT COMMENT IS MADE BY
 OTHER TRADES FOR REVIEW.
  
 3) NOTE: PLEASE SEE THE SPECIFICATION BOOK HAS A METHOD
 *A* SUBMITTED FOR ENERGY CALCULATIONS WHICH DOES NOT
 SEEM POSSIBLE. PLEASE SEE COMMENTS FROM MECHANICAL
 REVIEW.
 PLEASE KNOW THIS IS NOT A WHOLE BUILDING WITH ALL NEW
 COMPONENTS.
 PLEASE SEE THIS ALSO DOES NOT FALL UNDER RENOVATIONS.
 PLEASE SEE ENERGY CALCULATIONS ARE BEING SHOWN WITH ALL
 NEW LIGHTING YET THE SCOPE OF WORK AND PLANS SUBMITTED
 DO NOT COORDINATE WITH ANY OF THIS.
  
 PLEASE SEE FBC CHAPTER 13, 13-101.1 (ALL), 13-415.2 AND
 OTHER SECTIONS WHICH MAY BE REFLECTED UNDER MECHANICAL
 REVIEW.
  
 4) NOTE: PLEASE SEE ALL GROUNDING ON THE SECONDARY
 SIDES OF TRANSFORMERS SHALL BE CONNECTED TO AN
 EFFECTIVE GROUNDING ELECTRODE SOURCE. THE COLD WATER
 PIPE AS THE SOLE CONNECTION IS NOT ACCEPTABLE DUE TO
 SEVERAL INTERRUPTIONS IN A COLD WATER PIPE WHICH WILL
 AFFECT AN EFFECTIVE BOND. PLEASE KNOW FOR EXAMPLE: PVC
 INTERCONNECTION POINTS, UNION FITTINGS ETC.
 PLEASE SEE 250.30, 250.50, 250.53, 250.58 ETC. THIS
 COMMENT IS FOR NEW AS WELL AS EXISTING 225K UNIT WHICH
 ONLY NOTES CWP FOR CONNECTION.
  
 5) NOTE: PLEASE KNOW ANY CONNECTIONS OF SYSTEMS,
 PANELS, LOADS, CONDUCTORS ETC TO THE EXISTING SERVICE
 WILL REQUIRE THE SERVICE AS SHOWN(MAIN SWITCH GEAR)
 TO BE BROUGHT UP TO CODE.THE SERVICE AS SHOWN DOES
 NOT MEET CURRENT CODE FOR MANY ITEMS AND ANY CHANGE IN
 SERVICE OR SYSTEMS OF SERVICE WILL REQUIRE THIS TO BE
 BROUGHT UP TO CURRENT CODE.
 THIS WAS CONFIRMED ALL OTHER ELECTRICAL PLAN REVIEW
 STAFF AS WELL AS THE CHIEF ELECTRICAL INSPECTOR OVER
 INSPECTIONS. THE SERVICE AS SHOWN WHICH EXISTS DOES NOT
 COMPLY WITH THE CURRENT CODE OR CODES GOING BACK FOR
 DECADES. THERE ARE SEVERAL SAFETY ISSUES ON THIS
 SERVICE FROM PROTECTION OF CONDUCTORS, EFFECTIVE
 GROUNDING, TAPPED CONDUCTORS, OVER LOADING ETC. PLEASE
 SEE THE MAIN SWITCH BOARD DOES NOT SHOW ANY SEPARATION
 OF SYSTEMS BASED ON PLANS SUBMITTED. PLEASE SEE THE
 MAIN SWITCH BOARD DOES NOT INDICATE ALL POSSIBLE
 MAINS.
 PLEASE SEE THE MAIN SWITCH BOARD WHICH IS SHOWN FEEDING
 OUT TO THE 225K TRANSFORMER SHOWS THESE CONDUCTORS
 COMING BACK INTO A MLO 800A BUS WITH NO TERMINATION
 INTO A SINGLE MEANS OF OVER CURRENT PROTECTION OF ANY
 KIND.
 PLEASE SEE THE TAPPED CONDUCTORS ON THE SECONDARY SIDE
 OF THIS SAME 225K TRANSFORMER ARE NOT RATED FOR
 800AMPS.
 PLEASE SEE THE FEEDERS ON SCHEDULE SHOULD COORDINATE
 WITH RISER. FOR EXAMPLE: PLEASE SEE PANEL *C*. PLEASE
 SEE 240.4, 310.16, 230.70, 230.71, 230.2, 240.21,
 240.13, ETC
 THERE ARE TOO MANY SECTIONS TO LIST.
  
 * PLEASE KNOW AS THERE ARE SEVERAL ITEMS WHICH MAY
 CHANGE, THERE MAY VERY WELL BE NEW COMMENTS ON THE NEXT
 REVIEW.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-10-17 Cont ID  
Sent By mawillia Date 2008-10-17 Time 10:41 Rev Time 0.00
Received By mawillia Date 2008-10-17 Time 10:26 Sent To  
Notes
2008-10-17 10:40:09*****PROVISO*****
  
  
  
 THE APPROPIATE PLAN SHEETS WILL BE FIRE-STAMPED WHEN
 THE PERMIT HAS BEEN APPLIED FOR AND/OR IF ANY CHANGES
 MADE TO THIS PLAN ARE CODE COMPLIANT.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-06-03 Cont ID  
Sent By mawillia Date 2008-06-03 Time 15:59 Rev Time 0.00
Received By mawillia Date 2008-06-03 Time 15:49 Sent To  
Notes
2008-06-03 15:58:36*****PROVISO*****
  
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED; THE APPROPIATE PLAN SHEETS WILL BE
 FIRE-STAMPED WHEN THE OTHER REVIEWERS COMMENTS HAVE
 BEEN SATISFIED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-19 Cont ID  
Sent By mwennerg Date 2008-02-19 Time 14:25 Rev Time 0.00
Received By mwennerg Date 2008-02-19 Time 14:25 Sent To  
Notes
2008-02-19 14:50:20***DENIED***
  
 THIS PLAN HAS BEEN SUBMITTED FOR PLAN REVIEW ONLY AND
 NOT FOR PERMIT AT THIS TIME.
  
 1) HOW WILL THIS WORK IMPACT EXISTING BUILDING FIRE
 PROTECTION EQUIPMENT? (FIRE SPRINKLER, FIRE ALARM
 ETC.)
  
 2) REQUIRED MEANS OF EGRESS AND EXITS SHALL BE
 MAINTAINED AT ALL TIMES.
  
 3) THE SITE SHALL BE CLEANED DAILY OF EXCESS
 CONSTRUCTION DEBRIS.
  
 4) NEW FIRE DAMPERS TO BE TESTED FOR CLOSURE AND SHALL
 COMPLY WITH WITH UL 555 STANDARDS PRIOR TO FINAL
 INSPECTION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-09-15 Cont ID  
Sent By adarroug Date 2008-09-15 Time 09:11 Rev Time 0.00
Received By adarroug Date 2008-09-15 Time 09:11 Sent To  
Notes
2008-09-15 09:14:42TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 11:37 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 11:37 Sent To  
Notes
2008-05-07 11:37:23TO "COMM" BD#43

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-19 Cont ID  
Sent By mwennerg Date 2008-02-19 Time 14:57 Rev Time 0.00
Received By mwennerg Date 2008-01-18 Time 12:42 Sent To  
Notes
2008-01-18 12:42:45TO "COMM" BD#59

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-10-01 Cont ID  
Sent By rregueir Date 2008-10-01 Time 13:35 Rev Time 0.00
Received By rregueir Date 2008-10-01 Time 12:35 Sent To  
Notes
2008-10-01 13:35:16THIS PROJECT IS SUBMITTED FOR PLAN REVIEW ONLY.
 THEREFORE THE REVIEW WILL REMAIN IN "FAIL" STATUS
 PENDING SUBMISSION OF AN ACTUAL PERMIT APPLICATION. THE
 FOLLOWING ISSUE HAS NOT BEEN ADDRESSED AND MUST BE
 ADDRESSED PRIOR TO PERMIT ISSUANCE OR IT WILL BE
 COVERED BY PROVISO AS FOLLOWS:
  
 *****************PROVISO*****************
 ALL NEW MECHANICAL APPLIANCES SHALL BE DESIGNED AND
 INSTALLED TO RESIST WIND PRESSURES IN ACCORDANCE WITH
 FBCM 301.13. PROVIDE DOCUMENTATION FOROM THE APPLIANCE
 MANUFACTURERS DEMONSTRATING THAT THESE APPLIANCES ARE
 DESIGNED AND CONSTRUCTED TO RESIST WIND PRESSURES IN
 ACCORDANCE WITH THIS SECTION PRIOR TO INSTALLATION AND
 INSPECTION OF THE APPLIANCES.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status   Date 2008-09-22 Cont ID  
Sent By rregueir Date 2008-09-22 Time 10:58 Rev Time 0.00
Received By rregueir Date 2008-09-19 Time 14:15 Sent To  
Notes
2008-10-01 12:34:46DESIGNER HAS CHANGED OUT SHEETS IN LAST SUBMISSION OF
 PLANS TO CORRECT WALL DESIGNATIONS. BACK ON REVIEW
 CYCLE.
2008-09-22 10:58:11REVIEW ON HOLD PER ROBERT SHORR.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-23 Cont ID  
Sent By rregueir Date 2008-05-23 Time 08:46 Rev Time 0.00
Received By rregueir Date 2008-05-22 Time 09:39 Sent To  
Notes
2008-05-23 08:46:19REVIEW #: 2ND**PLAN CHACK ONLY**
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. AS STATED IN PREVIOUS REVIEW: "PLEASE INDICATE ON
 PLANS THE LOCATION OF ANY RATED WALL OR CEILING
 ASSEMBLIES AS WELL AS THE OPENING PROTECTIVE METHODS
 DEPLOYED..."
 WHILE DAMPER LOCATIONS ARE NOW SHOWN ON PLANS, THE
 LOCATION OF EXISTING RATED ASSEMBLIES WAS NOT PROVIDED
 AS REQUESTED IN PREVIOUS REVIEW. AN ATTEMPT WAS MADE
 DURING THIS REVIEW TO DETERMINE THE LOCATION OF RATED
 ASSEMBLIES BASED ON THE LOCATION OF DAMPERS NOW SHOWN
 ON PLANS BUT THIS WAS NOT POSSIBLE. WHEN LOOKING FOR
 THE LOGICAL CONTINUATION OF WALLS SHOWN AS RATED BASED
 ON THE LOCATION OF DAMPERS, IT APPEARS THAT THERE MAY
 BE ADDITIONAL DUCT PENETRATIONS OF RATED WALLS WHICH
 ARE NOT PROTECTED IN ACCORDANCE WITH FBCM 607.5. PLEASE
 PROVIDED THE INFORMATION NEEDED AND REQUESTED TO
 FACILITATE A COMPLETE REVIEW FOR CODE COMPLIANCE. FBCB
 106.1.1 AND FBCB 106.1.2.
  
 2 THROUGH 6: OK
  
 7. ACKNOWLEDGED. IF THIS ISSUE IS NOT RESOLVED AND
 BECOMES THE ONLY OUTSTANDING ISSUE PRIOR TO PERMIT
 ISSUANCE, IT CAN BE COVERED WITH A PROVISO TO ALLOW THE
 PROJECT TO PROCEED WHILE THE MANUFACTURER PREPARES
 THEIR DOCUMENTATION.
  
 8. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-13 Cont ID  
Sent By rregueir Date 2008-02-13 Time 19:20 Rev Time 0.00
Received By rregueir Date 2008-02-13 Time 10:44 Sent To  
Notes
2008-02-13 19:20:15REVIEW #: 1ST *PLAN CHECK ONLY*
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. INDEX PAGE, SHEET METAL DUCT INSTALLATION NOTES,
 NOTE #7: THIS NOTE INDICATES THAT THE EXCEPTION LISTED
 IN THE NOTE APPLIES TO DUCT PENETRATIONS IN RATED WALLS
 AND PARTITIONS. THIS IS NOT ACCURATE AS THE EXCEPTION
 MAY ONLY BE UTILIZED IN FIRE PARTITIONS AND IS NOT
 APPLICABLE IN FIRE BARRIERS OR FIRE WALLS. SEE FBC, M
 607.5 AND FBC 702 FOR DEFINITIONS. ALSO, THERE IS NO
 INDICATION ON DUCT FLOOR PLANS, PAGES M-103 THROUGH
 M-111, OF THE LOCATIONS OF RATED ASSEMBLIES WHERE
 OPENING PROTECTIVES WILL BE REQUIRED. A GENERAL NOTE
 CALLING FOR PROTECTION OF PENETRATIONS IN RATED WALLS
 IS NOT SUFFICIENT TO DEMONSTRATE CODE COMPLIANCE. THE
 SPECIFIC LOCATION AND INSTALLATION DETAILS OF EACH FIRE
 DOOR, FIRE DAMPER, CEILING DAMPER AND SMOKE DAMPER
 SHALL BE SHOWN AND PROPERLY IDENTIFIED ON THE BUILDING
 PLANS BY THE DESIGNER IN ACCORDANCE WITH FBC, M 607.8.
 PLEASE INDICATE ON THE PLANS THE LOCATION OF ANY RATED
 WALL OR CEILING ASSEMBLIES AS WELL AS THE OPENING
 PROTECTIVE METHODS DEPLOYED AT ALL PENETRATIONS OF
 THESE ASSEMBLIES TO DEMONSTRATE COMPLIANCE WITH THIS
 SECTION.
  
 2. INDEX PAGE, GENERAL SCOPE OF WORK, NOTE #7 CALLS FOR
 ALL EXISTING ATTIC INSULATION TO BE REMOVED WITH NEW
 R-19 INSULATION TO BE INSTALLED. DETAIL #1 ON PG M-502
 SHOWS INSULATION BEING INSTALLED ABOVE A HARD CEILING.
 HOWEVER, GENERAL HVAC NOTE #21 STATES THAT GYPSUM
 CEILING AREAS ARE LIMITED WHICH INDICATES THAT MOST
 CEILING AREAS CONSIST OF LAY-IN TILE TYPE CEILINGS. HOW
 WILL THE NEW INSULATION BE INSTALLED IN THESE GRID
 CEILING AREAS? ROOF INSULATION SHALL NOT BE INSTALLED
 ON A SUSPENDED CEILING WITH REMOVABLE CEILING PANELS IN
 ACCORDANCE WITH FBC 13-404.1.ABC.1. SHOW HOW NEW
 INSULATION IS TO BE INSTALLED IN THESE AREAS IN
 ACCORDANCE WITH THIS SECTION.
  
 3. ENERGY CALCULATIONS: METHOD A CALCULATIONS ARE NOT
 APPROPRIATE FOR THIS PROPOSED PROJECT. EXISTING
 BUILDINGS NOT MEETING THE DEFINITION OF A RENOVATION
 (SEE 13-202) IN WHICH NEW HEATING, COOLING, WATER
 HEATING, ELECTRICAL OR LIGHTING SYSTEMS ARE INSTALLED
 SHALL MEET THE BASIC PRESCRIPTIVE MINIMUM EFFICIENCIES
 LISTED IN THIS CODE FOR THE SYSTEM(S) BEING CHANGED IN
 ACCORDANCE WITH FBC 13-400.0.C.4. ALL NEW MECHANICAL
 COMPONENTS SHOWN ON PLANS ARE SHOWN TO MEET THE
 PRESCRIPTIVE MINIMUM EFFICIENCIES. NO COMPLIANCE FORM
 IS NEEDED TO DEMONSTRATE COMPLIANCE WITH THE MECHANICAL
 PORTIONS OF FBC CHAPTER 13. METHOD A CALCULATIONS SHALL
 ONLY BE USED UNDER THE CONDITIONS AS STATED IN FBC
 13-101.4.2. ENERGY CALCULATIONS WHICH HAVE BEEN
 SUBMITTED WILL NOT BE REVIEWED FOR MECHANICAL AS THEY
 ARE NOT NEEDED.
  
 4. PG M-501: DETAIL #3, CONDENSATE NOTE INDICATES
 CONDENSATE MAY DISCHARGE INTO A FLOOR/SANITARY DRAIN.
 AIR CONDITIONING CONDENSATE SHALL NOT DISCHARGE INTO
 THE SANITARY SEWER SYSTEM IN ACCORDANCE WITH CITY OF
 WPB MUNICIPAL CODE 31-62(5). ALSO, PLEASE SHOW MEANS
 AND LOCATION OF CONDENSATE FOR AHU-7 AND NEW MINI-SPLIT
 SYSTEM IN ACCORDANCE WITH FBC, M 307.2.1.
  
 5. PG M-501: DETAIL #6 PROVIDES A DETAIL FOR FIRE
 DAMPER INSTALLATION. FIRE DAMPERS, SMOKE DAMPERS,
 COMBINATION FIRE/SMOKE DAMPERS AND CEILING DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION AND SMOKE CONTROL
 SYSTEMS SHALL BE INSTALLED IN ACCORDANCE WITH THE
 REQUIREMENTS OF THIS SECTION, AND THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M 607.2.
 THE PROVIDED DETAIL MAY BE IN CONFLICT WITH
 MANUFACTURER?S INSTRUCTIONS.
 6. PG M-502: DETAIL #7, DOWNDRAFT RTUS SHALL HAVE
 AUXILIARY DRAIN PROTECTION IN ACCORDANCE WITH FBC, M
 307.2.3. THIS MAY BE ACCOMPLISHED WITH THE INSTALLATION
 OF A WATER LEVEL DETECTION DEVICE INSIDE THE UNIT ON
 THE PRIMARY DRAIN PAN. IF THE PRIMARY DRAIN WERE TO
 OVERFLOW, IT IS LIKELY IT WOULD DRAIN INTO THE BUILDING
 IN VIOLATION OF THIS SECTION.
  
 7. PG M-701 AND M-702: WIND LOAD CALCULATIONS FOR
 OUTDOOR UNITS ARE SUBJECT TO BUILDING PLAN REVIEW. IN
 ADDITION, EQUIPMENT AND APPLIANCES THAT ARE EXPOSED TO
 WIND SHALL BE DESIGNED AND INSTALLED TO RESIST THE WIND
 PRESSURES ON THE EQUIPMENT AND THE SUPPORTS AS
 DETERMINED IN ACCORDANCE WITH THE FLORIDA BUILDING
 CODE, BUILDING PER FBC, M 301.13. PROVIDE DOCUMENTATION
 SHOWING SPECIFIED EQUIPMENT HAS BEEN TESTED TO
 WITHSTAND ANTICIPATED WIND PRESSURES IN ACCORDANCE WITH
 THIS SECTION.
  
 8. PLEASE SEE ELECTRICAL REVIEW COMMENT #2 REGARDING
 DESIGN PROFESSIONAL LICENSURE REQUIREMENTS.
  
 NOTE: THIS PLAN HAS BEEN SUBMITTED FOR PLAN REVIEW ONLY
 AND NOT FOR PERMIT. ONCE PERMIT HAS BEEN APPLIED FOR,
 PLANS WILL BE REQUIRED TO COMPLY WITH THE CODE VERSION
 IN EFFECT AT THE TIME OF APPLICATION. ONCE ALL COMMENTS
 ARE ADDRESSED, REVIEW WILL REMAIN IN FAILED STATUS
 UNTIL TIME OF APPLICATION AND VERIFICATION THAT THE
 PLANS HAVE BEEN REVIEWED UNDER THE CORRECT CODE CYCLE.
  
 PLEASE RESPOND TO ALL REVIEW COMMENTS IN WRITING WITH
 INFORMATION ON HOW COMMENTS HAVE BEEN ADDRESSED AND
 WHERE THE REQUESTED INFORMATION CAN BE FOUND IN ORDER
 TO SPEED THE REVIEW PROCESS. ADDITIONALLY, PLEASE
 RETURN ONE SET OF OLD PLANS FOR REFERENCE.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]