Plan Review Details - Permit 08010430
Plan Review Stops For Permit 08010430
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-28 Cont ID  
Sent By rmcdouga Date 2008-02-28 Time 11:24 Rev Time 0.00
Received By rmcdouga Date 2008-02-28 Time 11:24 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By rmcdouga Date 2008-01-29 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2008-01-29 Time 10:38 Sent To  
Notes
2008-01-29 11:11:302004 FBC W/2007 REVISIONS
 LEVEL 3 ALTERATION
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE NEW 42"
 WIDE EXTERIOR IN-SWING METAL DOOR AND THE STORM PANELS
 FOR THE NEW WINDOW THAT WAS ADDED AS REQUIRED BY FAC
 RULE 9B-72.
  
 3)FBC 106.3* CITY AMENDMENTS. PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. THE ENGINEER THAT SEALED THE
 PLANS IS REQUIRED TO REVIEW AND APPROVE THE PRODUCT
 APPROVALS IN WRITING.
  
 4) SPECIFY THE APPLICABLE CODE AND DESIGN CRITERIA FOR
 THIS WORK ON THE PLANS. THE 2004 FBC W 2007 REVISIONS
 IS THE CODE. DESIGN CRITERIA INCLUDES THE WIND SPEED,
 IMPORTANCE FACTOR, EXPOSURE CATEGORY, ETC.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By btrobaug Date 2008-02-25 Time 08:13 Rev Time 0.00
Received By btrobaug Date 2008-02-25 Time 07:25 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 15:21 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 15:20 Sent To Z
Notes
2008-01-18 15:21:13 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE LIGHTING IN BATHROOM NEEDS TO MEET
 410.8 TO BE OUTSIDE SHOWER AREA OR MEETING THE
 EXCEPTIONS FOR HEIGHT/CLEARANCE REQUIREMENTS ALONG WITH
 CLOSED IN TYPE OF FIXTURES FOR SHOWER LOCATIONS.
 AS THIS AREA ALL APPEARS TO BE A SHOWER, THESE WILL BE
 REQUIRED TO BE RATED FOR SUCH LOCATIONS.
 110.3, 410.8 ETC
  
 2) NOTE: PLEASE CLARIFY RECEPTACLE SPACING ALONG
 KITCHEN COUNTER SPACES PER 210.52C1. IF NEW CABINETS,
 COUNTERS AND WALL AREAS ARE DONE, SPACING SHALL MEET
 CURRENT CODE.
  
 3) NOTE: PLEASE SEE NEW SWITCH IN DINING ROOM WHICH
 DOES NOT SHOW WHAT IS WILL BE CONTROLLING.
 PLEASE SHOW. 210.70
  
 4) NOTE: PLEASE PROVIDE PANEL SCHEDULE WITH THE MINIMUM
 NEW CIRCUITS BEING PROPOSED. FOR EXAMPLE: EXISTING
 PLANS DID NOT SHOW BATH ROOM CIRCUIT, YET NEW SHOW NEW
 GFI.
 PLEASE SEE 210.11C3 FOR REQUIRED DEDICATED 20AMP AND
 #12 BRANCH CIRCUITS.
 310.16, 408.4, 240.4 ETC
 FBC 106.3.5.4
  
 5) NOTE: PLANS INDICATE NEW DOOR OPENERS YET NO NEW
 ELECTRICAL IS BEING SHOWN FOR THESE SAME LOCATIONS.
 PLEASE COMPLETE INFORMATION.
 310.16, 240.4, ETC
  
 6) NOTE: PLEASE SEE THE EXISTING UTILITY ROOM IS NOW
 BEING SHOWN AND WILL BE CONSIDERED AN ADAPTABLE
 SLEEPING ROOM PER NFPA-72.
 PLEASE SEE AN ADDITIONAL SMOKE ALARMS (NOT DETECTORS)
 WILL BE REQUIRED INSIDE AND OUTSIDE THIS ROOM.
 11.5.1.1.1
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 10:43 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 10:43 Sent To Z
Notes
2008-02-20 10:43:23TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-29 Cont ID  
Sent By rmcdouga Date 2008-01-29 Time 10:39 Rev Time 0.00
Received By rmcdouga Date 2008-01-18 Time 12:03 Sent To  
Notes
2008-01-18 12:03:11TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-27 Cont ID  
Sent By tgordon Date 2008-02-27 Time 10:16 Rev Time 0.25
Received By tgordon Date 2008-02-27 Time 10:16 Sent To B
Notes
2008-02-27 10:17:42ONE BATHROOM EXHAUST FAN ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By tgordon Date 2008-01-23 Time 09:27 Rev Time 0.25
Received By tgordon Date 2008-01-23 Time 09:26 Sent To P
Notes
2008-01-23 09:36:59PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SCOPE OF WORK STATES INSTALL BATHROOM EXHAUST FAN,
 PLAN SHOWS NO BATHROOM EXHAUST FAN, SEE 2004 FBC R303.3
 EXCEPT. PLEASE CORRECT.
  
 2) SCOPE OF WORK ALSO STATES REPLACE A/C OUTLET FOR
 BATHROOM-SHOWER AREA, PLEASE SHOW ON PLAN, AND ANY
 OTHER MECHANICAL WORK TO BE DONE, SEE 2004 WPB AMEND.
 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-26 Cont ID  
Sent By mperson Date 2008-02-26 Time 15:32 Rev Time 0.00
Received By mperson Date 2008-02-26 Time 15:32 Sent To M
Notes
2008-02-26 15:33:05****************PROVISO****************
 PER FBC PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES (R-3) ONE AND TWO FAMILY
 DWELLINGS: PLEASE VERIFY THAT THERE IS AN EXISTING
 AUTOMATIC CLOTHES WASHER CONNECTOR. NOTE: IF THERE IS
 NOT AN EXISTING AUTOMATIC CLOTHES WASHER CONNECTOR A
 REVISION WILL BE REQUIRED TO PROVIDE ONE.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By mperson Date 2008-01-28 Time 16:44 Rev Time 0.00
Received By mperson Date 2008-01-28 Time 16:44 Sent To B
Notes
2008-01-28 16:57:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1.SHEET A1 EXISTING FLOOR PLAN IS INDICATING THE
 DEMOLITION OF THE EXISING SHOWER. PLEASE INDICATE THE
 FOLLOWING PLUMBING REQUIREMENTS ON THE RESUBMITTAL.
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT IS REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 2. PER FBC-2004 CHAPTER 1 CITY WPB AMENDMENTS, SECTION
 106.3.5.4 RESIDENTIAL (ONE AND TWO-FAMILY) PLEASE
 SUBMIT A PLUMBING SANITARY ISOMETRIC RISER DIAGRAM
 INDICATING ALL WASTE, VENTS, TRAPS AND SIZES WITH
 CLEANOUT LOCATIONS OF THE PROPOSED RELOCATED WATER
 CLOSET AND SHOWER.
  
 3. PER FBC PLUMBING TABLE 403.1 MINIMUM NUMBER OF
 REQUIRED PLUMBING FIXTURES (R-3) ONE AND TWO FAMILY
 DWELLINGS: PLEASE CLEARLY INDICATE THAT THERE IS AN
 EXISTING OR A NEW, 1 AUTOMATIC CLOTHES WASHER
 CONNECTOR.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-21 Cont ID  
Sent By choops Date 2008-02-21 Time 09:56 Rev Time 0.00
Received By choops Date 2008-02-21 Time 09:56 Sent To E
Notes
2008-02-21 09:57:27***APPROVED - RESUB #1 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT (DP OUT)

Review Stop Z ZONING
Rev No 1 Status P Date 2008-01-22 Cont ID  
Sent By choops Date 2008-01-22 Time 10:11 Rev Time 0.00
Received By choops Date 2008-01-22 Time 10:11 Sent To M
Notes
2008-01-22 10:11:51***APPROVED***
  
 INTERIOR WORK, SLAB IN REAR.