Plan Review Details - Permit 08010387
Plan Review Stops For Permit 08010387
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-06-19 Cont ID  
Sent By shill Date 2008-06-19 Time 15:35 Rev Time 0.00
Received By shill Date 2008-06-19 Time 15:35 Sent To  
Notes
2008-06-19 15:40:41****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
 1.HAVE THE DESIGNER OF RECORD REVIEW THE NEW CURB
 DETAIL.
  
 NOTE - NO FEE TO RESUBMIT (NO CODE REVIEW).NOTED IN
 FRONT SCREEN.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-19 Cont ID  
Sent By shill Date 2008-06-19 Time 15:34 Rev Time 0.00
Received By shill Date 2008-06-19 Time 15:34 Sent To  
Notes
2008-06-19 15:35:25FLASHING CONNECTOR DETAIL OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2008-06-04 Cont ID  
Sent By shill Date 2008-06-04 Time 16:19 Rev Time 0.00
Received By shill Date 2008-06-04 Time 16:18 Sent To  
Notes
2008-06-04 16:19:27REVISION OK, FASCIA DETAIL DATED 5/30/8

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 16:19 Rev Time 0.00
Received By shill Date 2008-05-08 Time 16:19 Sent To  
Notes
2008-05-08 16:23:17PROVISO - REVISE A3 ROOF PRESSURES
 SEPARATE PERMIT ROOF, NOA 06-0626.11, INSULATION
 07-0516.03

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status F Date 2008-05-08 Cont ID  
Sent By shill Date 2008-05-08 Time 16:14 Rev Time 0.00
Received By shill Date 2008-05-08 Time 15:31 Sent To  
Notes
2008-05-08 16:19:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.SEE PREVIOUS LIST REGARDING ROOF PRESSURES.SEE
 FBC TABLE 1609.6.2.1(2).ROOF PRESSURES DECLARED ARE
 IN THE 30S; ZONE 3 IS MINIMUM OF -89PSF.

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-05-01 Cont ID  
Sent By shill Date 2008-05-01 Time 16:52 Rev Time 0.00
Received By shill Date 2008-05-01 Time 15:17 Sent To  
Notes
2008-05-01 16:54:37****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 COMMENTS FROM PREVIOUS LIST:
  
 2B, 3.SHEET A2 WAS REVISED TO CORRECTLY STATE MIXED
 OCCUPANCY BUT SHEET A1 STILL STATES SINGLE OCCUPANCY
 MERCANTILE.PLEASE CORRELATE.
  
 4-8. ADDRESSED.
  
 9. ARCHITECT'S RESPONSE THAT LIGHT POLE CALCS WILL BE
 SUBMITTED IS ACKNOWLEDGED.THIS WILL BE A PROVISO
 ITEM.
  
 10-13. ADDRESSED.
  
 14. A5 AND ARCHITECT'S RESPONSE INDICATE THAT A NEW
 ROOF WILL BE INSTALLED.SEE SHEET A3, ROOF PLAN.ROOF
 DESIGN PRESSURES WERE DECLARED AS FOLLOWS; -27.4 FOR
 ZONE 1, -25 PSF FOR ZONE 2, -38.2 FOR ZONE 3.PROVIDE
 CALCULATIONS AS THESE PRESSURES ARE TOO LOW.ALSO
 EXPLAIN THE LOGIC OF A DESIGN PRESSURE LOWER IN ZONE 1
 THAN ZONE 2.SEE FBC 1609.
  
 15-17. ADDRESSED.
  
 18.ENERGY CALCS SHOW 8187 SF OF CARPET WITH A RUBBER
 PAD, PLANS SHOW TILE.INSULATION ON THE ENERGY CALC
 FOR ROOF IS SHOWN AS 15.4, PLANS SHOW R12.WITH THE
 RESUBMITTAL, PROVIDE ROOF INSULATION SPECIFICATIONS
 SHOWING R VALUE AND MANUFACTURER.
  
 NEW COMMENTS:
  
 19.OLD SHEETS AND ENERGY CALCS WERE NOT SUBMITTED.
 PLEASE PROVIDE.THEY ARE REQUIRED FOR REFERENCE.
 CHANGES TO THE PLAN SHOULD ALWAYS BE CLOUDED AND MARKED
 WITH A REVISION NUMBER AND OLD SHEETS SUBMITTED FOR
 REFERENCE, SEE FIRST CORRECTION LISTS (DEWEY PALMER AND
 JIM WITMER).
  
 20.THE OCCUPANT LOAD INCLUDES ONLY THE SALES AREA.
 SEE FBC1004.1, OCCUPANT LOAD IS TO BE BASED ON THE
 GREATER OF DESIGN LOAD OR THE OCCUPANT LOAD BASED ON
 SQUARE FOOT AREA AND FBC TABLE 1004.1.2.REVISE
 OCCUPANT LOAD TO INCLUDE ENTIRE BUILDING.
  
 21.MECHANICAL STANDS REQUIRE PRODUCT APPROVAL,
 FAC9B72, SEE SHEET A3.
  
 22.8INCHES IS SPECIFIED FROM THE BOTTOM OF THE A/C
 UNIT TO THE ROOF.SEE FBC1509.7 AND REVISE
 ACCORDINGLY.INCLUDE DIMENSIONS OF THE UNIT.SHEET
 A3.
  
 23.A STAND IS SHOWN ON SHEET A3 WHICH CONFLICTS WITH
 THE ROOF CURB SPECIFIED ON AC1.PLEASE CORRELATE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-04 Cont ID  
Sent By shill Date 2008-04-04 Time 10:28 Rev Time 0.00
Received By shill Date 2008-04-04 Time 07:48 Sent To  
Notes
2008-04-04 10:28:45****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 2B, MERCANTILE SINGLE OCCUPANCY DECLARED.SEE ALSO
 ITEM 3 FROM THE PREVIOUS LIST.THIS IS A MIXED USE AND
 MUST BE DECLARED AS SUCH AS THE WAREHOUSE (S1) AREA IS
 OVER 10%, FBC302.2.
  
 THE 1 HOUR WALL IS SHOWN, BUT NO FIRE RESISTANCE RATING
 REQUIREMENTS ARE SHOWN FOR THE DOORS IN THE 1 HOUR
 OCCUPANCY SEPARATION WALL.PLEASE STATE DESIGN
 CRITERIA, FBC715.3.
  
 3. DECLARE MIXED USE AS THE S1 AREA IS NOT LESS THAN
 10% OF THE STORY, FBC302.2.
  
 4. THE RESPONSE LETTER STATES THAT THERE IS NO STORAGE
 OF HAZARDOUS MATERIALS.PLEASE NOTE ON THE PLAN.
  
 5.THE FIRST COMMENT LIST STATED ?THE PLANS INDICATE
 THIS IS TO BE A MERCANTILE TYPE BUSINESS BUT THERE IS
 NOT INFORMATION ON THE INTERIOR TO INDICATE COMPLIANCE
 WITH 11-7, PLANS ARE NOT COMPLETE.?ARCHITECT?S
 RESPONSE WAS ?ALL ITEMS SHOWN ON PLAN ARE CASEWORK AND
 RACKS FOR CLOTHES, TOYS, NOVELTIES, ETC.?IF THIS IS A
 DOLLAR STORE AS STATE, THERE SHOULD BE A PLACE FOR
 CHECKOUT.PLEASE SEE FBC11-7 AND SHOW COMPLIANCE WITH
 ALL REQUIREMENTS ON THE PLAN.
  
 6-8. ADDRESSED OR INCLUDED IN OTHER COMMENTS.
  
 9. ARCHITECT?S RESPONSE THAT LIGHT POLE CALCS WILL BE
 SUBMITTED IS ACKNOWLEDGED.THIS WILL BE A PROVISO
 ITEM.
  
 NEW COMMENTS:
  
 10. AS DRAWN, THE DUMPSTER GATE ENCROACHES THE PROPERTY
 LINE WHEN IN THE FULLY OPEN POSITION.SEE FBC3202.2.
  
 11. THE 1 HOUR PARTITION DETAIL ON A5 DOES NOT SHOW THE
 NEW CEILING.SIGNAGE REQUIRED ABOVE THE CEILING,
 FBC712.5.
  
 12. ONE AISLE SHOWS A COLUMN IN THE MIDDLE, SEE
 FBC11-4.3.3.OTHER AISLES SHOW A COLUMN IN THE AISLE,
 BUT DOES NOT PROVIDE A DIMENSION SHOWING DISTANCE FROM
 THE SHELF.IT IS NOT CLEAR WHETHER THE 36IN MINIMUM IS
 MET.WITH THE EXCEPTION OF THE COLUMN IN THE MIDDLE OF
 THE AISLE, THIS COMMENT CAN BE ADDRESSED WITH A GENERAL
 NOTE.
  
 13. SEE F1, LEFT SIDE OF PLAN, CENTER.THE AREA WHICH
 APPEARS TO BE THE CASHIER AREA IS TO BE DESIGNED SO
 THAT INDIVIDUALS WITH DISABILITIES CAN APPROACH, ENTER,
 AND EXIT THE WORK AREA.SEE FBC11-4.1.1(3),
 FBC11-4.1.6(1)(B).
  
 14. ROOF PRODUCT APPROVALS SUBMITTED.PLEASE CLARIFY,
 PREFERABLY ON THE ROOF FRAMING PLAN WHERE ROOF WORK
 WILL BE DONE. DETAIL 8S3 SHOWS EXISTING ROOF DECK TO
 REMAIN.THE ROOF PRODUCT APPROVAL IS INCOMPLETE, LAST
 PAGE REQUIRED TO DETERMINE LIMITATIONS.ENHANCED
 FASTENING NOT SUBMITTED.THIS MAY BE DONE BY THE
 ROOFING CONTRACTOR AT THE TIME OF ROOF PERMIT
 APPLICATION, BUT FIRST PLEASE CLARIFY ROOF WORK TO BE
 PERFORMED UNDER THE SCOPE OF THIS PERMIT.
  
 15. SIGN THE OWNER/AGENT LINE OF THE ENERGY CALC,
 FBC13-103.1.
  
 16. SEE SHEET AC1, NO FIRE DAMPERS SHOWN AT PENETRATION
 THROUGH THE RATED WALL, FBC712.
  
 17. SHOW REQUIRED DETECTABLE WARNINGS, FBC11-4.29.5.
  
 18.THE DOORS ON THE ENERGY CALCS DO NOT MATCH THE
 PLAN.PLEASE CONFIRM ALL BUILDING COMPONENTS AS I ONLY
 SPOT CHECK ENERGY CALCS.THIS MAY NOT BE AN EXHAUSTIVE
 LIST.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-26 Cont ID  
Sent By jwitmer Date 2008-01-26 Time 19:05 Rev Time 0.00
Received By kdfreema Date 2008-03-13 Time 13:11 Sent To  
Notes
2008-01-26 19:18:02BUILDING PLAN REVIEW
 PERMIT: 08010387
 ADD: 4700 BROADWAY
 CONT: HALLMARK & SONS
 TEL: (561)644-3498
 JAN.26,2008
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE. NOTE ONLY ONE SET OF PLANS ARE IN
 THE PACKAGE!
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS, SHEET A-2 IS
 MISSING THE SUPPLEMENTS .
  
 2) SHEET A-2CODE SUMMARY PLEAE CORRECTTHE FOLLOWING
 INFORMATION OR MISSING INFORMATION.110.2* W. P. B.
 ADMINISTRATIVE CODE, INFORMATION THAT IS REQUIRED FOR
 RECORD KEEPING & FOR CERTIFICATE OF OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3. PLANS INDICATE OCCUPANCY CLASS
 FOR MERCANTILE AS "B" PLEASE CORRECT.
 C) THE TYPE OF CONSTRUCTION AS DEFINEDIN CHAPTER 6,
 TABLE 601. THE BUILDING CLASIFICATION IS FROM THE 2001
 FBC PLEASE UPDATE.
 D) THE OCCUPANT LOAD, SEE 1004.
 E) IF AN AUTOMATIC SPRINKLER SYSTEM IS PROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 .
 3)PLEASE PROVIDE SQ FT AREA FOR MERCANTILE AREA AS
 WELL AS THE WAREHOUSE TO SEE IF WAREHOUSE MEETS THE
 REQUIREMENTS OF A ACCESSORY USE AREA(302.3) NOT
 REQUIRING A FIRE RATED WALL. PLEASE PORVIDE
 CALCULATIONS. SHEETA-5 HAS A DETAIL# 4OF A 1 HR RATED
 WALL BUT THE FLOOR PLAN DOES NOT INDICATE WALL
 RATINGS?
  
 4) THE PERMIT PACKAGE SET OF DOCUMENTS ARE MORE OF A
 SHELL PERMIT THAN AN AN INTERIOR AND EXTERIOR
 RENOVATION PERMIT. SHEET A-2 DOES NOT PROVIDE ANY
 INTERIOR AISLES , CASE WORK OR REFRIGARATED UNITS,
 ADDITIONAL INFORMATION WILL BE REQUIRED FOR THE
 INTERIOR? SECTION 803.1, TABLE 803.5.
  
 5) THE PLANS INDICATE THIS IS TO BE A MERCANTILE TYPE
 BUSINESS BUT THERE IS NO INFORMATION ON THE INTERIOR TO
 INDICATE COMPLIANCE WITH 11-7, PLANS ARE NOT COMPLETE.
  
 6)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) HOLLOW METAL EXTERIOR DOORS
 B)STOREFRONT WINDOWS- MISSING FLORIDA COVERSHEET,
 MISSING MIAMI-DADE COVERSHEET AND SHEET E-2
 C)GLAZED EXTERIOR DOOR- MISSING FLORIDA COVERSHEET
 D) ROOFING REPORT DID NOT HIGHLIGHT WHICH SUB-SYSTEM
 THAT WILL BE INSTALLED, NOTE PRESSURES ,ANDLIMITAION
 EITHER 7 OR 9.
 E) HURRICANE RAFTER STRAPS- A-3 ANCHORING EQUIPMENT TO
 ROOF
  
 7)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 8)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 9) SHEET E-1 INDICATES THE USE OF LIGHT POLES SUBMIT
 CALCULATIONS FOR POLES AND FIXTURES FOR 140 WIND SPEED.
 1609.
  
 NOTE!!! A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME,
 AS A RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2008-04-16 Time 14:13 Sent To  
Notes
2008-04-16 14:15:47REDLINED THE INPUT DATA REPORT ON THE ENERGY
 CALCULATIONS AS THE METHOD OF CONTROL FOR LIGHTING
 STATES "MANUAL ON/OFF" YET THE CONTROLS AS REQUIRED BY
 CODE AND AS SHOWN ON PLANS IS "AUTOMATED" WITH
 SCHEDULING.
  
 REVISED CALCULATIONS WILL BE NEEDED BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-17 Cont ID  
Sent By dpalmer Date 2008-03-17 Time 08:52 Rev Time 0.00
Received By dpalmer Date 2008-03-17 Time 08:52 Sent To  
Notes
2008-03-17 08:52:48** DENIED2ND REVIEW**
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 REVIEW WHICH STILL NEED TO BE ADDRESSED.
  
  
 1) NOTE:PLEASE SEE PREVIOUS REVIEW NOTES WITH RESPECT
 TO RELEVANT CODES. PLEASE SEE SHEET A-2 WHICH STATES A
 2004 NFPA-70.
 PLEASE SEE FBC 2004W/2007 WHICH ADOPTS THE 2005
 NFPA-70.
 PLEASE ADJUST.
  
 2) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 ARE NOT AN ADOPTED VERSION PER FBC 13-400.3.B. THIS WAS
 CONFIRMED PREVIOUSLY WITH MO MADANI FROM DEPARTMENT OF
 COMMUNITY AFFAIRS THAT ONLY THE VERSION AS STATED IN
 SECTION NOTED IS ACCEPTABLE WHICH IS 2.5.
  
 3) NOTE: PLEASE SEE ENERGY CALCULATIONS SUBMITTED WHICH
 CONTAINS A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE
 WHICH IS NOT PERMITTED BY FS 481.221.
 PLEASE SEE THE PREVIOUS REVIEW STATED TO SUBMIT SIGNED
 AND SEALED AS REQUIRED.
 **MAY NOT PLACE A RAISED SEAL OVER PHOTO-COPIED
 SIGNATURE. ONE SET HAS BEEN RETAINED BY THIS OFFICE.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED
 DO NOT CORRELATE WITH PLANS.
 A) PLEASE SEE CONTROLS ARE NOTED AS *MANUAL ON/OFF *
 WHICH IS NOT POSSIBLE WHEN PLANS SHOW AUTOMATED
 CONTROLS
 B) PLEASE SEE THE WATTAGE ON FIXTURES ON CALCULATIONS
 DO NOT CORRELATE WITH THE FIXTURES ON FIXTURE LEGEND OR
 THE COUNT OF FIXTURES ON PLANS.
 FOR EXAMPLE: PLEASE SEE FIXTURES B AND BE WHICH ARE
 NOTED MODEL WITH 2-32 BULBS YET THE NUMBER OF LAMPS ARE
 NOTED AS 4-32W? IN EITHER CASE THESE DO NOT CORRELATE.
 FOR EXAMPLE: THE IDR NOTES 5-51W FIXTURES IN SALES AREA
 YET ONLY TWO TYPE *B* FIXTURES ARE LOCATED IN THIS
 SPACE.
 C) PLEASE SUBMIT FIXTURE INFORMATION/SPEC SHEET FOR
 PROPOSED FIXTURES.THIS OFFICE IS AWARE OF BALLAST
 EFFICIENCIES HOWEVER COULD NOT LOCATE THE MODEL AS
 NOTED.
 D) PLEASE SEE THE IDR AS THERE IS NOT WATER HEATER
 SHOWN, HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY SHOW
 ELECTRICAL WATER HEATER? 13-412.1.ABC.3.4
 PLEASE GO OVER ALL LIGHTING AND BE SURE THE IDR
 COORDINATES WITH THE PLANS.
 13-415.1.B, 13-415.2 ETC
  
 5) NOTE: PLEASE SEE THE ENERGY CALCULATIONS PERFORMANCE
 INFORMATION ON SHEET E-4 SHOWS A RETAIL VALUE OF 1.5,
 HOWEVER PLEASE SEE 2004 FBC WITH CURRENT SUPPLEMENTS
 WHICH 13-415.2.B WHICH SHOWS 1.7 FOR RETAIL.
 PLEASE ADJUST.
  
 6) NOTE: PLEASE SEE FEEDER SCHEDULE SHOWS *EQUIPMENT
 GROUNDING CONDUCTORS* BEFORE THE FIRST MEANS OF
 DISCONNECT FOR ALL THREE MAINS WHICH IS NOT PERMITTED.
 250.6, 250.24.
 PLEASE REMOVE.
  
 7) NOTE: PLEASE CORRELATE SERVICE ENTRANCE CONDUCTORS
 FOR MAIN PANEL *A* WHICH SHOWS 3/0 ON PANEL AND 4/0 ON
 RISER CONDUCTOR SCHEDULE.
  
 8) NOTE: PLEASE PROVIDE MORE DETAIL FOR LIGHTING
 CONTROLS.
 A) PLEASE SEE THE EXTERIOR LIGHTS ARE NOTED ON A TIME
 CLOCK HOWEVER IS THIS AN ASTRONOMICAL TIME CLOCK WITH
 10HR MINIMUM BACK UP? 13-415.1.ABC.1.4
 B) PLEASE VERIFY THE STANDARD SP SWITCH IN WAREHOUSE
 WHICH IS REQUIRED TO BE AN OVER RIDE PER
 13-415.1.ABC.1.1, .1.2.
 HOW DOES THIS SP WORK AS AN OVER RIDE?
  
 9) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. THIS IS ONLY A
 NOTICE GIVEN AT THIS TIME.
  
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 15:32 Sent To  
Notes
2008-01-24 15:32:17 
  
 ** DENIEDREVIEW **
  
  
 ** PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS DOWN THE
 LEFT HAND SIDE OF PLANS.
 THESE SHOULD BE PLACED INTO SEPARATE FOLDERS/BINDERS OR
 SOME OTHER FASHION.
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 PLACED ON ELECTRICAL PLANS FOR RELEVANT DESIGN.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70 (DONE)
 2003 NFPA-101
 2002 NFPA-72 (WHEN APPLICABLE).
  
 2) NOTE: PLEASE SEE THE REQUIRED ENERGY CALCULATIONS
 SUBMITTED ARE NOT SIGNED, DATED OR SEALED ON
 CERTIFICATION SHEETS AS REQUIRED PER FBC 13-103.1.1.1,
 FAC 61G15-23.002, FS 481.221, FS 471.025.
 PLEASE SEE THE SETS SUBMITTED ARE PHOTO-COPIES.
  
 3) NOTE: PLEASE SUBMIT INFORMATION ON HOW THE METHOD
 *A* IS BEING USED ON AN EXISTING BUILDING WHICH MEETS
 THE DEFINITION OF RENOVATIONS PER 13-101.1.3.
 THE CODE REQUIRES *B* OR *C*.
 PLEASE BE SURE ALL LIGHTING AS SHOWN ON PLANS
 COORDINATES WITH THE ELECTRICAL ON THE INPUT DATA
 REPORT.
  
 4) NOTE:PLEASE BE SURE ALL LIGHT FIXTURES SHOWN ON
 PLANS CONTAIN FIXTURE DESIGNATIONS.FOR EXAMPLE:
 PLEASE SEE REAR WAREHOUSE AREA WHICH SEEMS NOT TO SHOW
 ANY FIXTURE DESIGNATIONS.
 PLEASE CLARIFY HOW THE WATTAGE ON INPUT DATA REPORT
 SHOWS VA AT 102 FOR FIXTURES WITH 4-32W BULBS. PLEASE
 CONFIRM THE BALLAST/OUTPUT VA A RATING IS BEING USED AS
 REQUIRED PER 13-415.2.ABC.1.2
 PLEASE SEE MANY OF THESE FIXTURES ON IDR INDICATE
 COMPACT FLUORESCENT HOWEVER BASED ON FIXTURE LEGEND
 THIS IS NOT THE CASE.
 PLEASE BE SURE TO COORDINATE ALL.
 13-415.2
  
 5) NOTE: PLEASE SUBMIT ANY WIND LOAD CALCULATIONS FOR
 BUILDING REVIEW FOR OUTDOOR LIGHT POLES. PLEASE BE SURE
 THE EFFECTIVE PROJECTED AREA (EPA) IS SHOWN FOR
 PROPOSED FIXTURES.
 THIS IS ONLY NOTED AS THIS WILL BE PART OF BUILDING
 REVIEW.
  
 6) NOTE:PLEASE VERIFY THE GROUNDING ELECTRODES AS
 SHOWN ON PLANS.
 PLEASE SEE RISER SHOWS *STRUCTURAL STEEL* AS ON OF THE
 GROUNDING ELECTRODES. IF SHOWN, THEN THIS WILL BE
 REQUIRED.
 250.50
  
 7) NOTE: PLEASE SEE RISER NEEDS TO LABEL AND INDICATE
 ALL MAINS PER 230.2E (MAIN 1OF 3, 2 OF 3 ETC
  
 8) NOTE: PLEASE SEE 230.72 AS ALL MAINS ARE REQUIRED TO
 BE GROUPED. PLANS ONLY SHOW THE LOCATION OF THE PANEL
 *A* AND *B*. RISER SHOWS A/C MAINS BEING NEMA 3R WHICH
 IS BEING *ASSUMED* AS BEING OUTSIDE AND SHOWS PANEL *A*
 AS BEING NEMA 1 WHICH IS AN INDOOR RATED PIECE OF
 EQUIPMENT. THIS WOULD LEND TO THE FACT MAINS ARE NOT
 GROUPED AS NEEDED.
 PLEASE ALSO SEE POWER PLANS DO NOT SHOW LOCATIONS.
 240.24, 110.26, 230.72 ETC
 FBC ADMIN SECTION 106.3.5.1.2
  
 9) NOTE: PLEASE SEE RISER SHOWS MAIN ON PANEL *A* AS
 225AMPS, YET THE PANEL SCHEDULE ONLY SHOWS 200AMPS MAIN
 CIRCUIT BREAKER.
 PLEASE ALSO SEE THE SERVICE ENTRANCE CONDUCTORS FOR
 THIS SAME PANEL IS NOTED AS FEEDERS WHICH CAN NOTBE.
 PLEASE SEE THE SERVICE ENTRANCE CONDUCTORS ON PANEL *A*
 SCHEDULE SHOWS 3/0 WHICH ARE ONLY RATED FOR 200AMPS PER
 310.16, 110.14, 240.4 AND THE RISER SHOWS 4/0.
 PLEASE KNOW IF THE MAIN IS GOING TO BE 225AMPS, THE 4/0
 CONDUCTOR ARE RATED.
 PLEASE COORDINATE ALL OF THE ABOVE.
 240.4, 230.70, 310.16 ETC
 FBC 106.3.5.1.2, 106.1.2 ADMIN SECTION.
  
 10) NOTE: PLEASE SEE ALL CONDUITS TAPPED FROM THE
 GUTTER INDICATING AN EQUIPMENT GROUNDING CONDUCTOR
 BEFORE THE FIRST MEANS OF DISCONNECT WHICH IS NOT
 PERMITTED.
 PLEASE SEE 250.6, 250.24 AS THIS WOULD CREATE
 OBJECTIONABLE CURRENTS.
  
 ** PLEASE KNOW AS SOME INFORMATION WILL CHANGE, REVIEW
 FOR ALL ITEMS CAN NOT BE DONE AT THIS TIME.
 CHANGES MAY GENERATE NEW COMMENTS.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 3 Status N Date 2008-05-09 Cont ID  
Sent By rchokshi Date 2008-05-09 Time 10:54 Rev Time 0.00
Received By rchokshi Date 2008-05-09 Time 10:54 Sent To FIRE
Notes
2008-05-09 11:01:20CONTRACTOR HALLMARK & SONS INC.'S , LATTER DATED MAY 8,
 08 ALSO STATES THERE IS NO CHANGES MADEFOR
 ENGINEERING PLAN TO REVIEW.I LOOKED AT NO CHANGES ON
 ENG PLANS. THEREFORE, NO ENG REVIEW REQUIRED FOR THIS
 TIME.
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status P Date 2008-03-18 Cont ID  
Sent By rchokshi Date 2008-03-18 Time 08:46 Rev Time 0.00
Received By rchokshi Date 2008-03-18 Time 08:45 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By rchokshi Date 2008-01-18 Time 14:21 Rev Time 0.00
Received By rchokshi Date 2008-01-18 Time 14:15 Sent To  
Notes
2008-01-18 14:21:54FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 2. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 3. DUMPSTER & ITS ENCLOSURE DETAILS PER CITY OF WPB, &
 LOCATION MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-05-12 Cont ID  
Sent By mawillia Date 2008-05-12 Time 11:03 Rev Time 0.00
Received By mawillia Date 2008-05-12 Time 10:50 Sent To B1
Notes
2008-05-12 11:00:33*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A-2, F-1, AND E-3 WERE
 STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-05-02 Cont ID  
Sent By mawillia Date 2008-05-02 Time 15:01 Rev Time 0.00
Received By mawillia Date 2008-05-02 Time 14:38 Sent To  
Notes
2008-05-02 14:47:55*****PROVISO*****
  
 1.SHOW THE LOCATION OF THE 2A10BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 2.SPECIFY THE INTERIOR FINISH MATERIALS FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 WHEN THE ABOVE ITEMS AS WELL AS THE OTHER REVIEWERS
 COMMENTS HAVE BEEN ADDRESSED, THE APPROPIATE SHEETS TO
 BE FIRE-STAMPED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By mawillia Date 2008-04-03 Time 11:23 Rev Time 0.00
Received By mawillia Date 2008-04-03 Time 10:48 Sent To  
Notes
2008-04-03 10:52:35*****PROVISO*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED, HOWEVER THE APPROPIATE PLAN SHEET(S) TO
 BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN
 SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-22 Cont ID  
Sent By mwennerg Date 2008-02-22 Time 09:59 Rev Time 0.00
Received By mwennerg Date 2008-02-22 Time 09:59 Sent To  
Notes
2008-02-22 10:07:26***DENIED***
  
 1) DOORS PROVIDED WITH PANIC HARDWARE SHALL NOT BE
 EQUIPPED WITH ANY LOCKING DEVICE THAT PREVENTS RELEASE
 OF THE LATCH FROM THE EGRESS SIDE. NFPA 101, SECTION
 7.2.1.7.3.
  
 2) IN ADDITION TO THE HEIGHT REQUIREMENT, ADDRESS
 CHARACTERS SHALL BE MINIMUM OF 1" IN WIDTH AND
 CONTRASTING WITH THE BACKGROUND FOR VISIBILITY. SHT
 A-3
  
 3) CLEARLY IDENTIFY THE LOCATIONS OF EMERGENCY LIGHTING
 FACILITIES THAT ARE REQUIRED.
  
 4) EXIT SIGNS SHALL NOT BE GREATER THAN 100' APART AND
 ARE TO BE VISIBLE AND OBVIOUS FROM ALL POINTS OF THE
 MEANS OF EGRESS..
  
 5) PROVIDE MINIMUM INTERIOR FINISH CLASSIFICATION FOR
 WALLS AND CEILING.
  
 6) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-09-12 Cont ID  
Sent By adarroug Date 2008-09-12 Time 13:00 Rev Time 0.00
Received By adarroug Date 2008-09-12 Time 13:00 Sent To M
Notes
2008-09-12 13:01:13TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-13 Cont ID  
Sent By adarroug Date 2008-06-13 Time 14:16 Rev Time 0.00
Received By shill Date 2008-06-13 Time 14:16 Sent To M
Notes
2008-06-19 11:54:15TO TG DESK
  
2008-06-13 14:17:12TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 11:02 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 11:02 Sent To B
Notes
2008-06-03 11:02:48TO "SHILL" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-06 Cont ID  
Sent By adarroug Date 2008-05-06 Time 09:51 Rev Time 0.00
Received By adarroug Date 2008-05-06 Time 09:51 Sent To  
Notes
2008-05-06 09:54:20TO "COMM" BD#19

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-04-11 Cont ID  
Sent By adarroug Date 2008-04-11 Time 14:22 Rev Time 0.00
Received By adarroug Date 2008-04-11 Time 14:22 Sent To  
Notes
2008-04-11 14:29:06TO "COMM" BD#28

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 11:02 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 11:02 Sent To  
Notes
2008-03-06 11:02:44TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-22 Cont ID  
Sent By mwennerg Date 2008-02-22 Time 10:09 Rev Time 0.00
Received By mwennerg Date 2008-01-17 Time 16:11 Sent To  
Notes
2008-01-17 16:15:53TO "COMM" BD#35

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-09-15 Cont ID  
Sent By tgordon Date 2008-09-15 Time 09:01 Rev Time 0.30
Received By tgordon Date 2008-09-15 Time 09:01 Sent To  
Notes
2008-09-15 09:02:40REVISION TO MECH. PLAN AC-1.

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-06-19 Cont ID  
Sent By tgordon Date 2008-06-19 Time 12:15 Rev Time 0.20
Received By tgordon Date 2008-06-19 Time 12:15 Sent To B
Notes
2008-06-19 12:17:19SUBMITTED ENGINEERING FOR A/C ROOF CURB.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By tgordon Date 2008-04-15 Time 13:29 Rev Time 0.30
Received By tgordon Date 2008-04-15 Time 13:29 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-07 Cont ID  
Sent By tgordon Date 2008-03-07 Time 08:36 Rev Time 0.45
Received By tgordon Date 2008-03-07 Time 08:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By tgordon Date 2008-01-29 Time 13:45 Rev Time 0.30
Received By tgordon Date 2008-01-29 Time 13:45 Sent To  
Notes
2008-01-29 13:46:54PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ELECTRICAL REVIEW NOTES 2 AND 3, PLEASE
 CORRECT.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-17 Cont ID  
Sent By mperson Date 2008-04-17 Time 15:03 Rev Time 0.00
Received By mperson Date 2008-04-17 Time 15:03 Sent To  
Notes
2008-04-17 15:07:26****************PROVISO****************
 THE FULL-OPEN SHUT OFF VALVE SHALL BE INSTALLED BEFORE
 THE THERMAL CONTROL EXPANSION TANK. PER FBC PLUMBING
 SECTION 606.2(3).
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-10 Cont ID  
Sent By mperson Date 2008-03-10 Time 10:08 Rev Time 0.00
Received By mperson Date 2008-03-10 Time 10:07 Sent To  
Notes
2008-03-10 10:34:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOS PLUMBING REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. SEE ELECTRICAL REVIEW NOTES #2 AND #3 CONCERNING
 ENERGY CALCULATIONS, PLEASE CORRECT. ALSO THE NEW
 ELECTRIC WATER HEATER NEEDS TO COMPLY PER TABLE
 *13-412.1.ABC.3 AND HOT WATER PIPE INSULATION PER TABLE
 *611.1.ABC.1 ON THE RESUBMITTAL.
  
 **COMMENT RESPONSE NOTED FROM ARCHITECT TO SEE
 ENGINEERING, HOWEVER THERE IS NO COMMENT RESPONSE FROM
 ENGINEERING FOR PLUMBING. COMMENT WAS NOT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
  
 3. SHEET P-1 WASTE RISER AND PARTIAL PLUMBING PLAN:
 WATER CLOSETS REQUIRE A VENT. PER FBC PLUMBING, SECTION
 *901.2.1 VENTING REQUIRED.
  
 **COMMENT RESPONSE NOTED FROM ARCHITECT TO SEE
 ENGINEERING, HOWEVER THERE IS NO COMMENT RESPONSE FROM
 ENGINEERING FOR PLUMBING. COMMENT WAS NOT ADDRESSED.
  
 4. *NEW COMMENT* SHEET P-2 DETAIL A, THE WATER HEATER
 NEEDS PROTECTION FROM THERMAL EXPANSION CONTROL. PER
 FBC PLUMBING SECTION 607.3 AND 607.3.2 .
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By mperson Date 2008-02-12 Time 13:15 Rev Time 0.00
Received By mperson Date 2008-02-12 Time 13:15 Sent To  
Notes
2008-02-12 13:38:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SEE ELECTRICAL REVIEW NOTES #2 AND #3 CONCERNING
 ENERGY CALCULATIONS, PLEASE CORRECT. ALSO THE NEW
 ELECTRIC WATER HEATER NEEDS TO COMPLY PER TABLE
 *13-612.1.ABC.3.2 AND HOT WATER PIPE INSULATION PER
 TABLE *611.1.ABC.1 ON THE RESUBMITTAL.
  
 2. SHEET A-2 TYPICAL ADA TOILET: AN ELEVATION DETAIL
 OF THE FOLLOWING FIXTURES IS REQUIRED COMPLIANT WITH
 CHAPTER 11, FLORIDA ACCESSIBILITY CODE WITH THE
 FOLLOWING INFORMATION.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 **11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED WITH
 THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 3. SHEET P-1 WASTE RISER AND PARTIAL PLUMBING PLAN:
 WATER CLOSETS REQUIRE A VENT. PER FBC PLUMBING, SECTION
 *901.2.1 VENTING REQUIRED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 4 Status P Date 2008-05-07 Cont ID  
Sent By kdfreema Date 2008-05-07 Time 11:57 Rev Time 0.00
Received By kdfreema Date 2008-05-07 Time 11:57 Sent To  
Notes
2008-05-07 11:58:21ZONING PROVISO:
  
 1. THE PYGMY DATE PALM SHALL BE REPLACED WITH A
 GROUPING OF THREE (3) SABAL PALMS WITH UNDERPLANTING AT
 THE BASE.
 2. IRRIGATION SHALL BE INSTALLED IN THE RIGHT-OF-WAY
 ALONG THE SOUTH SIDE OF THE BUILDING. THE SOD SHALL BE
 REPLACED IF IT IS IN A POOR OR WEED-INFESTED
 CONDITION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-04-21 Cont ID  
Sent By kdfreema Date 2008-04-21 Time 10:47 Rev Time 0.00
Received By kdfreema Date 2008-04-21 Time 10:47 Sent To  
Notes
2008-04-21 10:48:35ZONING PROVISO:
  
 1. THE PYGMY DATE PALM SHALL BE REPLACED WITH A
 GROUPING OF THREE (3) SABAL PALMS WITH UNDERPLANTING AT
 THE BASE.
 2. IRRIGATION SHALL BE INSTALLED IN THE RIGHT-OF-WAY
 ALONG THE SOUTH SIDE OF THE BUILDING. THE SOD SHALL BE
 REPLACED IF IT IS IN A POOR OR WEED-INFESTED
 CONDITION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-13 Cont ID  
Sent By kdfreema Date 2008-03-13 Time 13:12 Rev Time 0.00
Received By kdfreema Date 2008-03-13 Time 13:12 Sent To  
Notes
2008-03-13 13:12:20ZONING PROVISO:
  
 1. THE PYGMY DATE PALM SHALL BE REPLACED WITH A
 GROUPING OF THREE (3) SABAL PALMS WITH UNDERPLANTING AT
 THE BASE.
 2. IRRIGATION SHALL BE INSTALLED IN THE RIGHT-OF-WAY
 ALONG THE SOUTH SIDE OF THE BUILDING. THE SOD SHALL BE
 REPLACED IF IT IS IN A POOR OR WEED-INFESTED
 CONDITION.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT 561-822-1435
 WITH QUESTIONS.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-29 Cont ID  
Sent By kdfreema Date 2008-01-29 Time 11:02 Rev Time 0.00
Received By kdfreema Date 2008-01-29 Time 11:02 Sent To  
Notes
2008-01-29 13:44:43***FAILED***
  
 1. PLEASE INCLUDE TWO COPIES OF A SIGNED AND SEALED
 SURVEY NO OLDER THAN 12 MONTHS.
  
 2. PLEASE CONTACT EMERY FABIAN, ENGINEERING SERVICES
 PROJECT COORDINATOR, AT 561-494-1040 REGARDING THE
 LOCATION OF THE DUMPSTER ENCLOSURE. IT APPEARS THERE
 MAY BE ACCESS ISSUES. PLEASE PROVIDE A SIGNOFF FROM HIM
 APPROVING THE FINAL LOCATION OF THE ENCLOSURE. NOTE
 THAT PER SEC. 94-221(D)(10) OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), THE DUMPSTER ENCLOSURE
 MUST BE CONSISTENT WITH THE ARCHITECTURE OF THE
 BUILDING.
  
 3. A 10 BY 25 FOOT LOADING ZONE IS REQUIRED. THIS CAN
 EASILY BE ACCOMODATED OUTSIDE THE SERVICE ENTRY AT THE
 REAR OF THE BUILDING.
  
 4. THE WINDOW DETAILS PROVIDED ARE NOT SUFFICIENTLY
 LEGIBLE. PLEASE NOTE THE REQUIREMENTS OF SEC.
 94-221(D)(6) OF THE ZLDRS AND ENSURE THAT ALL
 REQUIREMENTS ARE SATISFIED.
  
 5. REMOVE PARKING SPACE NO. 7. THE ZLDRS ALLOW A
 MAXIMUM OF 10 PARKING SPACES IN A SINGLE ROW WITHOUT
 AND LANDSCAPE ISLAND AND REQUIRES A MINIMUM 3 FOOT
 BACKOUT NOTCH FOR VEHICLES PARKED AT THE END OF TRAFFIC
 ROWS. THE REMOVAL OF SPACE NO. 7 WILL SATISFY BOTH OF
 THESE REQUIREMENTS.
  
 6. THE LANDSCAPE PLAN MUST BE SIGNED AND SEALED BY A
 REGISTERED LANDSCAPE ARCHITECT. PLEASE NOTE THE
 REQUIREMENTS OF SEC. 94-219(9) WITH RESPECT TO THE
 LANDSCAPING OF PARKING LOTS IN BMUD AS WELL AS ARTICLE
 XIV OF THE ZLDRS FOR GENERAL LANDSCAPING STANDARDS AS
 WELL AS THE REQUIREMENTS FOR LANDSCAPE PLANS.
  
 7. ALL LANDSCAPED AREAS DIRECTLY ABUTTING VEHICULAR
 CIRCULATION AREAS MUST BE PROTECTED BY MEANS OF WHEEL
 STOPS OR NON-MOUNTABLE D OR F CURBING. THE WHEELSTOP
 LAYOUT AS PROPOSED COMPLIES, BUT IT ISN'T CLEAR IF THE
 REMAINING AREA WILL BE CURBED OR OPEN.
  
 PLEASE CONTACT KELLY FREEMAN, PLANNER, AT
 [email protected] OR 561-822-1435 WITH QUESTIONS.