Plan Review Details - Permit 08010353
Plan Review Stops For Permit 08010353
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 16:28 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 16:28 Sent To PC
Notes
2008-01-18 16:28:38 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES SHALL
 BE STATED ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT MINIMUM PLANS/DRAWINGS SHOWING
 LOCATIONS OF NEW LIGHTING BEING INSTALLED.
 PLEASE SHOW CIRCUITING PER 700.12F.
 FBC 106.3.5.1.2
  
 3) NOTE: PLEASE DECLARE OCCUPANCY ON PLANS.
 FBC 106.1.2, 105.3, 106.1.1, 106.3.5.1.1
  
 4) NOTE: PLEASE BE SURE WHEN MEETING EXCEPTIONS OF FS
 481.229 OR 471.003 FOR PLANS BEING DONE BY DESIGN
 PROFESSIONALS ALL PLANS ARE REQUIRED TO CONTAIN THE
 PRINTED NAME AND SIGNATURE OF DESIGNER UNDER FS 468.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]