Plan Review Details - Permit 08010351
Plan Review Stops For Permit 08010351
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By mjacobs Date 2008-02-22 Time 11:21 Rev Time 0.00
Received By mjacobs Date 2008-02-22 Time 07:44 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By mjacobs Date 2008-01-22 Time 12:16 Rev Time 0.00
Received By mjacobs Date 2008-01-22 Time 08:04 Sent To  
Notes
2008-01-22 12:16:22 
 BUILDING PLAN REVIEW
 PERMIT: 08010351
 ADD: 846 SOUTHERN BLVD
 CONT: SOUTH EAST CONTRACTOR.
 TEL: (904)262-0588
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1)THE DRAWINGS INDICATES THE STOREFRONT WILL BE
 REDEVELOPED; CLEARLY INDICATE ON THE DRAWINGS THE AREAS
 WHERE THE WORK WILL BE DONE. IF ANY NEW STOREFRONT
 SYSTEM INCLUDING NEW STOREFRONT DOORS WILL BE
 INSTALLED, SUBMIT THE PRODUCT APPROVAL AND INDICATE THE
 ITEMS IN THE PACKAGE WHICH WILL BE USED. WPB AMENDMENTS
 106.1.2.
  
 2)SUBMIT AN EXISTING AND A PROPOSED FLOOR PLAN OF THE
 SPACE INDICATING CLEARLY ALL CHANGES, INCLUDING DEMO
 AREAS.
  
 3)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-29 Cont ID  
Sent By dpalmer Date 2008-02-29 Time 15:34 Rev Time 0.00
Received By dpalmer Date 2008-02-29 Time 15:34 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 16:15 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 16:15 Sent To  
Notes
2008-01-18 16:15:53 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING RELEVANT CODES SHALL
 BE STATED ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
  
 ** PLEASE SEE PLANS NOTE 2000 LS-101 AND 2001 FBC IN
 SOME LOCATIONS.
  
 2) NOTE: PLEASE SUBMIT COMPLETED LIGHTING PERFORMANCE
 CALCULATIONS FOR EXISTING AND NEW PROPOSED. MAY NOT ADD
 NEW LIGHTING UNLESS FALLING UNDER THE MAXIMUM
 ALLOWANCES PER 13-415.2.
  
 3) NOTE: PLEASE PROVIDE INFORMATION ON WEST EXISTING
 SPACE WHICH IS PART OF THE EXISTING STORE. HOW WILL THE
 EXISTING LIGHTING BE FED? HOW WILL THE MINIMUM SPACE
 LIGHTING MEET LS CODE WITHOUT ANYELECTRICAL BEING
 SHOWN TO THIS AREA.
 PLEASE KNOW THE SPACE WILL REQUIRE MINIMUM LIGHTING FOR
 LIFE SAFETY 101 7.8 AND 7.9
  
 4) NOTE: PLEASE SHOW WHAT CIRCUITS ON PANEL SCHEDULE
 ARE EXISTING AND WHICH ONES ARE NEW.
 408.4,
 FBC 106.1.2, 103.5.1.2 FOR ADDITIONAL INFORMATION.
  
 5) NOTE: PLEASE INDICATE ANY FIRE ALARMS HORNS AND
 STROBES IN COMPLIANCE WITH FBC 11-4.28.1,.2 AND .3(4).
 (WHERE APPLICABLE IF BUILDING CONTAINS FA PANEL/SYSTEM)
 ALREADY SHOWN AS FIRE SPRINKLED.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-22 Cont ID  
Sent By mwennerg Date 2008-02-22 Time 15:32 Rev Time 0.00
Received By mwennerg Date 2008-02-22 Time 15:32 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-28 Cont ID  
Sent By mawillia Date 2008-01-28 Time 16:30 Rev Time 0.00
Received By mawillia Date 2008-01-28 Time 15:47 Sent To  
Notes
2008-01-28 16:06:37*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.SUBMIT AN EXISTING FLOOR PLAN SO THAT COMPARITIVES
 MAY BE EXAMINED AGAINST PROPOSED FLOOR PLAN.
  
 3.PLEASE INDICATE IF THE BUILDING OR PORTIONS OF
 BUILDING WILL BE OCCUPIED DURING THE SCOPE OF WORK.IF
 SO, THIS SHALL BE PERMITTED ONLY WHERE REQUIRED MEANS
 OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN
 PLACE AND CONTINUOUSLY MAINTAINED.
  
 4.PLEASE INDICATE IF THE BUILDING HAS A FIRE ALARM
 SYSTEM.IF PROJECT SCOPE OF WORK HAS CAUSE FOR THE
 FIRE ALARM SYSTEM TO BE REMODELED, SEPARATE PLANS AND
 PERMIT WILL BE REQUIRED.
  
 5.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 6.SPECIFY THE NEW INTERIOR WALL FINISH MATERIALS IN
 TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 7.ON SHEET A-1 IN THE CAPTION FOR DOORS REGARDING
 EGRESS, ACCESSIBILITY, AND OPERATION, REFERENCE SHALL
 BE MADE TO THE 2003 EDITION OF NFPA.
  
 8. HOW WILL THE TENANT SPACES BE ADDRESSED AS SUCH TO
 DISTINGUISH ONE FROM THE OTHER?
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 INDICATING WHERE ON THE PLAN EACH ITEM HAS BEEN
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 09:10 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 09:10 Sent To  
Notes
2008-02-19 09:14:17TO "BOB"#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-28 Cont ID  
Sent By mawillia Date 2008-01-28 Time 15:48 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 09:03 Sent To  
Notes
2008-01-17 09:04:54TO "BOB"#10

Review Stop M MECHANICAL (A/C)
Rev No 2 Status N Date 2008-02-19 Cont ID  
Sent By tgordon Date 2008-02-19 Time 12:20 Rev Time 0.20
Received By tgordon Date 2008-02-19 Time 12:20 Sent To  
Notes
2008-02-19 12:21:08NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-23 Cont ID  
Sent By tgordon Date 2008-01-23 Time 15:49 Rev Time 0.30
Received By tgordon Date 2008-01-23 Time 15:49 Sent To  
Notes
2008-01-23 15:57:00PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLAN PAGE RS-1 CONSTRUCTION RESPONSIBILITY LISTS
 NUMEROUS HVAC WORK TO BE DONE, PLEASE SUBMIT MECHANICAL
 PLANS SHOWING ALL MECHANICAL WORK TO BE DONE WITH ALL
 PERTINENT INFORMATION. SEE 2004 FBC 106.3.5.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-26 Cont ID  
Sent By mperson Date 2008-02-26 Time 11:25 Rev Time 0.00
Received By mperson Date 2008-02-26 Time 11:25 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By mperson Date 2008-01-22 Time 16:41 Rev Time 0.00
Received By mperson Date 2008-01-22 Time 16:41 Sent To  
Notes
2008-01-22 16:57:36PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P-1 FLOOR PLAN: THE FLOOR PLAN DOES NOT
 REFLECT THE SANITARY PLUMBING RISER. THE FLOOR PLAN IS
 INDICATING THE NEW 4" SANITARY BEING TIED INTO THE
 WATER CLOSET STUB UP. THAT IS NOT COMPLIANT AND DOES
 NOT REFLECT THE SANITARY RISER DIAGRAM. THE NEW 4"
 SANITARY LINE MUST TIE IN DOWN STREAM OF THE WET VENTED
 BATHROOM. PLEASE REFLECT THE SANITARY RISER DIAGRAM,
 PER FBC PLUMBING SECTIONS *701.1 SCOPE AND *909.1 WET
 VENT PERMITTED.
  
 2. SHEET P-1 FLOOR PLAN AND SANITARY RISER DIAGRAM:
 PER FBC PLUMBING SECTION * 708.3.5 BUILDING DRAIN AND
 BUILDING SEWER JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER. PLEASE INDICATE THIS ON THE
 RESUBMITTAL.
  
 3. SHET P-1 FLOOR PLAN AND SANITARY RISER DIAGRAM: PER
 FBC PLUMBING SECTION *704.4 FUTURE FIXTURES. DRAINAGE
 PIPING FOR FUTURE FIXTURES SHALL TERMINATE WITH AN
 APPROVED CAP OR PLUG. PLEASE INDICATE THIS ON THE
 RESUBMITTAL.
  
 4. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR THE FUTURE COLD
 WATER INDICATING THE PIPE SIZE, VALVE LOCATION,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-17 Cont ID  
Sent By choops Date 2008-01-17 Time 14:38 Rev Time 0.00
Received By choops Date 2008-01-17 Time 14:38 Sent To  
Notes
2008-01-17 14:38:20*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.