Plan Review Details - Permit 08010322
Plan Review Stops For Permit 08010322
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-01 Cont ID  
Sent By amorse Date 2008-03-01 Time 09:39 Rev Time 0.00
Received By amorse Date 2008-03-01 Time 09:39 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By amorse Date 2008-01-18 Time 18:20 Rev Time 0.00
Received By amorse Date 2008-01-18 Time 18:20 Sent To P
Notes
2008-01-18 18:38:40 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)PROVIDE WIND DESIGN DATA ON DRAWINGS PER 1603.1.4
 FBC PLEASE NOTE THAT THE 2006 AMENDMENTS TO THE 2004
 FBC REQUIRE BUILDINGS LOCATED WITHIN EXP B TYPE TERRAIN
 THAT IS DIRECTLY ADJACENT TO EXP C TYPE TERRAIN SUCH AS
 OPEN GOLF COURSES AND BODIES OF WATER FOR A DISTANCE OF
 600 FEET OR MORE IN ANY QUADRANT TO BE IN AN EXP C
 CATEGORY. PLEASE ADJUST THE DESIGN PARAMETERS AND WIND
 PRESSURES ACCORDINGLY
  
 3)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 4)CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATUREAND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE PER 106.1.1 FBC*
 PLEASE PROVIDE A COMPLETE SCOPE OF WORK, PRODUCT
 APPROVALS WERE SUBMITTED FOR CASEMENT AND FIXED WINDOWS
 BUT DRAWINGS ONLY SHOW NEW FIXED WINDOW.
  
 5)PROVIDE DETAIL OF NEW OPENING THAT IS CREATED BY
 LARGER WINDOW, NEW POURED SILL OR IF OPENING IS MOVED
 UP, NEW LINTEL. ALSO IF NEW LINTEL IS INSTALLED PROVIDE
 PRODUCT APPROVAL
  
 6)PROVIDE SMOKE ALARMS TO EXISTING BUILDING PER
 R313.1.1 FBC RES.
  
 7)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 8)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
 ****PLEASE NOTE I HAVE WRITTEN THE FLORIDA APPROVAL
 NUMBERS AT THE TOP OF THE NOA'S*****
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-29 Cont ID  
Sent By dpalmer Date 2008-02-29 Time 17:14 Rev Time 0.00
Received By dpalmer Date 2008-02-29 Time 17:14 Sent To B
Notes
2008-02-29 17:14:50** REDLINED PLANS **
  
 1) NOTE: MISSING RECEPTACLE SPACING ALONG KITCHEN
 COUNTER SPACE PER 210.52C1
  
 2) NOTE: MISSING GFI PROTECTION ON ALL RECEPTACLES
 SERVING KITCHEN, BAR AND ISLAND COUNTER SPACES PER
 210.8A6.
  
 3) NOTE: SMOKE DETECTION DEVICES SHOULD BE SMOKE ALARMS
 WHICH DETECT AND SOUND. NFPA-72
  
 4) BREAKER FOR DISHWASHER AND DISPOSAL TO MEET 210.4B
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By dpalmer Date 2008-01-18 Time 14:31 Rev Time 0.00
Received By dpalmer Date 2008-01-18 Time 14:31 Sent To M
Notes
2008-01-18 14:31:57 
  
 ** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES SHALL BE STATED
 ON PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
  
 ** PLEASE ALSO SEE PLANS CONTAINS NOTES FOR PALM BEACH
 COUNTY HOWEVER SCOPE OF WORK AS APPLIED IS LOCATED IN
 THE CITY OF WEST PALM BEACH.
  
 2) NOTE: PLEASE SEE FBC R313 AND SHOW ALL NEW OR
 EXISTING LOCATIONS FOR SMOKE ALARMS MEETING THE CURRENT
 NFPA-72 11.5.1.1.1.
  
 3) NOTE: PLEASE SUBMIT PANEL SCHEDULE SHOWING THE SIZE
 OF THE EXISTING PANEL WITH NEW LOADS ALONG WITH
 EXISTING LOADS.
 PLANS INDICATE 200 AMPS, HOWEVER NEED TO SHOW THE
 ENTIRE EXISTING LOAD ON THE 200AMP SERVICE AS NOTED.
 PLANS INDICATE OTHER NEW DEDICATE CIRCUITS YET THE
 ABBREVIATED CALCULATIONS DO NOT INCLUDE THESE OTHER NEW
 LOADS. FOR EXAMPLE: PLEASE SEE OVEN> ETC
  
 4) NOTE: PLEASE SUBMIT AND INDICATE ON PANEL SCHEDULE
 THE MINIMUM CIRCUITS FOR NEW OR EXISTING SMALL
 APPLIANCE CIRCUITS PER 210.52B1, 210.11C1, 220.53.
 PLEASE SEE 220.83 FOR EXISTING SERVICE LOADS.
 PLEASE INDICATE THE BRANCH CIRCUIT SIZES OF CONDUCTORS
 AND OVER CURRENT PROTECTION.
 408.4, 240.4, 310.16 ETC
 FBC 106.3.5.4, 106.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
  
 5) NOTE: PLEASE SEE 210.8A6 AS ALL RECEPTACLES SERVING
 KITCHEN COUNTER SPACE SHALL BE GFI/GFI PROTECTED.
  
 6) NOTE: PLEASE SEE 210.52C1 FOR MISSING COUNTER SPACE
 RECEPTACLES REQUIRED.
  
 7) NOTE: PLEASE PLACE TYPE OF FIXTURES FOR RECESSED
 LIGHTING TO MEET FBC 13-606.1.ABC.1.2.4
  
  
 ** PLEASE KNOW AS SOME INFORMATION IS NOT YET SUBMITTED
 FULL REVIEW FOR CODE COMPLIANCE CAN BE DONE AT THIS
 TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2008-04-09 Cont ID  
Sent By mperson Date 2008-04-09 Time 09:20 Rev Time 0.00
Received By mperson Date 2008-04-09 Time 09:20 Sent To PC
Notes
2008-04-09 09:26:26NOTE: GAS PIPE HAS BEEN DELETED. REFERENCE SIGNED,
 SEALELED, AND DATED LETTER FROM ENGINEER. A SEPERATE
 GAS PERMIT (08040179) AND PLANS BY ABSOLUTE PLUMBING
 ARE ATTACHED TO THIS MASTER.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-04-02 Cont ID  
Sent By mperson Date 2008-04-02 Time 08:59 Rev Time 0.00
Received By mperson Date 2008-04-02 Time 08:59 Sent To PC
Notes
2008-04-02 09:55:44GAS PLAN REVIEW:
 DENIED 3RD TIME****: 1ST REVIEW FOR GAS WAS DONE UNDER
 THE PLUMBING REVIEW ON 1/22/08, THE 2ND** REVIEW WAS ON
 2/25/08 WITH AN ADDED GAS STOP.
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE LETTERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS DONE UNDER THE PLUMBING
 REVIEW AS WELL AS THE DESIGNER'S RESPONSES FOR THE
 PURPOSE OF CONTINUITY. **NOTE: THERE WERE NO COMMENT
 RESPONSES FROM THE DESIGNER 1/22/08. ALSO THERE WERE NO
 COMMENT RESPONSES FROM THE DESIGNER 2/25/08****.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS DO HAVE A
 GAS ISOMETRIC RISER DIAGRAM, HOWEVER THE EXISTING
 NATURAL GAS SYSTEM TO THE POOL HEATER AND BBQ ARE NOT
 BEING INDICATED. PLEASE REFERENCE THE PERMIT
 INFORMATION INDICATING EXISTING NATURAL GAS TO THESE
 APPLIANCES.
  
 ****NO COMMENT RESPONSE, THE RESUBMITTED PLANS NOW
 HAVE TWO GAS RISER DIAGRAMS. THE RESUBMITTED ORIGINAL
 GAS RISER BY PROF. ENGINEER ROBERT EUGENE FETROW (PE
 35867) ON SHEET 1 AND A GAS RISER DIAGRAM BY ABSOLUTE
 PLUMBING LLC. THE RESUBMITTED ORIGINAL GAS RISER
 DIAGRAM BY THE DESIGN PROFESSIONAL IS NOT CODE
 COMPLIANT, HOWEVER THE ONE SUBMITTED BY ABSOLUTE
 PLUMBING LLC IS. PER CHAPTER 471, FLORIDA STATUTES ANY
 CHANGES TO THE CONSTRUCTION DOCUMENTS MUST BE DONE BY
 THE ORIGINAL THE DESIGN PROFESSIONAL OF RECORD WHO IS
 PE (#35867) ROBERT EUGENE FETROW. IF IT IS THE INTENT
 TO USE ABSOLUTE PLUMBING'S GAS RISER DIAGRAM THE
 ORIGINAL GAS RISER DIAGRAM ON SHEET 1 MUST BE DELETED
 WITH A SIGNED, SEALED, AND DATED LETTER FROM THE DESIGN
 PROFESSIONAL STATING THAT THE GAS RISER ON SHEET 1, IS
 BEING DELETED.
  
 B} **OK** COMMENT ADDRESSED.
  
 C} **OK** COMMENT ADDRESSED.
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS ARE
 INDICATING A BTU LOAD FOR THE NEW GAS RANGE AS BEING
 15,000 BTU'S. PER THE SUBMITTAL OF THE APPLIANCE THE
 15,000 BTU LOAD FOR THE NEW GAS RANGE IS FOR ONE BURNER
 ONLY. PLEASE KNOW THAT THERE ARE THREE DIFFERENT MODELS
 IN THE SUBMITTAL PACKAGE AND ALL THREE WILL HAVE A
 DIFFERENT BTU LOAD. PLEASE CLEARLY INDICATE THE MODEL
 BEING USED AND CORRECTLY CALCULATE THE BTU LOAD OF THE
 MODEL. ALSO THE EXISTING BTU LOAD FOR THE POOL HEATER
 AND BBQ NEED TO BE ON THE RESUBMITTED PLANS.
  
 ****REFERENCE COMMENT 1.
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NO COMMENT RESPONSE, THE EXISTING NATURAL GAS SYSTEM
 FROM THE METER TO THE POOL HEATER AND BBQ NEEDS TO BE
 INCLUDED AS WELL AS THE GAS TO THE PROPOSED NEW RANGE.
 A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THE LONGEST
 LENGTH OF THE SYSTEM BEING KNOWN.
  
 ****REFERENCE COMMENT 1.
  
 F} **OK** N/A.
  
 G} **OK** COMMENT ADDRESSED.
  
 H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF
 WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO
 WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL
 EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN THE
 BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS
 PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE
 OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE
 CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE
 PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES
 (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE
 GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO
 PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SECTION 404.8 . (DETAIL REQUIRED)
 **NO COMMENT RESPONSE OR DETAIL PROVIDED, COMMENT NOT
 ADDRESSED. PLEASE REFERENCE THE UNDERGROUND GAS PIPE
 BENEATH BUILDING DETAIL ATTACHED TO THESE COMMENTS FOR
 THE RESUBMITTAL CORRECTION.
  
 ****REFERENCE COMMENT 1.
  
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NO COMMENT RESPONSE, THE SUBMITTED MANUFACTURER
 SHEETS OF THE PROPOSED RANGE HAVE THREE DIFFERENT
 MODELS BEING INDICATED, PLEASE CLEARLY INDICATE THE
 MODEL BEING USED AND CLEARLY INDICATE THE CORRECT BTU
 LOAD (SEE COMMENT "D" ABOUT CORRECT BTU'S FOR PROPOSED
 RANGE).
  
 ****REFERENCE COMMENT 1.
  
 J} **OK** N/A.
  
 K} **OK** N/A.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-02-26 Cont ID  
Sent By mperson Date 2008-02-26 Time 16:42 Rev Time 0.00
Received By mperson Date 2008-02-25 Time 16:42 Sent To E
Notes
2008-02-25 17:00:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED 2ND TIME, NOTE: 1ST REVIEW FOR GAS WAS DONE
 UNDER PLUMBING REVIEW:
  
 THE FOLLOWING COMMENTS ARE LETTERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS DONE UNDER THE PLUMBING
 REVIEW AS WELL AS THE DESIGNER'S RESPONSES FOR THE
 PURPOSE OF CONTINUITY. **NOTE: THERE WERE NO COMMENT
 RESPONSES FROM THE DESIGNER.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS DO HAVE A
 GAS ISOMETRIC RISER DIAGRAM, HOWEVER THE EXISTING
 NATURAL GAS SYSTEM TO THE POOL HEATER AND BBQ ARE NOT
 BEING INDICATED. PLEASE REFERENCE THE PERMIT
 INFORMATION INDICATING EXISTING NATURAL GAS TO THESE
 APPLIANCES.
  
 B} **OK** COMMENT ADDRESSED.
  
 C} **OK** COMMENT ADDRESSED.
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
 **NO COMMENT RESPONSE, THE RESUBMITTED PLANS ARE
 INDICATING A BTU LOAD FOR THE NEW GAS RANGE AS BEING
 15,000 BTU'S. PER THE SUBMITTAL OF THE APPLIANCE THE
 15,000 BTU LOAD FOR THE NEW GAS RANGE IS FOR ONE BURNER
 ONLY. PLEASE KNOW THAT THERE ARE THREE DIFFERENT MODELS
 IN THE SUBMITTAL PACKAGE AND ALL THREE WILL HAVE A
 DIFFERENT BTU LOAD. PLEASE CLEARLY INDICATE THE MODEL
 BEING USED AND CORRECTLY CALCULATE THE BTU LOAD OF THE
 MODEL. ALSO THE EXISTING BTU LOAD FOR THE POOL HEATER
 AND BBQ NEED TO BE ON THE RESUBMITTED PLANS.
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
 **NO COMMENT RESPONSE, THE EXISTING NATURAL GAS SYSTEM
 FROM THE METER TO THE POOL HEATER AND BBQ NEEDS TO BE
 INCLUDED AS WELL AS THE GAS TO THE PROPOSED NEW RANGE.
 A GAS PLAN REVIEW CAN NOT BE DONE WITHOUT THE LONGEST
 LENGTH OF THE SYSTEM BEING KNOWN.
  
 F} **OK** N/A.
  
 G} **OK** COMMENT ADDRESSED.
  
 H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF
 WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO
 WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL
 EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN THE
 BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS
 PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE
 OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE
 CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE
 PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES
 (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE
 GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO
 PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SECTION 404.8 . (DETAIL REQUIRED)
 **NO COMMENT RESPONSE OR DETAIL PROVIDED, COMMENT NOT
 ADDRESSED. PLEASE REFERENCE THE UNDERGROUND GAS PIPE
 BENEATH BUILDING DETAIL ATTACHED TO THESE COMMENTS FOR
 THE RESUBMITTAL CORRECTION.
  
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 **NO COMMENT RESPONSE, THE SUBMITTED MANUFACTURER
 SHEETS OF THE PROPOSED RANGE HAVE THREE DIFFERENT
 MODELS BEING INDICATED, PLEASE CLEARLY INDICATE THE
 MODEL BEING USED AND CLEARLY INDICATE THE CORRECT BTU
 LOAD (SEE COMMENT "D" ABOUT CORRECT BTU'S FOR PROPOSED
 RANGE).
  
 J} **OK** N/A.
  
 K} **OK** N/A.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 15:30 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 15:30 Sent To M
Notes
2008-04-18 15:30:32TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-08 Cont ID  
Sent By adarroug Date 2008-04-08 Time 09:25 Rev Time 0.00
Received By adarroug Date 2008-04-08 Time 09:25 Sent To G
Notes
2008-04-08 09:26:04TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-27 Cont ID  
Sent By adarroug Date 2008-03-27 Time 13:24 Rev Time 0.00
Received By adarroug Date 2008-03-27 Time 13:24 Sent To G
Notes
2008-03-27 13:25:04TO "G" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-19 Cont ID  
Sent By adarroug Date 2008-02-19 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-02-19 Time 09:50 Sent To Z
Notes
2008-02-19 09:52:07TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-22 Cont ID  
Sent By mperson Date 2008-01-22 Time 10:01 Rev Time 0.00
Received By mperson Date 2008-01-15 Time 16:25 Sent To  
Notes
2008-01-15 16:32:55TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2008-01-18 Cont ID  
Sent By tgordon Date 2008-01-18 Time 15:51 Rev Time 0.20
Received By tgordon Date 2008-01-18 Time 15:51 Sent To B
Notes
2008-01-18 15:52:14NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By mperson Date 2008-02-25 Time 16:28 Rev Time 0.00
Received By mperson Date 2008-02-25 Time 16:28 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By mperson Date 2008-01-22 Time 08:59 Rev Time 0.00
Received By mperson Date 2008-01-22 Time 08:59 Sent To PC
Notes
2008-01-22 10:00:51PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. PLEASE PROVIDE THE FOLLOWING INFORMATION ON THE
 RESUBMITTED PLANS FOR THE PROPOSED SHOWER.
  
 A} PER FBC PLUMBING SCTION *417.4.1 WALL AREA. THE
 WALL AREA ABOVE BUILT-IN TUBS WITH INSTALLED SHOWER
 HEADS AND IN SHOWER COMPARTMENTS SHALL BE CONSTRUCTED
 OF SMOOTH, NONCORROSIVE AND NONABSORBENT WATERPROOF
 MATERIALS TO A HEIGHT NOT LESS THAN 6 FEET (1829 MM)
 ABOVE THE ROOM FLOOR LEVEL, AND NOT LESS THAN 70 INCHES
 (1778 MM) WHERE MEASURED FROM THE COMPARTMENT FLOOR AT
 THE DRAIN. SUCH WALLS SHALL FORM A WATER-TIGHT JOINT
 WITH EACH OTHER AND WITH EITHER THE TUB, RECEPTOR OR
 SHOWER FLOOR.
  
 B} PER FBC PLUMBING SECTION *417.5 SHOWER FLOORS OR
 RECEPTORS.
 FLOOR SURFACES SHALL BE CONSTRUCTED OF IMPERVIOUS,
 NONCORROSIVE, NONABSORBENT AND WATERPROOF MATERIALS.
  
 C} PER FBC PLUMBING SECTION *424.3 SHOWER VALVES.
 SHOWER AND TUB-SHOWER COMBINATION VALVES SHALL BE
 BALANCED PRESSURE, THERMOSTATIC OR COMBINATION
 BALANCED-PRESSURE/THERMOSTATIC VALVES THAT CONFORM TO
 THE REQUIREMENTS OF ASSE 1016 OR CSA B125. SHOWER AND
 TUB-SHOWER COMBINATION VALVES REQUIRED BY THIS SECTION
 SHALL BE EQUIPPED WITH A MEANS TO LIMIT THE MAXIMUM
 SETTING OF THE VALVE TO 120?F (49?C), WHICH SHALL BE
 FIELD ADJUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS.
  
 D} PER FBC BUILDING SECTION *2406.3 (5) HAZARDOUS
 LOCATIONS.
 THE FOLLOWING SHALL BE CONSIDERED SPECIFIC HAZARDOUS
 LOCATIONS REQUIRING SAFETY GLAZING MATERIALS:
 5.GLAZING IN DOORS AND ENCLOSURES FOR HOT TUBS,
 WHIRLPOOLS, SAUNAS, STEAM ROOMS, BATHTUBS AND SHOWERS.
 GLAZING IN ANY PORTION OF A BUILDING WALL ENCLOSING
 THESE COMPARTMENTS WHERE THE BOTTOM EXPOSED EDGE OF THE
 GLAZING IS LESS THAN 60 INCHES (1524 MM) ABOVE A
 STANDING SURFACE.
 **PLEASE INDICATE THAT THE SHOWER DOORS ARE COMPLIANT
 IN THE RESUBMITTAL.
  
 **PLANS ARE INDICATING GAS TO A PROPOSED NEW KITCHEN
 ISLAND RANGE/OVEN. THE FOLLOWING INFORMATION WILL BE
 REQUIRED ON A SEPERATE GAS PERMIT APPLICATION FOR THE
 PROPOSED WORK. A LICENSED GAS OR PLUMBING CONTRACTOR
 SHALL SUBMIT PLANS WITH PERMIT APPLICATION. ALL GAS
 INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
 A} SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.
  
 B}SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.
  
 C} TYPE OF GAS, (LP OR NATURAL)
  
 D} BTU LOAD OF EACH APPLIANCE AND THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33).
  
 E} SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 F} SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 G} INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 H} 404.11 PIPING UNDERGROUND BENEATH BUILDINGS. PIPING
 INSTALLED UNDERGROUND BENEATH BUILDINGS IS PROHIBITED
 EXCEPT WHERE THE PIPING IS ENCASED IN A CONDUIT OF
 WROUGHT IRON, PLASTIC PIPE OR STEEL PIPE DESIGNED TO
 WITHSTAND THE SUPERIMPOSED LOADS. SUCH CONDUIT SHALL
 EXTEND INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN THE
 BUILDING, THE SPACE BETWEEN THE CONDUIT AND THE GAS
 PIPING SHALL BE SEALED TO PREVENT THE POSSIBLE ENTRANCE
 OF ANY GAS LEAKAGE. WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE, THE
 CONDUIT SHALL BE DESIGNED FOR THE SAME PRESSURE AS THE
 PIPE. SUCH CONDUIT SHALL EXTEND NOT LESS THAN 4 INCHES
 (102 MM) OUTSIDE THE BUILDING, SHALL BE VENTED ABOVE
 GRADE TO THE OUTDOORS AND SHALL BE INSTALLED SO AS TO
 PREVENT THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE WITH
 SECTION 404.8 . (DETAIL REQUIRED)
  
 I} SUBMIT MANUFACTURE SHEETS FOR ALL GAS EQUIPMENT TO
 VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 J} CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 K} CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 14:19 Rev Time 0.00
Received By choops Date 2008-02-19 Time 14:18 Sent To E
Notes
2008-02-19 14:19:57***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT (DP OUT)

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-17 Cont ID  
Sent By choops Date 2008-01-17 Time 14:34 Rev Time 0.00
Received By choops Date 2008-01-17 Time 14:34 Sent To  
Notes
2008-01-17 14:35:06***FAILED***
  
  
 1)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE BUILDING'S VALUE,
 LANDSCAPING SHALL BE IN COMPLIANCE WITH ALL APPLICABLE
 REGULATIONS FOUND IN ARTICLE XIV OF THE ZLDRS.PLEASE
 SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE WITH SECTION
 94-442 AND 94-445 OF THE ZLDRS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720