| Plan Review Stops For Permit 08010249 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
45 |
Status |
P |
Date |
2009-04-22 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-22 |
Time |
16:37 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-04-22 |
Time |
16:36 |
Sent To |
PC |
|
| Notes |
| 2009-04-22 16:37:55 | SUBMITTAL: PARAPET HANDRAIL AND INTERIOR LOBBY HANDRAIL |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
44 |
Status |
P |
Date |
2009-04-14 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-04-14 |
Time |
15:29 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2009-04-14 |
Time |
15:29 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
43 |
Status |
F |
Date |
2009-03-16 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-03-16 |
Time |
13:07 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2009-03-16 |
Time |
13:07 |
Sent To |
PC |
|
| Notes |
| 2009-03-16 13:26:20 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: ROOFTOP CAGES | | | | | | ACTION: DENIED | | | | | | 1) THIS PROJECT IS A THRESHOLD BUILDING REQUIRING (3) | | | ORIGINAL REPORTS TO BE SIGNED AND SEALED, NOT COPIES OF | | | REPORTS. | | | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED | | | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: | | | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, | | | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER | | | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | | | 2) THE ENGINEERING REPORT REVISED 1-20-09 BY RAUL A. | | | LESCANO P. E. DOES NOT SAY THAT HE IS THE P. E. WHO | | | DESIGNED THIS SYSTEM BUT HE DID A SITE VISIT, IS MR. | | | LESCANO THE DESIGNER OF THIS ENCLOSURE OR IS THIS A TO | | | BE A PIER REVIEW OF SOMEONE ELSES WORK. IN EITHER CASE | | | AGAIN THE INFORMATION IS COPIED AND NO ORIGINAL SIGNING | | | AND SEALING OF DOCUMENTS FOR PUBLIC | | | RECORD.61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & | | | SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER | | | THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER | | | OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER | | | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | | | 3) THE THIRD PROBLEM WITH THE DOCUMENTS SUBMITTED THE | | | ENGINEER OF RECORD TOM BOGACKI COVER LETTER AGAAIN IS A | | | PHOTOCOPY AND NONE OF THE THREE SUBMITTED ARE ORIGINALS | | | WITH RAISED SEAL AND ORIGINAL SIGNATURES. | | | 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED | | | BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE: | | | NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR, | | | THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE | | | NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER | | | OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER | | | IS PRACTICING (471.025 F.S. AND 471.023 F.S.). | | | | | | NOTE IF THE DOCUMENTS PROVIDED WERE ORIGINALS IN NATURE | | | WITH RAISED SEAL AND SIGNATURES THEY WOULD OF PASSED | | | THIS REVIEW. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
42 |
Status |
P |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2009-01-23 |
Time |
20:23 |
Rev Time |
3.50 |
| Received By |
jwitmer |
Date |
2009-01-23 |
Time |
20:23 |
Sent To |
|
|
| Notes |
| 2009-01-23 20:24:52 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISION# 7 REVIEW: | | | ACTION: ARCHITECTURAL AND STRUCTURAL -OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
41 |
Status |
P |
Date |
2008-12-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-12 |
Time |
16:43 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-12 |
Time |
16:43 |
Sent To |
PC |
|
| Notes |
| 2008-12-12 16:44:56 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: WON DOOR SUBMITTAL# 081100-3 | | | ACTION: REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
40 |
Status |
P |
Date |
2008-12-12 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-12 |
Time |
16:21 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-12 |
Time |
16:21 |
Sent To |
PC |
|
| Notes |
| 2008-12-12 16:40:25 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: FIRESTOPPING/ MEISNER ELECTRIC | | | ACTION: REVIEWED/ SUBMITTAL 078400-3 | | | | | | BUILDING PROVISO: THE DESIGNER OF RECORD SHALL | | | REQUIREONE BRAND NAME MATERIAL, APPROVED FOR FIRE | | | STOPPING PENETRATIONS, FOR WALLS, FLOOR CEILING | | | ASSEMBLIES. | | | WEST PALM BEACH THRESHOLD GUIDELINES COMMENT# 26. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
39 |
Status |
P |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-11 |
Time |
14:14 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-11 |
Time |
14:14 |
Sent To |
PC |
|
| Notes |
| 2008-12-11 14:15:34 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:ACCURATE GLASS SHOP DRAWINGS | | | ACTION: REVIEWED | | | | | | SUBMITTAL# 088000-12 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
38 |
Status |
P |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-11 |
Time |
14:13 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-11 |
Time |
14:13 |
Sent To |
|
|
| Notes |
| 2008-12-11 14:14:08 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: WINDOW CALCULATIONS | | | ACTION: REVIEWED | | | | | | SUBMITTAL# 088000-9 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
37 |
Status |
P |
Date |
2008-12-11 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-12-11 |
Time |
14:11 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-12-11 |
Time |
14:11 |
Sent To |
PC |
|
| Notes |
| 2008-12-11 14:12:53 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SHOP DRAWING | | | ACTION: REVIEWED | | | | | | SUBMITTAL# 088000-8-R1 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
36 |
Status |
F |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-24 |
Time |
16:41 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2008-11-24 |
Time |
16:41 |
Sent To |
PC |
|
| Notes |
| 2008-11-24 16:47:03 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: ALUMINIUM SHOP DRAWINGS | | | ACTION: DENIED | | | | | | 1) SHOIP DRAWINGS ARE SIGNED AND SEALED WITH CUT AND | | | PASTE SECTION ON VARIOUS SHEETS. W.P.B. ADMINISTRATIVE | | | CODE 106.1.1 | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
35 |
Status |
F |
Date |
2008-11-24 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-24 |
Time |
16:34 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-24 |
Time |
16:34 |
Sent To |
B |
|
| Notes |
| 2008-11-24 16:38:55 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL# 081100-3. | | | ACTION: DENIED | | | | | | STRUCTURAL SHEETS FROM O'DONNELL, NACCARATO, MIGNOGNA & | | | JACKSON, INC. ARE TO BE SIGNED AND SEALED. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)805-6731 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
34 |
Status |
P |
Date |
2008-11-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-17 |
Time |
15:30 |
Rev Time |
7.50 |
| Received By |
jwitmer |
Date |
2008-11-17 |
Time |
15:30 |
Sent To |
|
|
| Notes |
| 2008-11-17 15:32:05 | REVISION# 5 PROVISO: CALLED RODOLFO MISSING SHEET | | | A-101A IN CITY SET OF REVISIONS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
33 |
Status |
F |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-07 |
Time |
16:26 |
Rev Time |
0.22 |
| Received By |
jwitmer |
Date |
2008-11-07 |
Time |
16:26 |
Sent To |
PC |
|
| Notes |
| 2008-11-07 16:31:43 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: VENEER WALL YKK YCW 750 | | | ACTION: DENIED | | | | | | 1609.6.2.2 COMPONENTS AND CLADDING THIS JOB IS | | | CONSIDERED A THRESHOLD BUILDING AND WILL REQUIRE (3) | | | SETS OF SHOP DRAWING. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
32 |
Status |
P |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-07 |
Time |
16:23 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-07 |
Time |
16:22 |
Sent To |
|
|
| Notes |
| 2008-11-07 16:25:59 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL 042200-3 | | | ACTION: REVIEWED | | | | | | SHAFT WALL IN STAIRWELLS SUBSTITUTION REQUEST FORM TO | | | AERCON UL DESIGN # U920 | | | BUILDING PROVISO: PLANS ARE TO BE UPDATED TO REFLECT | | | THE NEW WALL TYPE FOR STAIRWELL. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
31 |
Status |
P |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-07 |
Time |
14:32 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-07 |
Time |
14:32 |
Sent To |
|
|
| Notes |
| 2008-11-07 14:34:05 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:SUBMITTAL# 089100-5 | | | ACTION:REVIEWED | | | | | | LOUVER NOA 07-1015.06 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
30 |
Status |
P |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-07 |
Time |
14:22 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-07 |
Time |
14:22 |
Sent To |
PC |
|
| Notes |
| 2008-11-07 14:23:47 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL# 055100-5 | | | ACTION : REVIEWED | | | | | | STEEL STAIR SHOP DRAWINGS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
29 |
Status |
P |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-11-07 |
Time |
14:20 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-11-07 |
Time |
14:20 |
Sent To |
PC |
|
| Notes |
| 2008-11-07 14:22:21 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL 055100-1 | | | ACTION: REVIEWED | | | STEEL STAIR CALCULATIONS | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
28 |
Status |
F |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-23 |
Time |
10:26 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-10-23 |
Time |
10:26 |
Sent To |
PC |
|
| Notes |
| 2008-10-23 10:48:52 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: EXTERIOR METAL STUD FRAMING | | | SUBMITTAL# 092214-7 | | | ACTION: DENIED | | | | | | THE ENGINEER OF RECORD IS TO AFFIX A SHOP DRAWING STAMP | | | OR A ORIGINAL COVER PAGE WITH INDEX OF ENGINEERING | | | UNDER THIER REVIEW, | | | NOTE THERE IS NO IDENTIFICATION AS TO THE ADDRESS NOR | | | THE PERMIT NUMBER ON THE DOCUMENT LINKING THE DOCUMENT | | | TO THE SHOP DRAWINGS. | | | 61G15-23.002/ 61G15-30.006 | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
27 |
Status |
F |
Date |
2008-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-17 |
Time |
11:32 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-10-17 |
Time |
11:32 |
Sent To |
PC |
|
| Notes |
| 2008-10-17 11:44:37 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL# 092116-04 REV#1 | | | ACTION: DENIED | | | | | | 1) THIS CONSTITUTES A REVISION AND SHOULD PAY REVISION | | | FEES | | | 2) PLEASE IDENTIFY WALL TYPES THAT THE INSULATION IS | | | CHANGING, PROVIDE PLANS INDICATING THE REVISION AND | | | WALL TYPES, NOTE THE CHANGE WILL NEED TO ALSO REFLECT | | | IN THE ENEERGY CALCULATIONS | | | THE EXTERIOR WALLS ; | | | TYPE 1C: INDICATE A 2 INCH INSULATION AND A R VALUE | | | (H.SF.F/BTU OF 9.1 | | | TYPE 1C- DETAIL 9/512 ALSO INDICATES A 2 INCH | | | INSULATION AND A R VALUE (H.SF.F/BTU) OF 10.6 | | | | | | PLEASE SUBMIT NEW ENERGY CALS WITH THE DECREASED VALUES | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
26 |
Status |
F |
Date |
2008-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-17 |
Time |
11:15 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-10-17 |
Time |
11:15 |
Sent To |
PC |
|
| Notes |
| 2008-10-17 11:19:00 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: SUBMITTAL 089100.5 | | | ACTION: DENIED | | | | | | 106.1.2 ADDITIONAL INFORMATION REQUIRED, 1609.6.2.2. | | | ONLY A PRODUCT APPROVAL WAS SUBMITTED, NO INFORMATION | | | AS TO THE LOCATION, SIZE NOR PRESSURES TO BE IMPOSED ON | | | THIS PRODUCT. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
25 |
Status |
P |
Date |
2008-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-17 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2008-10-17 |
Time |
11:10 |
Sent To |
PC |
|
| Notes |
| 2008-10-17 11:12:06 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:SUBMITTAL: 055000-8 | | | ACTION: REVIEWED | | | | | | STEEL BOLLARD & BASE PLATE |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
24 |
Status |
F |
Date |
2008-10-17 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-10-17 |
Time |
11:05 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-10-17 |
Time |
11:05 |
Sent To |
PC |
|
| Notes |
| 2008-10-17 11:08:20 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW:SUBMITTAL 05000-8 | | | ACTION: DENIED. | | | THE ATTACHED PLANS INDICATING THE LOCATION OF THE | | | BOLLARD ARE COPIES OF ORIGINAL PLANS, THESE PLANS ARE | | | NOT SIGNED NOR SEALED. | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | FL ADMIN CODE 61G16.003 ARCHITECTS | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
23 |
Status |
F |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-23 |
Time |
15:58 |
Rev Time |
7.55 |
| Received By |
jwitmer |
Date |
2008-09-23 |
Time |
15:58 |
Sent To |
PC |
|
| Notes |
| 2008-09-23 16:45:31 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | WINDOW SHOP DRAWING REVIEW: | | | ACTION: DENIED | | | | | | 1) SHEET 9 OF 12 | | | A) W2- NOTE DETAIL4/10 INDICATES NO ANCHORS REQUIREDAT | | | CONTINIOUS JAMB WHERE AS DETAIL INDICATES ANCHOR | | | SPACING ON SIDE JAMBS. DISCREPANCY 106.1.2 ADDITIONAL | | | INFORMATION 1609..6 | | | | | | B) W-2 ALSO INDICATS THAT THE JAMBS & MULLION ARE NOT | | | REINFORCED, THE TRIBUTARY AREA FOR THE HORIZONTAL | | | MULLION IS ROUGHLY 46.5"X72" SHEET 3 OF 7 MULLIONS W/O | | | REINFORCEMENT INDICATE A -80.0 WHERE AS | | | THE WINDOW INDICATES A NEGATIVE 89. | | | | | | C) W-2A IS THE SAME SIZE WINDOW WITH THE SAME SITUATION | | | AS THE W-2 WINDOW. | | | | | | D) W-3A NO DESIGNATION AS TO MUTTINS. | | | | | | E) W-3A THE JAMB AND MULLION DETAIL INDICATES | | | NON-REINFORCED WITH LOW PRESSURES FROM NOA SHEET 3 OF | | | 7.UN-REINFORCED JAMBS AND MULLIONS ARE GOOD TO 80 PSF | | | THIS WINDOW IS INDICATED AS A -89.LOW PRESSURE | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
22 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-18 |
Time |
15:15 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-18 |
Time |
15:15 |
Sent To |
PC |
|
| Notes |
| 2008-09-18 15:16:51 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW: # 05-5000-15 SEPERATOR BEAM LOCATED | | | WITHIN THE ELEVATOR SHAFT | | | ACTION: REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
21 |
Status |
N |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-18 |
Time |
13:58 |
Rev Time |
0.22 |
| Received By |
jwitmer |
Date |
2008-09-18 |
Time |
13:58 |
Sent To |
PC |
|
| Notes |
| 2008-09-18 14:01:34 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: ELEVATOR SUBMITTALS | | | ACTION: NONE ELEVATOR AND ASSOCIATED EQUIPMENT ARE | | | REVIEWED BY BUREAU OF ELEVATOR SAFETY OF THE DEPARTMENT | | | OF BUSSINESS AND PROFESSIONAL REGULATION SCOOPE 3001.1 | | | NOTE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
20 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-18 |
Time |
13:05 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-18 |
Time |
13:05 |
Sent To |
PC |
|
| Notes |
| 2008-09-18 13:40:18 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW: | | | #093000-21 ULTRAFLEX 1 STANDARD POLYMER-ENRICHED TILE | | | MORTER | | | 00-3000-5 PRECAST 4X4 CONCRETE SHOWER SILL | | | ACTION: REVIEWED | | | | | | BUILDING PROVISO: THIS REVIEW IS FOR THE USE OF | | | ULTRAFLEX 1 TO BE USED ON THE INSTALATIOJN OF THE | | | PRECAST 4X4 INCH CONCRETE SHOWER SILL ONLY. THE | | | CONTRACTOR HAS NOT PROVIDED WHAT TYPE OF MATERIALS WILL | | | BE SUBMITTED FOR SOUND DEADENING. THE SUBFLOOR FOR THIS | | | PRODUCT IS VERY LIMITED AS TO THE PRODUCT MUST COMPLY | | | WITH 1207.3 STRUCTURAL-BORNE SOUND . | | | 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES | | | BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A | | | PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE | | | AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS | | | THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE | | | WITH ASTM E 492. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
19 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-18 |
Time |
11:36 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-18 |
Time |
11:35 |
Sent To |
PC |
|
| Notes |
| 2008-09-18 11:39:41 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL # 055000-11 REVIEW: ELEVATOR HOIST BEAM | | | ACTION: REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
18 |
Status |
P |
Date |
2008-09-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-18 |
Time |
11:08 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-18 |
Time |
11:08 |
Sent To |
PC |
|
| Notes |
| 2008-09-18 11:14:51 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW # 078400-2 | | | ACTION: REVIEWED : TREMSTOPIA, SYSTEM # W-L-2420 | | | | | | BUILDING PROVISO: | | | 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR | | | THRESHOLD INSPECTORS #26. | | | ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR | | | SPECIFICATIONS ONE MATERIAL, | | | APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND | | | CEILINGS. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
17 |
Status |
P |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
14:10 |
Rev Time |
0.33 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
14:10 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 14:11:38 | 3'-6" CORNER GAURDS- OK |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
16 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
13:24 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
13:24 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 13:44:12 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOGACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | SHOP DRAWING: STEEL RACKS @ ROOF | | | | | | 1) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT THIS | | | SUBMITTAL IS TO BE USED FOR, IT APPEARS TO BE A | | | SCREENING ENCLOSURE TO HIDE THE RTU ON THE TOP OF THE | | | ROOF. IN DOING SO THIS WILL NEED TO UPDATE | | | SHEETS A-105-A AND A105-B AS TO THIS WOULD BE A | | | REVISION TO BE REVIEWED BY ZONING AND BUILDING. | | | | | | 2) THE SECOND ISSUE IS THIS DETAIL INDICATES CHAIN-LINK | | | BRACKETS BY OTHERS, BUT AGAIN IF FENCING IS TO BE | | | APPLIED AS A SCREENING TYPE MATERIAL, IT WOULD ALSO | | | NEED THE BLINDS INSERTED INTO EACH ROW CREATING A | | | NON-VIEWABLE FENCING THAT WOULD NOT ALLOW WIND TO | | | TRAVEL THROUGH, AND THERE IS NO INDICATION THAT THE | | | ENGINEER OF RECORD THIS REVISION SINCE THE STRUCTURAL | | | PLANS S106-A & S-106B ONLY INDICATE EMBEDS IN THE ROOF | | | SLAB AND THE ACTUAL RTU STANDS WILL BE SUPPLIED LATTER | | | AND REVIEWED AT THAT TIME. | | | | | | 3) THE SHOP DRAWING STAMP IS NOT EVEN ON THIS DOCUMENT | | | BUT A COPY ATTACHED TO ANOTHER PAGE. FL 61G-15-30.006 | | | (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED | | | ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR | | | REVIEW. | | | | | | 4) SINCE THIS IS DOES NOT SHOW UP ON ANY | | | ARCHITECTURALNOR STRUCTURAL SHEETS WHAT ARE THE WIND | | | CRITERIA THIS AREA IS DESIGNED TOO? | | | 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | | | | 5) IN REVIEWING THIS DOCUMENT WITH THE MECHANICAL PLAN | | | REVIEWER, IT WOULD APPEAR THIS STRUCTURE WOULD BE MORE | | | THAN A MERE FENCE ENCLOSURE THAT IS TO HIDE THE RTU | | | UNITS, BUT IN ACTUALLITY THIS MAY BE A STRUCTURE TO | | | HOLD THE ACTUAL CLADDING OR PORTIONS OF CLADDING OF THE | | | ROOF TOP UNITS THAT MAY BLOW OF IN A HIGH WIND EVENT. | | | JUNE 27/08 MECHANICAL PROVISO # 1 INDICATED THE NEED TO | | | ILLUSTRATE COMPLIANCE WITH 301.13 FBCM AND ALTERNATE | | | MEANS AND METHODS MAY BE ONE VEHICLE TO BE USED IF | | | ENGINEERING OF THESE UNITS WAS NOT SUBMITTED AND | | | REVIEWED AS CODE COMPLIANT. IN DOING SO ANY DOCUMENTS | | | TO BE SUBMITTED AS ALTERNATE MEANS AND METHODS WILL | | | NEED TO BE SUBMITTED IN WRITING WITH CALCULATIONS AND | | | TO BE REVIEWED BY THE BUILDING OFFICAL. THE SAME ISSUES | | | WILL OCCUR IF THIS STRUCTURE IS TO RESTRICT PORTIONS OF | | | THE RTU CLADDING WIND WILL NOT BE ABLE TO TRAVEL | | | THRUOGH, PROVIDE CALCULATIONS INDICATING COMPLIANCE | | | WITH 301.13 FBCM. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
15 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
13:09 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
13:09 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
14 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
12:15 |
Rev Time |
0.67 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
12:15 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 12:17:30 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | STEEL RACK @ ROOF |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
13 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
12:02 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
12:02 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 12:06:49 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | STEEL STAIR SHOP DRAWING & LETTER: | | | WITHIN THE LETTER FROM ONM& J IT STATES THAT" THE SHOP | | | DRAWINGS WERE SIGNED AND SEALED BY THE ENGINEER | | | RESPONSIBLE FOR THE STEELSTAIR SHOP DRAWINGS". | | | | | | PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS | | | PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR | | | PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE | | | DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT. | | | FL ADMIN CODE 61G15-23.002 ENGINEERS | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
12 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
11:43 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
11:43 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 12:00:42 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | STRUCTURAL STEEL STAIR CALCULATIONS: 61G15-23.002(2) | | | FL. ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR | | | ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET | | | MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION | | | & PREPARATION OF EACH SECTION OF THE ENGINEERING | | | SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER | | | SHEET OR INDEX. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
11 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
11:39 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
11:39 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 11:41:43 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | DECO-FIN PLEASE PROVIDE THE WIND CRITERIA THAT THIS | | | STRUCTURAL STEEL ELEMENT WAS DESIGNED TOO. | | | 1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | | | | 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | | | | 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES | | | IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION | | | OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT | | | SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
10 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
11:20 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
11:20 |
Sent To |
B |
|
| Notes |
| 2008-09-09 11:36:51 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | LOUVERS & MULLIONS: | | | | | | 1) RULE 9B-72 REQUIRES PRODUCT APPROVALS THAT ARE | | | LISTED WITH EITHER THE FLORIDA STATE WEBSITE OR ANOTHER | | | APPROVED AGENCY SUCH AS UL OR MIAMI-DADE WITH THIRD | | | PARTY QUALITY ASSURANCE PROGRAM IN EFFECTTHAT IS | | | REGISTERED WITH THE STATE. | | | | | | 2) 1609.1.4(5) LOUVERS. LOUVERS PROTECTING INTAKE AND | | | EXHAUST VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT | | | ARE LOCATED WITHIN 30 FEET (9144 MM) OF GRADE SHALL | | | MEET REQUIREMENTS OF THE LARGE MISSILE TEST. | | | IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES | | | THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN | | | POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA | | | BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE | | | SPECIMEN IS TO BE TESTED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
9 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
11:13 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
11:13 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 11:18:43 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE THE LOCATION THIS SEPERATOR BEAM WILL | | | BE INSTALLED WITHIN THE BUILDING. 106.1.2 ADDITIONAL | | | INFORMATION REQUIRED. | | | | | | 2) THE LEFT HAND DETAIL INDICATES (2) - 5/8" EXPANSION | | | ANCHORS WHILE THE PLAN INDICATES FOUR? 106.1.2. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
11:04 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
11:04 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 11:07:39 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | 1) EMBEDS- SHOP DRAWING DOES NOT PROVIDE THE LOCATION | | | THIS EMBED WILL BE INSTALLED, NOR THE TYPE OF MATERIAL | | | IT WILL BE CONSTRUCTED FROM NOR THE WELD SIZES FROM THE | | | NELSON STUD TO PLATE MATERIAL. | | | 106.1.2 ADDITIONAL INFORMATION REQUIRED. | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
10:59 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
10:59 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 11:01:31 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEW | | | ACTION: DENIED | | | | | | STEEL BOLLARD : PLEASE PROVIDE LOCATION THIS BOLLARD | | | WILL BE INSTALLED. 106.1.2 ADDITIONAL INFORMATION | | | REQUIRED. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2008-09-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-09-09 |
Time |
10:50 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-09-09 |
Time |
10:50 |
Sent To |
PC |
|
| Notes |
| 2008-09-09 10:58:02 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | SUBMITTAL REVIEWS | | | ACTION: DENIED | | | | | | 1) SUBMITTALS BROUGHT IN SHOULD BE BROKE OUT TO THE | | | CORRECT TRADES, NOT BUNCHED TOGETHER : | | | A) DUMPSTER GATE WILL BE REVIEWED BY ENGINEERING NOT | | | BUILDING | | | | | | B) BIKE RACK IS ZONING. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-08-29 |
Time |
13:54 |
Rev Time |
0.77 |
| Received By |
jwitmer |
Date |
2008-08-29 |
Time |
13:54 |
Sent To |
PC |
|
| Notes |
| 2008-08-29 13:56:39 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW SUBMITTAL #233713 -4 REVISION# 1 ELEVATOR LOUVER | | | ACTION: REVIEWED |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-07-21 |
|
|
Cont ID |
|
| Sent By |
lmartine |
Date |
2008-07-21 |
Time |
14:06 |
Rev Time |
0.00 |
| Received By |
lmartine |
Date |
2008-07-21 |
Time |
14:06 |
Sent To |
|
|
| Notes |
| 2008-07-21 14:41:23 | THE PREVIOUS COMMENT WAS PROCESSED IN ERROR, PLEASE | | | DISREGUARD,L.MARTINEZ#6710 | | 2008-07-21 14:07:44 | ANCHORING DETAILS AT ROOF TOP UNITS REVISIONOK | | | LM |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-25 |
Time |
16:40 |
Rev Time |
5.55 |
| Received By |
jwitmer |
Date |
2008-06-25 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2008-06-25 16:40:08 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | ARCH: PFVS/ GREGORY R PORTMAN | | | TEL: (404)503- 5000 | | | | | | STRUC: OMNJ/ THOMAS M BOG ACKI | | | TEL: (561)835-9994 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: REVIEWED | | | | | | 1) BUILDING PROVISO: EXTERIOR LIGHT GAUGE METAL FRAMING | | | TO BE SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED | | | AND APPROVED BY THE DESIGNER OF RECORD , STAMPED | | | APPROVED. | | | | | | 2) COMPACTOR SCISSOR LIFT SUBMIT SHOP DRAWINGS AND | | | MANUFACTURER'S SPECIFICATION WITHIN 90 DAYS OF PERMIT | | | ISSUANCE. | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-24 |
|
|
Cont ID |
|
| Sent By |
rbrown |
Date |
2008-05-24 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
rbrown |
Date |
2008-05-24 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2008-05-24 12:16:32 | BUILDING PLAN REVIEW | | | *******DENIED******* | | | ROBERT BROWN(561) 805 6652 | | | E-MAIL: [email protected] | | | | | | FBC = FLORIDA BUILDING CODE 2004 AS AMENDED/REVISED | | | FBC*= FLORIDA BUILD'G CODE (CITY AMEND) | | | F.S.= FLORIDA (STATE) STATUTE | | | | | | FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS | | | PER THE BUILDING PLAN REVIEW OF 2/25/08: | | | | | | 3B)FBC 715.3SHEET A-611,FIRE-RATED DOORS ON THE | | | EXIT ACCESS CORRIDOR SERVING THE CONFERENCE ROOM(S). | | | DOORS 127 AND 153 ARE NOT SHOWN AS FIRE-RATED ON DOOR | | | SCHEDULE SHEET A-611.REVISE THE DOOR SCHEDULE. | | | | | | 3C)FBC 715.3SHEET A-101A AND SHEET A-611, | | | FIRE-RATED DOORS REQUIRED IN OCCUPANCY SEPARATION WALL | | | BETWEEN PARKING GARAGE AND LOBBY.DOOR 131 IS NOT | | | SHOWN AS FIRE-RATED ON DOOR SCHEDULE SHEET A-611. | | | REVISE THE DOOR SCHEDULE. | | | | | | 3E)FBC 302.3.2SHEET A-102B (AND CORRESPONDING LIFE | | | SAFETY SHEET G-007) AND SHEET A-103B.ON SHEET A-102B | | | (AND CORRESPONDING LIFE SAFETY SHEET G-007), THE | | | MEZZANINE LEVEL WALL ON GRID 2 BETWEEN GRIDS A AND B.4 | | | IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR FIRE-RATED | | | OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE PARKING | | | GARAGE AND EMERGENCY ELECTRICAL ROOM.AMEND SHEET | | | A-102B.ALSO, ON SHEET A-103B, THE SECOND FLOOR LEVEL | | | WALL BETWEEN THE PARKING GARAGE AND THE GUEST LAUNDRY | | | NEAR GRID B/1.2 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR | | | FIRE-RATED OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE | | | PARKING GARAGE AND THE VESTIBULE AND ELECTRICAL ROOM. | | | AMEND SHEET A-103B. | | | | | | 3M) FBC 1012.1SHEET A-702, STAIR #2 - ROOF LEVEL | | | PLAN.STAIR ACCESS TO THE ROOF HAS BEEN PROVIDED BUT | | | THE GUARDRAIL DOES NOT CONTINUE TO THE SOUTH WALL.THE | | | LANDING SHALL HAVE GUARDING AGAINST FALLING.AMEND | | | SHEET A-702. | | | | | | 4I) FBC* 106.1.2SHEET AC-102.COMPACTOR SCISSOR | | | LIFT.SUBMIT SHOP DRAWINGS AND MANUFACTURER'S | | | SPECIFICATION WITHIN 90 DAYS OF PERMIT ISSUANCE. | | | | | | 5B) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN | | | PARKING GARAGE OCCUPANCY SEPARATION WALL.DOORS M004, | | | M005A, M013 ARE SHOWN AS 45 MINUTE OR 20 MINUTE | | | FIRE-RATED ON DOOR SCHEDULE SHEET A-611.THESE DOORS | | | SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.REVISE THE | | | DOOR SCHEDULE.ALSO, DOOR M005B IS SHOWN AS NON-RATED. | | | IT IS AN ELEVATOR LOBBY DOOR AND SHALL BE A MINIMUM OF | | | 20 MINUTE FIRE-RATED.REVISE THE DOOR SCHEDULE. | | | | | | 6B) FBC 707.2SHEET A-102B.CHASES AND PARTITION | | | WALLS ABOVE ROOMS 104-108.CONTRARY TO THE COMMENT | | | RESPONSE LETTER, WALL TYPE TAGS HAVE NOT BEEN ADDED TO | | | THE CHASES CALLING THEM OUT AS 2 HOUR FIRE-RATED | | | CHASES.ALSO, THE WALL TYPE TAGS ON THE PARTITIONS | | | SEPARATING THE ROOMS ON SHEET A-102B WOULD CLARIFY THE | | | INTENTION AT THIS LEVEL. | | | | | | 8D) FBC 707.4SHEET A-103A, DOOR 245 TO THE LINEN | | | SHAFT TERMINATION ROOM IS SHOWN ON DOOR SCHEDULE SHEET | | | A611 AS 45 MINUTE FIRE-RATED.THE DOOR SHALL BE A | | | MINIMUM OF 90 MINUTE FIRE-RATED.ALSO, THE WALL | | | BETWEEN THE TERMINATION ROOM AND THE VENDING/ICE ROOM | | | DOES NOT HAVE A WALL TYPE TAG TO SHOW THE REQUIRED | | | FIRE-RATING.AMEND SHEET A-103A. | | | | | | 9A) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN | | | PARKING GARAGE OCCUPANCY SEPARATION WALL.DOOR 237 IS | | | 20 MINUTE FIRE-RATED ON DOOR SCHEDULE SHEET A-611. | | | THIS DOOR SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED. | | | REVISE THE DOOR SCHEDULE. | | | | | | 11C) FBC 707.2SHEET A-104B.CHASES IN THE ELECTRICAL | | | ROOM 302/402/502 AND IN THE PARTITIONS BETWEEN HOTEL | | | ROOMS.CONTRARY TO THE COMMENT RESPONSE LETTER, WALL | | | TYPE TAGS HAVE NOT BEEN ADDED TO THE CHASE IN THE | | | ELECTRICAL ROOM.ALSO, THERE ARE NO WALL TYPE TAGS ON | | | THE CHASES IN THE PARTITION WALLS SEPARATING HOTEL | | | ROOMS. | | | | | | 20) PROVISO:EXTERIOR LIGHT GAUGE METAL FRAMING TO BE | | | SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE | | | DESIGNER OF RECORD, APPROVED AND STAMPED. | | | | | | 21) PROVISO:FIN WALL SHOWN ON SHEET A-511, DETAIL 9. | | | THE STEEL FRAME AND "CURTAIN WALL" FOR THIS DECORATIVE | | | ELEMENT OF THE BUILDING SHALL BE SUBMITTED AS SHOP | | | DRAWINGS AFTER BEING REVIEWED BY THE DESIGNER OF | | | RECORD, APPROVED AND STAMPED. | | | | | | 22D) MULLION PRODUCT APPROVAL.IT IS NOTED THAT THE | | | MULLION LENGTHS HAVE BEEN IDENTIFIED BY HIGHLIGHTER PEN | | | ON THE PRODUCT APPROVAL.PLEASE NOTE THAT WE REQUIRE | | | THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, ETC. IN | | | INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP WHEN THE | | | DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF THE | | | PROJECT UNDER THE MANDATORY RECORD RETENTION PROGRAM. | | | THIS APPLIES TO ALL IDENTIFICATION MARKING ON ALL | | | PRODUCT APPROVALS AND OTHER DOCUMENTS. | | | | | | 22I)PRE-ENGINEERED A/C EQUIPMENT STANDS.NO PRODUCT | | | APPROVAL OR COMMENT RESPONSE WAS SUBMITTED TO ADDRESS | | | THE COMMENT REQUIRING SUBMITTAL OF PRODUCT APPROVAL | | | DOCUMENTATION FOR PRE-ENGINEERED A/C EQUIPMENT STANDS. | | | | | | 22J) CARLISLE ROOFING PRODUCT APPROVAL.IT IS NOTED | | | THAT THE ROOFING PRODUCT APPROVAL DOCUMENTS HAVE BEEN | | | MARKED UP WITH HIGHLIGHTER PEN.PLEASE NOTE THAT WE | | | REQUIRE THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, | | | ETC. IN INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP | | | WHEN THE DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF | | | THE PROJECT UNDER THE MANDATORY RECORD RETENTION | | | PROGRAM.THIS APPLIES TO ALL IDENTIFICATION MARKINGS | | | ON ALL PRODUCT APPROVALS AND OTHER DOCUMENTS. | | | | | | 30A)FBC 903.2.7FIRE SPRINKLERS.CONTRARY TO THE | | | COMMENT RESPONSE LETTER, THE REVISED FIRE PROTECTION | | | PLANS DO NOT SHOW FIRE SPRINKLER COVERAGE IN THE | | | ELEVATOR SHAFT ABOVE THE SECOND FLOOR LEVEL.SEE | | | FP-204A AND FP-205A (BOTH REVISION B, SIGNED AND SEALED | | | ON 4/15/08). | | | | | | 30B)THERE IS STILL NO SHEET FP-205B.IF THIS IS | | | INTENTIONAL, IT WOULD BE MORE CLEAR IF SHEET FP-205A | | | HAD A NOTE TO THAT EFFECT RATHER THAN A "MATCHLINE". | | | | | | | | | **QUOTE PERMIT# ON ALL CORRESPONDENCE** | | | | | | END OF REVIEW COMMENTS | | | THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE: | | | (561) 805 6652ROBERT BROWN | | | E-MAIL: [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-25 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-25 |
Time |
12:22 |
Rev Time |
8.88 |
| Received By |
jwitmer |
Date |
2008-02-25 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2008-02-25 12:23:54 | BUILDING PLAN REVIEW | | | PERMIT: 08010249 | | | ADD: 295 LAKEVIEW AVE. | | | CONT: KAST CONSTRUCTION | | | TEL: (561)718-6141 | | | E-MAIL: [email protected] | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) INFORMATIONAL. PLEASE SUBMIT 2 OF ALL SURVEYS, | | | PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR | | | SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL | | | REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A | | | THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN | | | (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED | | | FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS | | | WEST PALM BEACH ADMINISTRATIVE CODE. | | | | | | 1C)INFORMATIONAL.106.1.1* W.P.B. ADMINISTRATIVE | | | CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN | | | INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO | | | THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO | | | CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION | | | SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE | | | CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR | | | ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC | | | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS | | | DETERMINED BY THE BUILDING OFFICIAL. | | | | | | 1D) INFORMATIONAL. PLANS SUBMITTED FOR PERMIT (FIRST | | | TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO | | | THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 2) W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT | | | FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS, | | | MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS | | | REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID | | | AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE | | | ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY. | | | | | | 108.3*BUILDING PERMIT VALUATION. | | | IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE | | | CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE, | | | ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS | | | APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE | | | PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES, | | | VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL | | | REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND | | | SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE | | | STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR | | | FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR | | | BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING | | | COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE. | | | VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED | | | DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES | | | (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS | | | FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE | | | CONGRESS. | | | | | | ICC TOTAL VALUATION FOR PROJECT IS $18,616,066.00 | | | | | | MINUS VIBRO-FLOTATION& STRUCTURAL-3,941,840.00 | | | VALUATION FOR THIS PERMIT $ | | | 14,674,226.00 | | | | | | FEES DUE THIS PERMIT | | | $163,439.36 | | | PAID TO DATE | | | $45,493.17 | | | FEE BALANCE | | | $117,946.19 | | | SEE FEE BALANCE SHEET ATTACHMENT. | | | | | | 3) SHEET A-101A: | | | 3A) WHEN THE CONFERENCE ROOMS 110, 111 & 117 ARE OPENED | | | INTO ONE LARGE CONFERENCE ROOM THE OCCUPANT LOAD WOULD | | | BE 68 REQUIRING 2 EXITS. WHEN AN ASSEMBLY OCCUPANCY IS | | | OVER 30 OCCUPANTS THE EXIT ACCESS CORRIDORS ARE | | | REQUIRED TO BE FIRE RATED 1 HOUR EVEN WITH FIRE | | | SPRINKLERS PLEASE SEE TABLE 1016.1. | | | | | | 3B) THE OTHER CONCERN IS WITH THE RATING OF THE | | | CORRIDOR, PLEASE REVIEW 1016.5 CONTINUITY OF CORRIDORS | | | AND THE FIRE RATING INTO THE LOBBY AND RECEPTION AREAS. | | | THIS WILL ALSO EFFECT THE DOOR RATINGS IN TABLE 715.3, | | | PROTECTION OF OPENINGS. | | | | | | 3C) THE FIRST FLOORDOORS CAN NOT BE CHECKED IN THE | | | DOOR SCHEDULE SHEET A-611, THE NUMBERING SEQUENCE IS SO | | | FAR OVER INTO THE LEFT MARGIN OF THE SHEET THAT THE | | | NUMBERING SEQUENCE COLUMN IS BOUND BY THE STAPLES, | | | PLEASE REPRINT THIS SHEET AND ALLOW FOR BINDING OF | | | PLANS TOGETHER. 106.1.1 INFORMATION ON CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF WORK PROPOSED AND | | | SHOW IN DETAIL THAT IT CONFORMS TO THE PROVISIONS OF | | | THIS CODE. | | | | | | 3D) THE EXTERIOR NORTH WALL OF THE BUILDING INDICATES | | | WALL TAGS OF 1 HOUR RATING, PLEASE REVIEW TABLE 602 , < | | | 5?-0? REQUIRES A 3 HR RATED WALL FOR THESE | | | OCCUPANCIES: | | | ASSEMBLY, BUSINESS OR RESIDENCE. PLEASE CORRECT PLAN. | | | | | | 3E) ADDITIONAL INFORMATION REQUIRED, 106.1.2. OCCUPANCY | | | SEPARATION, WALL TAGS ARE MISSING ON THE COMMON PARKING | | | GARAGE AND THE OTHER OCCUPANCIES, PLEASE SEE | | | TABLE302.3.2. | | | | | | 3F) PLEASE REVIEW THE ELEVATOR WALLS FOR WALL | | | IDENTIFICATION TAGS INDICATING THE RATING FOR SHAFTS, | | | SEE 707.4. | | | | | | 3G) THE MAIN ENTRY DOOR 131 APPEARS TO BE A PASSENGER | | | LOADING ZONE WITH A VALET SERVICE AND LUGGAGE AREA. THE | | | PLANS DO NOT INDICATE A DROPPED CURB NOR A PASSENGER | | | LOADING ZONE. | | | 11-4.1.2(5)?. ALSO SEE 11-4.2.9.5 DETECTABLE WARNING | | | DEVISES. | | | | | | 3H) THE DISABLED PARKING SPACE, WEST END OF, INDICATES | | | A RAMP NO INFORMATION ON HEIGHT OF RAMP, CHANGE IN | | | GRADE SEE 11-4.8(1-6). | | | | | | 3I) RESTROOMS 112 & 113 ARE INDICATED AS DETAIL# 2 | | | SHEET A-403, PLEASE CORRECT TO A-402. | | | | | | 3J) RESTROOMS 112 & 113 PLEASE PROVIDE IN DETAIL THE | | | CLEAR WIDTH OF THE ACCESSIBLE STALL DOOR, PLEASE SEE | | | FIGURE 30E. | | | | | | 3K) 106.1.2 ADDITIONAL INFORMATION REQUIRED, WHAT IS | | | THE PURPOSE OF THE E-ROOM? | | | | | | 3L) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3 | | | | | | 3M) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN | | | BUILDINGS 4 STORIES AND MORE, 1009.12.. | | | | | | 3N) THERE APPEARS TO BE A RAMP IN FRONT OF DOOR# 114, | | | THIS RAMP DOES NOT PROVIDE THE MAXIMUM ALLOWABLE SLOPE | | | INFORMATION, HANDRAILS OR BOTTOM LANDING INFORMATION, | | | PLEASE SEE 11-4.8. | | | | | | 3O)THIS PLAN INDICATES THE USE OF AN EMERGENCY | | | GENERATOR PLEASE PROVIDE ADDITIONAL INFORMATION ON THE | | | GENERATOR AND FUEL SUPPLY TANK. QUANTITY OF FUEL THAT | | | IS TO BE STORED ON SITE AND TYPE OF VAULT. DOES THIS | | | FUEL TANK HAVESECONDARY CONTAINMENT? | | | | | | 4) SHEET A-101B | | | 4A) THE NORTH AND EAST PROPERTY LINE WALLS HAVE WALL | | | IDENTIFICATION TAGS 1-B, PLEASE SEE | | | TABLE 602 FOR WALLS LOCATED LESS THAN 5?-0? FROM THE | | | PROPERTY LINE. TABLE 602 INDICATES | | | A 3HOUR WALL. | | | | | | 4B) PLEASE LOOK AT THE DOOR # 149 IN THE DOOR SCHEDULE, | | | SCHEDULE INDICATES NO FIRE RATING, | | | 1016.1 ANDTABLE 302.3.2 OCCUPANCY SEPARATION, OPENING | | | PROTECTIVE TABLE 715.3 . | | | | | | 4C) RAMP FROM DOOR# 149 TO THE EXTERIOR, THE PLANS ARE | | | MISSING THE TOP TURNING RADIUS. | | | PLEASE SEE 11-4.8.4(3). | | | | | | 4D) RAMP FROM DOOR # 149 IS MISSING THE HANDRAILS | | | REQUIRED BOTH SIDES11-4.8.5. | | | | | | 4E) RAMP BY DOOR 149 DOES NOT INDICATE THE BOTTOM | | | LANDING, 11-4.8.4(2). | | | | | | 4F) RAMP BY DOOR# 149 PLEASE PROVIDE THE CLEAR | | | DIMENSION AT THE BOTTOM OF THE RAMP FROM COLUMN TO | | | COLUMN. 11-4.8.3 WHEN PART OF A MEANS OF EGRESS MINIMUM | | | OF44? CLEAR. | | | | | | 4G) RAMP BY DOOR# 149 INDICATES A SLOPE OF 8% PLEASE | | | SEE 11-4.8.2 THE MAXIMUM SLOPE OF A RAMP IN NEW | | | CONSTRUCTION SHALL BE 1 TO 12. | | | | | | 4H)EAST SIDE OF THE BUILDING ROOM 103 THE EMERGENCY | | | GENERATOR ROOM INDICATES OPENINGS IN THE WALL, PLEASE | | | SEE TABLE 602 LESS THAN FIVE FOOT FROM THE PROPERTY | | | LINE, NO OPENINGS. | | | | | | 4I) COMPACTOR DETAIL FOUND ON SHEET AC-102 DETAIL 9 | | | INDICATES THE USE OF A SCISSOR LIFT, PLEASE PROVIDE | | | ADDITIONAL INFORMATION.106.1.2. | | | | | | 4J) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3 | | | | | | 4K) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN | | | BUILDINGS 4 STORIES AND MORE, 1009.12.. | | | | | | | | | 5)SHEET A-102A | | | 5A) PLEASE PROVIDE AREA CALCULATIONS HOW THIS LEVEL | | | CLASSIFIES AS A MEZZANINE?505.2 AREA LIMITATION.THE | | | AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN A | | | ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF THAT | | | ROOM OR SPACE IN WHICH THEY ARE LOCATED. | | | | | | 5B)DOORS ON THE A-102A & A-102B FLOOR PLANS DO NOT | | | SHOW UP ON THE DOOR SCHEDULE | | | SHEET A-611, PLEASE CORRECT, THIS SHEET CAN NOT BE | | | CHECKED FOR OPENING PROTECTIVES | | | TABLE 715.3. | | | | | | 5C) THIS COMMENT WILL NOT BE REPEATED FOR EVERY CASE | | | BOTH SHEET A-102A AND A-102B THE NORTH AND EAST | | | PROPERTY LINES ARE LESS THAN 5?-0? FROM THE PROPERTY | | | LINE REQUIRING 3 HR FIRE RATING. SEE TABLE 602. | | | | | | 5D) THERE IS A ROOM NOT IDENTIFIED, DOOR 155A LEADS | | | INTO THIS AREA. PLEASE PROVIDE ADDITIONAL INFORMATION | | | 106.1.2. | | | | | | 5E) ADDITIONAL INFORMATION REQUIRED 106.1.2. ON SHEET | | | A-101A THERE ARE ROOMS 118-123 | | | THE NEXT LEVEL UP (SHEET A-102A) THE PLAN INDICATES | | | CEILING BELOW BUT THERE IS NO CUT SECTIONS OF THIS AREA | | | INDICATING HEIGHT OF THE CEILING OR MATERIAL. PLEASE | | | PROVIDE HEIGHT OF THE CEILING AND STRUCTURAL COMPONENTS | | | OF THIS SYSTEM. | | | | | | 6) A-102B | | | 6A) THE ROOMS BELOW (105-108) ARE INDICATED AS CEILING | | | BELOW, PLEASE PROVIDE A CUT SECTION THROUGH INDICATING | | | TYPE OF CEILING, HEIGHT OF CEILING AND TYPE OF | | | STRUCTURAL COMPONENTS. 106.1.2. | | | | | | 6B) IN THE SAME ROOMS MENTIONED ABOVE THE PLANS APPEAR | | | TO HAVE (3) CHASES IN THE CENTER OF THIS AREA? PROVIDE | | | MORE DETAILS AND FIRE RATINGS. 106.1.2. ? 712.4. | | | | | | 6C) THERE IS A CONCRETE WALL ON GRID LINE B.4 BETWEEN | | | COLUMN LINE 2-3. THIS SHOULD BE A GUARD RAIL AS WELL AS | | | VEHICLE BARRIER, PLEASE PROVIDE COMPLIANCE WITH | | | 1607.7.3 | | | | | | 6D) THE OTHER AREA OF CONCERNS WITH GUARDS WOULD BE THE | | | DROP OFF EDGE WHERE THE RAMP RISES AND OR FALLS TO THE | | | NEXT LEVEL. PLEASE PROVIDE COMPLIANCE WITH 1607.7.3. | | | | | | 6E) THE NORTHEAST CORNER OF THE GARAGE THERE APPEARS TO | | | BE A SHAFT BUT NO WALL TAGS. | | | 707.4. | | | | | | 6F) CORRIDOR M114 IS INDICATED AS A 1 HR RATED WALL | | | WITH NO DOORS SEPARATING THE GARAGE FROM THE CORRIDOR. | | | 106.1.2. | | | | | | 7) SHEET A-103A: | | | 7A) EXIT WAY# 230 IS INDICATED AS NON RATED WALLS, THE | | | MECHANICAL SHEETS INDICATE FIRE DAMPERS, SEE TABLE | | | 1016.1 FOR FIRE RATINGS. | | | | | | 8) SHEET A-103A | | | 8A) ELEVATOR LOBBY 240, THIS COMMENT WILL STAND FOR ALL | | | FLOORS WITH R1 TYPE OCCUPANCY. | | | PLEASE SEE REQUIRED 1 HOUR RATING & OPENING PROTECTION, | | | 707.14.1, TABLE 1016.1 AND THE CODE COMMENTARY FOR | | | REQUIREMENTS FOR A 1 HR FIRE RATING, THIS COMMENT WILL | | | STAND FOR ALL COMMON FLOORS. | | | | | | 8B)STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN | | | THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE | | | STAIRS FROM THE ELECTRIC ROOM PLEASE IDENTIFY WALL TYPE | | | AND HOURLY RATING, 707.4 THIS COMMENT WILL STAND FOR | | | THE COMMON FLOORS. | | | | | | 8C) STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN | | | THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE | | | STAIRS FROM WHAT APPEARS TO BE A SHAFT WITHIN THE STAIR | | | TOWER, PLEASE IDENTIFY WALL TYPE AND HOURLY RATING, | | | 707.4. THIS COMMENT WILL STAND FOR ALL COMMON FLOORS. | | | | | | 8D) LAUNDRY ROOM 235 DOES NOT HAVE A TERMINATION ROOM | | | AS REQUIRED IN 707.13.4.THE TERMINATION ROOM SHALL | | | HAVE OPENING PROTECTION NOT LESS THAN ? HOURS AND BE | | | SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. | | | | | | 8E) LAUNDRY ROOM ITSELF WOULD NORMALLY ONLY REQUIRE THE | | | WALLS TO BE SMOKE RATED, AS THE WALLS THAT ARE SHARED | | | BY THE TRAINING AND HOUSE KEEPING ROOMS, PLEASE NOTE | | | THAT NON OF THE NON-RATED WALL TYPES ARE SPECIFIED AS | | | SMOKE PARTITIONS SEE SECTION 710. IN THIS CASE THE | | | LAUNDRY ROOM WALLS THAT ARE COMMON TO THE EXIT ACCESS | | | CORRIDOR WILL NEED TO BE 1 HR FIRE RATING BECAUSE OF | | | THE R1 OCCUPANCY, TABLE 1016.1. | | | | | | 8F) DOOR 230A IS STILL PART OF THE 1 HR RATED EXIT | | | ACCESS CORRIDOR THAT LEADS TO THE VERTICAL EXIT | | | STAIRWELL, THE DOOR SCHEDULE INDICATES THIS DOOR NOT | | | RATED, PLEASE CORRECT, TABLE 1016.1/ TABLE 715.3 | | | OPENING PROTECTIVE. | | | | | | 8G) DOOR 230A APPEARS TO BE MISSING THE REQUIRED 18? ON | | | THE PULL, LATCH SIDE OF THE DOOR. | | | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM | | | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC | | | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE | | | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES | | | SHALL BE CLEAR & LEVEL. | | | | | | 8H) LAUNDRY ROOM PLAN IS MISSING THE THROUGH | | | PENETRATIONS (2-LOUVERS) IN THE RATED WALL | | | COMMON WITH THE GARAGE. OPENING PROTECTION IS REQUIRED, | | | SEE TABLE 715.3. | | | | | | 8I) BETWEEN UNITS THERE ARE QUITE A FEW WALLS THAT DO | | | NOT HAVE WALL IDENTIFICATION TAGS, | | | SEE 1207.2. THIS COMMENT WILL STAND FOR ALL | | | SHEETS. | | | | | | 9) SHEET A-103B: | | | 9A) DOOR# 237APPEARS TO BE MISSING THE REQUIRED 18? | | | ON THE PULL, LATCH SIDE OF THE DOOR. | | | 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM | | | MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC | | | OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE | | | FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES | | | SHALL BE CLEAR & LEVEL. | | | | | | 9B) LAUNDRY ROOM 238 INDICATES ON THE MECHANICAL SHEETS | | | DRYER EXHAUST PENETRATINGA 1HR FIRE RATED WALL | | | INDICATE OPENING PROTECTION, TABLE 715.3. | | | | | | | | | | | | 10) A-104A COMMON TO THE 3RD, 4TH & 5TH FLOORS. | | | 10A) ROOM# 450 VENDING / ICEAND ROOM 451LINEN ROOM | | | THIS COMMON WALL IS PART OF THE | | | 1 HR RATED CORRIDOR IS MISSING WALL TAG, TABLE 715.3. | | | | | | 10B) THE LAUNDRY ROOM DOOR IS ALSO THE LAUNDRY CHUTE | | | ACCESS DOOR REQUIRING A ? HR OPENING PROTECTIVE AND BE | | | SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF | | | SMOKE. | | | IS FOR ALL COMMON FLOORS. NOT 20 MINUTE AS INDICATED IN | | | THE DOOR SCHEDULE, PLEASE CORRECT& SEE 707.13.4. THIS | | | COMMENT IS FOR ALL COMMON FLOORS. | | | | | | 10C)THE LAUNDRY ROOM ACCESS ROOM ALSO IS MISSING THE | | | WALL RATINGS OF BOTH SHAFT ENCLOSURES IN THIS ROOM. | | | 707.4. SHAFTS. THIS COMMENT IS FOR ALL COMMON FLOORS. | | | | | | 10D)BETWEEN UNITS 433 & 436 AT THE SHOWER LOCATIONS | | | THE PLANS INDICATE A WALL TAG | | | ?OC? NON-RATED WALL. 708.1(2) , 708.3 & 708.4. | | | | | | 10E) THE UNIDENTIFIED ROOM JUST LEFT OF STAIR TOWER# 2 | | | HAS A 25X45 MECHANICAL CHASE, THE SHAFT WALLS ARE NOT | | | IDENTIFIED WITH WALL TAGS. SEE 707.4. | | | | | | 10F) PLEASE IDENTIFY THE USAGE OF ROOM LISTED ABOVE. | | | 106.1.2. | | | | | | 11) SHEET A-104B COMMON TO 3RD, 4TH & 5TH FLOORS. | | | 11A) THIS SHEET THERE ARE NO WALL TAGS IDENTIFYING WALL | | | RATINGS. TABLE 1016.1, 708.1(2), 708.3 & 708.4. | | | | | | 11B) STAIR TOWER# 1 INDICATES A SHAFT LOCATED WITHIN | | | THE STAIR TOWER, SEE 707.4 & 1019.1.2. | | | | | | 11C) PLANS INDICATE A CHASE OR SHAFT IN THE ELECTRIC | | | ROOM 402, PLEASE SEE 707.4. | | | | | | 11D)THE EAST ELECTRICAL ROOM AND STORAGE ROOM DOORS | | | AND HALLWAY DOOR DO NOT HAVE IDENTIFICATION TAGS, FIRE | | | RATINGS? THIS IS A 1HR FIRE RATED CORRIDOR. TABLE | | | 1016.1. THE CORRIDOR WIDTH IN THE UPPER DETAIL IS NOT | | | PROVIDED?CONSIDER DOOR WIDTH VERSES CORRIDOR WIDTH. | | | 1005.2DOOR ENCROACHMENT. | | | | | | 12) SHEET A-105A: | | | 12A) NO ROOF ACCESS SEE COMMENT (3M) FOR STAIR ACCESS | | | TO ROOF. 1009.12. | | | | | | 13) SHEET A-105B: | | | | | | 13A) THE STAIRWELL# 2 IS NOT DEPICTED AS GOING THROUGH | | | TO THE ROOF LEVEL,SEE 1009.12. | | | | | | | | | 13B) THERE IS NO ROOF PLAN OF STAIR# 2 INDICATING THAT | | | DOES GO TO THE ROOF AND DOOR TO THE | | | ROOF LEVEL, THE DOOR SCHEDULE ALSO WILL NEED TO REFLECT | | | THIS DOOR AND FIRE RATING, 106.1.2, | | | & TABLE 715.3 OPENINGPROTECTION. | | | | | | 14) SHEET A-202, A-203 & A-204 ALL FAIL TO INDICATE THE | | | STAIRWELL# 2 CONTINUING THROUGH TO THE ROOF LEVEL. | | | ADDITIONAL INFORMATION REQUIRED, 106.1.2 & 1009.12. | | | | | | 15) SHEET A-307 DETAIL# 2 ON THE MEZZANINE AND 2ND | | | FLOOR LEVELS INDICATE WHAT APPEARS TO BE CONCRETE KNEE | | | WALLS WHERE IS THIS CUT SECTION TAKEN, SHEETS A-102A, | | | A-102B, A-103A | | | & A103B ALL INDICATE A 1HOUR RATED BLOCK WALL? | | | ADDITIONAL INFORMATION REQUIRED 106.1.2. | | | | | | 16)SHEET A-402 BUFFET PLEASE INDICATE COMPLIANCE WITH | | | 11-5.2, 11-5.4&11.5.5. | | | | | | 17)SHEET A-428 INDICATES THE USE OF A FIRE SHUTTER AT | | | THE ELEVATOR LOBBYPLEASE PROVIDE INFORMATION ON THE | | | RATING OF FIRE SHUTTER AND COMPLIANCE WITH 715.3.9. | | | | | | 18) SHEET A-429, A-430 &A-431 BOTH FAIL TO INDICATE | | | OPENING PROTECTION AT THE ELEVATOR LOBBY.PLEASE SEE | | | 707.14.1. | | | | | | 19) SHEET AR 401 DETAIL 3 INDICATES THE USE OF ACRYLIC | | | PANELS PLEASE PROVIDE THE AREA WHERE THIS CEILING WILL | | | TAKE PLACE AND HOW IT WILL BE HUNG? PLEASE PROVIDE THE | | | SMOKE DEVELOPMENT AND FLAME SPREAD FOR THIS PRODUCT IN | | | THIS APPLICATION. TABLE 803.5 & 803.1. | | | | | | 20)PROVISO: EXTERIOR LIGHT GAUGE METAL FRAMING TO BE | | | SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE | | | DESIGNER OF RECORD REVIEW AND APPROVAL. | | | | | | 21)A-511 FIN WALL DETAIL# 9 INDICATES THAT THE | | | FINWALL FRAME IS TO BE ATTACHED TO THE STRUCTURE PER | | | NOA REQUIREMENTS,THERE IS NO FIN WALL LISTED UNDER | | | EITHER MIAMI-DADE OR | | | THE FLORIDA STATE WEB SITE.THE PRODUCT TESTING REPORT | | | WILL NEED TO HAVE THIS TYPE WINDOW APPLICATION TESTED | | | AND SHOW THE REQUIRED ANCHORAGE. | | | 1714.5.4.1. WINDOW AND DOOR ASSEMBLIES SHALL BE | | | ANCHORED IN ACCORDANCE WITH THE PUBLISHED | | | MANUFACTURER?S RECOMMENDATIONS TO ACHIEVE THE DESIGN | | | PRESSURE SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED | | | FOR SUBSTRATES NOT SPECIFIED BY THE FENESTRATION | | | MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING | | | PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING | | | PRACTICE. | | | | | | 22)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE | | | DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE | | | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS | | | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF | | | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE | | | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES | | | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH | | | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS | | | OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE | | | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. | | | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE | | | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST. | | | 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1 | | | M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL | | | MISSILE TEST. | | | | | | | | | FL BLD CODE 1609.1.4: COMPONENTS & CLADDING, | | | PROVIDE 2 COPIES, | | | 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING | | | REPORTS, MISSING REPORTS ARE AS FOLLOWS: | | | 22A) STOREFRONT UNITS- OK COMPLIED | | | 22B) FIXED WINDOWS- TRACO WINDOWS DID NOT MEET THE -89 | | | IN END ZONES | | | 22B) HORIZONTAL SLIDING UNITS TRACO- CIRCLE GLAZING | | | TYPE FOR PRESSUES | | | 22C) FINWALL WINDOW SYSTEMS- NO REPORT SUBMITTED | | | 22D) MULLIONS- PGT MULLIONS CIRCLE MULLION LENGTHS TO | | | BE USED/ FOR PRESSURES | | | 22E) WALL LOUVERS- OK REVIEWED | | | 22F)EXTERIOR HOLLOW METAL DOORS, SINGLE & PAIR OF | | | DOORS | | | 22G) EXTERIOR AUTOMATIC SLIDING DOORS- OK REVIEWED | | | 22H) EXTERIOR GLAZED SWING DOORS- OK COMPLIED | | | 22I)PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED | | | 22J) ROOFING ASSEMBLIES- CARLISLE REPORT, REQUIRES | | | SHOP DRAWINGS AND AN APPROVED ROOFING | | | CONTRACTOR TO BE SIGNED ON. | | | | | | 23) FOR FLAT ROOF THESE ARE THE MOST COMMON MISTAKES IN | | | SUBMITTING ROOFING REPORTS | | | _XX__ THE SUB-SYSTEM PROVIDED IN THE REPORT IS NOT | | | HIGHLIGHTED. | | | __XX__ THE SUB-SYSTEM PICKEDHAS A LOWPRESSURE FOR | | | ZONE _2&3__ . | | | __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD | | | THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS | | | DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER | | | SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA | | | REGISTEREDPROFESSIONAL ENGINEER, REGISTERED | | | ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE | | | SUBMITTED. | | | __XX_ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO | | | ENHANCED FASTENING ALLOWED. | | | | | | 24)PRODUCT APPROVALS SUBMITTED WITH PERMIT | | | APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO | | | COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR | | | INFORMATION PLEASE SEE THE STATE WEBSITE AT | | | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE | | | APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER | | | SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE | | | STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL, | | | SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR | | | SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT. | | | WWW.FLORIDABUILDING.ORG | | | | | | 25) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 26) S-207 EAST ELEVATION PRESSURES ARE NOT PROVIDED FOR | | | WALL LOUVER AT EAST LOWER LEFT | | | ELEVATION. | | | | | | 27) NOTE: AWNINGS REQUIRE A SEPARATE PERMIT. WILL NOT | | | BE PART OF THIS REVIEW. | | | | | | 28)SHEET A-711/ ELEVATORS: | | | 28A)BUILDINGS 4 STORIES IN HEIGHT, AT LEAST ONE | | | ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT | | | EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CARS | | | SHALL BE OF SUCH SIZE AND ARRANGEMENT TO ACCOMMODATE A | | | 24-INCH BY 76-INCH AMBULANCE STRETCHER IN THE | | | HORIZONTAL, OPEN POSITION AND SHALL BE IDENTIFIED BY | | | THE INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES | | | (STAR OF LIFE). | | | | | | 28B)THERE IS NO FIRE ALARM PLANS AND THE ELECTRICAL | | | PLANS DO NOT INDICATE THE USE OF SMOKE DETECTORS IN | | | EACH LEVEL OF THE ELEVATOR LOBBIES NOR IN THE MACHINE | | | ROOM. PLEASE SEE 3002.8. | | | ALSO SEE THE REQUIREMENTS FOR IF HOIST-WAY IS OR IS NOT | | | FIRESPRINKLED. | | | | | | 28C)PLEASE SEE REQUIREMENTS FOR ELEVATOR VENTING FOR | | | R! OCCUPANCIES 3 STORIES AND GREATER.3004.2 LOCATION | | | OF VENTS | | | 3004.3 AREA OF VENTS | | | | | | 29) SHEET A-513: | | | 29A) PLANS FAIL TO INDICATE THE USE OF FIRE SPRINKLERS | | | AS REQUIRED IN 707.13.6 & 903.2.10.2. | | | | | | 29B) PLANS INDICATE 2 SHAFTS IN THIS PLAN BOTH | | | INDICATING THEY ARE 2 HR CONSTRUCTION, PLEASE PROVIDE | | | AN ASSEMBLY NUMBER FORTHESE SHAFTS. 707.4. | | | | | | 30) FP-205: | | | 30A) FP-205A IS THE FIRE SPRINKLER PLAN FOR THE ROOF | | | LEVEL WEST PORTION OF THE BUILDING, NO INFORMATION IF | | | FIRE SPRINKLERS WILL BE IN THE ELEVATOR SHAFT. | | | | | | 30B) FP-205B THIS SHEET IS MISSING TOTALLY, STAIRWELL | | | AND STANDPIPE THAT PROVIDES ROOF ACCESS. | | | | | | 31) PLEASE COORDINATE PLANS BETWEEN A-101A AND FP-201 A | | | DOOR 114 ON THE FP SWINGS AGAINST THE EGRESS FLOW, SEE | | | 1008.1.2. | | | | | | 32) PLEASE PROVIDE FIRE ALARM INFORMATION 907.2.10.1.1. | | | / 106.3.5.1.1(5) & (6) EARLY WARNING SYSTEMS. WILL ALSO | | | REQUIRE A SEPARATE PERMIT AND REVIEW NOT UNDER THIS | | | PERMIT. | | | | | | A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A | | | RESULT OF THE ADDITIONAL INFORMATION REQUESTED | | | ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF | | | THIS REVIEW. | | | | | | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS | | | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF | | | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST | | | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT | | | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC | | | REQUIREMENT, THE SPECIFIC | | | REQUIREMENT SHALL BE APPLICABLE. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. | | | | | | | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
33 |
Status |
P |
Date |
2009-05-20 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-20 |
Time |
19:59 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-20 |
Time |
19:59 |
Sent To |
FIRE |
|
| Notes |
| 2009-05-20 20:00:28 | ASKING FOR FIRE TO CONFIRM THAT THEY REQUESTED/APPROVED | | | RELOCATION AND REMOVAL OF EXIT SIGNAGE AND WALL PACKS. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
32 |
Status |
F |
Date |
2009-05-18 |
|
|
Cont ID |
|
| Sent By |
dwise |
Date |
2009-05-18 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
dwise |
Date |
2009-05-12 |
Time |
08:58 |
Sent To |
|
|
| Notes |
| 2009-05-18 09:00:32 | HOLDING FOR CORRECTIONS TO PLANS. REVISIONS CLOUDED BY | | | HAND NOT SIGNED BY DESIGN PROFESSIONAL. SPOKE WITH EOR, | | | WILL OVERNIGHT CLOUDED "AS-BUILT" ELECTRICAL REVISIONS | | | DIRECTLY TO ME. DBW |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
31 |
Status |
P |
Date |
2009-02-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-17 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-17 |
Time |
14:13 |
Sent To |
PC |
|
| Notes |
| 2009-02-17 14:16:05 | REVISED COORDINATION STUDY AND SHORT CIRCUIT | | | CALCULAITONS. OK. | | | | | | OK FOR TCO AND STILL NEED FINAL REVISED PLANS AND | | | ENERGY CALCULATIONS BEFORE FINAL. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
30 |
Status |
F |
Date |
2009-02-16 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-16 |
Time |
10:47 |
Rev Time |
3.00 |
| Received By |
dpalmer |
Date |
2009-02-16 |
Time |
10:47 |
Sent To |
PC |
|
| Notes |
| 2009-02-16 10:47:30 | ** DENIED REVIEW ** | | | | | | ** REVISIONS | | | | | | | | | 1) NOTE: ALL SUBMITTED REPORTS FOR COORDINATION STUDY | | | AND SHORT CIRCUIT CALCULATIONS NEED TO BE SIGNED, DATED | | | AND SEALED BY THE ENGINEER OF RECORD. | | | FAC 61G15-23.002 | | | FS 471.023 | | | | | | 2) NOTE: THE COORDINATION STUDY NEEDS TO INCLUDE ALL | | | EQUIPMENT/PANELS/MAIN BREAKERS AND CONDUCTORS FOR LIFE | | | SAFETY (700 SYSTEMS) AND LEGALLY REQUIRED (701) | | | SYSTEMS. 700.27,701.18 AND 240.12. THIS IS IMPERATIVE | | | FOR THESE SYSTEMS TO COORDINATE. AT ANY GIVEN POINT THE | | | LACK OF COORDINATION COULD RESULT IN A LOSS OF AN | | | ENTIRE PANEL, MULTIPLE PANELS OR AN ENTIRE EMERGENCY OR | | | LEGALLY REQUIRED SYSTEM. | | | PLEASE SEE THE FOLLOWING ITEMS WHICH COULD NOT BE FOUND | | | IN THE COORDINATION STUDY. THERE WILL BE COMMENTS BELOW | | | ALSO WITH RESPECT TO THE SHORT CIRCUIT CALCULATIONS AND | | | ANALYSIS. | | | | | | A) PLEASE SEE PANEL ELSW2 IS NOT LOCATED IN THE | | | COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION | | | ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. | | | | | | B) PLEASE SEE PANEL EMLW2 IS NOT LOCATED IN THE | | | COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION | | | ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION. | | | | | | C) PLEASE BE SURE TO INCLUDE THE LARGEST CIRCUIT | | | CONTRIBUTION IS INCLUDED ON BOTH OF THESE PANELS. | | | | | | D) MSB IS NOTED AS MDP. (SAME HOWEVER ONLY MISPRINTED | | | FOR IDENTIFICATION). | | | | | | E) PLEASE INCLUDE CONDUCTOR CONTRIBUTION FOR ALL | | | EQUIPMENT. THE CONDUCTORS ARE NOTED FOR EDPLS, TLSE2 | | | FEEDER, CONDUCTORS FOR ELSE2 AND FIRE PUMP. HOWEVER | | | WHERE ARE THE OTHERS? | | | | | | F) PLEASE ALSO SEE MISSING TLSW-2. | | | | | | 3) NOTE: PLEASE BE SURE THE SHORT CIRCUIT CALCULATIONS | | | SCHEDULE ALSO COORDINATES WITH THE IDENTIFICATION OF | | | ALL EQUIPMENT ON THE STUDY AND THE PLANS. THE SHORT | | | CIRCUIT CALCULATIONS WILL BE NOTED AS SCC FOR THE | | | REMAINDER OF THESE COMMENTS. SAME CODE SECTIONS AS | | | NOTED ABOVE. | | | | | | FOR EXAMPLE: THE LIST OF PANELS AND EQUIPMENT ON THE | | | THIRD PAGE OF THE SCC IN INDICATES AN ELSE3, YET THERE | | | IS NO SUCH EQUIPMENT NOTED ON PLANS OR COORDINATION | | | STUDY. | | | THE RISER AT THE BACK OF THE SCC ALSO DOES NOT INCLUDE | | | THIS ELSE3 PANEL. IF THIS IS REALLY THE ELSW2 PANEL, | | | PLEASE ADJUST BOTH THE SCC AND THE SCC RISER. | | | | | | FOR EXAMPLE: THE LIST ON THIS SAME PAGE THREE OF THE | | | SCC DOES NOT LIST EMLW2. THE RISER ON THE BACK OF THE | | | SCC DOES INCLUDE THIS EMLW2 PANEL. | | | | | | | | | **THE COMMENTS ABOVE IN NOTE #2 ALREADY GIVE THE NOTE | | | WITH RESPECT TO THE COORDINATION STUDY MISSING THE | | | ELSW2 AND EMLW2. | | | | | | 4) NOTE: PLEASE IDENTIFY RECEPTACLES NOTED ON PANEL | | | SCHEDULE EMLW2 FOR CIRCUITS 15, 17 /19. THE SCHEDULE | | | INDICATES REC HOWEVER THE INFORMATION ON THE RISER | | | ACTUALLY SHOWS THESE AS CIRCUITS TO THE GENERATOR. THE | | | OCP FOR CIRCUIT 17/19 SEEMS TO BE A LARGER BREAKER OR | | | CIRCUIT WHICH WILL BE A REVISED PORTION OF THE STUDY. | | | THIS NEEDS TO BE VERIFIED BEFORE REVISED THE | | | COORDINATION STUDY. | | | 408.4 | | | FBC 106.1.1, 106.5 FOR CLARITY, COORDINATION OF RECORD | | | PLANS. | | | | | | 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL | | | CHANGES WITH RESPECT TO PLANS FROM AIC RATINGS, | | | CONDUCTORS ETC FROM PREVIOUS PLANS A NEW ELECTRICAL | | | INSPECTION WILL BE REQUIRED BEFORE THE TCO. | | | | | | | | | 6) NOTE: SHEETS E-102A, 102B, 103A ,203 AND 204 ARE OK. | | | THESE SHEETS RETAINED FOR FILE. | | | THE OTHER SHEETS SUCH AS RISER, AND PANEL SCHEDULE | | | SHEETS NEED TO BE BROUGHT BACK IN IF THEY ARE NOT | | | REVISED. | | | | | | *** ALL COMMENTS WERE GONE OVER WITH THE ENGINEER OF | | | RECORD. THE ORIGINAL COMMENTS E-MAILED TO THE ENGINEER | | | HAVE BEEN ADJUSTED FOR THESE POSTED NOTES. ONE COMMENT | | | WAS REMOVED AS THE PRINTED SHEET WAS NOT EASILY | | | READABLE AND ENGINEER CLARIFIED INFORMATION. THE | | | COMMENT #4 ABOVE WAS REVISED ALSO FOR MORE INFORMATION | | | AND COORDINATION NEEDED. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
29 |
Status |
F |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-02-12 |
Time |
18:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-02-12 |
Time |
18:03 |
Sent To |
|
|
| Notes |
| 2009-02-12 18:03:44 | ** DENIED REVIEW ** | | | | | | REVISION #9 | | | | | | 1) NOTE: PLANS SUBMITTED WERE FOR REVISION #9 WHICH WAS | | | FOR NEW SUPPLY FAN AND EXHAUST FANS ADDED. IN THE | | | REVIEW OF PAGE E-502 A REVISION #8 WAS LOCATED ON PANEL | | | SCHEDULE ELSW2 FOR CO CONTROL PANEL. HOWEVER A REVISION | | | #8 WAS NEVER SUBMITTED AND THE REVISED PLANS SHOWING | | | REVISIONS UP THROUGH REVISION #9 DOES NOT SHOW OR | | | INDICATE THIS NEW CO PANEL. | | | AS PLANS FOR ALL REVISED PANELS SHOWING ALL REVISED | | | LOADS WERE NOT SUBMITTED THESE OTHER ITEMS COULD NOT BE | | | REVIEWED. | | | SPOKE TO KAST CONSTRUCTION REPRESENTATIVE ON THE PHONE | | | AND REVISED ELECTRICAL SHEETS FOR FANS WILL NOT BE | | | NEEDED AT THIS TIME. FIELD INSPECTION WAS DONE AND FANS | | | ARE ALREADY TESTED BY INSPECTORS. THIS IS ALSO TO BE | | | VERIFIED WITH THE ELECTRICAL INSPECTOR. | | | THESE WILL BE PART OF REVISIONS TO BE SUBMITTED ON | | | 2/13/09. | | | | | | ** A CALLED BY PLACED TO TLC ENGINEERS @ 5:55PM TO GO | | | OVER COMMENTS. A MESSAGE WAS LEFT ON VOICE MAIL BRIEFLY | | | EXPLAINING THESE ITEMS AND TO RETURN PHONE CALL TO THIS | | | OFFICE. | | | | | | 2) NOTE: PLEASE BE SURE TO COORDINATE ALL REVISED | | | SHEETS TO DATE WHEN SUBMITTING REVISED PLANS AND | | | COORDINATION STUDY FOR REVIEW. | | | | | | | | | ** IMPORTANT ** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
28 |
Status |
F |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
12:00 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:40 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 12:01:03 | *** DENIED*** | | | | | | | | | 1) NOTE: THE LOCATION NOTES OF T-STAT DEVICE E528 ON | | | ENLARGE GUEST ROOM LIGHTING CONTROLS PLANS NEED TO BE | | | UPDATED OR REMOVED. THE NOTES STATE THE DEVICE BY THE | | | DOOR DOES NOT PROVIDE COVERAGE AND NOTES AN ADDITIONAL | | | DEVICE IS NEEDED FOR FULL COVERAGE. AFTER A PHONE | | | MEETING WITH ELECTRICAL DESIGNERS AS WELL AS THE | | | LIGHTING SYSTEM MANUFACTURE IT WAS STATED THE SWITCH | | | DEVICES AT BED LOCATIONS ALSO ACT AS AN OVER RIDE | | | WHETHER OR NOT THE T-STAT/E528 DEVICE SENSES AN | | | OCCUPANT OR NOT. | | | THE NOTES ON THESE SHEETS WILL BE UPDATED. | | | 13-415.1.ABC.1, NFPA-101 7.8 | | | | | | 2) NOTE: AS NOTED ON PREVIOUS SUBMITTAL REVIEW OF POOL | | | HEATER THIS UNIT IS NOT LISTED ON THE INPUT DATA REPORT | | | OF THE SUBMITTED CALCULATIONS. | | | 13-412, 13-400.A.3 | | | THERE ARE OTHER ITEMS WITH THE SUBMITTED CALCULATIONS | | | WHICH ARE NOT COORDINATING WITH PLANS. FIXTURE TYPE T | | | APPEARS TO BE OVER ALONG WITH M HOWEVER OTHER FIXTURES | | | AS R/RE APPEAR TO BE A LITTLE UNDER. | | | PLEASE VERIFY EXTERIOR LIGHTING AS INSTALLED IN THE | | | FIELD WITH WHAT IS SHOWN ON PLANS AND IN THE | | | IDR.13-415.2.ABC.1.3 | | | | | | 3) NOTE: AS NOTED IN PREVIOUS SUBMITTED THERE ARE NOTES | | | PERTAINING TO THE AIC RATINGS OF SOME PANELS/BREAKERS | | | INSTALLED AND NOTED ON SHOP DRAWINGS. THESE ITEMS NEED | | | TO BE CONFIRMED THEY HAVE BEEN CORRECTED AND NOT | | | CHANGED ANY BREAKERS ETC FROM THE PREVIOUS COORDINATION | | | STUDY SUBMITTED. | | | ANY CHANGES WITH A LOWER RATING WHICH WOULD AFFECT THE | | | COORDINATION OF ANY LIFE SAFETY OR LEGALLY REQUIRED | | | SYSTEM WOULD NEED TO BE ADDRESSED AT THIS TIME. | | | 240.12, 700.27, 701.18 | | | | | | 4) NOTE: THE FIXTURE ON THE SECOND LEVEL PARAPET WALL | | | MAY BE OVER THE ACTUAL PROPERTY LINE IF MOUNTED ON THE | | | NORTH WALL. PLEASE VERIFY. | | | | | | 5) NOTE: PLEASE BE SURE TO REVISE ALL CIRCUITING, | | | EQUIPMENT AND ITEMS ADDED FOR POOL PANEL. AN EXAMPLE IS | | | THE NEW SUBMITTAL FOR ELECTRIC POOL HEATER WHICH IS NOT | | | ON PANEL PL. | | | PLEASE REVISE ALL LOADS ETC. | | | 220,408,310.16,240.4 ETC | | | FBC 106.5, 106.1.1 FOR COORDINATION AND CLARITY OF | | | RECORD PLANS. | | | | | | | | | | | | ** ONCE NOTES FOR SUBMITTALS AND ITEMS ABOVE HAVE BEEN | | | ADDRESSED SOME SHEETS IN SETS MAY NOT NEED TO BE | | | REVISED. SHEETS WHICH DO NOT NEED REVISIONS SHOULD BE | | | BROUGHT BACK IN WITH OTHER REVISED ITEMS. | | | | | | | | | FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
27 |
Status |
F |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:40 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:26 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:40:39 | *** DENIED*** | | | | | | POOL PAK HEATER | | | | | | 1) NOTE: THE SUBMITTAL FOR THIS ITEM WAS NOT STAMPED OR | | | REVIEWED BY THE ELECTRICAL ENGINEERING FIRM/DESIGNER OF | | | RECORD. COMMENTS WILL ALSO BE MADE AT THIS HEATING UNIT | | | IS NOT INCLUDED WITH THE SUBMITTED ENERGY CALCULATIONS. | | | FBC13-412, 13-412.1.ABC.3 EQUIPMENT PERFORMANCE | | | STANDARDS. | | | THE SPECS SUBMITTED CONTAIN IDENTIFICATION OF MULTIPLE | | | VOLTAGES. SOME SHEETS HAVE SOME HAND DRAWN CORRECTIONS | | | AND OTHER SHEETS STILL HAVE 460/480V CIRCLED. PLEASE | | | COORDINATE THESE ITEMS | | | PLEASE SEE 13-412.1.ABC.3. WHERE DO THE SUBMITTED | | | DOCUMENTS SHOW ANY INFORMATION OR COMPLIANCE WITH THIS | | | TABLE FOR MINIMUM REQUIREMENTS? | | | | | | FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS. | | | | | | | | | | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
26 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:20 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:24:57 | *** NOTED *** | | | | | | GROUNDING AND BONDING FITTINGS AND CONNECTORS. | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | DEVICES AS SHOWN ARE OK | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
25 |
Status |
F |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:18 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:13 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:20:23 | *** NOTED *** | | | | | | CABLES, WIRE NUTS, WIRE CONNECTORS ETC | | | | | | 1) NOTE: THE SUBMITTAL CONTAINS NOTES FROM THE | | | ENGINEERING FIRM WHICH STATES MC CABLE WAS NOT | | | SPECIFIED. THE INSTALLATION AND USE IS BY DESIGN, | | | LOCATIONS BY NEC AND CONTRACTOR. | | | THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED OR | | | NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR THESE | | | TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN | | | WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
24 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:08 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:12:58 | *** NOTED *** | | | | | | BROAD BAND SYSTEM, FITTINGS AND CABLES | | | | | | 1) NOTE: THE PRODUCRT DATA SUBMITTED FOR TYPE OF CABLE | | | DOES INDICATE IF PLENUM RATED. THE INSTALLATION IN | | | FILED MAY BE INSTALLED IN CONDUIT. THIS SHALL BE FEILD | | | VERIFIED FOR TYPE OF CABLE AND METHOF OF INSTALLATION. | | | | | | 2) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
23 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:06 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:08:05 | *** NOTED *** | | | | | | SLEEVE SEALS | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
22 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
10:00 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:03:56 | *** NOTED *** | | | | | | HANGERS AND SUPPORTS | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
21 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:59 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:56 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 10:00:36 | *** NOTED *** | | | | | | RACEWAYS AND BOXES | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
20 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:44 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:40 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:44:38 | *** NOTED *** | | | | | | ENCLOSED SAFETY SWITCHES | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
19 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:36 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:38:31 | *** NOTED *** | | | | | | TRANSFORMERS | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
18 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:32 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:34:44 | *** NOTED *** | | | | | | STRUCTURED CABLING SYSTEM | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR | | | THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE | | | RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING | | | FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
17 |
Status |
F |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:23 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:18 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:29:12 | *** NOTED *** | | | | | | SWITCH BOARD | | | | | | 1) NOTE: THE SUBMITTAL FOR THE SWITCH BOARD WOULD NEED | | | TO CORECTED AS NOTED BY THE ENGINEERING FIRM. THE | | | SUBMITTAL IS NOT REQUIRED HOWEVER MAY BE PART OF THE | | | RECORD PLANS IF CORRECTED AS NOTED. THE PLANS SHOWS THE | | | SAME INFORMATION. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
16 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:15 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:16:51 | *** NOTED *** | | | | | | IDENTIFICATION METHODS/IDENTIFICATION | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUEST TO BE | | | PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN WITH | | | ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
15 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:12 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:13:12 | *** NOTED *** | | | | | | TRANSIENT VOLTAGE SURPRESSORS | | | | | | 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED | | | OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUEST TO BE | | | PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN WITH | | | ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
14 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:06 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:03 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:07:43 | *** NOTED *** | | | | | | MOTOR CONTROLLERS | | | | | | 1) NOTE: THE SUBMITTAL FOR THE MOTOR CONTROLERS DEVICES | | | ARE NOT REQUIRED OR NEEDED BY THIS OFFICE. IF | | | CONTRACTOR REQUEST TO BE PART OF SUBMITTALS FOR RECORD | | | PLANS PLEASE RETURN WITH ANY CORRECTIONS AS NOTED BY | | | THE ENGINEERING FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
13 |
Status |
N |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
09:03 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
09:01 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 09:03:38 | *** NOTED *** | | | | | | WIRING DEVICES | | | | | | 1) NOTE: THE SUBMITTAL FOR WIRING DEVICES ARE NOT | | | REQUIRED OR NEEDED BY THIS OFFICE. IF CONTRACTOR | | | REQUEST TO BE PART OF SUBMITTALS FOR RECORD PLANS | | | PLEASE RETURN WITH ANY CORRECTIONS AS NOTED BY THE | | | ENGINEERING FIRM. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
12 |
Status |
F |
Date |
2009-01-31 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-31 |
Time |
08:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-31 |
Time |
08:41 |
Sent To |
PC |
|
| Notes |
| 2009-01-31 08:58:31 | *** DENIED *** | | | | | | PANEL BOARD/ BREAKERS SUBMITTAL. | | | | | | 1) NOTE: PLEASE CORRECT THE SUBMITTALS AS NOTED BY THE | | | ENGINEERING FIRM. THERE ARE SEVERAL ITEMS WHICH DO NOT | | | COORDINATE WITH PLANS. IF AIC RATINGS ARE BEING REVISED | | | ON THE ACTUAL EQUIPMENT INSTALLED IN FIELD THEN IT WILL | | | BE REQUIRED TO REVISE THE COORDINATION STUDY. | | | THE RATINGS ON EMERGENCY EQUIPMENT, PANELS AND BREAKERS | | | PER 240.12, 700.27, AND 701.18 ARE REQUIRED AS A LIFE | | | SAFETY REQUIREMENT. | | | ** IMPORTANT** | | | THERE ARE OTHER ITEMS ON THE SUBMITTALS WHICH ARE NOT | | | NOTED BY ENGINEERING FIRM WHICH DO NOT COORDINATE WITH | | | PLANS. AN EXAMPLE IS THE RATINGS OF BREAKERS IN SOME | | | PANELS. ONE WOULD BE THE PLANS ON REV #7 SUBMITTED | | | CONTAINS A 2-POLE 80AMP BREAKER ON PANEL HP2LW (SECT 1) | | | FOR AHU #6, HOWEVER THE ITEM #16 FOR THIS SAME PANEL ON | | | SUBMITTALS DOES NOT INDICATE THIS BREAKER. | | | THIS IS ONE EXAMPLE ONLY. | | | | | | FBC 106.1.1 FOR COORDINATION WITH PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
11 |
Status |
F |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-29 |
Time |
19:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-29 |
Time |
19:20 |
Sent To |
PC |
|
| Notes |
| 2009-01-29 19:20:38 | *** DENIED *** | | | | | | 1) NOTE: LIGHTING SUBMITTALS FOR INTERIOR LIGHTING IN | | | GUEST ROOMS CONTAINS GENERAL NOTES WITH RESPECT TO THE | | | INNCOM LIGHTING SYSTEM. | | | THE GENERAL NOTES STATES THE T-STAT E528 DEVICE WILL | | | NOT PROVIDE SUFFICIENT COVERAGE FOR THE CONTROL OF | | | LIGHTING IN ROOMS BASED ON THE LOCATION AS SHOWN. THE | | | NOTE ALSO STATES AN ADDITIONAL K594 DEVICE WOULD BE | | | REQUIRED FOR FULL COVERAGE. THE DEVICE SCHEDULE HOWEVER | | | DOES NOT CONTAIN ANY ADDITIONAL DEVICE FOR REQUIRED | | | COVERAGE. | | | THE LIGHTING SUBMITTAL SUBMITTED BY THE CONTRACTOR DOES | | | HOWEVER INDICATE THE T-STAT E528 DEVICE IN A DIFFERENT | | | LOCATION WHICH IS MORE CENTRAL TO ROOM. PLEASE | | | COORDINATE THE ELECTRICAL PLANS AS THESE ARE THE FINAL | | | DESIGN DOCUMENTS FOR THE ROOM. | | | IF AN OCCUPANT IS LOCATED IN BED AREA AND THE T-STAT | | | WHICH IS LOCATED AT THE DOOR DOES NOT PROVIDE COVERAGE | | | THEN AN OCCUPANT WOULD NOT BE ABLE TO TURN LIGHTING FOR | | | EGRESS AROUND THE GUEST ROOM OR EGRESS OUT OF THE ROOM. | | | FBC 13-415.1.ABC.1.3, NFPA-101 7.8 | | | | | | FBC 106.1.1 FOR COORDINATION WITH PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
10 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-29 |
Time |
18:31 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-29 |
Time |
18:31 |
Sent To |
PC |
|
| Notes |
| 2009-01-29 18:32:25 | LIGHTING CONTROLS SUBMITTAL. OK. STAMPED AND RETAINED | | | ONE COPY FOR FILE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
9 |
Status |
P |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-29 |
Time |
17:48 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-29 |
Time |
17:48 |
Sent To |
PC |
|
| Notes |
| 2009-01-29 17:51:43 | SUBMITTAL FOR GENERATOR AND ATS DEVICES. | | | REDLINED THE *EMERGENCY DISCONNECT* IN SUBMITTED. THE | | | GLASS TYPE SHUNT TRIP IS NOT A RATED DISCONNECT. THE | | | DISCONNECTTING MEANS RATED FOR THE LOAD SERVED IS | | | LOCATED ON RISER. SHOWN ON EMDP,EDPLS AND EACH BREAKER | | | ON THE GENERATOR. THIS GLASS BREAK TYPE OF BUTTON IS IN | | | ADDITION TO THE RATED DISCONNECTS AS SHOWN. | | | 230.76,230.79,225.39 ETC |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
8 |
Status |
F |
Date |
2009-01-29 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2009-01-29 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2009-01-29 |
Time |
07:30 |
Sent To |
|
|
| Notes |
| 2009-01-29 17:26:46 | *** DENIED *** | | | | | | 1) NOTE: LIGHTING SUBMITTALS FOR INTERIOR LIGHTING HAS | | | SEVERAL FIXTURES WHICH WERE REJECTED BY THE ENGINEERING | | | FIRM OF RECORD. IF THE LIGHTING SUBMITTALS ARE NOT THE | | | SAME AS PLANS THESE ARE ALSO REJECTED BY THIS OFFICE AS | | | THEY DO NOT COORDINATE WITH THE SUBMITTED PLANS. PLEASE | | | ALSO BE SURE ANY LIGHTING SUBMITTALS CONTAIN A LISTING | | | FROM A NRTL. SOME OF THE FIXTURES DO INDICATE A LISTING | | | HOWEVER NOT ALL. AN EXAMPLE OF THIS IS TYPE BR. | | | 110.3 | | | FBC 106.1.1 FOR COORDINATION WITH PLANS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
7 |
Status |
F |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-07 |
Time |
10:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-07 |
Time |
10:11 |
Sent To |
|
|
| Notes |
| 2008-11-07 10:12:41 | ** DENIED REVISIONS ** | | | | | | ** A CALLED WAS PLACED TO ENGINEER ON 11/6/08 IN THE | | | AFTERNOON HOWEVER HE WAS OUT OF THE OFFICE. SOME OF | | | THESE ITEMS WILL NEED TO BE GONE OVER. | | | | | | ** THANK YOU FOR NARRATIVE ON REVISIONS. IT IS MOST | | | HELPFUL. | | | | | | 1) NOTE: NOTED FOR INFORMATION. AS THERE ARE SEVERAL | | | LIGHTING FIXTURES ADDED AND INCLUDING REVISIONS OF THE | | | TYPES OF LIGHTING FIXTURES, PER FBC 13-415.2, | | | 13-415.2.ABC.1.1,.1.2, .1.3 AND 13-400.3A COMPLETED | | | REVISED ENERGY CALCULATIONS WILL BE REQUIRED. THIS | | | SHOULD BE SUBMITTED ONCE ALL KNOWN COMPONENTS TO | | | BUILDING ARE COMPLETED. | | | | | | 2) NOTE: PLEASE KNOW FOR ITEMS SUCH AS CAMERAS AND | | | OTHER LOW VOLTAGE WHICH WAS NOT PART OF ORIGINAL PLANS | | | NEED TO BE PERMITTED. THE VALUE FOR THESE ITEMS IN THE | | | SCOPE OF WORK NEEDS TO BE APPLIED TO LOW VOLTAGE | | | PERMITS REQUIRED. | | | 105.1, 108.3. | | | NEC 800 | | | | | | ** AS OF THIS REVIEW ONLY THE LOW VOLTAGE FOR DATA AND | | | CATV HAS BEEN APPLIED FOR AND PERMITTED. | | | | | | 3) NOTE: PLEASE SUBMIT COMPLETED LIGHTING CONTROL PANEL | | | SCHEDULES. FOR EXAMPLE: POOL AREA LIGHTING IS ONE AREA | | | NOTED WHICH MENTIONS TO WIRE THROUGH LIGHTING CONTROL | | | PANEL HOWEVER THE PANELS SUBMITTED DO NOT INDICATE | | | THIS. THIS IS ONE EXAMPLE ONLY.. | | | 13-415.1.ABC.1.1, .1.2, .1.3. | | | | | | 4) NOTE: INFORMATION IS NEEDED FOR NEW WAP ( WIRELESS | | | ACCESS POINTS) ADDED TO PLANS. THE PLANS SPECIFICALLY | | | CALL OUT FOR *RECEPTACLES*. THIS LENDS TO THESE BEING | | | INSTALLED IN THE HALLWAYS WITH EQUIPMENT WHICH WILL BE | | | PLUGGED IN. THESE WOULD BE REQUIRED TO BE INSTALLED | | | BELOW THE CEILING HANGING IN THE HALLWAY. | | | PLEASE SEE 400.8. THE FOLLOWING HAS BEEN EXTRACTED FROM | | | THE CODE FOR REVIEW. | | | **400.8 | | | USES NOT PERMITTED | | | UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS | | | AND CABLES SHALL NOT BE USED FOR THE FOLLOWING: | | | (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE | | | (2) WHERE RUN THROUGH HOLES IN WALLS, STRUCTURAL | | | CEILINGS, SUSPENDED CEILINGS, DROPPED CEILINGS, OR | | | FLOORS | | | (3) WHERE RUN THROUGH DOORWAYS, WINDOWS, OR SIMILAR | | | OPENINGS | | | (4) WHERE ATTACHED TO BUILDING SURFACES | | | EXCEPTION TO (4): FLEXIBLE CORD AND CABLE SHALL BE | | | PERMITTED TO BE ATTACHED TO BUILDING SURFACES IN | | | ACCORDANCE WITH THE PROVISIONS OF 368.56(B) | | | SECTION 368.56(B) PROVIDES THE REQUIREMENTS FOR THE | | | INSTALLATION OF FLEXIBLE CORDS INSTALLED AS BRANCHES | | | FROM BUSWAYS. | | | (5) WHERE CONCEALED BY WALLS, FLOORS, OR CEILINGS OR | | | LOCATED ABOVE SUSPENDED OR DROPPED CEILINGS | | | (6) WHERE INSTALLED IN RACEWAYS, EXCEPT AS OTHERWISE | | | PERMITTED IN THIS CODE | | | THE FLEXIBLE CORDS AND CABLES REFERRED TO IN ARTICLE | | | 400 ARE NOT LIMITED TO USE WITH PORTABLE EQUIPMENT. | | | THEY MAY NOT BE USED, HOWEVER, AS A SUBSTITUTE FOR THE | | | FIXED WIRING OF A STRUCTURE OR WHERE CONCEALED BEHIND | | | BUILDING WALLS, FLOORS, OR CEILINGS (INCLUDING | | | STRUCTURAL, SUSPENDED, OR DROPPED-TYPE CEILINGS). SEE | | | 240.5, 590.4(B), AND 590.4(C) FOR THE USES OF | | | MULTICONDUCTOR FLEXIBLE CORDS FOR FEEDER AND | | | BRANCH-CIRCUIT INSTALLATIONS AND FOR OVERCURRENT | | | PROTECTION REQUIREMENTS FOR FLEXIBLE CORD. SEE 410.30 | | | FOR CORD-CONNECTED LUMINAIRES. | | | (7) WHERE SUBJECT TO PHYSICAL DAMAGE | | | ** | | | PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT INFORMATION. | | | | | | 5) NOTE: PLEASE SEE THE LIGHTING ON PLANS AS NOTED ON * | | | PROVISO * ISSUED WHEN PERMIT WAS ISSUED HAS NOT BEEN | | | ADDRESSED. PLEASE SEE E201 AS SOME OF THE LIGHTING | | | STILL NOT COORDINATE WITH THE LIGHTING ON THE ROOM | | | LAYOUT PLANS FOR LIGHTING CONTROLS ON E 203,204 ETC. | | | EXAMPLES ON THREE PREVIOUS REVIEWS WERE GIVEN AND THEY | | | WILL BE GIVEN AGAIN. SEE KING ACCESSIBLE, AND DOUBLE | | | QUEEN ACCESSIBLE ETC. | | | 13-415.1.ABC.1.1, .1.2, .1.3 | | | FBC 106.1.1 FOR CLARITY, COORDINATION OF PLANS. | | | *** CALL TO GO OVER THESE AS THEY CAN BE POINTED OUT. | | | | | | 6) NOTE: THE FOLLOWING SHEETS SIGNED, DATED AND SEALED | | | OCT 9TH APPEAR TO BE OK AT THIS TIME HOWEVER BASED ON | | | THE COMMENTS ABOVE THE OTHER SHEETS IN SETS MAY ALL | | | NEED REVISIONS. THE FOLLOWING SHEETS IF NO CHANGES ARE | | | MADE WILL BE STAMPED ONCE RESUBMITTED AND NO | | | CORRECTIONS ARE NEEDED. | | | PLEASE CALL TO GO OVER IF NEEDED. NO REVISION FEE WILL | | | BE CHARGED FOR THESE SHEETS WHEN BRINGING BACK | | | CORRECTED PLANS AS LONG AS NO CHANGES ARE MADE. | | | 107A, 107B, 205,301,302, AND 403. THESE SHEETS DO NOT | | | APPEAR TO NEED REVISIONS AT THIS TIME ALTHOUGH THAT MAY | | | CHANGE. | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | | **IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED | | | INTO TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT | | | TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO | | | CONTACT THIS REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
N |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-11-04 |
Time |
11:54 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-11-04 |
Time |
11:54 |
Sent To |
FIRE |
|
| Notes |
| 2008-11-04 11:55:31 | FIRE ALARM SUBMITTAL NOT REVIEWED. | | | NOT SIGNED BY ENGINEER OF RECORD. | | | SENT TO FIRE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-07-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-24 |
Time |
16:26 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-24 |
Time |
16:26 |
Sent To |
|
|
| Notes |
| 2008-07-24 16:26:47 | ** PROVISO ** | | | | | | ** PLEASE SEE THE FOLLOWING ITEMS NEED TO BE REVISED | | | AND SUBMITTED FOR REVIEW WITH IN 30DAYS OF ISSUANCE OF | | | PERMIT. IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | 1) NOTE: CARBON MONOXIDE DETECTORS REQUIRED PER RULE | | | 9B-3.0472IN UNITS. | | | | | | 2) NOTE: PLEASE SEE LIGHTING SHOWN AND IDENTIFIED ON | | | SHEET E-201 NEEDS TO COORDINATE WITH THE LIGHTING SHOWN | | | ON GUEST ROOMS. EXAMPLES OF ENLARGED KING, ACCESSIBLE | | | KING AND DOUBLE QUEEN WERE GIVEN ON PREVIOUS REVIEW. | | | PLEASE SEE THE FIXTURES SHOWN ON E-201 ARE WALL SCONCES | | | BASED ON FIXTURE IDENTIFICATION AND FIXTURE LEGEND. THE | | | GUEST ROOM LIGHTING CONTROL PLANS CALL FOR SCONCES IN | | | MANY LOCATIONS FOR GR1, GR2, GR3 ETC HOWEVER PLEASE SEE | | | SOME OF THESE ON THE GUEST ROOM LIGHTING CONTROL PLANS | | | ARE CALLING FOR *LAMPS* WITH SENSORS. TABLE LAMPS WITH | | | SENSORS ARE NOT THE SAME AS WALL SCONCES WITH A | | | LIGHTING CONTROL SYSTEM. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-07-18 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-07-18 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-07-18 |
Time |
16:20 |
Sent To |
|
|
| Notes |
| 2008-07-18 16:20:59 | * DENIED 4TH REVIEW** | | | | | | | | | | | | 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS> | | | PLEASE SEE COMPLIANCE SUMMARY ON SHEET 2 WHICH APPEARS | | | TO DROP THE 7TH DIGIT FROM THE CRITERIA. CALLED AND | | | SPOKE TO JIM MULLENS FROM TLC AND THEY WILL WORK ON | | | TRYING TO FIX THIS. | | | 13-400.3.A. | | | | | | 2) NOTE: PLEASE SEE ONE SET OF PLANS IS MISSING E201. | | | NEED THREE COMPLETE SETS. | | | FBC 106.1 | | | | | | 3) NOTE: PLEASE SEE THE LIGHTING SHOWN ON E-201 DOES | | | NOT COORDINATE WITH THE LIGHTING WHICH IS NOW SHOWN ON | | | SHEETS E 203,204,ETC. | | | FOR EXAMPLE: | | | PLEASE SEE ENLARGED KING, ACCESSIBLE KING, DOUBLE | | | QUEEN. | | | 13-415.1.ABC.1.1, .1.2 | | | | | | 4) NOTE: PLEASE KNOW THE M FIXTURES ON PHOTO-METRICS | | | ARE STILL SHOWN. THESE CAN BE REDLINED OFF THE PLANS. | | | | | | 5) NOTE: SMOKE/CARBON MONOXIDE DETECTORS WERE NOT | | | REVISED. WILL BE PART OF PROVISO. | | | | | | ** PLACED CALL TO CONTRACTOR REP AND LEFT MESSAGE. | | | | | | ** PLACED CALL TO ENGINEER WHICH IS ON VACATION. | | | ENGINEER OF RECORD WILL CALL BACK TO WORK OUT ITEMS ON | | | PLANS FOR NEW SHEETS. | | | | | | | | | | | | | | | IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-06-30 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-30 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-30 |
Time |
15:22 |
Sent To |
|
|
| Notes |
| 2008-06-30 15:23:07 | ** DENIED THIRD REVIEW ** | | | | | | PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS ARE | | | IN NEED OF ADDRESSING. | | | PLEASE SEE SOME COORDINATION OF OTHER COMMENTS BELOW | | | WITH SUPPORTING DOCUMENTS. | | | | | | 1) NOTE: THE PREVIOUS REVIEWS REQUESTED FOR SUBMITTALS | | | OF MANUFACTURES SPECS/CUT SHEETS FOR THE ATS, | | | GENERATOR, FIRE PUMP AND FIRE PUMP CONTROLLER. | | | THE RESPONSE MENTIONS TO SEE SPECS IN THE SUBMITTAL | | | BOOKS. PLEASE BE SURE TO COORDINATE SUBMITTALS. FOR | | | EXAMPLE: | | | PLEASE SEE THERE ARE TWO SUBMITTALS FOR FIRE PUMP: ONE | | | SHOWS AURORA, THE OTHER SHOWS MORSE FAIRBANKS. PLEASE | | | SEE THERE ARE TWO SUBMITTALS FOR THE FIRE PUMP | | | CONTROLLER: ONE SHOWS METRON WHICH DOES NOT INDICATE | | | ANY LISTING AND THE OTHER IS A HUBBELL FOR FIRE PUMP | | | AND JOCKEY PUMP WHICH DOES SHOW LISTING. | | | PLEASE SEE THE ATS SPECS: ONE SHOWS AN ASCO AND THE | | | OTHER A CATERPILLAR. | | | PLEASE SEE THE GENERATOR SPACES: ONE SHOWS AN ONAN AND | | | THE OTHER A CATERPILLAR. | | | | | | ** PLEASE REMOVE THE DOCUMENTS FORREVIEW AND RECORD | | | PLANS. PLEASE BE SURE THE FINAL SPECS DO CONTAIN THE | | | LISTING. IF THIS WERE THE ONLY COMMENT A REPRESENTATIVE | | | WOULD BE ABLE TO CORRECT IN OFFICE. | | | 110.3, 90.7, 695 OF NFPA-70, CHAPTER 9 AND 10. | | | FBC 106.1.1 FOR CLARITY OF CONSTRUCTION DOCUMENTS. | | | | | | 2) NOTE: PLEASE SEE THE SUBMITTED COORDINATION STUDY | | | WHICH WAS PREVIOUSLY REQUESTED. THE INFORMATION ON THE | | | STUDY DOES NOT COORDINATE WITH THE SUBMITTED ELECTRICAL | | | PLANS. PLEASE SEE SOME EXAMPLES GIVEN. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE RISER WHICH SHOWS 1-SET OF 3/0 FROM | | | GENERATOR TO FIRE PUMP YET THE COORDINATION STUDY SHOWS | | | 2-SETS OF 4/0. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE RISER SHOWS 225 FOR ATS-LS, YET THE | | | COORDINATION STUDY SHOWS 250AMPS. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THERE IS NO NORMAL FEED TO THE FIRE PUMP. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE BREAKER OR RISER FOR FIRE PUMP ON THE | | | GENERATOR IS SHOWN AS 450AMPS, YET THE COORDINATION | | | STUDY SHOWS BREAKER AT 600AMPS. | | | | | | ** THESE ARE SOME EXAMPLES. | | | | | | ** PLEASE BE AWARE THAT THESE MUST BE SIGNED, DATED AND | | | SEALED BY THE DESIGNER OF RECORD. THESE WERE NOT | | | SIGNED, DATED OR SEALED. | | | FAC61G15-23.002, 61G15-33.0002, FS 471.025 | | | NEC 240.12 | | | | | | 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO | | | *MINIMUM* LIGHTING REQUIRED FOR LIFE SAFETY. PLEASE SEE | | | NFPA-101 7.8.1.3, 7.8, 7.9, 7.9.2 | | | AS THE MINIMUM LEVELS FOR WALK AREAS (NOT STAIRS) IS | | | REQUIRED TO BE 1FT CANDLE UNDER NORMAL AS WELL AS 1FT | | | CANDLE UNDER EMERGENCY. THERE ARE SOME EXAMPLES GIVEN | | | WHICH THE LIGHTING LEVELS ARE AS LOW HALF THE *MINIMUM* | | | REQUIRED BY THE LIFE SAFETY CODE. | | | | | | FOR EXAMPLE: | | | PLEASE SEE E-101C AND E-101D CORRIDOR #149 WHICH SHOWS | | | .04 FT CANDLES YET THE MINIMUM NEEDS TO BE A MINIMUM OF | | | 1FT CANDLE. | | | | | | FOR EXAMPLE: | | | PLEASE SEE 603C, 603DAS THE LIGHTING IN AREAS 237, | | | 242 AND 230 ARE ALL BELOW THE 1FT CANDLE MINIMUM FOR | | | EMERGENCY EGRESS. THESE LEVELS ARE SHOWN AS .5 IN | | | CORRIDOR 237, .5 IN CORRIDOR 242 AND .6 INEGRESS PATH | | | 230. | | | | | | ** THESE ARE EXAMPLES GIVEN AS A BENEFIT TO DESIGN | | | TEAM. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH | | | RESPECT TO ALL LIGHTING ON PLANS AND THE NEED FOR | | | COORDINATION WITH THE SUBMITTED FLA-COM ENERGY | | | CALCULATIONS. | | | PLEASE SEE SECTIONS, 13-415.2, 13-415.2.ABC.1.1, .1.2 | | | AND .1.3. | | | THIS IS TO INCLUDE ALL INTERIOR AND EXTERIOR LIGHTING. | | | SOME EXAMPLES WILL BE GIVEN BELOW. THESE ARE GIVEN AS A | | | BENEFIT ONLY. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE EXTERIOR LIGHTS SUCH AS THE *M* FIXTURES | | | SHOWN ON PLANS ON THE SOUTH SIDEWALK YET THESE ARE NOT | | | IN ANY EXTERIOR OR INTERIOR LIGHTING IN THE INPUT DATA | | | REPORTS. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE INTERIOR ELEVATOR LOBBY MISSING THE SAS | | | FIXTURE IN THE IDR. PLEASE ALSO SEE THE SAME ARE FOR | | | THE *SP* FIXTURE COUNT. | | | ** THIS SAME AREA ON THE METHOD OF CONTROLS INDICATES | | | OCCUPANCY SENSORS YET NO OCCUPANCY SENSORS ARE SHOWN ON | | | PLANS. THIS APPEARS TO BE AN ERROR IN THE CHOICE OF | | | LIGHTING CONTROLS OPTION. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE INTERIOR LIGHTING IN THE GUEST ROOMS | | | NEED TO COORDINATE WITH THE INPUT DATA REPORT. THE | | | LIGHTING PLANS ON E-201 AND E-205 ARE NOT THE SAME. IN | | | FACT SOME EXAMPLES OF THIS WILL BE GIVEN. | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE KING SUITES.E-201 SHOWS A TOTAL OF 11 | | | FIXTURES YET THE OTHER LIGHTING PLANS FOR CONTROLS ON | | | E-205 SHOW ONLY 8 FIXTURES. | | | IN EITHER CASE THE IDR OF THE SUBMITTED ENERGY | | | CALCULATIONS ONLY SHOW 7 FIXTURES. | | | ** PLEASE LOOK AT LIGHTING PLANS FOR TYPES OF FIXTURES | | | AS THERE IS THE DIFFERENCE OF 4 FIXTURES IN EACH OF | | | THESE ALONE. | | | COORDINATE TYPES OF FIXTURES. (WALL SCONCES ETC) | | | | | | FOR EXAMPLE: | | | PLEASE SEE THE ENLARGED KING ACCESSIBLE UNIT: THIS | | | SHOWS DIFFERENT FIXTURES ON E-201 COMPARED TO FIXTURES | | | ON E-205. ALL OF THESE UNITS ALSO SHOW A LOWER NUMBER | | | OF FIXTURES ON THE IDR. IT IS NOT JUST ONE FIXTURE | | | TOTAL, IT IS ONE FIXTURE FOR EACH UNIT. | | | ** PLEASE ALSO COORDINATE TYPES OF FIXTURES. (WALL | | | SCONCES) | | | | | | ** THESE WERE S FEW EXAMPLES GIVEN AS A BENEFIT TO | | | DESIGN TEAM. THIS IS NOT ALL FIXTURES AS THERE ARE | | | OTHERS FOR OTHER UNITS WHICH E201 DOES NOT COORDINATE | | | WITH E-205. | | | | | | 5) NOTE: PLEASE BE AWARE OF NEW FLORIDA ADMINISTRATIVE | | | CODE RULE 9B-3.0472. THIS REQUIRES ALL BUILDING PERMITS | | | ISSUED AFTER JULY 1ST TO CONTAIN CO SENSORS WHEN | | | MEETING THE PROVISIONS AND DEFINITIONS AS FOLLOWS. | | | PLEASE SEE THIS RULING BECAME IN AFFECT AFTER ADOPTION | | | OF FS 553.885. | | | ** THIS CAN BE A PROVISO TO ADJUST ALL DEVICES ON PLANS | | | HOWEVER PLANS ARE GOING BACK FOR CORRECTIONS AT THIS | | | TIME. | | | | | | | | | ********** | | | | | | (1) DEFINITIONS: FORPURPOSES OF THIS RULE, THE | | | FOLLOWING DEFINITIONS SHALL APPLY: | | | (A) CARBON MONOXIDE ALARM. A DEVICE FOR THEPURPOSE OF | | | DETECTING CARBON MONOXIDE, THAT PRODUCES A DISTINCT | | | AUDIBLE ALARM,AND IS LISTED OR LABELED WITH THE | | | APPROPRIATE STANDARD, EITHER ANSI/UL 2034 -96, | | | STANDARD FOR SINGLE AND MULTIPLE STATION CO ALARMS, | | | INCORPORATED HEREIN BYREFERENCE, OR UL 2075 - 04, GAS | | | AND VAPOR DETECTOR SENSOR, INCORPORATED HEREINBY | | | REFERENCE, IN ACCORDANCE WITH ITS APPLICATION. BOTH | | | DOCUMENTS MAY BE OBTAINEDBY WRITING TO: CODES AND | | | STANDARDS SECTION, DEPARTMENT OF COMMUNITY AFFAIRS, | | | 2555 SHUMARD OAK BOULEVARD, TALLAHASSEE, FLORIDA | | | 32399-2100. | | | | | | (B) FOSSIL FUEL. COAL, KEROSENE,OIL, FUEL GASES, OR | | | OTHER PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS | | | CARBONMONOXIDE AS A BY-PRODUCT OF COMBUSTION. | | | | | | (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW | | | CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A | | | FOSSIL-FUEL-BURNINGHEATER OR APPLIANCE, A FIREPLACE, | | | OR AN ATTACHED GARAGE SHALL HAVE ANOPERATIONAL CARBON | | | MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM | | | USED FORSLEEPING PURPOSES. | | | | | | (3) IN NEWCONSTRUCTION, ALARMS SHALL RECEIVE THEIR | | | PRIMARY POWER FROM THE BUILDING WIRINGWHEN SUCH | | | WIRING IS SERVED FROM THE LOCAL POWER UTILITY. SUCH | | | ALARMS SHALL HAVEBATTERY BACK UP. | | | | | | (4)COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE | | | LISTED OR LABELED BY ANATIONALLY RECOGNIZED TESTING | | | LABORATORY. | | | SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED | | | 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS. | | | HISTORY,NEW 11-18-07. | | | | | | | | | | | | ** IMPORTANT** | | | ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP | | | FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE | | | ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED | | | SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. | | | DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID | | | ANY DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-05-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-02 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-02 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2008-05-02 16:08:01 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL | | | IN NEED OF ADDRESSING. | | | **PLEASE ALSO KNOW THERE ARE SEVERAL NEW COMMENTS DUE | | | TO DOCUMENTS SUBMITTED ALONG WITH NEW COMMENTS DUE TO | | | SOME NEW CODE INFORMATION. | | | | | | 1) NOTE: PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND | | | ALL SUPPORTING DOCUMENTS FOR REVIEW AND STAMPING. | | | PLEASE KNOW ONLY TWO BINDERS WITH RESPONSES, SPECS, | | | PRODUCT APPROVAL ETC WERE SUBMITTED. THREE DIVISION | | | SPEC BOOKS WERE SUBMITTED AND THREE SETS OF PLANS | | | HOWEVER ONLY TWO OTHER BOOKS AS MENTIONED. | | | THIS IS A THRESHOLD PROJECT. | | | FBC 106.1, ETC FOR ADDITIONAL INFORMATION AND | | | COORDINATION. | | | | | | 2 NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH | | | COORDINATE WITH THE SUBMITTED PLANS. TWO DAYS AFTER | | | PLANS WERE RE-SUBMITTED ON APRIL 17TH, THIS REVIEW WAS | | | SPEAKING TO ELECTRICAL ENGINEER OF RECORD. THE ENERGY | | | CALCULATIONS WERE STILL BEING COMPLETED. THIS REVIEW | | | WAS TOLD THE REVISED CALCULATIONS WOULD BE IN THIS | | | OFFICE WITHIN A COUPLE OF DAYS. ONE WEEK LATER THE | | | CALCULATIONS WERE NOT SUBMITTED. THIS REVIEWER SPOKE | | | WITH KAST CONSTRUCTION PROJECT COORDINATOR WITH RESPECT | | | TO THE CALCULATIONS WHICH HAD NOT YET BEEN SUBMITTED. | | | THE REVIEW WAS PUSHED BACK PAST OTHER PROJECTS IN DATED | | | ORDER WAITING FOR THE CALCULATIONS TO BE SUBMITTED. | | | PLEASE KNOW AS OF THIS REVIEW DATE 5/2/08 NO REVISED | | | ENERGY CALCULATIONS WERE SUBMITTED. THE REVISED | | | CALCULATIONS WILL BE REVIEWED ON THE NEXT RE-SUBMITTAL | | | OF PLANS. | | | *** IMPORTANT *** | | | PLEASE BE SURE *ALL* INFORMATION ON PLANS INCLUDING | | | LIGHTING, MECHANICAL, BUILDING COMPONENTS ETC ARE | | | PLACED INTO THE CALCULATIONS. THIS IS ONE OF THE MAIN | | | REASONS PLANS ARE REJECTED FOR NON-CODE COMPLIANCE. | | | PLEASE BE SURE TO SEE 13-400.3.A, 13-415.2, | | | 13-415.2.ABC.1.1, .1.2, .1.3. | | | PLEASE SEE 13-411, 13-412 ETC. | | | COMPLIANCE FOR CHAPTER 13 AND LIGHTING AND OTHER | | | EFFICIENCIES OF THIS BUILDING HAS NOT BEEN MET AND | | | PERMIT SHALL NOT BE ISSUED. | | | RESPONSE LETTER MENTIONS IN MORE THAN ONE LOCATION TO | | | SEE SECTION 7 AND TAB 11 FOR CALCULATIONS HOWEVER THESE | | | ARE EMPTY. | | | | | | 3) NOTE: PLEASE GO THROUGH ALL LIGHTING FIXTURES ON THE | | | FIXTURE LEGEND. THERE ARE STILL FIXTURES WHICH DO NOT | | | SEEM TO BE ACCURATE. AN EXAMPLE OF FIXTURE *SZ* ON | | | PREVIOUS REVIEW WAS GIVEN HOWEVER THIS SAME FIXTURE IS | | | STILL SHOWN W/ 200VA? | | | MANY OF THESE ITEMS CAN NOT BE VERIFIED DUE TO COMMENT | | | #2 ABOVE. | | | PLEASE COORDINATE ALL. | | | FBC 13-415.2, 106.1.2, 106.13.5.1.2 | | | | | | 4) NOTE: PLEASE SEE THE INFORMATION ON THE FIRE PUMP | | | CONTROLLER SPECS/MANUFACTURES CUT SHEETS IS STILL IN | | | QUESTION. THIS WAS BROUGHT UP IN MEETING HELD BEFORE | | | PLANS WERE SUBMITTED OF SOME OF THE INFORMATION FOR | | | NFPA-20 COMPLIANCE WAS STILL NOT SHOWN ON SPECS/CUT | | | SHEETS. THE RESPONSE IN MEETING WAS THAT NEW SPECS/CUT | | | SHEETS WOULD BE OBTAINED AND SUBMITTED IN THE BINDERS. | | | THIS WAS NOT DONE. | | | CAN NOT VERIFY SEVERAL ITEMS FROM NFPA-20. | | | PLEASE SEE NO ISOLATION SWITCH, MAIN DISCONNECT ETC | | | PLEASE SEE NO NRTL WAS INDICATED ON THESE SAME SHEETS. | | | PLEASE SEE NEC 695, 110.3, 90.7 | | | PLEASE SEE NFPA-20, CHAPTERS 9 AND 10. PLEASE SEE THE | | | BELOW IS TEXT EXTRACTED FROM NFPA-20 WHICH WILL GIVE | | | SOME EXAMPLES WHICH THIS OFFICE NEEDS TO VERIFY IF THIS | | | EQUIPMENT IS MEETING *MINIMUM* CODE COMPLIANCE. | | | | | | **10.3 CONSTRUCTION. | | | 10.3.1 EQUIPMENT. ALL EQUIPMENT SHALL BE SUITABLE FOR | | | USE IN LOCATIONS SUBJECT TO A MODERATE DEGREE OF | | | MOISTURE, SUCH AS A DAMP BASEMENT. | | | 10.3.2 MOUNTING. ALL EQUIPMENT SHALL BE MOUNTED IN A | | | SUBSTANTIAL MANNER ON A SINGLE NONCOMBUSTIBLE | | | SUPPORTING STRUCTURE. | | | 10.3.3 ENCLOSURES. | | | 10.3.3.1* THE STRUCTURE OR PANEL SHALL BE SECURELY | | | MOUNTED IN, AS A MINIMUM, A NATIONAL ELECTRICAL | | | MANUFACTURERS ASSOCIATION (NEMA) TYPE 2, DRIPPROOF | | | ENCLOSURE(S). | | | 10.3.3.2 WHERE THE EQUIPMENT IS LOCATED OUTSIDE, OR | | | WHERE SPECIAL ENVIRONMENTS EXIST, SUITABLY RATED | | | ENCLOSURES SHALL BE USED. | | | 10.3.3.3 THE ENCLOSURE(S) SHALL BE GROUNDED IN | | | ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE, | | | ARTICLE 250. | | | 10.3.4 CONNECTIONS AND WIRING. | | | 10.3.4.1 ALL BUSBARS AND CONNECTIONS SHALL BE READILY | | | ACCESSIBLE FOR MAINTENANCE WORK AFTER INSTALLATION OF | | | THE CONTROLLER. | | | 10.3.4.2 ALL BUSBARS AND CONNECTIONS SHALL BE ARRANGED | | | SO THAT DISCONNECTION OF THE EXTERNAL CIRCUIT | | | CONDUCTORS WILL NOT BE REQUIRED. | | | 10.3.4.3 PROVISIONS SHALL BE MADE WITHIN THE CONTROLLER | | | TO PERMIT THE USE OF TEST INSTRUMENTS FOR MEASURING ALL | | | LINE VOLTAGES AND CURRENTS WITHOUT DISCONNECTING ANY | | | CONDUCTORS WITHIN THE CONTROLLER. | | | 10.3.4.4 MEANS SHALL BE PROVIDED ON THE EXTERIOR OF THE | | | CONTROLLER TO READ ALL LINE CURRENTS AND ALL LINE | | | VOLTAGES WITHIN "5 PERCENT OF FULL SCALE. | | | 10.3.4.5 CONTINUOUS-DUTY BASIS. | | | 10.3.4.5.1 UNLESS THE REQUIREMENTS OF 10.3.4.5.2 ARE | | | MET, BUSBARS AND OTHER WIRING ELEMENTS OF THE | | | CONTROLLER SHALL BE DESIGNED ON A CONTINUOUS-DUTY | | | BASIS. | | | 10.3.4.5.2 THE REQUIREMENTS OF 10.3.4.5.1 SHALL NOT | | | APPLY TO CONDUCTORS THAT ARE IN A CIRCUIT ONLY DURING | | | THE MOTOR STARTING PERIOD, WHICH SHALL BE PERMITTED TO | | | BE DESIGNED ACCORDINGLY. | | | 10.3.4.6 A FIRE PUMP CONTROLLER SHALL NOT BE USED AS A | | | JUNCTION BOX TO SUPPLY OTHER EQUIPMENT. | | | 10.3.4.7 ELECTRICAL SUPPLY CONDUCTORS FOR PRESSURE | | | MAINTENANCE (JOCKEY OR MAKE-UP) PUMP(S) SHALL NOT BE | | | CONNECTED TO THE FIRE PUMP CONTROLLER. | | | 10.3.5 PROTECTION OF AUXILIARY CIRCUITS. CIRCUITS THAT | | | ARE NECESSARY FOR PROPER OPERATION OF THE CONTROLLER | | | SHALL NOT HAVE OVERCURRENT PROTECTIVE DEVICES CONNECTED | | | IN THEM. | | | 10.3.6* EXTERNAL OPERATION. ALL SWITCHING EQUIPMENT FOR | | | MANUAL USE IN CONNECTING OR DISCONNECTING, OR STARTING | | | OR STOPPING, THE MOTOR SHALL BE EXTERNALLY OPERABLE. | | | 10.3.7 ELECTRICAL DIAGRAMS AND INSTRUCTIONS. 10.3.7.1 | | | AN ELECTRICAL SCHEMATIC DIAGRAM SHALL BE PROVIDED AND | | | PERMANENTLY ATTACHED TO THE INSIDE OF THE CONTROLLER | | | ENCLOSURE. | | | 10.3.7.2 ALL THE FIELD WIRING TERMINALS SHALL BE | | | PLAINLY MARKED TO CORRESPOND WITH THE FIELD CONNECTION | | | DIAGRAM FURNISHED. | | | 10.3.7.3* COMPLETE INSTRUCTIONS COVERING THE OPERATION | | | OF THE CONTROLLER SHALL BE PROVIDED AND CONSPICUOUSLY | | | MOUNTED ON THE CONTROLLER. | | | 10.3.8 MARKING. | | | 10.3.8.1 EACH MOTOR CONTROL DEVICE AND EACH SWITCH AND | | | CIRCUIT BREAKER SHALL BE MARKED TO PLAINLY INDICATE THE | | | NAME OF THE MANUFACTURER, THE DESIGNATED IDENTIFYING | | | NUMBER, AND THE ELECTRICAL RATING IN VOLTS, HORSEPOWER, | | | AMPERES, FREQUENCY, PHASES, AND SO FORTH, AS | | | APPROPRIATE. | | | 10.3.8.2 THE MARKINGS SHALL BE SO LOCATED AS TO BE | | | VISIBLE AFTER INSTALLATION. | | | 10.4 COMPONENTS. | | | 10.4.1* VOLTAGE SURGE ARRESTER. | | | 10.4.1.1 UNLESS THE REQUIREMENTS OF 10.4.1.3 OR | | | 10.4.1.4 ARE MET, A VOLTAGE SURGE ARRESTER COMPLYING | | | WITH ANSI/IEEE C62.1, IEEE STANDARD FOR GAPPED | | | SILICON-CARBIDE SURGE ARRESTERS FOR AC POWER CIRCUITS, | | | OR C62.11, IEEE STANDARD FOR METAL-OXIDE SURGE | | | ARRESTERS FOR ALTERNATING CURRENT POWER CIRCUITS (>1 | | | KV), SHALL BE INSTALLED FROM EACH PHASE TO GROUND. (SEE | | | 10.3.2.) | | | 10.4.1.2 THE SURGE ARRESTER SHALL BE RATED TO SUPPRESS | | | VOLTAGE SURGES ABOVE LINE VOLTAGE. | | | 10.4.1.3 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2 | | | SHALL NOT APPLY TO CONTROLLERS RATED IN EXCESS OF 600 | | | V. (SEE SECTION 10.6.) | | | 10.4.1.4 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2 | | | SHALL NOT APPLY WHERE THE CONTROLLER CAN WITHSTAND | | | WITHOUT DAMAGE A 10 KV IMPULSE IN ACCORDANCE WITH | | | ANSI/IEEE C62.41, IEEE RECOMMENDED PRACTICE FOR SURGE | | | VOLTAGES IN LOW-VOLTAGE AC POWER CIRCUITS. | | | 10.4.2 ISOLATING SWITCH. | | | 10.4.2.1 GENERAL. | | | 10.4.2.1.1 THE ISOLATING SWITCH SHALL BE A MANUALLY | | | OPERABLE MOTOR CIRCUIT SWITCH OR A MOLDED CASE SWITCH | | | HAVING A HORSEPOWER RATING EQUAL TO OR GREATER THAN THE | | | MOTOR HORSEPOWER. | | | 10.4.2.1.2* A MOLDED CASE SWITCH HAVING AN AMPERE | | | RATING NOT LESS THAN 115 PERCENT OF THE MOTOR RATED | | | FULL-LOAD CURRENT AND ALSO SUITABLE FOR INTERRUPTING | | | THE MOTOR LOCKED ROTOR CURRENT SHALL BE PERMITTED. | | | 10.4.2.1.3 A MOLDED CASE ISOLATING SWITCH SHALL BE | | | PERMITTED TO HAVE SELF-PROTECTING INSTANTANEOUS | | | SHORT-CIRCUIT OVERCURRENT PROTECTION, PROVIDED THAT | | | THIS SWITCH DOES NOT TRIP UNLESS THE CIRCUIT BREAKER IN | | | THE SAME CONTROLLER TRIPS. | | | 10.4.2.2 EXTERNALLY OPERABLE. THE ISOLATING SWITCH | | | SHALL BE EXTERNALLY OPERABLE. | | | 10.4.2.3* AMPERE RATING. THE AMPERE RATING OF THE | | | ISOLATING SWITCH SHALL BE AT LEAST 115 PERCENT OF THE | | | FULL-LOAD CURRENT RATING OF THE MOTOR. | | | 10.4.2.4 WARNING. | | | 10.4.2.4.1 UNLESS THE REQUIREMENTS OF 10.4.2.4.2 ARE | | | MET, THE FOLLOWING WARNING SHALL APPEAR ON OR | | | IMMEDIATELY ADJACENT TO THE ISOLATING SWITCH: WARNING | | | DO NOT OPEN OR CLOSE THIS SWITCH WHILE | | | THE CIRCUIT BREAKER (DISCONNECTING MEANS) | | | IS IN CLOSED POSITION. | | | 10.4.2.4.2 INSTRUCTION LABEL. THE REQUIREMENTS OF | | | 10.4.2.4.1 SHALL NOT APPLY WHERE THE REQUIREMENTS OF | | | 10.4.2.4.2.1 AND 10.4.2.4.2.2 ARE MET. 10.4.2.4.2.1 | | | WHERE THE ISOLATING SWITCH AND THE CIRCUIT BREAKER ARE | | | SO INTERLOCKED THAT THE ISOLATING SWITCH CAN BE NEITHER | | | OPENED NOR CLOSED WHILE THE CIRCUIT BREAKER IS CLOSED, | | | THE WARNING LABEL SHALL BE PERMITTED TO BE REPLACED | | | WITH AN INSTRUCTION LABEL THAT DIRECTS THE ORDER OF | | | OPERATION. | | | 10.4.2.4.2.2 THIS LABEL SHALL BE PERMITTED TO BE PART | | | OF THE LABEL REQUIRED BY 10.3.7.3. | | | 10.4.2.5 OPERATING HANDLE. | | | 10.4.2.5.1 UNLESS THE REQUIREMENTS OF 10.4.2.5.2 ARE | | | MET, THE ISOLATING SWITCH OPERATING HANDLE SHALL BE | | | PROVIDED WITH A SPRING LATCH THAT SHALL BE SO ARRANGED | | | THAT IT REQUIRES THE USE OF THE OTHER HAND TO HOLD THE | | | LATCH RELEASED IN ORDER TO PERMIT OPENING OR CLOSING OF | | | THE SWITCH. | | | 10.4.2.5.2 THE REQUIREMENTS OF 10.4.2.5.1 SHALL NOT | | | APPLY WHERE THE ISOLATING SWITCH AND THE CIRCUIT | | | BREAKER ARE SO INTERLOCKED THAT THE ISOLATING SWITCH | | | CAN BE NEITHER OPENED NOR CLOSED WHILE THE CIRCUIT | | | BREAKER IS CLOSED. | | | 10.4.3 CIRCUIT BREAKER (DISCONNECTING MEANS). 10.4.3.1* | | | GENERAL. | | | 10.4.3.1.1 THE MOTOR BRANCH CIRCUIT SHALL BE PROTECTED | | | BY A CIRCUIT BREAKER THAT SHALL BE CONNECTED DIRECTLY | | | TO THE LOAD SIDE OF THE ISOLATING SWITCH AND SHALL HAVE | | | ONE POLE FOR EACH UNGROUNDED CIRCUIT CONDUCTOR. | | | 10.4.3.1.2 WHERE THE MOTOR BRANCH CIRCUIT IS | | | TRANSFERRED TO AN ALTERNATE SOURCE SUPPLIED BY AN | | | ON-SITE GENERATOR AND IS PROTECTED BY AN OVERCURRENT | | | DEVICE AT THE GENERATOR (SEE 9.6.5), THE LOCKED ROTOR | | | OVERCURRENT PROTECTION WITHIN THE FIRE PUMP CONTROLLER | | | SHALL BE PERMITTED TO BE BYPASSED WHEN THAT MOTOR | | | BRANCH CIRCUIT IS SO CONNECTED. | | | 10.4.3.2 MECHANICAL CHARACTERISTICS. THE CIRCUIT | | | BREAKER SHALL HAVE THE FOLLOWING MECHANICAL | | | CHARACTERISTICS: | | | (1)IT SHALL BE EXTERNALLY OPERABLE. (SEE | | | 10.3.6.) | | | | | | (2)IT SHALL TRIP FREE OF THE HANDLE. | | | (3)A NAMEPLATE WITH THE LEGEND "CIRCUIT BREAKER " | | | DISCONNECTING MEANS" IN LETTERS NOT LESS THAN 10 MM ( | | | IN.) HIGH SHALL BE LOCATED ON THE OUTSIDE OF THE | | | CONTROLLER ENCLOSURE ADJACENT TO THE MEANS FOR | | | OPERATING THE CIRCUIT BREAKER. | | | | | | 10.4.3.3* ELECTRICAL CHARACTERISTICS. | | | 10.4.3.3.1 THE CIRCUIT BREAKER SHALL HAVE THE FOLLOWING | | | ELECTRICAL CHARACTERISTICS: | | | (1)A CONTINUOUS CURRENT RATING NOT LESS THAN 115 | | | PERCENT OF THE RATED FULL-LOAD CURRENT OF THE MOTOR (2) | | | OVERCURRENT-SENSING ELEMENTS OF THE NONTHERMAL TYPE | | | (3)INSTANTANEOUS SHORT-CIRCUIT OVERCURRENT | | | PROTECTION | | | (4)*AN ADEQUATE INTERRUPTING RATING TO PROVIDE | | | THE SUITABILITY RATING 10.1.2.2 OF THE CONTROLLER (5) | | | CAPABILITY OF ALLOWING NORMAL AND EMERGENCY STARTING | | | AND RUNNING OF THE MOTOR WITHOUT TRIPPING (SEE | | | 10.5.3.2.) | | | (6)AN INSTANTANEOUS TRIP SETTING OF NOT MORE THAN | | | 20 TIMES THE FULL-LOAD CURRENT | | | | | | 10.4.3.3.2* CURRENT LIMITERS, WHERE INTEGRAL PARTS OF | | | THE CIRCUIT BREAKER, SHALL BE PERMITTED TO BE USED TO | | | OBTAIN THE REQUIRED INTERRUPTING RATING, PROVIDED ALL | | | THE FOLLOWING REQUIREMENTS ARE MET: | | | (1)THE BREAKER SHALL ACCEPT CURRENT LIMITERS OF | | | ONLY ONE RATING. | | | (2)THE CURRENT LIMITERS SHALL HOLD 300 PERCENT OF | | | FULL-LOAD MOTOR CURRENT FOR A MINIMUM OF 30 MINUTES. | | | (3)THE CURRENT LIMITERS, WHERE INSTALLED IN THE | | | BREAKER, SHALL NOT OPEN AT LOCKED ROTOR CURRENT. (4) | | | A SPARE SET OF CURRENT LIMITERS OF CORRECT RATING SHALL | | | BE KEPT READILY AVAILABLE IN A COMPARTMENT OR RACK | | | WITHIN THE CONTROLLER ENCLOSURE. | | | | | | 10.4.4 LOCKED ROTOR OVERCURRENT PROTECTION. 10.4.4.1 | | | THE ONLY OTHER OVERCURRENT PROTECTIVE DEVICE THAT SHALL | | | BE REQUIRED AND PERMITTED BETWEEN THE ISOLATING SWITCH | | | AND THE FIRE PUMP MOTOR SHALL BE LOCATED WITHIN THE | | | FIRE PUMP CONTROLLER AND SHALL POSSESS THE FOLLOWING | | | CHARACTERISTICS: | | | (1)FOR A SQUIRREL-CAGE OR WOUND-ROTOR INDUCTION | | | MOTOR, THE DEVICE SHALL BE AS FOLLOWS: | | | | | | (A)OF THE TIME-DELAY TYPE HAVING A TRIPPING TIME | | | BETWEEN 8 SECONDS AND 20 SECONDS AT LOCKED ROTOR | | | CURRENT | | | (B)CALIBRATED AND SET AT A MINIMUM OF 300 PERCENT | | | OF MOTOR FULL-LOAD CURRENT | | | (2)FOR A DIRECT-CURRENT MOTOR, THE DEVICE SHALL | | | BE AS FOLLOWS: | | | | | | (A)OF THE INSTANTANEOUS TYPE | | | (B)CALIBRATED AND SET AT A MINIMUM OF 400 PERCENT | | | OF MOTOR FULL-LOAD CURRENT | | | (3)*THERE SHALL BE VISUAL MEANS OR MARKINGS | | | CLEARLY INDICATED ON THE DEVICE THAT PROPER SETTINGS | | | HAVE BEEN MADE. | | | (4)IT SHALL BE POSSIBLE TO RESET THE DEVICE FOR | | | OPERATION IMMEDIATELY AFTER TRIPPING, WITH THE TRIPPING | | | CHARACTERISTICS THEREAFTER REMAINING UNCHANGED. (5) | | | TRIPPING SHALL BE ACCOMPLISHED BY OPENING THE CIRCUIT | | | BREAKER, WHICH SHALL BE OF THE EXTERNAL MANUAL RESET | | | TYPE. | | | | | | 10.4.4.2 WHERE THE MOTOR BRANCH CIRCUIT IS TRANSFERRED | | | TO AN ALTERNATE SOURCE SUPPLIED BY AN ON-SITE GENERATOR | | | WHOSE CAPACITY IS 225 PERCENT OR LESS OF THE CAPACITY | | | OF THE FIRE PUMP MOTOR AND IS PROTECTED BY AN | | | OVERCURRENT DEVICE AT THE GENERATOR (SEE 9.6.5), THE | | | LOCKED ROTOR OVERCURRENT PROTECTION WITHIN THE FIRE | | | PUMP CONTROLLER SHALL BE PERMITTED TO BE BYPASSED WHEN | | | THAT MOTOR BRANCH CIRCUIT IS SO CONNECTED. | | | | | | ** IT WAS MENTIONED IN THE PREVIOUS MEETING THIS WAS | | | NOT NEEDED HOWEVER BASED ON ONLY SOME SECTIONS OF THE | | | EXTRACTED CODE IT CAN BE SEEN THIS OFFICE WILL REVIEW | | | THESE DOCUMENTS ONCE SUBMITTED. | | | PLEASE SUBMIT. | | | FBC 106.1.2. | | | | | | 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS | | | FOR THE GENERATOR AND TRANSFER SWITCHES. | | | NFPA-110, NFPA-70, 110.3, 90.7 ETC | | | FBC 106.1.2FOR ADDITIONAL INFORMATION/COORDINATION. | | | | | | 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH MENTIONED THE | | | METER FOR 700S OLIVE WAS NOT TO BE LOCATED ON THIS | | | BUILDING. ONE REVISED SITE SHEET DOES SHOW THE | | | METER/SERVICE LOCATED OVER AT THE ACTUAL ADDRESS. | | | PLEASE SEE THE RESPONSE LETTER EVEN MENTIONS THE PLANS, | | | SPECIFICALLY SHEET E-101B WAS REVISED TO RELOCATE. | | | PLEASE SEE THE SHEET MENTIONED IN RESPONSE LETTER STILL | | | SHOWS THIS METER FOR 700 S OLIVE STILL LOCATED ON | | | PLANS. | | | PLEASE REMOVE AND UPDATE PLANS. | | | FBC 106.1.2 FOR COORDINATION. | | | | | | 7) NOTE: PLEASE KNOW IN THE PREVIOUS MEETING HELD ABOUT | | | ONE MONTH BEFORE THIS REVIEW IT WAS MENTIONED A | | | POSSIBLE *PROVISO* FOR CODE COMPLIANCE FOR SELECTIVE | | | COORDINATION. THE EQUIPMENT FOR THIS PROJECT SHOULD BE | | | IN ORDER STATUS WITHIN SHORT FASHION. PLEASE KNOW THIS | | | INFORMATION WILL BE REQUIRED WITHIN 30DAYS. | | | THESE PLANS WILL BE BACK OUT FOR CORRECTIONS AND | | | SELECTIVE COORDINATION MAY BE SUBMITTED WITH REVISED | | | PLANS. | | | 240.12 | | | FBC 106.1.2 | | | | | | 8) NOTE: PLEASE SEE LIGHTING CONTROLS FOR FBC AND | | | CHAPTER 13 STILL HAVE SOME ITEMS TO RESOLVE. | | | 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4. | | | | | | A) PLEASE CLARIFY WHERE MAXIMUM TIMES FOR OCCUPANCY | | | DEVICES ARE LOCATED ON PLANS. THE WORDING IN THE | | | RESPONSE LETTER FOR ROOMS AND OTHER DEVICES DO STATE | | | PERMISSIBLE TIMES ALLOWED BY THE CODE HOWEVER THESE | | | SHOULD BE STATED ON PLANS. | | | PLEASE SEE THE SYMBOLS FOR SOME OF THESE DEVICES ON | | | PLANS COULD NOT BE LOCATED ON SYMBOL LEGEND. | | | FOR EXAMPLE: | | | OC DEVICE IN MANY ROOMS ARE NOT ON SYMBOL LEGEND. | | | PLEASE SEE THE NEW ITEMS FOR THE UNITS/GUEST ROOMS | | | APPEAR TO BE OK, HOWEVER TWO QUESTIONS FOR THIS | | | PROPOSED SYSTEM EXIST. | | | PLEASE GIVE SYSTEM FUNCTION ON PLANS. THE RESPONSE | | | LETTER IS NOT PART OF THE RECORD PLANS FOR CODE | | | COMPLIANCE. THIS WILL INCLUDE MAXIMUM TIMES. PLEASE | | | CLARIFY HOW THE PHONE LINE CONNECTION WORKS WITH SYSTEM | | | FROM DESK/SYSTEM. | | | PLEASE VERIFY THAT BASED ON THE NEW *LOAD CENTER* NOW | | | ON PLANS THAT THIS PANEL/EQUIPMENT DOES NOT CONTAIN ANY | | | OVER CURRENT PROTECTION. PLEASE SEE 110.26, 408.1, | | | 240.24 AS NO OVER CURRENT PROTECTION DEVICES SHALL BE | | | LOCATED IN CLOTHES CLOSETS. | | | | | | B) PLEASE VERIFY AND SHOW DETAIL ON HOW *ALL* OUTSIDE | | | LIGHTS COMPLY FOR CONTROLS AS REQUIRED PER .1.4. PLANS | | | DO CONTAIN AN OCTAGONAL NOTE #5 FOR SOME FIXTURES ON | | | THE OUTSIDE OF THE STRUCTURE HOWEVER NOT FOR ALL. WILL | | | ALL LIGHTS BE CONTROLLED BY PHOTO-SENSOR ON ROOF? WILL | | | THE STREET LEVEL NOT BE DARKER THAN THE ROOF LEVEL? | | | WILL THE LIGHTS BE CONTROLLED BY AN ASTRONOMICAL TIME | | | CLOCK? IF SO PLEASE SEE MINIMUM TIMES FOR BATTERY BACK | | | UP OF PROGRAMMING SHALL BE 10HRS. | | | PLEASE SEE OTHER LIGHTS FOR EXAMPLE CIRCUITHP2LW1-36 | | | WHICH IS NOT CLEAR ON HOW THESE MEET EITHER CONTROL. | | | | | | C) PLEASE SEE THE LIGHTING CONTROL DEVICES (SWITCHES) | | | SHOWN ON LIGHTING SUBMITTALS IN BINDERS DO NOT | | | COORDINATE WITH THE LIGHTING CONTROLS AS SHOWN ON | | | PLANS. | | | PLEASE REVISE PLANS FOR CODE COMPLIANCE. PLANS WILL BE | | | THE RECORD SET OF DOCUMENTS NOT THESE SEPARATE | | | SUBMITTALS. | | | | | | 9) NOTE: PLEASE SEE ELEVATOR MACHINE ROOM LIGHTING | | | CIRCUIT AS THIS IS REQUIRED TO BE DEDICATED PER 620.23. | | | PLEASE SEE PANEL SCHEDULE FOR ELSW2-18 WHICH MENTIONS | | | *MEZZANINE LIGHTING*. | | | | | | 10) NOTE: PLEASE SEE EQUIPMENT IN GUEST LAUNDRY ROOM. | | | PLEASE SEE DRYERS WHICH ARE SHOWN AS 30AMPS ON | | | EQUIPMENT SCHEDULE YET THE PANEL SCHEDULES SHOW | | | 50AMPS. | | | PLEASE COORDINATE. | | | FBC 106.1.2 | | | NEC 408.4, 240.4 ETC | | | | | | 11) NOTE: PLEASE VERIFY THE RECEPTACLES ON THESE SAME | | | DRYERS IN GUEST LAUNDRY ROOM AS THE PLANS INDICATE A | | | RECEPTACLE SYMBOL AND BASED ON SYMBOL LEGEND THESE ARE | | | PLUG IN UNITS. HOWEVER PLEASE SEE EQUIPMENT SCHEDULE | | | FOR THESE SAME UNITS AS THIS STATES THESE ARE | | | HARDWIRED. | | | PLEASE COORDINATE. | | | PLEASE ALSO KNOW AS PER 422.31 IF THESE ARE HARDWIRE | | | UNITS, DISCONNECTS WILL BE REQUIRED. | | | | | | 12) NOTE: PLEASE SEE NEC 700, 701 AND 702. | | | PLEASE KNOW LOADS CONSIDERED LIFE SAFETY SHALL BE THE | | | ONLY LOADS ON ATS0LS. PLEASE KNOW OTHER LOADS | | | CONSIDERED UNDER LEGALLY REQUIRED OR OPTIONAL STAND-BY | | | IS NOT PERMITTED ON THE SAME ATS, PANELS OR EQUIPMENT. | | | PLEASE SEE THE SAME GOES FOR THE LEGALLY REQUIRED ITEMS | | | (LOADS ON WITHIN 60 SECONDS) AND LOADS REQUIRED BY | | | CODES, ETC SHALL NOT CONTAIN LIFE SAFETY LOADS OR | | | OPTIONAL STAND-BY LOADS. | | | FOR EXAMPLE; | | | PLEASE SEE ITEMS SUCH AS DATA RECEPTACLES, SMOKE | | | DAMPERS ETC SHALL NOT BE ON THE LS SYSTEMS. | | | PLEASE SEE THESE ITEMS ABOVE WOULD ACTUALLY BE ON TWO | | | SYSTEMS. | | | SMOKE DAMPERS WOULD BE LEGALLY REQUIRED AND DATA | | | RECEPTACLES WOULD BE OPTIONAL STAND-BY. | | | PLEASE EXPLAIN WHY THE RECEPTACLE IN THE GUEST LAUNDRY | | | ROOM #238 WOULD BE ON THE LS SYSTEM? ( ELSE2-9)? PLEASE | | | SEE ITEMS SUCH AS GENERATOR OIL PUMP WOULD NEED TO BE | | | ON THE LS SYSTEM AS THIS IS CRITICAL FOR THE RUNNING OF | | | THE GENERATOR WHICH IS LIFE SAFETY. PLEASE COORDINATE | | | ALL. PLEASE CONTACT THIS OFFICE TO GO OVER ITEMS. | | | AT THIS POINT AN OPTIONAL STAND-BY ATS WILL BE REQUIRED | | | AS THERE ARE SEVERAL ITEMS WHICH CAN NOT BE CONSIDERED | | | LIFE SAFETY OR LEGALLY REQUIRED BY CODE. | | | 700.9, 701.10, 702.9 ETC | | | | | | 13) NOTE: PLEASE SEE THE PHOTO-METRIC LEVELS ON ALL | | | EGRESS AREAS AS PREVIOUSLY REQUESTED NEED TO BE | | | COMPLETED. | | | PLEASE SEE SOME AREAS LIKE THE GARAGE DOES NOT HAVE THE | | | LIGHTING LEVELS COMPLETED. | | | THIS CAN BE SEEN ON E-603C, 603D FOR ONE EXAMPLE. | | | PLEASE SEE THE LIGHTING LEVELS ARE NOT SHOWN ON ANY | | | TABLES SO THE AVERAGE IS NOT STATED, SHOWN ETC. FOR | | | EXAMPLE: | | | PLEASE SEE ONE LOCATION WHICH THERE IS QUESTION ON WHAT | | | FIXTURES WERE USED AND APPEARS LEVELS DO NOT MEET | | | MINIMUM REQUIRED BY CODE IS THE EGRESS EXIT ACCESS | | | HALLWAY JUST TO THE WEST OF THE DRIVE ON THE SOUTH SIDE | | | OF THE BUILDING. | | | THIS HALLWAY CONTAINS ME FIXTURES ALONG WITH WALL | | | MOUNTED BATTERY BACK UP LIGHTS. | | | IF THE NORMAL LEVEL FIGURES THESE ME FIXTURES AND THESE | | | FIXTURES ARE BATTERY BACK UP BASED ON THE FIXTURE | | | LEGEND HOW IS IT THE LIGHTING LEVELS GO DOWN AS MUCH AS | | | SHOWN? NORMAL LEVEL SHOWS IN EXCESS OF 20 FC, YET UNDER | | | EM, IT APPEARS TO BE LESS THAN 1 FC. | | | PLEASE VERIFY THIS ALONG WITH THE LEVEL SHOWN. | | | FOR EXAMPLE: | | | PLEASE SEE POOL AREA EGRESS PATHS WHICH DO NOT MEET | | | MINIMUM LEVELS PER LIFE SAFETY CODE UNDER EMERGENCY | | | CONDITIONS. | | | PLEASE SEE MINIMUM LEVELS NEED TO BE SHOWN ON ALL | | | SHEETS ON TABLE FOR AREAS. | | | *** IMPORTANT *** | | | IT IS IMPORTANT TO KNOW THAT THESE ARE TWO EXAMPLES | | | ONLY. THIS IS GIVEN AS A BENEFIT ONLY AND IS IN NO WAY | | | AN EXHAUSTED LIST OF ALL POSSIBLE AREAS IN QUESTION. | | | PLEASE SEE 2003 NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2 | | | | | | 14) NOTE: PLEASE SEE THE PREVIOUS REVIEW WHICH | | | REQUESTED THE PHOTO-METRIC LEVELS FOR SWIMMING POOL | | | AREA BE SUBMITTED TO THE PALM BEACH COUNTY HEALTH | | | DEPARTMENT FOR REVIEW AND STAMPING. THE RESPONSE | | | MENTIONS THIS WILL BE DONE, HOWEVER BASED ON THE | | | SUBMITTED PLANS NO REVIEW STAMPS FROM THE ABOVE | | | MENTIONED PBCHD WAS LOCATED ON SAID PLANS. | | | THIS IS AND WILL BE REQUIRED. | | | | | | 15) NOTE: PLEASE KNOW AS NOTED PREVIOUSLY ON NOTES, PER | | | PLANS AND RESPONSE LETTER: *ALL* ACCESS CONTROLS | | | SYSTEMS SHALL BE UNDER SEPARATE PERMIT AND COMPLETED | | | PLANS, SIGNED, DATED AND SEALED BY A FLORIDA LICENSED | | | PE. IF THIS INFORMATION IS INCLUDED ON THESE PLANS THIS | | | WILL NOT BE REQUIRED. | | | ** THIS NOTED ONLY FOR INFORMATIONAL PURPOSE. | | | | | | 16) NOTE: PLEASE KNOW THE LS1 FIXTURES WHICH APPEAR AS | | | STREET POLE LIGHTS WILL NOT BE PART OF THIS BUILDING | | | PLANS, PERMITS, CONTROLS ETC. IF THESE ARE LOCATE DIN | | | THE RIGHT OF WAY THESE WILL BE FED FROM RIGHT OF WAY | | | POWER AND WILL NOT BE PART OF THE BUILDING. THIS IS IN | | | CONFLICT HOWEVER WITH THE NOTE #5 ON SHEET E101C AS | | | THESE MENTION TO BE CONTROLLED BY RELAY | | | PANEL/PHOTO-SENSOR. | | | PLEASE VERIFY THIS AT THIS TIME AS THIS WILL AFFECT | | | ENERGY CALCULATIONS, LOAD CALCULATIONS, CONTROLS, | | | PERMITTING ETC. | | | FBC 106.1.2 | | | | | | 17) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) IS BEING | | | GIVEN AT THIS TIME AS THERE ARE SOME CODE COMPLIANCE | | | COMMENTS REPEATED THE SECOND TIME. | | | PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME. | | | | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-06 |
Time |
15:42 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-29 |
Time |
08:06 |
Sent To |
|
|
| Notes |
| 2008-02-06 15:42:19 | | | | | | | ** DENIED REVIEW ** | | | | | | HYATT HOTEL | | | 295 LAKEVIEW AVE. | | | | | | 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT | | | CODES ARE STATED ON PLANS. AT THIS POINT IN TIME SOME | | | ARE ALREADY SHOWN ON SOME SHEETS HOWEVER NOT ALL. THE | | | FOLLOWING WILL NEED TO BE PART OF ARCHITECTURAL, | | | ELECTRICAL AND FIRE PROTECTION PLANS WHICH WERE NOT YET | | | SUBMITTED | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2003 NFPA-20 | | | 2002 NFPA-110 | | | FBC 2004 W/2007 REVISIONS. | | | | | | ** PLEASE BE AWARE PLANS NOTE JURISDICTION AS *PALM | | | BEACH COUNTY * AS WELL AS CITY OF WEST PALM BEACH. THIS | | | IS ONLY LOCATED IN THE CITY OF WEST PALM BEACH. | | | | | | | | | 2) NOTE: PLEASE KNOW AS THERE WERE SOME ITEMS NOT | | | SUBMITTED FOR REVIEW A COMPLETE AND FULL REVIEW COULD | | | NOT BE DONE. PLEASE ALSO SEE NOTES BELOW WITH RESPECT | | | TO FBC AND CHAPTER 13. | | | PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND ALL | | | DOCUMENTATION. | | | PLEASE SUBMIT FIRE SPRINKLER PLANS. WHILE THESE WILL BE | | | UNDER SEPARATE PERMIT AND REVIEWED BY OTHER TRADES AS | | | WELL, THE BASE SET OF BUILDING PLANS AS IT IS REQUIRED | | | TO BE SPRINKLED WILL BE REQUIRED TO SHOW A BASE | | | DESIGNED SYSTEM. | | | PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS | | | MECHANICAL FOR SYSTEMS WHICH ARE NOT COMPLETE FOR | | | ELECTRICAL CONNECTIONS AS WELL AS MECHANICAL. (EXAMPLE: | | | GARAGE VENTILATION, ETC) | | | AT THIS TIME CROSS REFERENCE AND REVIEW OF FIRE | | | EQUIPMENT AND OTHER SYSTEMS CAN NOT BE COMPLETED. FBC | | | 106.1.2, 106.3.5.1.2 ETC ADMIN SECTION. | | | FBC MECHANICAL CODE, FIRE CODE NFPA-1, LIFE SAFETY 101 | | | ETC. | | | FS 633 | | | | | | 3) NOTE: PLEASE SEE THE NEW BUILDING IS SHOWING THE | | | SERVICE METER FOR 700 S OLIVE LOCATED ON THE SIDE OF | | | THIS BUILDING WHICH IS NOT PERMITTED. THE FPL VAULT | | | AREA IS REQUIRED TO HAVE AN FPL EASEMENT ALONG WITH ANY | | | UNDERGROUND EASEMENTS TO RE-FEED THE EXISTING BUILDING | | | LOCATED ON THE NORTH SIDE OF PROPERTY. THE METERING | | | DEVICE(S) WOULD BE LOCATED ON THE PROPERTY OF 700 S. | | | OLIVE. | | | PLEASE RELOCATE. | | | | | | 4) NOTE: PLEASE CONTACT FPL WITH RESPECT TO ELECTRICAL | | | PERMITTED INSIDE THEIR VAULT AREA. PLANS SHOW LIGHTING, | | | EXIT SIGNS, AND RECEPTACLES WHICH BY THE FPL STANDARDS | | | AND GUIDES IS NOT PERMITTED. | | | THIS IS KNOWN TO THIS OFFICE AND IS BEING GIVEN FOR | | | INFORMATIONAL PURPOSE TO REVISE PLANS AT THIS TIME. | | | | | | 5) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM BUILDING | | | TRADE WITH RESPECT TO ANY EGRESS STAIRS OR HALLWAY DOOR | | | SWINGS. THIS IS NOT AN ELECTRICAL ISSUE HOWEVER WOULD | | | AFFECT THE ELECTRICAL PLANS. THIS IS FOR INFORMATION | | | ONLY AND NOT A REVIEW COMMENT FOR CODE COMPLIANCE. | | | | | | 6) NOTE: PLEASE SEE 240.12 AND SUBMIT A SELECTIVE | | | COORDINATION STUDY FOR LIFE SAFETY AND LEGALLY REQUIRED | | | EQUIPMENT. THIS IS ALSO REQUIRED UNDER NFPA-110 6.5.2, | | | 6.5.3 ETC | | | | | | 7) NOTE: PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING | | | DOCUMENTS FOR FBC REQUIRED CHAPTER 13 COMPLIANCE. | | | PLEASE SEE SUB SECTIONS BELOW ARE BROKEN UP FOR CHAPTER | | | 13. PLEASE SEE REFERENCES IN NOTES BELOW TO THE INPUT | | | DATA REPORT WILL BE ABBREVIATED AS IDR. | | | | | | A) ** PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS PER | | | FBC 13-400.3.A, AND 13-415.2. PLEASE SEE THERE ARE | | | SEVERAL ITEMS WHICH ARE IN NEED OF ADDRESSING. PLEASE | | | SEE SEVERAL EXAMPLES WILL BE GIVEN BUT IS IN NO WAY ALL | | | ITEMS FOUND: | | | PLEASE SEE THE METHOD OF CONTROL IS ALL BEING SHOWN AS | | | *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED | | | SYSTEMS ARE REQUIRED ON MOST. | | | PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR SHOWS A | | | TOTAL OF ONLY 9 FIXTURES. HOW IS THIS POSSIBLE WHEN THE | | | PLANS SHOW MANY MORE FIXTURES THAN THIS? | | | PLEASE SEE NO LIGHTING FOR GARAGE AREAS ARE SHOWN | | | FIGURED INTO THE IDR. HOW IS THIS POSSIBLE? THIS | | | ACCOUNTS FOR HUNDREDS OF FIXTURES. 13-415.2.ABC.1.3 | | | PLEASE SEE NO BREAK UP FOR TRACK LIGHTING. THIS IS | | | NOTED SPECIFICALLY AS THIS IS A COMMON ISSUE. | | | 13-415.2.ABC.1.2 | | | PLEASE SEE 13-415.2, | | | ** PLEASE CALL TO GO OVER THE LIGHTING CALCULATIONS IS | | | THERE ARE ANY QUESTIONS. | | | | | | B) ** PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS IN | | | FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED | | | SIGNATURE ON ALL SETS SUBMITTED. THIS IS ALSO THE CASE | | | FOR THE MECHANICAL CALCULATIONS ALSO ATTACHED TO THE | | | ENERGY CALCULATIONS. | | | PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA | | | ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES AN | | | *ORIGINAL* SIGNATURE AND DATE ON ALL DOCUMENTS. THIS | | | COMMENT IF ALL TRADES AND FOR ALL DOCUMENTS WHETHER OR | | | NOT COMMENT IS MADE BY OTHER REVIEW TRADES. | | | FBC 13-103.1.1.1 | | | | | | C) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE | | | CERTIFICATION SHEETS ONCE NEW METHOD *A* CALCULATIONS | | | ARE COMPLETE BEFORE RESUBMITTING PLANS. 13-103.1 | | | | | | D) ** PLEASE SEE THERE ARE SEVERAL FIXTURE WATTAGES ON | | | THE IDR FOR INTERIOR LIGHTING WHICH DOES NOT CORRELATE | | | WITH THE SAME FIXTURE WATTAGES ON THE FIXTURE LEGEND | | | SUBMITTED ON PLANS. THERE ARE SOME EXAMPLES BUT IN NO | | | WAY ALL. | | | PLEASE SEE LS-2 70W AND 200W, | | | PLEASE SEE IDR WITH 75W FIXTURES AND NONE ON PLANS. | | | PLEASE SEE R, RE NO 250W ON IDR, | | | PLEASE SEE SH WHICH SHOWS A 120W MR-16, (HOW IS THIS | | | POSSIBLE?) | | | PLEASE SEE SZ SHOWS 200VA ON FIXTURE LEGEND FOR MR-16? | | | PLEASE SEE SAXE WHICH SHOWS 75W T-8 WITH A TOTAL OF | | | 150VA? (HOW IS THIS POSSIBLE?) | | | PLEASE SEE GR2 AND GR3 WHICH SHOWS 2-17W BULBS WHICH IS | | | SHOWING A TOTAL OF 13WATTS. HOW IS THIS POSSIBLE? (2X17 | | | IS 34) | | | | | | THESE ARE SOME EXAMPLES HOWEVER NOT ALL ITEMS. THIS | | | OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE MAKE SURE ALL | | | LIGHTING WHICH IS SHOWN ON PLANS COORDINATES WITH NOT | | | ONLY THE FIXTURE LEGEND BUT MORE IMPORTANTLY THE INPUT | | | DATA REPORT AND INFORMATION INSERTED INTO THE ENERGY | | | CALCULATIONS. | | | | | | E) ** PLEASE SUBMIT MORE INFORMATION ON PROPOSED | | | LIGHTING CONTROLS FOR COMMONS AREAS. THE INFORMATION | | | SUBMITTED NEEDS TO PROVIDE MORE DETAILS ON TIMES, OVER | | | RIDE DEVICES AND LOCATIONS. PLANS SHOW LIGHTING CONTROL | | | PANELS IN MANY LOCATIONS HOWEVER NO OVER RIDE DEVICES | | | AS REQUIRED PER THE FBC COULD BE LOCATED FOR MOST | | | AREAS. | | | PLEASE SE E13-415.1.ABC.1.1, .1.2 AND .1.3 | | | PLANS SHOWS LIGHTING CONTROL PANELS/DIMMING PANELS ON | | | MOST FIXTURES YET COULD NOT LOCATE MORE DETAILED | | | INFORMATION ON HOW COMMON AREAS ARE BEING CONTROLLED BY | | | DIMMING PANELS. (SEE COMMENTS WITH RESPECT TO EGRESS | | | LIGHTING) | | | | | | F) ** PLEASE INDICATE ALL MAXIMUM TIMES ON ALL | | | OCCUPANCY SENSORS SHOWN ON PLANS AND OVER RIDES PER | | | 13-415.1.ABC.1.1, .1.2. | | | PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH ARE NOT | | | REFLECTED ON SYMBOL LEGEND OR ON LIGHTING CONTROL | | | DETAIL SHEETS. | | | | | | G) ** PLEASE SUBMIT MORE DETAILS AND COMPLETE | | | INFORMATION FOR GUEST ROOM CONTROLS. THE PLANS MAKE | | | NOTE OF SOME SORT OF SYSTEM ON E201 YET NOT ENOUGH FOR | | | REVIEW. 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | H) ** PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 FOR | | | REQUIRED NOTES TO BE PLACED ON PLANS. | | | | | | I) ** PLEASE SEE THE SQUARE FOOTAGE ON ENERGY | | | CALCULATIONS NEEDS TO COORDINATE WITH THE PLANS. | | | | | | J) ** PLEASE CLARIFY THE TYPE OF OCCUPANCY SENSOR | | | DEVICE WHICH IS LOCATED IN BATHROOMS. PLEASE VERY | | | FAILSAFE ON OR MULTIPLE SENSING. MAY NOT ONLY BE MOTION | | | SENSING DEVICE ON BATHROOMS MORE THAN SINGLE POINT | | | USE. | | | | | | ** PLEASE SEE ALL OF CHAPTER 13 FOR ELECTRICAL AND | | | OTHER TRADES. THE ABOVE NOTES ARE EXAMPLES OF ITEMS AND | | | AREAS OF CONCERN. | | | | | | 8) NOTE: PLEASE INCLUDE COLOR CODING FOR 277/480V | | | SYSTEMS AS BROWN, PURPLE, AND YELLOW. | | | THE NEC DOES NOT PROVIDE COLOR CODING FOR THESE | | | SYSTEMS. THESE SYSTEMS OF THIS SAME VOLTAGE IN THIS | | | COUNTY AND CITY UNDER THE PREVIOUS ADOPTED TECHNICAL | | | AMENDMENTS FOR SEVERAL DECADES HAS HAD THIS SAME COLOR | | | CODING AND IN THE INTEREST OF SAFETY AND AS WELL AS | | | CONSISTENCY THIS AHJ REQUIRES THE ABOVE COLORING. 90.4 | | | FBC 106.1.2 | | | | | | 9) NOTE: PLEASE SUBMIT FIRE PUMP CONTROLLER | | | MANUFACTURES SPECS AND CUT SHEETS WHICH REFLECT A | | | LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING | | | LABORATORY). | | | 110.4, 659.4, 90.7 | | | NFPA-20 CHAPTER 9 (ALL AS THERE ARE TOO MANY TO LIST) | | | AND 10 ETC. 10.4.3.3.1, 10.4.4, ETC | | | PLEASE PROVIDE INFORMATION ON ROUTING OF CONDUITS FROM | | | FPL VAULT TO THE FIRE PUMP CONTROLLER AND FIRE PUMP. | | | PLEASE SHOW ON PLANS AS WELL AS PROTECTIONS OF THE | | | INSTALLATIONS DEPENDING ON DESIGN. | | | AT THIS TIME AS INFORMATION WAS NOT CLEAR OR SUBMITTED | | | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH | | | CAN NOT BE MADE AT THIS TIME. | | | | | | 10) NOTE: PLEASE SUBMIT MINIMUM FUEL TIMES ON THE | | | GENERATOR FOR BACK UP OF FIRE PUMP AND OTHER LIFE | | | SAFETY AND LEGALLY REQUIRED SYSTEMS. | | | NFPA-70, 700, 701, NFPA-110, CHAPTER 7, 7.9, NFPA-20 | | | 9.6.2.2 | | | PLEASE ACTUALLY INDICATE THE ELEVATION OF THE | | | EQUIPMENT. THE PLANS STATE A NOTE TO BE ABOVE THE 100 | | | YEAR STORM SURGE LEVEL, HOWEVER PLEASE INDICATE WHERE | | | AND/OR WHAT THAT LEVEL IS. PLEASE SEE NFPA-110 7.2.3 ** | | | PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH RESPECT | | | TO LOCATION OF GENERATOR, EXHAUST, MAKE UP AIR ETC. | | | | | | 11) NOTE: PLEASE SEE NFPA-110 7.3.3 WHICH REQUIRES A | | | MINIMUM OF 30FT CANDLES OF LIGHTING IN ROOM. PLEASE BE | | | SURE TO INCLUDE THIS ON PLANS OR ON THE LIGHTING | | | PHOTO-METRICS. (PLEASE SEE OTHER COMMENTS WITH RESPECT | | | TO PHOTO-METRICS). | | | | | | 12) NOTE: PLANS SHOW A NOTE WITH RESPECT TO FIRE ALARM | | | DEVICES AND MINIMUM LEVELS, HOWEVER PLEASE SEE | | | 11-4.28.1, .2 AND .3. PLEASE BE SURE ALL MINIMUM LEVELS | | | ARE SHOWN. | | | | | | 13) NOTE: PLEASE KNOW EVEN AS MANY LOW VOLTAGE | | | SYSTEMS/ITEMS ARE SHOWN ON PLANS, SEPARATE PERMITS WILL | | | BE REQUIRED. PLEASE KNOW ANY INSTALLED LOW VOLTAGE | | | SYSTEMS WHICH ARE NOT COMPLETED ON THESE PLANS WILL | | | REQUIRE SEPARATE PLANS. | | | FIRE ALARM SYSTEM IS SEPARATE PERMIT AND PLANS. PLEASE | | | KNOW THE LIGHTNING PROTECTION SYSTEM AS NOTED ON PLANS | | | WILL REQUIRE SEPARATE PLANS AND PERMIT.A COMPLETE | | | SYSTEM IS NOT SHOWN. | | | ** THIS IS PROVIDED FOR INFORMATION AT THIS TIME. | | | | | | 14) NOTE: PLEASE SUBMIT MORE INFORMATION ON ACCESS | | | CONTROLS AS SHOWN ON PLANS. PLEASE SHOW AND INDICATE | | | HOW THE EGRESS PATHS ARE AFFECTED IN THE EVENT OF NOT | | | ONLY POWER FAILURE BUT ALSO IN AN EMERGENCY. PLEASE SEE | | | THE DETAIL SHOWN ON SHEET E-406 DOES NOT PROVIDE ENOUGH | | | INFORMATION AT THIS TIME. | | | PLEASE SEE NFPA-101 7.5.1,7.5.2, 7.1.9, 7.2.1.6.2 ETC | | | PLEASE PROVIDE FAIL SAFE OPERATIONS AND BE AWARE OF | | | REVIEW FROM FIRE MARSHAL. | | | PLEASE SUBMIT INFORMATION ON GATE OPERATIONS IN THE | | | SAME SCENARIO AS STATED ABOVE. | | | | | | 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL | | | EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS. | | | THIS SHOULD INCLUDE GARAGE AREAS, GENERATOR ROOM | | | PREVIOUSLY NOTED ABOVE, ALL STAIR LOCATIONS. PLEASE | | | KNOW THE STAIR POINT BY POINT DOES NOT SHOW ALL AREAS | | | OF THE STAIR WALKING SURFACES AS AN AVERAGE UNDER EACH. | | | PLEASE CLARIFY WHY HOW THE SAME AMOUNT OF FIXTURES ARE | | | SHOWING LESS LIGHTING UNDER EMERGENCY CONDITION. IS THE | | | BATTERY BACK UP BALLAST BASED ON LOWER LUMENS BACK UP? | | | PLEASE ALSO PROVIDE MINIMUM LEVELS FOR ELEVATOR PIT PER | | | 620.23 ( PLEASE SEE NEC WHICH REFERENCES MINIMUM LEVELS | | | PER ASME A17.1-2004 WHICH REFLECT SAFETY CODE FOR | | | ELEVATORS AND ESCALATORS. | | | ** MOST IMPORTANT, WILL BUILDING REMAIN *OCCUPIED* | | | UNDER GENERATOR POWER PAST THE MINIMUM LEVELS FOR | | | FUEL? | | | | | | WILL THE FAILURE OF THE SINGLE MAIN BREAKER ON THE | | | EMERGENCY PANEL OR GENERATOR LEAVE NO EGRESS LIGHTING | | | IN AREAS? | | | PLEASE KNOW WHEN A BUILDING IS OCCUPIED AND UNDER | | | GENERATOR POWER AND AN EMERGENCY EVENT OF SOME NATURE | | | OCCURS, THE FAILURE OF THE GENERATOR, MAIN BREAKER ETC | | | WILL LEAVE ANY EGRESS AREA IN TOTAL DARKNESS? THE STAIR | | | TOWERS AND MANY LOCATIONS DO CONTAIN BATTERY BACK UP | | | FIXTURES OF SOME SORT DURING AN EMERGENCY FOR OCCUPANTS | | | TO FIND THEIR WAY OUT OF THE BUILDING BUT NOT ALL. | | | PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF | | | EMERGENCY AND EXIT LIGHTS. MANY ARE SHOWN CIRCUITED TO | | | A LOCAL BRANCH CIRCUIT AS REQUIRED BUT NOT ALL. THERE | | | ARE EXCEPTIONS TO THIS SECTION OF THE CODE BUT ONLY FOR | | | UNINTERRUPTED AREAS CONTAINING 3 OR MORE BRANCH | | | CIRCUITS. | | | PLEASE EXPLAIN HOW MANY OF THESE LIGHT FIXTURES ARE | | | SHOWN ON DIMMING PANELS? PLANS CONTAIN NOTES FOR SOME | | | CIRCUITING BUT NOT ALL. | | | PLEASE KNOW THE FOLLOWING LOCATIONS WILL REQUIRE | | | BATTERY BACK UP FIXTURES OF SOME SORT: FIRE PUMP ROOM, | | | FIRE CONTROL AREA WHICH SHOWS FACP AND GAP, GENERATOR | | | ROOM, MAIN ELECTRICAL ROOM, AND ELEVATOR MACHINE ROOM. | | | PLEASE KNOW SOME OF THESE ARE SHOWN BUT NOT ALL. PLEASE | | | SEE NOTES ABOVE WITH RESPECT TO FBC CHAPTER 13 AS THIS | | | WILL AFFECT ALL LIGHTING IN BUILDING. PLEASE SEE | | | NFPA-101 7.8., 7.8.1.3, 7.9, 7.9.2.2 ETC. FAC | | | 61G15-33.004 | | | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION | | | NEEDED. | | | NEC 700.12F, 700.16 | | | | | | 16) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR | | | POOL/SPA AREAS STAMPED FROM PALM BEACH COUNTY HEALTH | | | DEPARTMENT. AS THIS AREA IS INSIDE BUILDING AND NOT | | | OPEN TO SUN LIGHT LEVELS DURING DAY OR NIGHT, ANY DUSK | | | TO DAWN NOTES OR RULES WOULD NOT APPLY. | | | PLEASE OBTAIN STAMPS. | | | FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION. | | | | | | 17) NOTE: PLEASE SEE 2005 NFPA-70 WHICH REQUIRES GFI | | | PROTECTION ON ALL 15/20 AMP 120V RECEPTACLES IN KITCHEN | | | AREAS AND THE LIKE. PLEASE KNOW THIS ALSO IS REQUIRED | | | FOR DEDICATED EQUIPMENT SUCH AS REFRIGERATORS ETC. | | | PLEASE SEE FOR EXAMPLE: KITCHEN PLANS, KP1-7. THIS IS | | | ONLY ONE EXAMPLE AND THERE ARE SEVERAL OTHERS INCLUDING | | | SERVING AREAS/BUFFET ETC. | | | THIS WAS CHANGED IN THE 2002 NEC AS WELL AS MINOR | | | MODIFICATIONS IN THE 2005. | | | | | | 18) NOTE: PLEASE COMPLETE INFORMATION ON FOOD SERVICE | | | PLANS FOR TITLE BLOCKS AND DESIGN PROFESSIONAL(S). | | | PLEASE SEE FAC 61G15-23.002. | | | | | | 19) NOTE: PLEASE COMPLETE ALL ROOM AND AREA | | | DESIGNATIONS ON PLANS. REVIEW OF CIRCUITING AND | | | NUMEROUS OTHER ITEMS FOR LIGHTING CONTROL RISER ETC IS | | | NEEDED. | | | SOME ROOMS AND AREAS COULD BE FIGURED OUT BUT NOT ALL. | | | PLEASE SEE SOME ROOMS FOR EXAMPLE LIKE ROOMS ON EACH | | | FLOOR NORTH OF ELECTRIC ROOM 402, 502 ETC | | | FBC 106.3.1, 106.3.5.1.2 ETC ADMIN SECTION FOR | | | ADDITIONAL INFORMATION. | | | NEC 240.4, 310.16 AND 408.4 WHICH REQUIRES ALL CIRCUITS | | | TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. | | | AS MANY OF THE ROOMS ARE NOT ALPHA OR NUMERICALLY | | | LABELED, MANY CAN NOT BE CONFIRMED. | | | | | | 20) NOTE: PLEASE SEE NEC 620.23 AS THIS REQUIRES | | | DEDICATED CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE | | | SEE THE LIGHTING SHOWN ON PLANS COMES FROM THE SAME | | | CIRCUIT WHICH FEEDS OTHER AREAS. | | | PLEASE ADJUST CIRCUITING. | | | | | | 21) NOTE: PLEASE SEE SYMBOLS ON PLANS NEED TO MATCH | | | WITH THE LEGEND. PLEASE SEE HOST AREA FOR EXAMPLE WHICH | | | SHOWS A F1/1 BUT COULD NOT LOCATE THE DEFINITIONS ON | | | THE LEGEND FOR THESE SAME DESIGNATIONS. | | | PLEASE SEE THE NEXT COMMENT WHICH ALSO RELATES TO THIS | | | COMMENT. | | | | | | 22) NOTE: PLEASE SEE SYMBOL IN MAIN ELECTRICAL ROOM | | | WHICH IS SHOWN AS WS IN A SQUARE BOX WHICH SEEMS TO BE | | | PART OF THE LIGHTING CONTROL. THIS IS UNCLEAR WHAT THIS | | | DEVICE IS. PLEASE SEE 110.26D FOR ILLUMINATION CONTROLS | | | WHICH DOES NOT ALLOW ONLY ONE SINGLE AUTOMATED | | | CONTROL. | | | | | | 23) NOTE: PLEASE CLARIFY THE OCTAGONAL NOTE #4 ON | | | E-201. MENTIONS LOAD USED FOR CALCULATIONS AND FIXTURE | | | WATTAGES FOR THE SAME NOTE. | | | PLEASE REVIEW AND CLARIFY. | | | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. | | | 220, OR CHAPTER 13. | | | | | | 24) NOTE: PLEASE SEE OCTAGONAL NOTE #6 ON E-102B FOR | | | LIGHTS IN EMERGENCY ROOM. PLEASE ADJUST. | | | | | | 25) NOTE: PLEASE SEE EMERGENCY ROOM WHICH IS LABELED AS | | | UTILITY ROOM M003. | | | DEDICATED ROOMS PER 110.26 | | | | | | 26) NOTE: PLEASE PROVIDE NOTES ON PLANS PER 230.2E, | | | 700.8, 701.9 FOR REQUIRED SIGNAGE AND MAPPING IN EACH | | | ROOM LOCATION AND ALSO FIRE COMMAND AREA. | | | | | | 27) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY | | | SIDE OF THE TRANSFORMER ARE REQUIRED TO MEET OR EXCEED | | | THE OVER CURRENT PROTECTION IN WHICH THE TAPPED | | | CONDUCTORS ARE TERMINATING. | | | PLEASE SEE 240.21, 240.4, 310.16, 110.14 | | | MOST TAPPED CONDUCTORS ARE OK HOWEVER SOME NOTED FOR | | | EXAMPLE: T-4W, T-3W, T-1W WHICH ARE BELOW RATING. | | | PLEASE ADJUST AND REVIEW ALL. | | | | | | 28) NOTE: PLEASE SEE THE RISER WHICH INDICATES *GFI* | | | PROTECTION ON THE 3000AMPS MSB. PLEASE SEE 240.13, | | | 230.95 AND CONFIRM TYPE OF PROTECTION SHOWN. PLEASE SEE | | | THAT GFI IS TYPICALLY CLASS A PROTECTION FOR PERSONNEL | | | WHICH IS DIFFERENT FROM THE GFP (GROUND FAULT | | | PROTECTION) AS NOTED IN NFPA-70 SECTIONS GIVEN. | | | | | | 29) NOTE: PLEASE CLARIFY EMERGENCY RELAY PANELS? THIS | | | FALLS IN LINE WITH THE NOTES ABOVE WITH RESPECT TO | | | LIGHTING CONTROLS AND LIFE SAFETY NOTES FOR LIGHTING. | | | THIS WILL NEED TO BE GONE OVER. | | | THIS IS THE FIRST TIME A REVIEW OF THIS TYPE OF SYSTEM | | | IS BEING SUBMITTED/PROPOSED. | | | LS 101 7.8, 7.9 | | | | | | 30) NOTE: PLEASE SUBMIT A PANEL SCHEDULE FOR THE MSB | | | SWITCHBOARD. COULD NOT LOCATE THIS ON PLANS. PLEASE BE | | | SURE TO COORDINATE ALL INFORMATION ON PANEL SCHEDULE | | | AND RISER. | | | 408.4, 310.16, 240.4 ETC | | | FBC 106.1.2, 106.3.5.1.2 | | | | | | 31) NOTE: PLEASE SEE HP2LW WHICH SHOWS A 500AMP RATED | | | MAIN CIRCUIT BREAKER ON A 400AMP RATED PANEL. 110.3, | | | 90.7, 240 ETC | | | FBC 106.1.2 FOR COORDINATION. | | | | | | 32) NOTE: PLEASE COORDINATE THE PANEL SCHEDULE ON E501 | | | FOR PANEL EMDP WITH THAT OF THE INFORMATION SHOWN ON | | | RISER. PLEASE SEE THERE ARE SEVERAL ITEMS WHICH ARE NOT | | | THE SAME. FOR EXAMPLE: PLEASE SEE OVER CURRENT | | | PROTECTION ON RISER FOR ALL SPARES ARE 150,60,60 AND | | | 30, YET THE SCHEDULE SHOWS 20,30,20,20 AND OTHER LOADS | | | SUCH AS EXHAUST FANS WHICH ARE NOT ON THE RISER EMDP. | | | FBC 106.1.2 FOR COORDINATION. | | | 408.4, 240.4, 310.16 ETC NEC. | | | | | | 33) NOTE: PLEASE SEE EDPLS WHICH ON RISER IS NOT THE | | | SAME AS THE SCHEDULE FOR DEVICES AND OVER CURRENT | | | PROTECTION DEVICES AS LISTED ON RISER. | | | PLEASE SEE FOR EXAMPLE: THE RISER SHOWS TWO 70AMP | | | CIRCUITS FOR EACH TRANSFORMER T-LSE2 AND T-LSW-2 YET | | | THE PANEL SCHEDULE ON E-501 SHOWS THESE WITH 150AMP | | | OVER CURRENT PROTECTION WHICH EXCEEDS CONDUCTOR | | | RATINGS,(310.16, 240.4)THE MAXIMUM OVER CURRENT | | | PROTECTION PER 450.3 ETC. | | | PLEASE ALSO SEE THERE ARE OTHER ITEMS SUCH AS THE OVER | | | CURRENT PROTECTION DEVICES FOR SPARES. | | | PLEASE COORDINATE ALL. | | | FBC 106.1.2 FOR COORDINATION AND SECTIONS NOTED FOR | | | NEC. | | | | | | ** PLEASE BE AWARE THE COMMENTS ARE BASED ON PLANS AND | | | DOCUMENTS SUBMITTED FOR REVIEW. ANY CHANGES IN DESIGN, | | | LOCATIONS AND/OR ADDITIONAL INFORMATION SUBMITTED WHICH | | | COULD NOT YET BE REVIEW MAY GENERATE NEW COMMENTS WHICH | | | COULD NOT BE MADE AT THIS TIME. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2008-02-05 16:04:54 | | | | REVIEW COMMENCED ON 2/4 AND COMPLETED 2/5. REVIEW WILL | | | GO INTO "F" STATUS. NOTES TO FOLLOW. | | 2008-01-29 08:06:34 | 1-ROLL OF MEP IN ELECTRICAL FOR REVIEW ALONG WITH ONE | | | SPEC BOOK |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
4 |
Status |
P |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
mgonzale |
Date |
2008-11-18 |
Time |
15:55 |
Rev Time |
1.00 |
| Received By |
mgonzale |
Date |
2008-11-18 |
Time |
15:54 |
Sent To |
ENG |
|
| Notes |
| 2008-11-18 15:57:34 | - PASSED - | | | | | | TRASH COMPACTOR WILL BE SERVICE THRU PRIVATE PICK-UP. | | | COMPLIANCE WAS COORDINATED THRU EMERY FABIAN AT | | | ENGINEERING DEPT. (561) 494-1078 | | | SANITATION DEPT. WAS ALSO CONTACTED IN THE DICUSSION. | | | ANY QUESTIONS FEEL TO CONTACT ME. | | | | | | MANUEL J GONZALEZ, PROJECT COORDINATOR | | | LOCATION ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | 1000 - 45TH STREET, SUITE 15 | | | WEST PALM BEACH FL 33407 | | | MAILING ADDRESS: | | | CITY OF WEST PALM BEACH | | | ENGINEERING SERVICES DEPARTMENT | | | P.O. BOX 3506 | | | WEST PALM BEACH FL 33401 | | | TELEPHONE: | | | 45TH STREET OFFICE : 561-494-1040 | | | 45TH DIRECT: 561-494-1085 | | | FAX: 561-494-1117 | | | CITY HALL OFFICE: (561) 805-6723 | | | CITY HALL DIRECT: (561) 805-6327 | | | CITY HALL FAX: (561) 805-6731 OR 805-6676 | | | NEXTEL: 561-644-7301 | | | NEXTEL DIRECT CONNECT: 159*28165*38 | | | EMERGENCIES: | | | CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210 | | | E-MAIL: | | | [email protected] | | | |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
3 |
Status |
F |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-09-24 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-09-24 |
Time |
13:35 |
Sent To |
|
|
| Notes |
| 2008-09-24 13:42:45 | *** FAILED ***** | | | | | | | | | PLEASE EXPLAIN WHAT DID YOU CHANGE FROM PREVIOUS | | | DESIGN?? NEED NEW LENGTH, WIDTH OF THE DUMPSTER GATE, | | | NEED SLAB LOCATION DIMENSIONS, HOW IS IT GOING TO FIT? | | | IS CITY TRUCK ACCESSIBLE TO PICK UP YOUR DUMPSTER? | | | PLEASE EXPLAIN ALL OF THESE. YOUR DRAWING SUBMITTED | | | DOES NOT EXPLAIN ANY OF THESE ITEMS. | | | | | | RASIK CHOKSHI 805-6723 |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
2 |
Status |
N |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-05-14 |
Time |
11:02 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-05-14 |
Time |
11:02 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
ENG |
ENGINEERING CSD |
| Rev No |
1 |
Status |
P |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
rchokshi |
Date |
2008-01-17 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
rchokshi |
Date |
2008-01-17 |
Time |
10:46 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
7 |
Status |
P |
Date |
2009-05-21 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-05-21 |
Time |
15:26 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-05-21 |
Time |
14:24 |
Sent To |
|
|
| Notes |
| 2009-05-21 15:33:27 | *****REVISION #11, APPROVED***** | | | | | | VARIOUS ELECTRICAL SHEETS WERE REVIEWED IN REFERENCE TO | | | THE ADDITIONS, DELETIONS, AND/OR ANY OTHER CHANGES | | | REGARDING THE EXIT AND EMERGENCY LIGHTS. THOSE "E" | | | SHEETS WERE APPROVED, HOWEVER NO-FIRE-STAMPING | | | NECESSARY. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
6 |
Status |
P |
Date |
2009-01-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2009-01-26 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2009-01-26 |
Time |
10:42 |
Sent To |
|
|
| Notes |
| 2009-01-26 12:12:19 | *****REVISION #7, DATED NOV.2008, APPROVED***** | | | | | | | | | REVISED SHEETS G-007, G-008, A-611, FP-201A, AND E101'S | | | A, B, & C WERE STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
5 |
Status |
P |
Date |
2008-11-19 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-11-19 |
Time |
16:21 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-11-19 |
Time |
16:14 |
Sent To |
|
|
| Notes |
| 2008-11-19 16:21:24 | REVISION # 5 | | | | | | 1. ON PAGE E-101 C EXIT SIGNS STILL APOPEAR TO DIRECT | | | PERSONS INTO GARAGE AREA WHICH IS CONSIDERED MORE | | | HAZARDOUS THAN THE AREA THEY ARE EXISTING FROM. PLEASE | | | REMOVE THESE EXIT SIGNS SO PERSONS DO NOT EXIT INTO A | | | MORE HAZARDOUS AREA. | | | | | | 2. THE CARBON MONOXIDE DETECTORS (CO) SHALL BE PROPERLY | | | TESTED WITH CALIBRATION GAS AT THE ESTABLISHED SET | | | POINTS OF THE MANUFACTURER. | | | | | | 3. THE KNOX BOX SHOULD BE INSTALLED NEAR THE MAIN | | | INGRESS/EGRESS DOOR FOR THE HOTEL. | | | | | | 4. CARD READERS OR ANY SECURITY DEVICES SHALL NOT | | | INTERFERE WITH REQUIRED EXITING FROM THE BUILDING. | | | | | | 5. NATURAL GAS INSTALLATION SHALL COMPLY WITH | | | APPROPRIATE NFPA STANDARDS AND RECOGNIZED SAFE | | | PRACTICES. | | | | | | | | | APPROVED PROVISO: | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-07-17 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-07-17 |
Time |
16:15 |
Sent To |
|
|
| Notes |
| 2008-07-17 16:17:22 | THE FIRE SPRINKLER PLANS WERE REVIEWED AND APPROVED ON | | | JULY 17, 2008 AND WAS THE ONLY REMAINING FIRE RESCUE | | | OUTSTANDING ISSUE RELATED TO THE PLANS. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-06-12 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-06-12 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-06-12 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2008-06-12 15:09:23 | 1. THE PREVIOUS PLAN REVIEW COMMENTS APPEAR TO HAVE | | | BEEN PROPERLY ADDRESSED WITH THE REVISED PLANS AND | | | COMMENT LETTER. | | | | | | 2. THERE STILL APPEARS TO BE CONFUSION RELATED TO THE | | | FIRE PROTECTION DRAWINGS. THE FIRE PROTECTION KEYED | | | NOTES INDICATES THAT A CLASS III MANUAL WET STANDPIPE | | | SYSTEM WITH 2 1/2 TO 1 1/2 REDUCERS WITH CAPS ATTACHED | | | TO A CHAIN ARE GOING TO BE PROVIDED. PER NFPA 14, THE | | | STANDARD FOR STANDPIPE SYSTEMS A MANUAL WET STANDPIPE | | | SYSTEM IS DEFINED AS A WET STANDPIPE SYSTEM CONNECTED | | | TO A SMALL WATER SUPPLY FOR THE PURPOSE OF MAINTAINING | | | WATER WITHIN THE SYSTEM OR SHARING A WATER SUPPLY WITH | | | AN AUTOMATIC SPRINKLER SYSTEM BUT NOT HAVING A WATER | | | SUPPLY ATTACHED TO IT. THIS PROPSOSED SYSTEM IS A | | | SYSTEM THAT RELIES ON THE FIRE DEPARTMENT TO CONNECT TO | | | THE FIRE DEPARTMENT CONNECTION TO SUPPLY SYSTEM DEMAND. | | | FURTHER A CLASS III STANDPIPE SYSTEM PROVIDES HOSE | | | STATIONS FOR USE BY BUILDING OCCUPANTS. BUILDING | | | OCCUPANTS AND STAFF CANNOT BE SUFFICIENTLY TRAINED TO | | | USE CLASS III STANDPIPES. | | | | | | 3. NO PRIOR APPROVAL FOR THE MANUAL WET STANDPIPE | | | SYSTEM ARRANGEMENT HAS OCCURRED WITH THIS OFFICE. SOME | | | TIME AGO THIS INFORMATION WAS DISCUSSED AS THE PREVIOUS | | | PLANS DID NOT SEEM TO COORDINATE WITH OTHER DRAWINGS. | | | NO APPROVAL FOR A MANUAL WET STANDPIPE SYSTEM WILL BE | | | ALLOWED FOR THIS NEW HOTEL. | | | | | | 4. ON PAGE FP-205A A COMBINATION CLASS II STANDPIPE | | | SYSTEM HAS BEEN CALLED OUT FOR THE ROOF MANIFOLD. | | | | | | 5. ON PAGE FP-201A A SIX INCH FIRE LINE IS DESCRIBED. A | | | 100 PSI ELECTRIC PUMP IS ALSO NOTED ALTHOUGH THE EXACT | | | GPM FOR THE PUMP COULD NOT BE LOCATED. | | | | | | 6. NO FIRE PUMP DETAILS OR SPECIFIC DRAWINGS COULD BE | | | LOCATED. | | | | | | 7. THE FIRE LINE APPEARS TO LEAVE THE EXISTING TWELVE | | | INCH FIRE MAIN AND ENTERS PRIVATE PROPERTY AND IS | | | REDUCED TO SIX INCHES AND ENTERS THE SPRINKLER BFP | | | ROOM. WHERE IS THE POINT OF SERVICE BEING CONSIDERED | | | AND WHERE IS THE FIRE SPRINKLER RISER LOCATED. | | | | | | 8. TWELVE FIFTY IS REFERENCED ON THE FIRE PROTECTION | | | PLANS HOWEVER ONLY THREE TEST HEADERS ARE AVAILABLE | | | WHICH EQUATES TO ONE THOUSAND GPM'S. | | | | | | 9. A CAREFUL REVIEW OF THE CIVIL AND FIRE PROTECTION | | | DRAWINGS NEEDS TO OCCUR SO THE DESIGN INTENT IS | | | APPARANT. A MANAUL WET STANDPIPE SYSTEM IS NOT APPROVED | | | AND SHALL BE REMOVED FROM THE DRAWINGS. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-05-20 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-05-20 |
Time |
11:41 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-05-20 |
Time |
11:26 |
Sent To |
|
|
| Notes |
| 2008-05-20 11:41:35 | 1. PLEASE EXPLAIN CARD READERS ON STAIR # 1 DOORS. THE | | | USE OF EXIT DOORS SHALL NOT REQUIRE THE USE OF A CARD | | | SO THAT THEY CAN BE UTILIZED. CARD READERS ALSO NOTED | | | ON EXITWAY DOOR AND OTHER LOCATIONS PER THE DOOR | | | SCHEDULE DISPLAYED ON PAGE A-611. PLEASE EXPLAIN | | | RATIONALE. ALL RATED FIRE DOORS AND APPURTENANT | | | EQUIPMENT SHALL COMPLY WITH NFPA 80, THE STANDARD FOR | | | FIRE DOORS AND WINDOWS AND BE EQUIPPED WITH | | | SELF-CLOSING DEVICES TO CAUSE THE DOORS TO POSITIVELY | | | LATCH WHEN CLOSED. | | | | | | 2. PLEASE PROVIDE FLAMESPREAD DATE FOR CANOPY SHOWN ON | | | PAGE A-202. | | | | | | 3. THE FIRE DEPARTMENT CONNECTION SHALL BE EQUIPPED | | | WITH LOCKING KNOX-BOX CAPS. | | | | | | 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF | | | THREE FEET FROM AIR CONDITIONER DIFFUSERS. | | | | | | 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | NOTE # 11 ON ARCHITECTURAL SHEETS REGARDING TACTILE | | | SIGNAGE MAY BE CONFUSING TO SOME. | | | | | | 6. KEY NOTES # 2 "KEY CARD ACCESS ON ARCHITECTURAL | | | SHEETS NEEDS TO BE FURTHER EXPLAINED. EXIT ACCESS AND | | | EXIT DOORS SHALL NOT REQUIRE THE USE OF AKY, TOOL, | | | SPECIAL KNOWLDEGE TO EXIT. | | | | | | 7. THE GREASE DUCT ILLUSTRATED ON PAGE A-100D SHALL | | | MEET ALL OF THE REQUIREMENTS OF NFPA 96. | | | | | | 8. EMERGENCY INSTRUCTIONS FOR RESIDENTS AND GUESTS ARE | | | REQUIRED ON EVERY HOTEL ROOM DOOR. FIRE SAFETY | | | INFORMATION SHALL BE PROVIDED TO GUESTS. | | | | | | 9. LISTED QUICK RESPONSE OR LISTED RESIDENTIAL | | | SPRINKLERS SHALL BE PROVIDED FOR THE FIRE SPRINKLER | | | SYSTEM. | | | | | | 10. HEARING IMPAIRED ROOMS SHALL BE EQUIPPED WITH | | | VISIBLE NOTIFICATION APPLIANCES. | | | | | | 11. MECHANICAL DRAWINGS DISPLAY SEVERAL DEFICIENCIES | | | THAT HAVE BEEN HIGHLIGHTED IN RED BY THE MECHANICAL | | | PLAN REVIEWER. SEVERAL ARE RELATED TO FIRE AND LIFE | | | SAFETY. | | | | | | 12. THE NO EXIT SIGNS SHALL COMPLY WITH THE | | | REQUIREMENTS OF CHAPTER 7 OF THE LIFE SAFETY CODE. | | | | | | 13. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE | | | CORRECTED. | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4724 PHONE | | | 804-4774 FAX |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
mcarsill |
Date |
2008-03-24 |
Time |
09:05 |
Rev Time |
0.00 |
| Received By |
mcarsill |
Date |
2008-03-24 |
Time |
08:34 |
Sent To |
|
|
| Notes |
| 2008-03-24 09:05:03 | 1. FIRE AND LIFE SAFETY CODE 2004 FLORIDA BUILDING CODE | | | SHOULD READ FLORIDA FIRE PREVENTION CODE ON PAGE | | | G-000. | | | | | | 2. FIRE WALL RATINGS BETWEEN PORTIONS OF THE HOTEL AND | | | PARKING GARAGE APPEARS TO BE ONLY ONE HOUR RATED ON | | | PAGE G-007. A TWO HOUR RATING IS REQUIRED BETWEEN | | | PARKING GARAGES AND OTHER PORTIONS OF THE BUILDING. | | | | | | 3. EXIT SIGN IN MEETING ROOM # 110 DIRECTS PERSONS INTO | | | CLOSET ON PAGE G-007. | | | | | | 4. SOME EXIT SIGNS APPEAR TO BE DIRECTING PERSONS TO | | | EXIT INTO GARAGE. THE GARAGE IS A MORE HAZARSOUS AREA | | | THAN THE HOTEL. PLEASE SEE PAGE G-007. EXITING IS NOT | | | PERMITTED TO PASS INTO A MORE HAZARDOUS AREA. | | | | | | 5. EXIT TRAVEL ROUTE ON PAGE G-007 IN GARAGE ON | | | MEZZANINE LEVEL TRAVELS OVER COLUMN TO REACH STAIR # | | | 2. | | | | | | 6. FIRE RATED WALLS BETWEEN GARAGE AND MEZZANINE ARE | | | ONLY ONE HOUR ON PAGE G-007. | | | | | | 7. OTHER EXIT ROUTE FROM GARAGE TOWARDS STAIR # 1 | | | APPEARS TO TRAVEL OVER A SHAFT, LIFE SAFETY MEZZANINE. | | | | | | 8. TRAVEL DISTANCE ROUTE ON THE LIFE SAFETY, SECOND | | | LEVEL APPEARS TO TRAVEL OVER PARKING STALLS ON PAGE | | | G-008. | | | | | | 9. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN | | | CORRIDOR ON SECOND LEVELS AND TYPICAL LEVELS ON PAGE | | | G-008. | | | | | | 10. FIRE RATED WALLS APPEAR TO BE ONE HOUR BETWEEN | | | GARAGE AND OTHER AREAS ON PAGE G-008. | | | | | | 11. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON SECOND | | | LEVEL ON PAGE G-008. | | | | | | 12. THE PROPOSED LIVE OAK TREE DISPLAYED ON LP1 SHALL | | | NOT OBSTRUCT OR INTERFERE WITH THE PROPOSED FIRE | | | DEPARTMENT CONNECTION SHOWN ON THE OLIVE AVENUE SIDE | | | ELEVATION. | | | | | | 13. WHAT CHEMICALS IF ANY OR ANY PLANNED TO BE STORED | | | IN THE SPA EQUIPMENT ROOM 141 ON PAGE AC-103. IF | | | CHEMICALS ARE PLANNED WHAT TYPES AND WHAT QUANTITIES. | | | | | | 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS | | | FOR ALL HANDRAILS AND GUARDRAILS PLANNED FOR THE | | | PROJECT. | | | | | | 15. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ELEVATOR | | | LOCATIONS. | | | | | | 16. PLEASE PROVIDE DETAILS ON FIRE SHUTTER CALLED OUT | | | ON PAGE A100C. | | | | | | 17. DOORS LOCATED ADJACENT TO STAIR # 1 AND STAIR # 2 | | | THAT MAY BE CONFUSED AS EXITS SHALL BE PROPERLY | | | IDENTIFIED WITH SIGNS INDICATING "NO EXIT". | | | | | | 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS. | | | | | | 19. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING | | | PARTITIONS IN MEETING ROOM 111 ON PAGE A-101A. | | | | | | 20. REFLECTED CEILING PLAN SYMBOLS DOES NOT IDENTIFY | | | WHAT A HALF DARKENED CIRCLE IS. PLEASE IDENTIFY AR | | | SHEETS. | | | | | | 21. BUILDING ADDRESS SHALL BE SHOWN ON PROPER EXTERIOR | | | ELEVATION DRAWING. | | | | | | 22. COULD NOT LOCATE ANY SMOKE DETECTOR IN KING | | | ELECTRICAL PLAN ON PAGE A-421. | | | | | | 23. ARCHITECTURAL SOFFIT SHALL NOT INTERFERE WITH ANY | | | OPERATION OF ANY FIRE SPRINKLER HEADS. | | | | | | 24. TRASH CHUTE TO COMPLY WITH NFPA 82. | | | | | | 25. DOOR SCHEDULE ON PAGE A-611 WILL HAVE INCORRECT | | | DOOR RATINGS DUE TO ONE HOUR WALLS WHEN TWO HOUR WALLS | | | SHOULD HAVE BEEN PROVIDED. | | | | | | 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD, | | | DUCT, AND FIRE SUPPRESSION SYSTEM SHOWN ON PAGE E-202. | | | | | | 27. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM | | | SYSTEM. FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE | | | MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR | | | CENTRAL STATION SERVICE. | | | | | | 28. PLEASE FURTHER DEFINE NOTE # 9 ON PAGE E-303. | | | | | | 29. SEPERATE PLANS AND PERMITS REQUIRED FOR THE FIRE | | | SPRINKLER SYSTEM. ENTIRE BUILDING SHALL BE COMPLETELY | | | FIRE SPRINKLER PROTECTED. THIS INCLUDES ALL VERTICAL | | | SHAFTS, ELECTRICAL, MECHANICAL AND ELEVATOR ROOMS. | | | | | | 30. FIRE PROTECTION SYSTEM GENERAL NOTES # 1 SHOULD | | | INCLUDE NFPA 20. | | | | | | 31. ALL FIRE DAMPERS ILLUSTRATED ON THE MECHAICAL PLANS | | | ARE TO BE DROP TESTED TO ENSURE PROPER OPERATION AFTER | | | INSTALLATION. | | | | | | 32. CARBON MONOXIDE DETECTORS ILLUSTRATED IN THE | | | PARKING GARAGE SHALL BE TESTED TO ENSURE PROPER | | | OPERATION. THESE DETECTORS SHALL BE TESTED WITH | | | CALIBRATION GAS AT THE PROPER SET POINT OF THE | | | DETECTORS. INFORMATION SHALL BE PROVIDED FOR THE CARBON | | | MONOXIDE DETECTORS SELECTED. | | | | | | 33. STAIRWELL IDENTIFICATION SIGNS REQUIRED. STAIR | | | IDENTITY, FLOOR LEVEL, TERMINUS TOP AND BOTTOM SHALL BE | | | PROVIDED. | | | | | | 34. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS | | | SHALL BE PROVIDED. | | | | | | 35. GAS EQUIPMENT AND RISER INSTALLATIONS TO COMPLY | | | WITH NFPA STANDARDS THAT ARE SHOWN ON PAGE P-602. | | | | | | 36. FIRE MARSHAL NOTES NOTED ON PLANS SHALL BE | | | FOLLOWED. | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION | | | 804-4709 PHONE | | | 804-4776 FAX |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
10 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-13 |
Time |
19:34 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-13 |
Time |
19:34 |
Sent To |
|
|
| Notes |
| 2009-02-13 19:35:46 | REVISION OK -- SHT P-602 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
9 |
Status |
P |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-24 |
Time |
23:18 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-24 |
Time |
23:18 |
Sent To |
|
|
| Notes |
| 2009-01-24 23:19:20 | REVISIONS OK -- SHTS P-201A, P-202A (PROVISO: DIRECT | | | VENTS FOR THE WATER HEATERS ARE NOT APPROVED AS | | | INDICATED THRU THE ZERO LOT LINE WALL - REVISION | | | REQUIRED), AND P-203A. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
8 |
Status |
F |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-24 |
Time |
23:14 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-24 |
Time |
23:14 |
Sent To |
|
|
| Notes |
| 2009-01-24 23:16:45 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FLORIDA STATUTES | | | | | | 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE | | | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE | | | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE | | | PLUMBING PLAN REVIEW. FS 589. | | | | | | 2. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM | | | 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). -- | | | THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE | | | THROUGH A WALL ON THE ZERO LOT LINE. | | | | | | 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
7 |
Status |
P |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-24 |
Time |
23:13 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-24 |
Time |
23:13 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
6 |
Status |
F |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-31 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-31 |
Time |
16:10 |
Sent To |
|
|
| Notes |
| 2008-10-31 16:11:28 | GAS REVISION DENIED FOR SHT P-602. SEE COMMENTS ON | | | PLUMBING REVIEW STOP #9. |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
5 |
Status |
P |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-31 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-29 |
Time |
16:50 |
Sent To |
|
|
| Notes |
| 2008-10-31 16:10:05 | REVISIONS OK -- SHTS P-201A, P-202A & P-302 |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
4 |
Status |
P |
Date |
2008-07-16 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-16 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-16 |
Time |
17:18 |
Sent To |
|
|
| Notes |
| 2008-07-16 17:21:36 | | | | | | | PASSED/PROVISO | | | | | | MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT REQUIRED AT THE TIME OF APPLICATION FOR | | | REQUIRED GAS PERMIT. | | | | | | | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
3 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-03 |
Time |
11:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-02 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:34:10 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT | | | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS | | | APPLICATION IS APPLIED FOR). | | | | | | I. N/A | | | J. N/A | | | | | | **********NEW COMMENTS********** | | | | | | 1B. OK | | | 2B. OK | | | 3B. OK | | | | | | ***********NEW COMMENT*********** | | | | | | 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL | | | Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS | | | INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-26 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-26 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:32:45 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT | | | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS | | | APPLICATION IS APPLIED FOR). | | | | | | I. N/A | | | J. N/A | | | | | | **********NEW COMMENTS********** | | | | | | | | | 1B. THE GAS REGULATOR SUBMITTAL IS NOT APPROVED FOR ALL | | | GAS APPLIANCES. THE ONLY SIZE INDICATED IN THE | | | SUBMITTAL IS 3/4" BUT THE SHUT OFF VALVE AND REGULATOR | | | SHALL BE SIZED PER THE PIPE SIZE REQUIRED TO EACH | | | APPLIANCE. | | | | | | 2B. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. THIS IS REQUIRED FOR THE | | | GRIDDLE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-10 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-10 |
Time |
11:10 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:30:45 | DENIED | | | REFERENCE: FBC-2004 FUEL GAS | | | | | | 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC | | | DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER | | | HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE | | | ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH | | | SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE | | | ENDS.PLEASE CORRELATE. SECTION 106.1.1. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE | | | SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE | | | INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE | | | 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6). | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | E. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602 | | | INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS | | | PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES | | | AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE | | | INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT | | | DELIVERY PRESSURE. | | | | | | G. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | I. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | J. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
37 |
Status |
N |
Date |
2009-04-20 |
|
|
Cont ID |
|
| Sent By |
swurafti |
Date |
2009-04-20 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
swurafti |
Date |
2009-04-20 |
Time |
16:36 |
Sent To |
B |
|
| Notes |
| 2009-04-20 16:36:45 | TO "JWITMER" DESK |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
36 |
Status |
|
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
|
Time |
|
Rev Time |
0.00 |
| Received By |
jwitmer |
Date |
2009-04-13 |
Time |
09:47 |
Sent To |
|
|
| Notes |
| 2009-04-13 09:48:50 | 4/13/09 INCOMING TO J WITMER SUBMITTAL FOR ROOF TOP | | | CAGES FOR MECHANICAL EGUIPMENT. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
35 |
Status |
N |
Date |
2009-03-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-03-05 |
Time |
10:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-03-05 |
Time |
10:03 |
Sent To |
B |
|
| Notes |
| 2009-03-05 10:03:50 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
34 |
Status |
N |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-13 |
Time |
16:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-13 |
Time |
16:06 |
Sent To |
|
|
| Notes |
| 2009-02-13 16:11:01 | TO "COMM" BD#33 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
33 |
Status |
N |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-12 |
Time |
16:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-12 |
Time |
16:23 |
Sent To |
|
|
| Notes |
| 2009-02-12 16:25:25 | TO "COMM" BD#33 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
32 |
Status |
N |
Date |
2009-02-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-02-02 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-02-02 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2009-02-02 10:36:02 | TO "COMM" BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
31 |
Status |
N |
Date |
2009-01-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2009-01-23 |
Time |
09:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2009-01-23 |
Time |
09:56 |
Sent To |
|
|
| Notes |
| 2009-01-23 09:56:24 | TO "COMM" BD#40 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
30 |
Status |
N |
Date |
2008-12-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-24 |
Time |
09:48 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-24 |
Time |
09:48 |
Sent To |
L |
|
| Notes |
| 2008-12-24 09:48:53 | TO "Z" BOX/REV--LANDSCAPING |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
29 |
Status |
N |
Date |
2008-12-19 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-19 |
Time |
08:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-19 |
Time |
08:47 |
Sent To |
M |
|
| Notes |
| 2008-12-19 08:48:56 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
28 |
Status |
N |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-12-04 |
Time |
16:59 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-12-04 |
Time |
16:59 |
Sent To |
B |
|
| Notes |
| 2008-12-04 17:00:16 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
27 |
Status |
N |
Date |
2008-12-04 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-12-04 |
Time |
09:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-12-04 |
Time |
09:42 |
Sent To |
B |
|
| Notes |
| 2008-12-04 09:43:11 | ROUTED TO JIM WITMER'S DESK MMILLER |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
26 |
Status |
N |
Date |
2008-11-26 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-26 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-26 |
Time |
09:00 |
Sent To |
B |
|
| Notes |
| 2008-11-26 09:00:57 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
25 |
Status |
N |
Date |
2008-11-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-18 |
Time |
11:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-18 |
Time |
11:24 |
Sent To |
B |
|
| Notes |
| 2008-11-18 11:24:52 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
24 |
Status |
N |
Date |
2008-11-07 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-07 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-07 |
Time |
16:53 |
Sent To |
B |
|
| Notes |
| 2008-11-07 16:53:38 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
23 |
Status |
N |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-05 |
Time |
11:27 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-05 |
Time |
11:27 |
Sent To |
B |
|
| Notes |
| 2008-11-05 11:28:11 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
22 |
Status |
N |
Date |
2008-11-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-11-04 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-11-04 |
Time |
13:00 |
Sent To |
B |
|
| Notes |
| 2008-11-04 13:01:50 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
21 |
Status |
N |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-27 |
Time |
16:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-27 |
Time |
16:50 |
Sent To |
B |
|
| Notes |
| 2008-10-27 16:51:19 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
20 |
Status |
N |
Date |
2008-10-23 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-23 |
Time |
09:50 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-23 |
Time |
09:50 |
Sent To |
B |
|
| Notes |
| 2008-10-23 09:50:45 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
19 |
Status |
N |
Date |
2008-10-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-22 |
Time |
10:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-22 |
Time |
10:56 |
Sent To |
P |
|
| Notes |
| 2008-10-22 10:57:03 | TO "P" BOX/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
18 |
Status |
N |
Date |
2008-10-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-16 |
Time |
15:06 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-16 |
Time |
15:06 |
Sent To |
|
|
| Notes |
| 2008-10-16 15:09:58 | TO "COMM" BD#16 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
17 |
Status |
N |
Date |
2008-10-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-08 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-08 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2008-10-08 16:41:45 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
16 |
Status |
N |
Date |
2008-10-06 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-10-06 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-10-06 |
Time |
09:13 |
Sent To |
B |
|
| Notes |
| 2008-10-06 09:13:59 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
15 |
Status |
N |
Date |
2008-09-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-24 |
Time |
09:36 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-24 |
Time |
09:36 |
Sent To |
B |
|
| Notes |
| 2008-09-24 09:37:01 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
14 |
Status |
N |
Date |
2008-09-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-16 |
Time |
15:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-16 |
Time |
15:47 |
Sent To |
B |
|
| Notes |
| 2008-09-16 15:48:09 | TO "JWITMER" DESK/6 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
13 |
Status |
N |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-10 |
Time |
13:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-10 |
Time |
13:00 |
Sent To |
B |
|
| Notes |
| 2008-09-10 13:00:37 | TO "JWITMER" DESK/2 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
12 |
Status |
N |
Date |
2008-09-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-08 |
Time |
09:47 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-08 |
Time |
09:47 |
Sent To |
M |
|
| Notes |
| 2008-09-08 09:47:34 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
11 |
Status |
N |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-02 |
Time |
15:56 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-02 |
Time |
15:56 |
Sent To |
B |
|
| Notes |
| 2008-09-02 15:56:32 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-28 |
Time |
14:03 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-28 |
Time |
14:03 |
Sent To |
P |
|
| Notes |
| 2008-08-28 14:03:38 | TO "PLUMB"KEN S. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-08-25 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-08-25 |
Time |
14:00 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-08-25 |
Time |
14:00 |
Sent To |
|
|
| Notes |
| 2008-08-25 14:01:15 | SUBMITTALSSENT TO"COMM" BD #9 (RACK) |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-08-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-18 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-18 |
Time |
08:17 |
Sent To |
B |
|
| Notes |
| 2008-08-18 08:17:54 | TO "JWITMER" DESK/11 SUBMITTALS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-14 |
Time |
14:02 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-14 |
Time |
14:02 |
Sent To |
M |
|
| Notes |
| 2008-08-14 14:03:06 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-08-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-08-14 |
Time |
13:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-08-14 |
Time |
13:54 |
Sent To |
P |
|
| Notes |
| 2008-08-14 13:55:15 | TO "P" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-07-10 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-07-10 |
Time |
14:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-07-10 |
Time |
14:10 |
Sent To |
|
|
| Notes |
| 2008-07-10 14:13:21 | TO "COMM" BD#26/PLANS ON RACK/4 ROLLS, 1 LARGE BOX | | | W/BINDERS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-06-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-03 |
Time |
15:03 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-03 |
Time |
15:03 |
Sent To |
|
|
| Notes |
| 2008-06-03 15:05:39 | TO "COMM" BD#1/ PLANS ON RACK/ 6 ROLLS/ 1 BOX OF | | | BINDERS AND 1 BINDER ON THE SIDE |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-14 |
Time |
08:43 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-14 |
Time |
08:43 |
Sent To |
|
|
| Notes |
| 2008-05-14 08:44:07 | ROUTED TO "COMM" BD#21 W/RESUB ALREADY IN REVIEW. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-04-18 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-04-18 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-04-18 |
Time |
10:13 |
Sent To |
|
|
| Notes |
| 2008-04-18 10:17:10 | TO "COMM" BD#21--PLANS ON RACK/5 ROLLS |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2008-03-24 |
Time |
|
Rev Time |
0.00 |
| Received By |
spalmer |
Date |
2008-01-11 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2008-01-11 10:45:37 | TO COMM BOARD # 27 |
|
|
| Review Stop |
L |
LANDSCAPING |
| Rev No |
1 |
Status |
F |
Date |
2008-12-24 |
|
|
Cont ID |
|
| Sent By |
rkussner |
Date |
2008-12-24 |
Time |
11:06 |
Rev Time |
0.00 |
| Received By |
rkussner |
Date |
2008-12-24 |
Time |
11:06 |
Sent To |
PC |
|
| Notes |
| 2008-12-24 11:16:28 | ***LANDSCAPE REVIEW FAILED*** | | | | | | 1. ALTHOUGH THE REMOVAL OF THE GREEN BUTTONWOOD TREES | | | PLANTED WITHIN THE RIGHT-OF-WAY ADJACENT TO LAKEVIEW | | | WAS NOT PERMITTED THROUGH THE CITY, THE APPLICANT SHALL | | | PROVIDE DOCUMENTATION TO THE CITY REGARDING THE STATUS | | | OF THOSE TREES. IF THEY NEED TO BE REPLACED, THEN THE | | | PLANS SHOULD REFLECT THEIR LOCATIONS. | | | | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT EITHER ROBERT | | | KUSSNER @ (561) 822-1462 OR MATTHEW FLIS @ (561) | | | 822-1445. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
20 |
Status |
P |
Date |
2009-02-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-15 |
Time |
08:41 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-15 |
Time |
08:40 |
Sent To |
|
|
| Notes |
| 2009-02-15 08:41:31 | PAGE M101B REVISION 10 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
19 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-12 |
Time |
18:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-12 |
Time |
18:55 |
Sent To |
PC |
|
| Notes |
| 2009-02-12 18:56:30 | PAGE M002, M101A, M102A REVISION 9 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
18 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-02-12 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-02-12 |
Time |
18:54 |
Sent To |
PC |
|
| Notes |
| 2009-02-12 18:55:14 | PAGE M101A REVISION 8 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
17 |
Status |
P |
Date |
2009-01-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2009-01-22 |
Time |
19:59 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2009-01-22 |
Time |
19:58 |
Sent To |
|
|
| Notes |
| 2009-01-22 19:59:00 | REVUSED M101A THROUGH M104A AND FOOD SERVICE |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
16 |
Status |
P |
Date |
2008-12-20 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-12-20 |
Time |
15:23 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-12-20 |
Time |
15:22 |
Sent To |
PC |
|
| Notes |
| 2008-12-20 15:23:49 | PAGES M-101A, M-101B, M-102A, M-102B, M-103B REVISION | | | #7 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
15 |
Status |
P |
Date |
2008-11-08 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-11-08 |
Time |
12:08 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-11-08 |
Time |
12:05 |
Sent To |
|
|
| Notes |
| 2008-11-08 12:08:06 | REVISED M-002, M-101A, M-101B, M-102A, M-102B, M-103A, | | | M-103B, M-104A, M-104B, M-105A, M-105B, M-402, M-408 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
14 |
Status |
F |
Date |
2008-09-15 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-15 |
Time |
08:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-12 |
Time |
11:12 |
Sent To |
|
|
| Notes |
| 2008-09-15 08:17:47 | REVIEW #: REVISION 5 | | | ACTION:DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. PAGE M-101B: THIS PLAN SHOWS SEVERAL CHANGES TO THE | | | GENERATOR ROOM EXHAUST SYSTEM. HOWEVER, THESE CHANGES | | | ARE NOT IDENTIFIED ON THE PLANS AS A PERT OF THIS | | | REVISION. CLEARLY MARK AND INDENTIFY ON PLANS ALL | | | CHANGES FROM THE CURRENT PERMIT DOCUMENTS TO FACILITATE | | | AN ACCURATE REVIEW OF THE AMENDED CONSTRUCTION | | | DOCUMENTS IN ACCORDANCE WITH FBCB 106.4. ALSO, PLEASE | | | MAINTAIN THE REVISION HISTORY AT THE TITLE BLOCKS ON | | | THE PLANS TO AID IN TRACKING AND RECORDS RETENTION. | | | REVISION #4, WHICH HAS BEEN INCORPORATED INTO THE | | | PERMIT SET OF PLANS, NO LONGER APPEARS IN THE REVISION | | | HISTORY. | | | | | | NOTE: THIS IS ONE EXAMPLE OF ONE CHANGE WHICH HAS NOT | | | BEEN IDENTIFIED. PLEASE CHECK THE ENTIRE REVISION SET | | | AND ENSURE ALL REVISIONS ARE CLEARLY INDICATED ON PLANS | | | PRIOR TO RESUBMISSION. | | | | | | 2. PAGE M-101B: THERE IS AN UNNECESSARY LAYER SHOWING | | | KITCHEN EQUIPMENT IN THE GARAGE AND TRASH COMPACTOR | | | AREA. PLEASE REMOVE ERRONEOUS LAYERS AND PROVIDE PLANS | | | WHICH ARE OF SUFFICIENT CLARITY TO INDICATE THE | | | LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED IN | | | ACCORDANCE WITH FBCB 106.1.1. | | | | | | 3. PAGE M-101B: GENERATOR ROOM NOTE INDICATES THAT THE | | | DUCT FROM EF-7 IS TO ATTACH TO THE GENERATOR WITH | | | FLEXIBLE DUCT CONNECTIONS. IT IS UNCLEAR AS TO WHY THE | | | DUCT WOULD CONNECT TO THE GENERATOR ITSELF. PROVIDE | | | ADDITIONAL DETAIL WHICH CLARIFIES THE INTENT OF THIS | | | DESIGN AND DEMONSTRATES COMPLIANCE WITH FBCM 915.2 AND | | | FBCM 304.1. | | | | | | 4. PAGE M-101B: THE CHANGES TO THE GENERATOR ROOM | | | VENTILATION AND GENERATOR EXHAUST SYSTEMS WILL HAVE AN | | | IMPACT ON THE DESIGN AS SHOWN ON SEVERAL OTHER PAGES OF | | | THE PLANS. HOWEVER, THESE OTHER PAGES ARE NOT A PART OF | | | THIS REVISION. PLEASE COORDINATE CHANGES ON THIS PAGE | | | WITH ALL OTHER PAGES WHICH MAY ME AFFECTED BY THEM. | | | SUBMIT ALL PAGES WHICH ARE PART OF THIS CHANGE WITHIN | | | THE SAME REVISION TO FACILITATE AN ACCURATE REVIEW AND | | | DEMONSTRATE COMPLIANCE WITH THE PROVISIONS OF FBCM | | | 915.2, FBCM 401.5, 401.6 AND FBCM CHAPTER 5. | | | | | | 5. PAGES M-103B THROUGH M-104B AND M-408: FLOOR PLANS | | | HAVE BEEN CHANGED TO SHOW 6 INCH ROUND EXHAUST DUCTS | | | GOING TO EXHAUST RISERS. HOWEVER, RISER DIAGRAMS ARE | | | STILL SHOWING 4 INCH ROUND DUCTS IN SEVERAL LOCATIONS. | | | PLEASE CLARIFY BY COORDINATING DUCT SIZES ON FLOOR | | | PLANS WITH DETAILS AND RISER DIAGRAMS IN ACCORDANCE | | | WITH FBCM 603.1 AND FBCB 106.1.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
13 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-02 |
Time |
09:38 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
09:37 |
Sent To |
PC |
|
| Notes |
| 2008-09-02 09:38:08 | SUBMITTAL # 230529-3: CONCRETE DECK ANCHORS FOR EXHAUST | | | FANS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
12 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-02 |
Time |
09:30 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
09:29 |
Sent To |
PC |
|
| Notes |
| 2008-09-02 09:30:36 | SUBMITTAL #233300-2: SMOKE DAMPER, ACTUATOR |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
11 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-02 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
09:12 |
Sent To |
PC |
|
| Notes |
| 2008-09-02 09:12:38 | SUBMITTAL #233713-3 REV 1: LINEAR DIFFUSERS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
10 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-02 |
Time |
09:02 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
08:47 |
Sent To |
PC |
|
| Notes |
| 2008-09-02 09:02:52 | SUBMITTAL #233713-2: CO SENSORS,VFD, HVAC CONTROLS, | | | DAMPER MOTORS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
9 |
Status |
P |
Date |
2008-09-02 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-09-02 |
Time |
08:34 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-09-02 |
Time |
08:33 |
Sent To |
PC |
|
| Notes |
| 2008-09-02 08:34:14 | SUBMITTAL #233713-1 DIFFUSERS, REGISTERS, GRILLS, FANS, | | | LOUVERS, DAMPERS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
8 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-29 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-29 |
Time |
16:53 |
Sent To |
|
|
| Notes |
| 2008-08-29 16:53:56 | SUBMITTAL #237433-4 ADDISON SPLIT SYSTEM |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
7 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-29 |
Time |
16:19 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-29 |
Time |
16:17 |
Sent To |
|
|
| Notes |
| 2008-08-29 16:18:38 | SUBMITTAL #237433-3 AAON OARTU'S |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
6 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-29 |
Time |
16:02 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-29 |
Time |
15:40 |
Sent To |
|
|
| Notes |
| 2008-08-29 16:02:31 | SUBMITTAL #237433-1 TRANE SPLIT A/C SYSTEMS |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
5 |
Status |
P |
Date |
2008-08-29 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-29 |
Time |
15:35 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-29 |
Time |
15:16 |
Sent To |
|
|
| Notes |
| 2008-08-29 15:35:16 | SUBMITTAL #236200-02 AMANA DIGISMART PTAC |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
4 |
Status |
P |
Date |
2008-08-28 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-08-28 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-08-28 |
Time |
09:45 |
Sent To |
PC |
|
| Notes |
| 2008-08-28 14:55:59 | REVISED PAGES M-101B, M-103A, M-103B, M-104A, M-104B, | | | M-408 REVISION #4 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-27 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-06-27 |
Time |
09:43 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-06-25 |
Time |
16:51 |
Sent To |
|
|
| Notes |
| 2008-06-27 08:36:42 | ************PROVISOS************* | | | | | | 1. COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS | | | SHALL BE DEMONSTRATED PRIOR TO INSTALLATION AND | | | INSPECTION OF OUTDOOR APPLIANCES AND EQUIPMENT EXPOSED | | | TO WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. ANY | | | ALTERNATE MATERIALS AND METHODS PROPOSALS SHALL BE | | | SUBMITTED TO THE BUILDING OFFICIAL IN WRITING. | | | | | | 2. A STAIR PRESSURIZATION TEST SHALL BE PERFORMED PRIOR | | | TO FINAL INSPECTION TO VERIFY STAIRWAY DOOR OPENING | | | FORCES ARE WITHIN ALLOWED RANGE IN COMPLIANCE WITH FBCB | | | 11-4.13.11. | | | | | | 3. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL | | | PROVIDE AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF 1,500 | | | TO 2,500 FEET PER MINUTE. KEF-1 ON SCHEDULE (M-002) IS | | | TOO SMALL TO PROVIDE REQUIRED EXHAUST VOLUME AND IS | | | SMALLER THAN SUPPLY FAN. DEMONSTRATE COMPLIANCE WITH | | | FBCM 506.3.4 AND FBCB 13-409.1.ABC.3.6.1. REVISE PLANS | | | PRIOR TO ROUGH INSPECTION. | | | | | | 4. ROOF KEF DETAIL (M-404) SHOWS CLEARANCE UNDER FAN AT | | | 14 INCHES. CLEARANCE UNDER FAN TO ROOF SHALL BE IN | | | ACCORDANCE WITH FBCB TABLE 1509.7. REVISE PLANS PRIOR | | | TO ROUGH INSPECTION. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-07 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-05-07 |
Time |
16:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-05-06 |
Time |
11:35 |
Sent To |
|
|
| Notes |
| 2008-05-07 16:11:08 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | ONE SET OF PLANS HAS BEEN MARKED-UP DURING REVIEW TO | | | ASSIST WITH CLARITY OF COMMENTS. | | | | | | 1 THROUGH 3: OK | | | | | | 4 THROUGH 9: THESE COMMENT RESPONSES ARE NOT ABLE TO BE | | | REVIEWED AT THIS TIME. THEY ALL INVOLVE CORRECTIONS TO | | | THE ENERGY CALCULATIONS, WHICH WERE NOT INCLUDED WITH | | | THIS RESUBMITTAL. PLEASE PROVIDE CORRECTED ENERGY | | | CALCULATIONS FOR REVIEW PRIOR TO PERMIT ISSUANCE IN | | | ACCORDANCE WITH FBCB 13-103.3. | | | | | | 10. OK | | | | | | 11. PG M-101A: | | | A) FIRE-RESISTANCE RATED WALLS HAVE BEEN ADDED TO | | | CORRIDOR AND LOBBY AREA AS SHOWN ON PG A-101A, A-401 | | | AND A-402. BASED ON THESE LOCATIONS, THERE ARE AT LEAST | | | FOUR DUCT PENETRATIONS OF RATED WALLS AT OFFICE 124 AND | | | OFFICE 126 WHICH ARE NOT PROTECTED. SHOW HOW THESE | | | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH | | | FBCM 607.5. COORDINATE ANY AND ALL CHANGES IN WALL | | | TYPES BETWEEN ARCHITECTURAL, LIFE SAFETY AND MECHANICAL | | | PLANS. | | | NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA | | | WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE | | | DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE | | | DESIGN INTENT. | | | B) THE 18X20 GREASE EXHAUST DUCT FROM KITCHEN 115 IS | | | NOW SHOWN PENETRATING TWO RATED WALL ASSEMBLIES. A | | | GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A | | | FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE | | | ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET | | | TERMINAL IN ACCORDANCE WITH FBCM 506.3.10. SHOW HOW | | | THIS DUCT IS TO BE ENCLOSED IN ACCORDANCE WITH THIS | | | SECTION OR EXCEPTION #1. | | | C) DISHWASHER EXHAUST DUCT IS SHOWN PENETRATING | | | CORRIDOR WALL WITH FIRE/SMOKE DAMPER AT WALL | | | PENETRATION. THIS DUCT WILL BE CONVEYING HOT, | | | MOISTURE-LADEN AIR TO THE OUTDOORS. IS THE FIRE/SMOKE | | | DAMPER AND DUCT USED AT THIS LOCATION DESIGNED FOR | | | THESE CONDITIONS? DUCTS CONVEYING MOISTURE-LADEN OR | | | WASTE-HEAT-LADEN AIR SHALL BE CONSTRUCTED, JOINED AND | | | SEALED IN AN APPROVED MANNER IN ACCORDANCE WITH FBCM | | | 506.4.2. PLEASE PROVIDE ADDITIONAL DETAILS FOR THIS | | | APPLICATION. | | | | | | 12 THROUGH 19: OK | | | | | | 20. PG M-102A: NOTES HAVE BEEN CORRECTED AND MADE | | | LEGIBLE. HOWEVER, TWO OF THE CO SENSORS IN THIS AREA | | | ARE BEING DESIGNATED BY MECHANICAL NOTE #2 RATHER THAN | | | NOTE #7. PLEASE CORRECT FBCM 404, FBCB 106.1.1. | | | | | | 21 THROUGH 23: OK | | | | | | 24.M-102A: OK EXCEPT: STAIR PRESSURIZATION TEST WILL | | | BE REQUIRED FOR BOTH PRESSURIZED STAIRS TO VERIFY | | | COMPLIANCE WITH MAXIMUM DOOR OPENING FORCES ALLOWED PER | | | FBCB 11-4.13.11. THIS WILL BE A PROVISO ON IN EFFECT | | | UNTIL FINAL MECHANICAL INSPECTION HAS PASSED. ALSO, PG | | | M-404 STILL SHOWS STAIR PRESSURIZATION FANS CONNECTED | | | TO A BUILDING SMOKE CONTROL SYSTEM WHICH DOES NOT | | | EXIST. PLEASE CORRECT. IN ADDITION, BOTH SF-2 AND SF-3 | | | WILL REQUIRE DUCT SMOKE DETECTORS FOR FAN SHUT-DOWN IN | | | ACCORDANCE WITH FBCM 606.2. | | | | | | 25 THROUGH 28: OK | | | | | | 29. PG M-103A: THE DESIGN INTENT IN THIS AREA REMAINS | | | UNCLEAR. WHILE ARCHITECTURAL PLANS NOW SHOW THESE DUCTS | | | IN A RATED ENCLOSURE, THIS PAGE ALSO SHOWS TWO | | | FIRE/SMOKE DAMPERS AT THE FLOOR PENETRATION WHILE PG | | | M-102A SHOWS TWO FIRE DAMPERS AT THE FLOOR PENETRATION. | | | | | | NOTE: WHILE THE DESIGN IS PERMITTED TO EXCEED MINIMUM | | | CODE REQUIREMENTS, A SHAFT ENCLOSURE IS NOT REQUIRED AT | | | THIS LOCATION IN ACCORDANCE WITH FBCM 607.6.1. | | | PROVIDING THE TWO FIRE DAMPERS SHOWN ON M-102A AND TWO | | | FIRE DAMPERS AT THE WALL PENETRATIONS BETWEEN ROOMS 231 | | | AND 235 WOULD ELIMINATE THE NEED FOR A SHAFT ENCLOSURE | | | AND THE 6 COMBINATION FIRE/SMOKE DAMPERS SHOWN ON | | | M-103A. THIS, OF COURSE, DEPENDS ON THE DESIGN INTENT. | | | | | | 30. PG M-103A: IN EXITWAY 230, PROVIDE A | | | THROUGH-PENETRATION FIRESTOP SYSTEM DETAIL FOR THE 6 | | | INCH ROUND EXHAUST DUCT PENETRATING THE RATED WALL INTO | | | EXITWAY 230 WITH NO FIRE DAMPER IN ACCORDANCE WITH FBCM | | | 607.1.1. | | | NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA | | | WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE | | | DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE | | | DESIGN INTENT. | | | | | | 31 THROUGH 38: OK | | | | | | 39. M-105A AND M-105B: PLEASE SEE COMMENT #24 ABOVE. | | | ALSO, WIND RESISTANCE CRITERIA FOR OUTDOOR APPLIANCES | | | WILL BE COVERED BY PROVISO ONCE ALL OTHER OUTSTANDING | | | COMMENTS ARE ADDRESSED AND PRIOR TO PERMIT ISSUANCE. | | | | | | 40. OK | | | | | | 41. PG M-404: PLEASE SHOW HEIGHT OF EXHAUST DISCHARGE | | | ABOVE ROOF TO BE MINIMUM 40 INCHES IN ACCORDANCE WITH | | | FBCM 506.3.12.1. ALSO, PLEASE SEE PG M-105A REGARDING | | | THE LOCATION OF KEF-1. EXHAUST OUTLETS SHALL BE LOCATED | | | NOT LESS THAN 10 FEET HORIZONTALLY FROM PARTS OF THE | | | SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY LINES | | | AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE | | | WITH FBCM 506.3.12.3. THE MINIMUM HORIZONTAL DISTANCE | | | BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE | | | BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH | | | STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN | | | DISCHARGE OPENING IN ACCORDANCE WITH FBCM 506.5.5. | | | | | | 42. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-11 |
Time |
14:01 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-01-23 |
Time |
18:05 |
Sent To |
|
|
| Notes |
| 2008-02-11 14:01:12 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. M-001: HVAC GENERAL NOTE #11, DAMPERS WITH MOVING | | | PARTS AND SOME DUCT MATERIALS MAY NOT BE PAINTED AS IT | | | CAN VIOLATE THEIR LISTING AND IMPACT THEIR PERFORMANCE. | | | EXAMPLES: FIRE DAMPERS, SMOKE DAMPERS AND FIBERGLASS | | | DUCT BOARD SHALL NOT BE PAINTED. | | | | | | 2. M-001: GARAGE VENTILATION RATE CALCULATION, THERE IS | | | NO VENTILATION RATE SHOWN FOR THE GARAGE DURING THE | | | MODE WHERE THE FANS ARE NOT BEING OPERATED BY THE CO | | | SENSORS. PROVIDE CALCULATIONS FOR THE REQUIRED | | | VENTILATION RATE DURING THIS MODE IN ACCORDANCE WITH | | | FBC, M 404.2. SEE COMMENT #3 BELOW. | | | | | | 3. M-002: FAN SCHEDULE, NOTE #7 CALLS FOR FANS TO BE | | | CONTROLLED BY CO SENSOR. THIS NOTE IS NOT ATTRIBUTED TO | | | ANY FANS ON THE SCHEDULE (IT?S LIKELY THAT EF-1 AND | | | EF-2 A/B ARE INTENDED, BUT THIS IS NOT SHOWN ON | | | SCHEDULE). NOTE: IF THESE FANS ARE TO BE CONTROLLED BY | | | CO SENSORS, THERE WOULD BE NO VENTILATION IN THE GARAGE | | | WHEN THE CO LEVELS ARE UNDER 25 PPM. A MINIMUM | | | CONTINUOUS VENTILATION RATE OF 0.05 CFM/S.F. IS | | | REQUIRED IN ACCORDANCE WITH FBC, M 404.2. PLEASE | | | CLARIFY THE DESIGN INTENT AND SHOW COMPLIANCE WITH ALL | | | PROVISIONS OF FBC, M SECTION 404. | | | | | | 4. M-002: PACKAGED MAKE-UP AIR UNIT SCHEDULE, OAU-1 | | | CALLS FOR 29.5 MIN. TONS. HOWEVER, ACCORDING TO THE | | | MANUFACTURER (WWW.AONNET.COM/RM.ASPX) THE MAXIMUM | | | CAPACITY OF THE MODEL SHOWN ON THE SCHEDULE IS 26 TONS, | | | WELL UNDER THE MINIMUM AS STATED ON THE SCHEDULE. ALSO, | | | THE VALUES ON THE SCHEDULE DO NOT CORRESPOND WITH THE | | | VALUES LISTED ON THE SYSTEM SIZING SUMMARY PROVIDED IN | | | THE SPEC BOOK. IN ADDITION, NOTE #9 IN THE SCHEDULE | | | CALLS FOR A MINIMUM EER RATING OF 11 WHILE THE | | | MANUFACTURER SHOWS THIS UNIT?S EER RATING TO BE 9.5. | | | THIS INFORMATION IS ALSO MISREPRESENTED IN THE ENERGY | | | CALCULATIONS AS THE INPUT DATA REPORT SHOWS AN | | | EFFICIENCY RATING OF 13.0 FOR OAU-1. PLEASE COORDINATE | | | THE SCHEDULE, SYSTEM SIZING SUMMARY AND ENERGY | | | CALCULATIONS TO PROVIDE ACCURATE INFORMATION AND | | | DEMONSTRATE COMPLIANCE WITH FBC, M 304.1; FBC 13-103.2 | | | AND FBC 13-407.1.ABC.1. | | | | | | 5. M-002: PACKAGED MAKE-UP AIR UNIT SCHEDULE, OAU-2 | | | VALUES ON THE SCHEDULE DO NOT CORRESPOND WITH THE | | | VALUES LISTED ON THE SYSTEM SIZING SUMMARY PROVIDED IN | | | THE SPEC BOOK. ALSO, ACCORDING TO THE MANUFACTURER | | | (WWW.AONNET.COM/RN.ASPX) THE EER RATING FOR THE MODEL | | | LISTED ON THE SCHEDULE IS 11.7. THIS INFORMATION IS | | | MISREPRESENTED IN THE ENERGY CALCULATIONS AS THE INPUT | | | DATA REPORT SHOWS AN EFFICIENCY RATING OF 13.0 FOR | | | OAU-2. PLEASE COORDINATE THE SCHEDULE, SYSTEM SIZING | | | SUMMARY AND ENERGY CALCULATIONS TO PROVIDE ACCURATE | | | INFORMATION AND DEMONSTRATE COMPLIANCE WITH FBC | | | 13-103.2 AND FBC 13-407.1.ABC.1. | | | | | | 6. M-002: DX SPLIT SYSTEM SCHEDULE, THE EFFICIENCIES | | | LISTED IN THE SCHEDULE COULD NOT BE VERIFIED | | | (WWW.ARIDIRECTORY.ORG) BASED ON THE MODEL NUMBERS | | | PROVIDED. EQUIPMENT EFFICIENCY VERIFICATION IS REQUIRED | | | IN ACCORDANCE WITH FBC 13-407.1.ABC.3.1.1. PROVIDE | | | MODEL NUMBERS OR ARI REFERENCE NUMBERS WHICH CAN BE | | | USED FOR EFFICIENCY VERIFICATION TO SHOW COMPLIANCE | | | WITH THIS SECTION. | | | | | | 7. M-002: DX SPLIT SYSTEM SCHEDULE CALLS FOR ALL | | | EQUIPMENT TO HAVE MIN. 13 SEER. HOWEVER, UNITS LARGER | | | THAN 65,000 BTU/H ARE NOT RATED BY SEER, SUCH AS CU-1 | | | AND CU-6. PROVIDE ACTUAL AND CORRECT RATINGS FOR ALL | | | EQUIPMENT TO DEMONSTRATE COMPLIANCE WITH MINIMUM | | | EFFICIENCIES REQUIRED BY FBC TABLE 13-407.1.ABC.3.2A | | | | | | | | | 8. M-002: DX SPLIT SYSTEM SCHEDULE, AHU-4 /CU-4 IS NOT | | | LISTED IN THE INPUT DATA REPORT PORTION OF THE ENERGY | | | CALCULATIONS. ALL PERTINENT DATA AND FEATURES OF THE | | | BUILDING AND THE EQUIPMENT/SYSTEMS SHALL BE INCLUDED IN | | | THE ENERGY CALCULATIONS IN ACCORDANCE WITH FBC | | | 13-103.2. | | | | | | 9. M-002: PTAC UNITS COULD NOT BE LOCATED IN ANY | | | EQUIPMENT SCHEDULES ON THIS PAGE. PROVIDE ALL RELEVANT | | | INFORMATION AS REQUIRED TO VERIFY SYSTEM SIZING AND | | | REQUIRED EFFICIENCIES AS COVERED UNDER PREVIOUS REVIEW | | | COMMENTS. | | | | | | 10. M-101A: EF-5 AND EF-11 ARE LOCATED ABOVE A GYPSUM | | | BOARD CEILING IN CORRIDOR 148. CLEARANCES AROUND | | | APPLIANCES TO ELEMENTS OF PERMANENT CONSTRUCTION SHALL | | | BE SUFFICIENT TO ALLOW INSPECTIONS, SERVICE, REPAIR OR | | | REPLACEMENT WITHOUT REMOVING SUCH ELEMENTS OF PERMANENT | | | CONSTRUCTION OR DISABLING THE FUNCTION OF A REQUIRED | | | FIRE RESISTANCE-RATED ASSEMBLY. SHOW HOW THESE FANS | | | WILL BE ACCESSIBLE FOR SERVICE AND REPLACEMENT IN | | | ACCORDANCE WITH FBC, M 306.1. | | | | | | 11. M-101A: CORRIDOR 148 IS LIKELY TO REQUIRE A FIRE | | | RESISTANCE RATING IN ACCORDANCE WITH FBC TABLE 1016.1 | | | (SEE BUILDING PLAN REVIEW COMMENTS FOR ALL REQUIREMENTS | | | RELATED TO FIRE RESISTANCE RATED ASSEMBLIES). IF THIS | | | IS THE CASE, THERE ARE SEVERAL DUCT PENETRATIONS WHICH | | | WOULD REQUIRE OPENING PROTECTIVES SUCH AS FIRE AND | | | POSSIBLY SMOKE DAMPERS IN ACCORDANCE WITH FBC, M | | | 607.5.3 AND 607.5.4. ANY SMOKE DAMPERS REQUIRED SHALL | | | BE ACTUATED IN ACCORDANCE WITH FBC, M 607.5.4.1. | | | COORDINATION WITH ARCHITECTURAL PLANS PRIOR TO | | | RESUBMITTAL IS CRITICAL TO THESE COMMENTS BEING | | | ADEQUATELY ADDRESSED. | | | | | | 12. M-101A: KITCHEN AREA 115 | | | A) THIS AREA SHOWS A RETURN AIR DROP ADJACENT TO THE | | | COMMERCIAL KITCHEN GREASE EXHAUST HOOD. THIS CONDITION | | | IS PROHIBITED PER FBC, M 407.1 AS THIS IS A | | | NON-DEDICATED KITCHEN HVAC SYSTEM. AHU #6 SERVES AREAS | | | OUTSIDE OF THE KITCHEN SUCH AS RESTROOMS AND CORRIDORS. | | | CONCENTRATED SOURCES OF CONTAMINANTS OR POLLUTANTS | | | SHALL BE CONTROLLED AT THE SOURCE BY CONTAINMENT, LOCAL | | | EXHAUST SYSTEMS, OR BOTH. RECIRCULATION OF AIR FROM THE | | | KITCHEN TO OTHER SPACES OF THE BUILDING WOULD HAVE A | | | NEGATIVE IMPACT ON INDOOR AIR QUALITY IN ACCORDANCE | | | WITH FBC, M 407.1 AND FBC 13-409.1.ABC.1. | | | B) THIS LOCATION IS LIKELY TO ADVERSELY EFFECT THE | | | COOLING LOADS FOR AHU #6. ARE THESE ADDITIONAL LOADS | | | ACCOUNTED FOR IN THE COOLING LOAD CALCULATIONS FOR THE | | | RETURN TO BE IN THIS LOCATION? FBC 13-407.1.ABC.1. C) | | | THE RETURN AT THIS LOCATION HAS THE POTENTIAL TO DRAW | | | GREASE LADEN VAPORS FROM THE COOKING AREA SERVED BY THE | | | GREASE EXHAUST HOOD SYSTEM. THE FAN FOR AHU #6 IS | | | ACTUALLY DESIGNED TO DRAW MORE AIR THAN THE EXHAUST FAN | | | SERVING THE HOOD SYSTEM AND WOULD BE COMPETING WITH | | | KEF-1 FOR AIR. ACCUMULATION OF GREASE IN A DUCT WHICH | | | IS NOT DESIGNED IN ACCORDANCE WITH FBC, M 506.3 WOULD | | | CREATE A SERIOUS FIRE HAZARD. | | | | | | 13. M-101A: AIR QUANTITIES SHOWN ON FLOOR PLAN FOR SOME | | | SYSTEMS DO NOT MATCH THE VALUES SHOWN ON THE AIR | | | BALANCE SCHEDULE ON M-002. THE FOLLOWING IS AN | | | EXAMPLE: | | | AHU-1 ON THE SCHEDULE CALLS FOR 6010 CFM OF RETURN AIR. | | | FLOOR PLAN FOR AHU-1 SHOWS 5230 CFM OF RETURN. CHECK | | | ALL VALUES AND COORDINATE WITH FLOOR PLANS TO ASSURE | | | AIR BALANCE WILL BE AS INDICATED ON SCHEDULE AS | | | REQUIRED BY FBC 13-409.1.ABC.1.2. | | | | | | 14. M-101A: EXHAUST OUTLET FOR TOILET ROOMS 137 AND 138 | | | IS SHOWN DISCHARGING ONTO A WALKWAY ON THE WEST SIDE OF | | | THE BUILDING. EXHAUST AIR SHALL NOT BE DISCHARGED ONTO | | | WALKWAYS IN ACCORDANCE WITH FBC, M 401.5.2. A SIMILAR | | | CONDITION MAY EXIST WITH THE POOL HEATER VENTS. CONSULT | | | MANUFACTURER?S INSTALLATION INSTRUCTIONS. | | | | | | 15. M-101A: THE 24X24 WALL LOUVER AT SPRINKLER RISER | | | ROOM 144 IS PENETRATING A 2-HOUR RATED WALL AS | | | INDICATED ON PG A-101A AND A-601. SHOW HOW THIS OPENING | | | SHALL BE PROTECTED IN ACCORDANCE WITH FBC, M 607.5 | | | | | | 16. M-101A: THE 10X6 DUCT PENETRATING THE WALL BETWEEN | | | CORR. 148 AND CORR. 149 IS REQUIRED TO BE PROTECTED | | | WITH A SMOKE DAMPER IN ADDITION TO THE FIRE DAMPER | | | ALREADY SHOWN ON PLANS IN ACCORDANCE WITH FBC, M | | | 607.5.4. | | | NOTE: THIS CONDITION MAY BE AFFECTED BY CHANGES RELATED | | | TO COMMENT #11 ABOVE. | | | | | | 17. M-101A: MECHANICAL NOTE #3 IS FOR 10X8 EXHAUST DUCT | | | TO DISHWASHER HOOD. WHAT IS THE RELATIONSHIP TO THE | | | CARBON MONOXIDE SENSORS IN THE PARKING GARAGE?PLEASE | | | CLARIFY AS THIS SAME NOT IS ATTACHED TO THE DETECTORS. | | | | | | 18. M-101B: THE 4X6 OA DUCTS PENETRATING THE FLOOR | | | CEILING ASSEMBLY ABOVE THE FIRST FLOOR DOES NOT SHOW | | | ANY OPENING PROTECTIVE. WHILE IT DOES SHOW OPENING | | | PROTECTIVES AT THE PENETRATIONS OF THE WALL MEMBRANES | | | BETWEEN ROOMS 105/106 AND BETWEEN ROOMS 107/108. THE OA | | | DUCT PENETRATION FOR ROOM 105 (THE OTHER 105, ROOMS | | | APPEAR TO BE MISLABELED ON PG A-101B) IS NOT CLEAR | | | WHETHER IT IS INSIDE OR OUTSIDE THE RATED EXHAUST | | | CHASE. IF IT IS INSIDE THE EXHAUST CHASE, IT SHALL BE | | | PROTECTED WITH FIRE AND SMOKE DAMPER IN ACCORDANCE WITH | | | FBC, M 607.5.5.1. THE DESIGN AND INTENT IN THESE AREAS, | | | ALONG WITH THE CORRESPONDING AREAS ON PAGES M-120B AND | | | M-103B ARE UNCLEAR. PLEASE PROVIDE CLARIFICATION OF THE | | | DESIGN IN THESE AREAS RELATED TO OA DUCTS AND | | | PENETRATIONS FOR THOROUGH REVIEW. | | | | | | 19. M-101B: PROVIDE MANUFACTURER?S SUBMITTAL WITH | | | INSTALLATION INSTRUCTIONS FOR CARBON MONOXIDE SENSORS | | | FOR REVIEW. INSTALLATION INSTRUCTIONS ARE REQUIRED TO | | | DETERMINE COVERAGE AREA, MAXIMUM SPACING AND | | | INSTALLATION HEIGHT OF THE DETECTORS. ALSO, SOME | | | MANUFACTURERS REQUIRE CIRCULATION FANS TO ENSURE PROPER | | | SAMPLING OF THE AIR IN THE SPACES BEING MONITORED. | | | | | | 20. M-102A: MECHANICAL NOTES APPEAR TO HAVE BEEN | | | CUT-OFF AND INCOMPLETE. REVIEW OF THIS PAGE WILL BE | | | BASED ON THE INFORMATION PROVIDED. PROVIDE MISSING | | | INFORMATION WITH COMPLETE NOTES AND RESUBMIT. FBC | | | 106.1.1. | | | | | | 21. M-102A: SEVERAL DUCTS ARE SHOWN PENETRATING A RATED | | | WALL (TYPE 1B) AT ELECTRICAL ROOM M008. SHOW HOW THESE | | | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH | | | FBC, M 607.5. COORDINATE THE LOCATION OF RATED | | | ASSEMBLIES AND PENETRATIONS WITH ARCHITECTURAL PLANS. | | | | | | 22. M-102A: 10X8 AND 10X10 EXHAUST DUCTS FROM EF-5 AND | | | EF-11 ARE SHOWN PENETRATING A 1-HOUR RATED WALL (TYPE | | | 1C) BEFORE REACHING 24X12 LOUVER. SHOW HOW THESE | | | PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH | | | FBC, M 607.5. | | | | | | 23. M-102A: NOTE #5 REFERS TO AHU-6 BUT ON FLOOR PLAN | | | IT DOES NOT RELATE TO AHU-6. IS THIS REFERENCE INTENDED | | | FOR AHU-4? PLEASE CLARIFY. | | | | | | 24. M-102A: NW STAIR VENTILATION DUCT RISER, IS THIS | | | DUCT FOR THE PURPOSE OF STAIR PRESSURIZATION AS | | | INDICATED ON PG M-404? THE STAIR RISER DIAGRAM ON | | | M-102A DOES NOT SHOW ANY TYPE OF RELIEF OPENING, SUCH | | | AS A BAROMETRIC RELIEF DAMPER, TO ASSURE THAT STAIRS | | | ARE PRESSURIZED WITHIN THE STATED RANGE OF 0.05 INCHES | | | WC TO 0.25 INCHES WC. EXCESSIVE PRESSURE IN STAIR COULD | | | ALSO NEGATIVELY IMPACT THE MAXIMUM DOOR OPENING FORCE | | | AS ALLOWED UNDER FBC 11-4.13.11.IN ADDITION, PG M-404 | | | INDICATES THESE FANS ARE TO BE OPERATED BY A SMOKE | | | CONTROL SYSTEM PANEL. THERE IS NO INDICATION ANYWHERE | | | ELSE IN PLANS OF THE EXISTENCE OF A SMOKE CONTROL | | | PANEL. PLEASE CLARIFY. THIS COMMENT APPLIES TO ALL | | | STAIRWAYS. | | | | | | 25. M-102A AND M-102B: GARAGE EXHAUST FOR EF 2A AND EF | | | 2B, WHAT IS THE SOURCE OF MAKE-UP AIR FOR THESE FANS? | | | THERE ARE NO OPENINGS TO THE OUTSIDE SHOWN ON THIS | | | PLAN. SHOW MEANS OF MAKE-UP AIR FOR EXHAUST TO PROVIDE | | | THE VENTILATION RATES AS REQUIRED BY FBC, M 403.1 AND | | | FBC, M 404.2. | | | | | | 26. M-102B: GENERATOR VENTILATION RISER SHOWS GENERATOR | | | ROOM EXHAUST DUCT PENETRATING FLOOR/CEILING ASSEMBLY | | | BETWEEN FIRST FLOOR AND MEZZANINE/GARAGE LEVEL. LIFE | | | SAFETY PLAN G-007 SHOWS THIS ROOM TO BE A 2-HOUR | | | FIRE-RATED ENCLOSURE. THERE IS NO INDICATION ON PLANS | | | AS TO HOW THE REQUIRED FIRE-RESISTANCE RATED SEPARATION | | | WILL BE MAINTAINED IN THIS LOCATION. SHOW HOW THIS | | | SEPARATION IS TO BE MAINTAINED IN ACCORDANCE WITH FBC, | | | M 607.5. | | | | | | 27. M-103A: OAU-1 RISER DIAGRAM SHOWS THE SHAFT | | | TERMINATING AT THE THIRD FLOOR AND OPEN AT THE BOTTOM. | | | SHAFTS THAT DO NOT EXTEND TO THE BOTTOM OF THE BUILDING | | | OR STRUCTURE SHALL BE ENCLOSED AT THE BOTTOM IN | | | ACCORDANCE WITH FBC 707.11. SHOW THE SHAFT CONSTRUCTION | | | AT THE BOTTOM TO TERMITE IN ACCORDANCE WITH THIS | | | SECTION. | | | | | | 28. M-103A: VENDING EXHAUST RISER, WHILE SHOWING | | | FIRE/SMOKE DAMPERS AT EACH BRANCH, IS NOT SHOWN TO BE | | | IN A SHAFT ENCLOSURE ON FLOOR PLAN OR IN RISER DIAGRAM. | | | THERE IS ALSO NO SHAFT SHOWN AT THE DUCT LOCATION ON | | | ARCHITECTURAL FLOOR PLAN. SHOW THIS DUCT TO BE | | | PROTECTED IN ACCORDANCE WITH FBC 707.2. | | | | | | 29. M-103A: AHU-10 DUCT IN HOUSEKEEPING ROOM 231 IS | | | SHOWN WITH MULTIPLE FIRE DAMPERS PENETRATING WALLS | | | WHICH ARE NOT SHOWN TO BE FIRE RATED ACCORDING TO PG | | | A-103A. HOWEVER, ON LIFE SAFETY PLAN PG G-008 THE WALL | | | BETWEEN HOUSEKEEPING 231 AND LAUNDRY 235 IS SHOWN TO BE | | | 1-HOUR RATED. ON NO PLAN ARE THE WALLS BETWEEN ROOM 231 | | | AND 232 OR BETWEEN ROOM 232 AND ROOM 233 SHOWN TO BE | | | RATED. PLEASE COORDINATE WITH ARCHITECTURAL AND LIFE | | | SAFETY PLANS, SHOWING OPENING PROTECTIVES TO BE | | | PROVIDED ONLY IN RATED WALL ASSEMBLIES. FIRE DAMPERS | | | LOCATED WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE | | | INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS | | | SECTION, AND THE MANUFACTURER?S INSTALLATION | | | INSTRUCTIONS AND LISTING PER FBC, M 607.2. | | | NOTE: MECHANICAL FLOOR PLAN SHOWS AN ENCLOSURE AROUND | | | DUCT RISERS WHILE ARCHITECTURAL PLAN DOES NOT. PLEASE | | | COORDINATE PLANS. | | | | | | 30. M-103A: EXITWAY 230 MAY BE ACTING AS AN EXIT ACCESS | | | CORRIDOR FROM PARKING GARAGE AREA. AS SUCH, THE DUCT | | | PENETRATIONS WOULD REQUIRE SMOKE DAMPERS IN ADDITION TO | | | THE FIRE DAMPERS ALREADY SHOWN IN ACCORDANCE WITH FBC, | | | M 607.5.4. CHECK WITH BUILDING PLAN REVIEW FOR THESE | | | REQUIREMENTS AND SHOW COMPLIANCE WITH THIS SECTION AS | | | NEEDED. | | | | | | 31. M-103A: LAUNDRY ROOM 235 SHOWS THREE 16 INCH ROUND | | | DUCTS TO TIE INTO LINT FILTER SYSTEM. PROVIDE THE | | | FOLLOWING: | | | A) A DETAIL SHOWING HOW THE DRYER EXHAUST DUCTS ARE TO | | | TIE INTO THE FILTER SYSTEM WITHOUT BEING MANIFOLDED. B) | | | A SUBMITTAL FOR THE LINT FILTER SYSTEM SHOWING LISTING | | | AND INSTALLATION INSTRUCTIONS. | | | THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING TYPE 2 | | | CLOTHES DRYERS SHALL COMPLY WITH THE APPLIANCE | | | MANUFACTURER?S INSTALLATION INSTRUCTIONS IN ACCORDANCE | | | WITH FBC, M 504.7. | | | | | | | | | 32. M-103A AND M-103B: EF-1, EF-2A AND EF-2B ARE SHOWN | | | IN SOME KIND OF WALL ENCLOSURES. CLEARANCES AROUND | | | APPLIANCES TO ELEMENTS OF PERMANENT CONSTRUCTION, | | | INCLUDING OTHER INSTALLED EQUIPMENT AND APPLIANCES, | | | SHALL BE SUFFICIENT TO ALLOW INSPECTIONS, SERVICE, | | | REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH ELEMENTS OF | | | PERMANENT CONSTRUCTION IN ACCORDANCE WITH FBC, M 306.1. | | | SHOW THESE APPLIANCES TO BE ACCESSIBLE FOR SERVICE AND | | | REPLACEMENT IN ACCORDANCE WITH THIS SECTION. | | | | | | 33. M-103B: LAUNDRY ROOM 238, WHAT IS THE SOURCE OF | | | MAKE-UP AIR FOR ELECTRIC DRYERS? PROVIDE MODEL NUMBERS | | | OR MANUFACTURER?S INSTRUCTIONS TO SHOW THE QUANTITIES | | | OF MAKEUP AIR REQUIRED IN THIS AREA. SHOW THE SOURCE OF | | | THIS REQUIRED MAKEUP AIR. CLOTHES DRYERS SHALL BE | | | EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S | | | INSTRUCTIONS PER FBC, M 504.1. ALSO, INSTALLATIONS | | | EXHAUSTING MORE THAN 200 CFM SHALL BE PROVIDED WITH | | | MAKEUP AIR IN ACCORDANCE WITH FBC, M 504.5. | | | | | | 34. M-103B: FLOOR PLAN SHOWS OAU-2 RISER DUCT | | | PENETRATING STAIR #1 RATED ENCLOSURE. PENETRATIONS INTO | | | AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED | | | EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY FOR | | | INDEPENDENT PRESSURIZATION IN ACCORDANCE WITH FBC | | | 1019.1.2. SHOW THIS DUCT TO BE SEPARATED FROM THE STAIR | | | ENCLOSURE IN ACCORDANCE WITH THIS SECTION AND | | | COORDINATE WITH ARCHITECTURAL PLANS. | | | | | | 35. M-103B: GENERATOR EXHAUST RISER TERMINATES ON THIS | | | LEVEL WHICH IS OUTDOORS AND THEREFORE SHALL BE | | | PROTECTED WITH LOUVERS AND SCREENS IN ACCORDANCE WITH | | | FBC, M 401.6. | | | | | | 36. M-104A: GREASE EXHAUST DUCT RISER IN ONE NOTE CALLS | | | FOR 18? ROUND DUCT AND IN ANOTHER NOTE CALLS FOR 26X18. | | | WHICH ONE IS CORRECT? PLEASE CLARIFY. | | | | | | 37. M-104A: LIFE SAFETY PLAN G-008 SHOWS THE WALL | | | BETWEEN VENDING ROOM 450 AND LINEN ROOM 451 AS 1-HOUR | | | RATED. THIS WALL WOULD BE A CONTINUATION OF THE RATING | | | OF THE CORRIDOR AND WOULD REQUIRE THE 6 INCH ROUND DUCT | | | PENETRATION TO BE PROTECTED WITH FIRE AND SMOKE DAMPER | | | IN ACCORDANCE WITH FBC, M 607.5.3 AND 607.5.4. SHOW | | | PENETRATIONS TO BE PROTECTED IN ACCORDANCE WITH THIS | | | SECTION. COORDINATE WITH ARCHITECTURAL AND LIFE SAFETY | | | PLANS. | | | | | | 38. M-104B: OAU-2 RISER LOCATED IN STAIR ENCLOSURE, SEE | | | COMMENT #34 ABOVE. ALSO, DUCT IS PENETRATING A SHAFT | | | ENCLOSURE AND REQUIRES FIRE AND SMOKE DAMPERS IN | | | ACCORDANCE WITH FBC, M 607.5.5.1. | | | | | | 39. M-105A AND M-105B: ROOFTOP OR OUTDOOR EQUIPMENT, NO | | | INFORMATION COULD BE FOUND ON PLANS OR IN SUBMITTALS | | | REGARDING OUTDOOR EQUIPMENT WIND RESISTANCE RATINGS. | | | MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE | | | EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO | | | RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE | | | SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA | | | BUILDING CODE, BUILDING PER FBC, M 301.13. EQUIPMENT | | | SUBJECT TO THIS REQUIREMENT INCLUDES BUT MAY NOT BE | | | LIMITED TO THE FOLLOWING: CONDENSING UNITS (CU-#), | | | OUTSIDE AIR UNITS (OAU-#), EXHAUST FANS (EF-#), | | | ELEVATOR RELIEF VENTILATORS. CONSULT WITH MANUFACTURERS | | | TO DETERMINE IF EQUIPMENT HAS BEEN TESTED FOR | | | INSTALLATION IN THE 140 MPH WIND ZONE WITH THE | | | ANTICIPATED WIND PRESSURES. ALL ROOFTOP EQUIPMENT AND | | | DUCT SUPPORT DETAILS SHALL BE CONFIRMED WITH WIND LOAD | | | CALCULATIONS AND SUBMITTED FOR BUILDING PLAN REVIEW. | | | | | | 40. M-401: PIPE PENETRATION DETAILS, NOTE THAT THROUGH | | | PENETRATION FIRESTOP SYSTEMS DETAILED ON PLANS ARE FOR | | | STEEL PIPE ONLY AND THE INSULATED PIPE IS WITH CALCIUM | | | SILICATE AND FIBERGLASS INSULATION. NEITHER OF THESE | | | SYSTEMS IS APPLICABLE TO COPPER PIPE WITH FOAM RUBBER | | | INSULATION. PROVIDE DETAIL FOR A SYSTEM WHICH WILL | | | COVER THIS TYPE OF PIPING SYSTEM AS IT WILL BE | | | PREVALENT WITH SPLIT AIR CONDITIONING SYSTEMS. SEE FBC | | | 712.1 | | | | | | 41. M-404: ROOF UPBLAST EXHAUST FAN DETAIL, IS THIS | | | DETAIL FOR KEF-1? THIS DOES NOT APPEAR TO BE AN | | | INSTALLATION FOR A GREASE EXHAUST FAN AS IT SHOWS A | | | BACKDRAFT DAMPER AND IS MISSING OTHER COMPONENTS | | | NECESSARY FOR GREASE EXHAUST IN ACCORDANCE WITH FBC, M | | | SEC. 507. ALSO, KEF-1 IS SHOWN TO PROVIDE 2375 CFM OF | | | EXHAUST. THIS AIR IS MOVED THROUGH AN 18 INCH ROUND | | | DUCT. AT THAT VOLUME, THE AIR WILL BE MOVING AT A | | | VELOCITY OF APPROXIMATELY 1342 FEET PER MINUTE (FPM). | | | GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE | | | DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY | | | WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER | | | MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE IN | | | ACCORDANCE WITH FBC, M 506.3.4. | | | NOTE: NOT ENOUGH INFORMATION WAS PROVIDED IN PLANS FOR | | | A COMPLETE REVIEW OF THE KITCHEN HOOD EXHAUST SYSTEM. | | | PROVIDE COMPLETE PLANS AND DETAILS FOR THE TYPE I HOOD | | | AND EXHAUST SYSTEM. SEPARATE PERMITS ARE REQUIRED FOR | | | HOODS, SUPPRESSION SYSTEMS AND WALK-IN | | | COOLERS/FREEZERS. | | | | | | 42. ADDITIONAL INFORMATION REQUIRED: NO INFORMATION WAS | | | PROVIDED REGARDING FUEL STORAGE FOR THE STANDBY | | | GENERATOR. PROVIDE DETAIL FOR THE FUEL STORAGE SYSTEM | | | TO BE USED AND DEMONSTRATE COMPLIANCE WITH NFPA 37-02 | | | IN ACCORD ANCE WITH FBC, M 915.1. AND 915.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
14 |
Status |
P |
Date |
2009-02-13 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-13 |
Time |
19:36 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-13 |
Time |
19:35 |
Sent To |
|
|
| Notes |
| 2009-02-13 19:37:52 | REVISIONS OK -- SHTS P-001, P-101B, P--301 & P-501 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
13 |
Status |
P |
Date |
2009-02-12 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-02-12 |
Time |
17:26 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-02-12 |
Time |
17:26 |
Sent To |
|
|
| Notes |
| 2009-02-12 17:27:23 | REVISIONS OK -- SHTS P-101A, P-202A & P-600 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
12 |
Status |
F |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-24 |
Time |
22:27 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-24 |
Time |
22:27 |
Sent To |
|
|
| Notes |
| 2009-01-24 22:44:15 | DENIED | | | REFERENCE: | | | FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 BUILDING | | | FLORIDA STATUTES | | | | | | 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE | | | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE | | | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE | | | PLUMBING PLAN REVIEW. FS 589. | | | | | | 2. SHT P-301 THE FLOOR SINK SHALL CONNECT TO THE VENTED | | | LINE, NOT THE BRANCH LINE TO ANOTHER FIXTURE. SECTION | | | 912.2.4. ALL INDIRECT PIPING THAT EXCEEEDS 2 FEET | | | HORIZONTALLY SHALL BE TRAPPED. SECTION 802.2. EACH | | | PLUMBING FIXTURE SHALL BE SEPARATELY TRAPPED SECTION | | | 1002.1. DOUBLE TRAPS ARE NOT ALLOWED. SECTION 1002.1. | | | | | | 3. SHT P-302 IDENTIFY ITEM 33. THIS IS NOT SHOWN ON THE | | | KITCHEN SCHEDULE. SECTIONS 106.1.2 & 601.1. | | | | | | 4. SHT P-501 THE EXHAUST FROM THE GENERATOR SHALL BE | | | INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE | | | EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE | | | PLUMBING PLAN REVIEW. FS 589. -- THE FLOOR SINK SHALL | | | CONNECT TO THE VENTED LINE, NOT THE BRANCH LINE TO | | | ANOTHER FIXTURE. SECTION 912.2.4. ALL INDIRECT PIPING | | | THAT EXCEEEDS 2 FEET HORIZONTALLY SHALL BE TRAPPED. | | | SECTION 802.2. EACH PLUMBING FIXTURE SHALL BE | | | SEPARATELY TRAPPED SECTION 1002.1. DOUBLE TRAPS ARE NOT | | | ALLOWED. SECTION 1002.1. -- REVISION 5 NOT CLOUDED IN | | | THE GANG BATHS & AT THE DELETED RISER SAN/18. CLOUD & | | | NUMBER ALL REVISIONS SUBMITTED FOR REVIEW. SECTION | | | 106.1.3. | | | | | | 5. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM | | | 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). -- | | | THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE | | | THROUGH A WALL ON THE ZERO LOT LINE. | | | | | | 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
11 |
Status |
P |
Date |
2009-01-24 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2009-01-24 |
Time |
22:23 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2009-01-24 |
Time |
22:23 |
Sent To |
|
|
| Notes |
| 2009-01-24 22:27:09 | REVISIONS OK -- SHTS P-OO1, P-101A, P-102A, P-201A, | | | P-202A (PROVISO: DIRECT VENTS FOR THE WATER HEATERS ARE | | | NOT APPROVED AS INDICATED THRU THE ZERO LOT LINE WALL - | | | REVISION REQUIRED), P-203A, P-500, P-503 (PROVISO: | | | BACKFLOW SHALL BE INSTALLED MAXIMUM 4 FT ABOVE THE | | | FLOOR FOR MAINTENANCE & CERTIFICATION), P-600. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
10 |
Status |
P |
Date |
2008-11-05 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-11-05 |
Time |
18:55 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-11-05 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2008-11-05 18:55:42 | VARIOUS PLUMBING SUBMITTALS APPROVED. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
9 |
Status |
F |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-31 |
Time |
13:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-31 |
Time |
13:52 |
Sent To |
|
|
| Notes |
| 2008-10-31 15:46:24 | REVISION FAILED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P-203A INDICATES 3 GAS DRYERS, BUT ONLY 2 GAS | | | DRYERS ARE SHOWN. NO CHANGE IN DRYER AMOUNTS SHOWN ON | | | FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 402.1. | | | | | | 2. SHT P-500 THE FLOOR DRAINS (3) ADDED NEAR THE BASE | | | OF STACK SAN-13 AND BY THE TOILET ROOMS FOR THE SPA'S | | | ARE NOT VENTED. SECTIONS 901.2.1 & 908.3. | | | | | | 3. SHT P-501 THE SANITARY RISER DIAGRAM DOES NOT | | | REFLECT THE FLOOR PLAN AT THE WASH MACHINES FOR THE | | | GUEST LAUNDRY ROOM. THE TRAP & LAUNDRY BOX ARE SHOWN ON | | | EACH SIDE OF THE STACK ON THE FLOOR PLAN, BUT ARE SHOWN | | | ON ONE SIDE OF THE STACK ON THE RISER DIAGRAM. ALSO THE | | | SECOND TRAP IS NOT SHOWN CONNECTING TO THE STACK. | | | SECTIONS 106.1.1 & 706.3. | | | | | | 4. SHT P-503 REVISION #4 HAS BEEN DELETED FROM THE | | | REVISION INDEX. PLEASE KEEP ALL PREVIOUS REVISION | | | NUMBERS IN INDEX THROUGH OUT THE PERMIT CYCLE. NO NEW | | | CHANGES INDICATED ON THE SHEET AS REVISION #5. IF NO | | | CHANGES/REVISIONS NOT REQUIRED FOR PUBLIC RECORD. | | | SECTION 106.1.3. | | | | | | 5. SHT P-602 NATURAL GAS SIZING TABLE. NOT ALL CHANGES | | | HAVE BEEN INDICATED WITH A CLOUD OR REVISION NUMBER. | | | SEE SECTION LOAC (CFH) FOR A, J, K & L AS WELL AS APPL | | | LOAD (CFH) FOR J. PIPE SECTION N SECTION LOAD TO BE 700 | | | AND THE LONGEST RUN TO BE SECTION P, NOT O. PLEASE | | | CORRELATE ALL CHANGES TO NATURAL GAS SIZING TABLE AND | | | CLOUD ALL REVISIONS AND INDICATE WITH A REVISION | | | NUMBER. SECTION 106.1.3. | | | | | | 6. SHT P-602 GAS RISER DIAGRAM INDICATES SECTION P TO | | | BE 1/2", BUT IT ALSO SHOWS 3/4" GAS VALVE AND CAP. | | | PLEASE CLARIFY. SECTIONS 106.1.1 AND 402.1. | | | | | | 7. SHT P-602 GAS RISER DIAGRAM DOES NOT SHOW SECTION O. | | | PLEASE CORRELATE WITH GAS SIZING TABLE. SECTIONS | | | 106.1.1 & 402.1. | | | | | | 8. SHT P-602 GAS RISER DIAGRAM. UNIONS ARE REQUIRED | | | DOWNSTREAM OF THE SHUT OFF VALVES FOR EACH REGULATOR AT | | | THE WATER HEATERS AND THE POOL HEATER. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
8 |
Status |
P |
Date |
2008-10-31 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-10-31 |
Time |
13:50 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-10-29 |
Time |
13:58 |
Sent To |
|
|
| Notes |
| 2008-10-31 13:52:40 | REVISIONS OK -- SHT P-002, P-101A, P-101B, P-102A, | | | P-102B, P-103A, P-103B, P-104A, P-104B, P-105A, P-201A | | | (GAS), P-202A (GAS), P-302 (GAS), P-402, P-506, P-507, | | | P-600 & P-601. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
7 |
Status |
P |
Date |
2008-09-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-09-03 |
Time |
06:48 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-09-03 |
Time |
06:48 |
Sent To |
|
|
| Notes |
| 2008-09-03 06:49:13 | REVISION OK -- SHT P-600 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
6 |
Status |
F |
Date |
2008-08-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-18 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-18 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2008-08-18 09:11:23 | REVISION DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | | | | 1. SHT P-600 REVISIONS DO NOT REFLECT THE CHANGES SHOWN | | | ON THE FLOOR PLAN. SECTIONS 106.1.1 & 1106. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
5 |
Status |
P |
Date |
2008-08-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-08-18 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-08-18 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2008-08-18 09:09:10 | REVISIONS OK --SHTS P-101A, P-201A, P-500 & P-503. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-07-17 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-17 |
Time |
08:11 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-16 |
Time |
17:17 |
Sent To |
|
|
| Notes |
| 2008-07-17 08:13:40 | | | | | | | PASSED/PROVISO | | | | | | REVISION REQUIRED FOR SHT P-501 SHOWING THE FIXTURES | | | FOR THE GUEST LAUNDRY ROOM, (2 W/M'S AND A FLOOR | | | DRAIN), AND THE CONNECTION OF THE VENT STACK TO THE | | | SANITARY STACK FOR RISER "I". | | | | | | | | | | | | | | | | | | . |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-07-03 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-07-03 |
Time |
08:52 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-07-02 |
Time |
17:52 |
Sent To |
|
|
| Notes |
| 2008-07-03 11:08:29 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FHA-98 DESIGN MANUAL | | | CITY WPB MUNICIPAL CODES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | ******FROM PREVIOUS REVIEWS: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. OK | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 | | | GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING | | | TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. | | | INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW | | | METHOD. SECTIONS 106.1.2 & 608. | | | ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A | | | MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE | | | RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED | | | FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW | | | PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM | | | BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE | | | DRYERS. | | | ******RESPONSE NOTED, BUT THE 950XLU BACKFLOW PREVENTOR | | | IS STILL SHOWN ON SHEETS P203A & P-504. PLEASE SHOW THE | | | N36 VACUUM BREAKER. | | | | | | 16. OK | | | 17. OK | | | 18. OK | | | 19. OK | | | 20. OK | | | 21. OK | | | 22. OK | | | 23. OK | | | 24. OK | | | 25. OK | | | 26. OK | | | 27. OK | | | 28. OK | | | 29. OK | | | 30. OK | | | 31. OK | | | 32. OK | | | 33. OK | | | 34. OK | | | 35. OK | | | 36. OK | | | 37. OK | | | 38. OK | | | 38A. OK | | | 39. OK | | | 40 OK | | | 41. OK | | | 42. OK | | | 43. OK | | | 44. OK | | | 45. OK | | | 46. OK | | | 47. OK | | | 48. OK | | | 49. OK | | | 50. OK | | | 51. OK | | | | | | 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK | | | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER | | | SECTION 903.4. | | | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT | | | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK | | | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE | | | DRAINAGE STACKS. | | | ******RESPONSE NOTED, BUT RISER "I" DOES NOT SHOW THE | | | BENT FROM THE 2ND FLOOR OR CONNECTION TO THE SANITARY | | | STACK. (SHT 502). | | | | | | 53. OK | | | 54. OK | | | 55. OK | | | 56. OK | | | 57. OK | | | 58. OK | | | 59. OK | | | 60. OK | | | 61. OK | | | 62. OK | | | 63. OK | | | 64. OK | | | 65. OK | | | 66. OK | | | 67. OK | | | 68. OK | | | 69. OK | | | 70. OK | | | 71. OK | | | 72. OK | | | 73. OK | | | 74. OK | | | 75. OK | | | 76. OK | | | 77. OK | | | | | | 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 | | | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | ******RESPONSE NOTED, BUT COMMENT STILL NOT ADDRESSED. | | | BRANCH LINE SHOWN UPSTREAM OF CONDENSATE CONNECTION AND | | | ST13 ON SHT P-101A. PLEASE CORRELATE. | | | | | | 79. OK | | | 80. OK | | | 81. OK | | | 82. OK | | | 83. OK | | | 84. OK | | | 85. OK | | | 86. OK | | | 87. OK | | | 88. OK | | | 89. OK | | | | | | 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT | | | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS | | | APPLICATION IS APPLIED FOR). | | | | | | I. N/A | | | J. N/A | | | | | | **********NEW COMMENTS********** | | | | | | 1B. OK | | | 2B. OK | | | 3B. OK | | | | | | ***********NEW COMMENT*********** | | | | | | 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL | | | Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS | | | INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-04-26 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-26 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-25 |
Time |
19:00 |
Sent To |
|
|
| Notes |
| 2008-04-26 17:04:20 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FHA-98 DESIGN MANUAL | | | CITY WPB MUNICIPAL CODES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. OK | | | 2. OK | | | 3. OK | | | 4. OK | | | | | | 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE | | | SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE | | | INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201 | | | THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS | | | P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE | | | SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES | | | ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT | | | REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX | | | WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3. | | | ****RESPONSE NOTED, BUT THE INDEX OF DRAWINGS STILL | | | DOES NOT RELFECT THE SHEETS SUBMITTED. MANY SHEETS | | | SHOWN ON THE INDEX WERE NOT SUBMITTED. SOME SHEETS | | | SUBMITTED ARE NOT SHOWN ON THE INDEX. | | | | | | 6. OK | | | 7. OK | | | 8. OK | | | 9. OK | | | 10. OK | | | 11. OK | | | 12. OK | | | 13. OK | | | 14. OK | | | | | | 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 | | | GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING | | | TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. | | | INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW | | | METHOD. SECTIONS 106.1.2 & 608. | | | ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A | | | MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE | | | RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED | | | FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW | | | PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM | | | BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE | | | DRYERS. | | | | | | 16. OK | | | | | | 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY | | | FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A | | | DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER. | | | IF CONNECTING TO THE STORM SEWER, A RELIEF VENT, | | | (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE | | | BUILDING. SECTION 314.2.1. | | | ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3 | | | SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE | | | BRANCH LINE TO ST-13. | | | | | | 18. OK | | | 19. OK | | | 20. OK | | | 21. OK | | | 22. OK | | | 23. OK | | | 24. OK | | | 25. OK | | | 26. OK | | | 27. OK | | | 28. OK | | | 29. OK | | | 30. OK | | | 31. OK | | | 32. OK | | | 33. OK | | | | | | 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE | | | IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN | | | BE FOUND. SECTION 106.1.2. | | | ****RESPONSE NOTED, BUT SHT P-101 WAS NOT SUBMITTED OR | | | INDICATED ON SHT G-001A DRAWING INDEX. | | | | | | 35. OK | | | 36. OK | | | | | | 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE | | | REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.-- | | | THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN | | | DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE | | | INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL | | | EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT | | | MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART. | | | INDICATE MODEL NUMBERS. SECTION 607.3.2. ****RESPONSE | | | NOTED, BUT THE EXPANSION TANK CALCULATION SUBMITTED | | | INDICATES THE REQUIRED SIZE IS 28.5 GAL. THE MODEL | | | INDICATED IS ONLY 25 GAL. TANK NOT APPROVED. | | | | | | 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK | | | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER | | | SECTION 903.4. | | | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT | | | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK | | | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE | | | DRAINAGE STACKS. | | | | | | 38A. OK | | | 39. OK | | | 40 OK | | | 41. OK | | | 42. OK | | | 43. OK | | | 44. OK | | | 45. OK | | | 46. OK | | | 47. OK | | | 48. OK | | | 49. OK | | | 50. OK | | | 51. OK | | | | | | 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK | | | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER | | | SECTION 903.4. | | | ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT | | | STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK | | | ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE | | | DRAINAGE STACKS. | | | | | | 53. OK | | | 54. OK | | | 55. OK | | | 56. OK | | | | | | 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT | | | REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | ****RESPONSE NOTED, BUT THE CLEANOUT IS MISSING | | | UPSTREAM OF THE BRANCH LINE TO RISER 2A AND THE OFFSET | | | AT THE BASE OF RISER 1A IS NOT INDICATED. | | | | | | 58. OK | | | | | | 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY | | | FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE BRANCH LINE TO THE FLOOR | | | DRAIN DOES NOT REFLECT THE FLOOR PLAN, NOR IS IT | | | VENTED. SECTION 901.2.1. | | | | | | 60. OK | | | 61. OK | | | 62. OK | | | 63. OK | | | 64. OK | | | 65. OK | | | 66. OK | | | 67. OK | | | 68. OK | | | 69. OK | | | 70. OK | | | 71. OK | | | 72. OK | | | 73. OK | | | 74. OK | | | 75. OK | | | 76. OK | | | | | | 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR | | | PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR | | | ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION | | | 106.1.1. | | | ****RESPONSE NOTED, BUT THE OFFSET BELOW THE ROOF IS | | | NOT SHOWN ON THE RISER DIAGRAM. | | | | | | 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 | | | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | | | 79. OK | | | | | | 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE | | | OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE | | | AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM | | | DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED. | | | | | | 81. OK | | | 82. OK | | | 83. OK | | | | | | 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM | | | THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). | | | ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3 | | | SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE | | | BRANCH LINE TO ST-13. | | | | | | 85. OK | | | 86. OK | | | 87. OK | | | 88. OK | | | 89. OK | | | | | | 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. OK | | | B. OK | | | C. OK | | | D. OK | | | E. OK | | | F. OK | | | G. OK | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT | | | SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS | | | APPLICATION IS APPLIED FOR). | | | | | | I. N/A | | | J. N/A | | | | | | **********NEW COMMENTS********** | | | | | | 1B. SHT P-104A FIXTURES ARE NOT SHOW ON THE FLOOR PLAN | | | FOR THE BATHROOM AT RISER SAN/10B. SECTION 106.1.2. | | | PLEASE SHOW ALL FIXTURES ON THE FLOOR PLAN. | | | | | | 2B. THE GAS REGULATOR SUBMITTAL IS NOT APPROVED FOR ALL | | | GAS APPLIANCES. THE ONLY SIZE INDICATED IN THE | | | SUBMITTAL IS 3/4" BUT THE SHUT OFF VALVE AND REGULATOR | | | SHALL BE SIZED PER THE PIPE SIZE REQUIRED TO EACH | | | APPLIANCE. | | | | | | 3B. EMERGENCY HOOD SHUT DOWN SHUT OFF | | | VALVE TO BE BELOW CEILING. MANUAL SHUT | | | OFF VALVE TO BE UPSTREAM. UNION TO BE | | | DOWN STREAM OF MANUAL VALVE. THIS IS REQUIRED FOR THE | | | GRIDDLE. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-03-10 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-10 |
Time |
11:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-05 |
Time |
19:01 |
Sent To |
|
|
| Notes |
| 2008-03-10 15:57:52 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 BUILDING | | | FBC-2004 FUEL GAS | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | FHA-98 DESIGN MANUAL | | | CITY WPB MUNICIPAL CODES | | | | | | 1. SHT G.000 GUESTROOM MATRIX. THE TOTAL FOR FOR THE | | | QUEEN STANDARD IS SHOWN AS 81, BUT ADDS UP TO 72. | | | PLEASE RECHECK THE CALCULATIONS. SECTIONS 106.1.2 & | | | 11-9.1.2. | | | | | | 2. SHT G.000 GUESTROOM MATRIX DOES NOT COMPLY WITH | | | SECTION 11-9.1.4 AS THERE IS NOT ACCESSIBLE BOARDROOM | | | SUITE AVAILABLE. | | | | | | 3. SHT G.000 PER SECTION 11-9.1.2, PURSANT TO CHAPTER | | | 509, FLORIDA STATUTES, A NUMBER OF ROOMS EQUALLING AT | | | LEAST 5% OF THE GUEST ROOMS MINUM THE NUMBER OF | | | ACCESSIBLE ROOMS REQUIRED BY TABLE BELOW SHALL PROVIDE | | | ADDITIONAL FEATURES OF SECTION 11-9.2.3. ONE ROOM IS | | | REQUIRED, PLEASE INDICATE THE ROOM NUMBER & LOCATION OF | | | THE REQUIRED ROOM. | | | | | | 4. SHTS G-00- THRU G-009 & SHTS AC-101 THRU A-812. THE | | | PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS IS | | | REQUIRED ON EACH SHEET. FAC 61G1-16.004(6) & FS | | | 481.2055. | | | | | | 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE | | | SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE | | | INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201 | | | THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS | | | P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE | | | SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES | | | ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT | | | REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX | | | WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3. | | | | | | 6. SHT AC-102 SHOWS A COMPACTOR PAD FLOOR DRAIN. PLEASE | | | INDICATE IF THE COMPACTOR WILL BE COMPACTING GREASY | | | WASTE. ALSO THE STORM WATER CAN NOT DRAIN INTO THE | | | SANITARY SYSTEM. INDICATE THE METHOD OF KEEPING THE | | | STORM WATER OUT OF THE SANT. SYSTEM. ARTICLE III, | | | SECTION 90-125(B)(5). IN THE PAST WHEN THIS ISSUE CAME | | | UP, WE INDICATED THAT THE DRAIN IS NOT REQUIRED. PLEASE | | | CLARIFY. | | | | | | 7. ALL PLUMBING SHEETS THAT INDICATE "TYPICAL LEVEL | | | PLAN". PLEASE INDICATE WHAT FLOORS THE PLANS ARE | | | TYPICAL OF. SECTIONS 106.1.1 & 106.1.2. | | | | | | 8. SHT A-100D IS INDICATED AS TYPICAL LEVEL PLAN 4TH | | | FLOOR. ARE THE 3RD & 5TH FLOORS DIFFERENT. THESE FLOORS | | | HAVE NOT BEEN SUBMITTED. SECTIONS 106.1.1 & 106.1.2. | | | | | | 9. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT. | | | OF BUSINESS REGULATION. (DBPR), DIVISION OF HOTEL AND | | | RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO | | | RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF 3 | | | SETS OF PLANS WITH THE DBPR REVIEW SHALL BE SUBMITTED. | | | THE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE | | | SHEET WITH THE DBPR PLAN REVIEW STAMP. SECTION | | | 102.2.1. | | | | | | 10. SHT A-423 DETAILS 1, 3, 7 & 8 THE TURNING AREA | | | SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE | | | TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 8 | | | SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV | | | PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2. | | | | | | 11. SHT A-425 DETAILS 1, 3, 4 & 5 THE TURNING AREA | | | SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE | | | TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 5 | | | SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV | | | PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2. | | | | | | 12 SHT A-4.26 DETAIL 1 THE TURNING AREA SHALL BE | | | UNOBSTRUCTED. THE W/C CAN NOT BE IN THE TURNING AREA. | | | SECTION 11-4.22.3.--DETAILS 1 & 6 SHALL SHOW THE | | | CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV PER SECTIONS | | | 11-4.16.2, 11-4.19.3 & 11-4.20.2. | | | | | | 13. SHT A-612 THE WALL FINISH FOR THE TOILET ROOMS 112, | | | 113, 137 & 138 IS STATED AS "VARIES"PLEASE SHOW | | | COMPLIANCE WITH SECTION 1210.2 REQUIREMENT FOR THE | | | WALLS WITHIN 2 FT OF THE TOILETS OR URINALS SHALL HAVE | | | A "SMOOTH, HARD, NONABSORBENT" SURFACE. | | | | | | 14. ALL MECH, PLMG & ELECT SHEETS. THE ADDRESS OF THE | | | ENGINEER FIRM ON THE TITLE BLOCKS DOES NOT REFLECT THE | | | ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE. | | | PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE SO | | | THEY REFLECT PRIOR TO RESUBMITTING TO THE CITY FOR | | | REVIEW. IF MULTIPLE ADDRESS, PLEASE ADD THE ADDRESS OF | | | RECORD TO TITLE BLOCKS. FAC 61G15-23.002(2) & FS | | | 471.025. | | | | | | 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02 | | | GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING | | | TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF. | | | INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW | | | METHOD. SECTIONS 106.1.2 & 608. | | | | | | 16. SHT P-101A A 2-WAY CLEANOUT IS REQUIRED AT THE | | | INLET AND EXIT OF EACH GREASE INTERCEPTOR. PLEASE | | | INDICATE ON THE CLEANOUT BETWEEN THE GREASE | | | INTERCEPTORS. UTILITY STANDARD FOR GREASE INTERCEPTORS | | | & SECTION 708.3.2. | | | | | | 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY | | | FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A | | | DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER. | | | IF CONNECTING TO THE STORM SEWER, A RELIEF VENT, | | | (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE | | | BUILDING. SECTION 314.2.1. | | | | | | 18. SHT P101AINDICATES "6 INCH PDD DN 4546SF. PLEASE | | | SHOW WHERE THE LINE IS AND INDICATE WHAT PDD STANDS FOR | | | AS IT IS NOT INDICATED ON THE ABBREVIATION SCHEDULE ON | | | SHT P-001. SECTION 106.1.2. | | | | | | 19. SHT P-101B THE COMPACTOR INDICATES4" GREASE | | | (4DFU'S), BUT SHOWS THE FLOOR DRAIN CONNECTING TO THE | | | SANITARY SYSTEM. PLEASE SEE COMMENT #6. SECTION | | | 106.1.1 | | | | | | 20. SHT P-101B CLEANOUTS ARE REQUIRED ON THE SANITARY & | | | STORM SYSTEMS PER SECTIONS 708.3.5 & 1101.8. | | | | | | 21. SHTS P-102A P-102B, P-103A & P-103B THE CONDENSATE | | | SHALL DRAIN FROM THE BUILDING SEPARATELY. (SEE COMMENT | | | #17).--THE BACKWATER VALVES ARE NOT REQUIRED IF THE | | | RELIEF VENTS ARE INSTALLED. | | | | | | 22. SHT P-103A THE W/C & LAV ARE NOT SHOWN ON THE FLOOR | | | PLAN IN ROOM 219. PLEASE SHOW ALL FIXTURES ON FLOOR | | | PLAN. SECTION 106.1.1. | | | | | | 23. SHT P-103A SAN-8A RISER "B" SHOWS TUBS ON THE | | | RISER, BUT SHOWERS ON THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 24. SHT P-103A SHOWERS ARE NOT SHOWN ON THE FLOOR PLAN | | | IN ROOMS 213 THRU 216, 224 & 225.--PLEASE SHOW | | | RISER DESIGNATIONS FOR RISERS ST/14 & STO/14. SECTION | | | 106.1.2. | | | | | | 25. SHT P-103B SANITARY RISER SAN-4A SHOWS SHOWERS ON | | | THE FLOOR PLAN, BUT TUBS ON THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 26. SHT P-104A KING ROOMS 449, *48, 447, 445, 432, 430, | | | 429 & 431 SHOW SHOWERS ON THE FLOOR PLAN, BUT TUBS ON | | | THE RISER DIAGRAMS. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 27. SHT P-104A INDICATES RISER "C" ON THE FLOOR PLAN, | | | BUT RISER "C" NOT SUBMITTED. PLEASE CLARIFY. SECTION | | | 106.1.1. | | | | | | 28. SHT P-104A RISER SAN-10A THE SINK, (S-1) SHALL | | | DISCHARGE DOWNSTREAM OF THE WET VENT FOR THE BATHROOM | | | FIXTURES. SECTION 909.1. | | | | | | 29. SHT P-104B KING ROOMS 413, 414, 415 &416 SHOWS | | | SHOWERS ON THE FLOOR PLAN, BUT SHOWS TUBS ON THE RISER | | | DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 30. SHTS P-105A & P-105B INDICATE THE RISER DESIGNATION | | | NUMBERS AT THE ROOF DRAINS/OD'S TO TRACK RISER THRU | | | BUILDING. SECTION 106.1.2. | | | | | | 31. SHT P-203A THE SHOWERS ARE NOT SHOWN ON THE FLOOR | | | PLAN IN MANY ROOMS/UNITS. PLEASE SHOW ALL FIXTURES ON | | | THE FLOOR PLAN. SECTION 106.1.1. | | | | | | 32. SHT P-203A SUBMIT THE RISER DIAGRAM FOR THE LAUNDRY | | | ROOM. SHOW ALL PIPE SIZES, VALVES & REQUIRED WATER | | | HAMMER ARRESTORS. SECTIONS 103.5.1.3, 604.1, 604.9, | | | 606.2(1). | | | | | | 33. SHT. P-203A IDENTIFY FIXTURE (TMV-3) SHOWN AT COL. | | | LINE D BETWEEN COLS 10 & 11. SECTION 106.1.2. | | | | | | 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE | | | IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN | | | BE FOUND. SECTION 106.1.2. | | | | | | 35. SHT P-302 IDENTIFY COLD WATER RISER NEAR COL. LINE | | | E/8.5. (NOT SHOWN ON THE RISER DIAGRAM). SECTION | | | 106.1.2. | | | | | | 36. SHT P-302 HOT WATER SUPPLY ONLY SHOWN TO RISER #45 | | | ON THE FLOOR PLAN, BUT THE NOTE INDICATES HW & CW TO | | | RISER. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE | | | REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.-- | | | THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN | | | DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE | | | INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL | | | EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT | | | MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART. | | | INDICATE MODEL NUMBERS. SECTION 607.3.2. | | | | | | 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK | | | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER | | | SECTION 903.4. | | | | | | 38. SHT P-500 RISER SAN-10B SHOWS A DRY HORIZONTAL VENT | | | PAST FIXTURE BT-1. THIS IS PROHIBITED PER SECTIONS | | | 905.3 & 905.4. | | | | | | 39. SHT P-500 RISER SAN-10A THE S-1 SINK SHALL | | | DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM | | | FIXTURES. SECTION 909.1. | | | | | | 40 SHT P-500 RISER SAN-9A DOES NOT REFLECT THE FLOOR | | | PLAN AT THE 2ND FLOOR AND NOT ALL FIXTURES ARE VENTED. | | | PLEASE CORRELATE. SECTIONS 106.1.1 & 901.2.1. | | | | | | 41. SHT P-500 RISER SAN-8A DOES NOT REFLECT THE FLOOR | | | PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 42. SHT P-500 FIXTURE UPSTREAM OF RISER SAN-10 DOES NOT | | | REFLECT THE FLOOR PLAN. SHOWER INDICATED ON THE FLOOR | | | PLAN, FLOOR DRAIN ON RISER DIAGRAM. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 43. SHT P-500 CONNECTIONS TO THE BUILDING DRAIN AT | | | RISER SAN-10 & BRANCH LINE DO NOT REFLECT THE FLOOR | | | PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 44. SHT P-500 RISER SAN-8/9 OFFSET IN THE 1ST FLOOR | | | CEILING DOES NOT REFLECT THE FLOOR PLAN OFFSET. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 45. SHT P-500 RISERS SAN-6A, 7A, 8A, 12A & 13 DO NOT | | | REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 46. SHT P-500 RISER SAN-6 DOES NOT REFLECT THE FLOOR | | | PLAN AT THE OFFSET BELOW THE 3RD FLOOR. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 47. SHT P-500 RISER SAN-11 DOES NOT REFLECT THE FLOOR | | | PLAN AT THE BASE OF THE STACK. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 48. SHT P-500 VENTING ABOVE TOILET ROOMS 137 & 138 DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 49. SHT P-500 RISER SAN-12A DOES NOT REFLECT THE FLOOR | | | PLAN AT TOILET ROOM 2ND FLOOR. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 50. SHT P-500 RISER SAN-13 DOES NOT REFLECT THE FLOOR | | | PLAN 2ND FLOOR. FLOOR PLAN SHOWS SHOWER,RISER SHOWS | | | TUB. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 51. SHT P-500 2 WAY CLEANOUT REQUIRED BETWEEN THE | | | GREASE INTERCEPTORS. UTILITY STANDARD & SECTION | | | 708.3.2. | | | | | | 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK | | | SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER | | | SECTION 903.4. | | | | | | 53. SHT P-501 SHOW ALL PIPE SIZES FOR THE GREASE | | | SYSTEM. SECTIONS 701.1 AND TABLES 710.1(1) & 710.1(2). | | | | | | 54. SHT P-501 THE VENT PIPING FROM TOILET ROOMS 112 & | | | 113 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 55. SHT P-501 RISERS SAN-5A, 4A, 3A & 2A DO NOT REFLECT | | | THE FLOOR PLAN, NOR DO THEY MEET CODE REQUIREMENTS FOR | | | VENTING FOR THE SECOND FLOOR FIXTURES. PLEASE | | | CORRELATE. SECTIONS 106.1.1 & 901.2.1. | | | | | | 56. SHT P-501 RISERS FOR ROOMS 104, 105, 106 & 107 DO | | | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT | | | REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 58. SHT P-501 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR | | | PLAN AT THE COMPACTOR, BUT ONLY ONE IS SHOWN ON THE | | | RISER DIAGRAM. PLEASE CLARIFY & PLEASE CORRELATE. | | | SECTION 106.1.1. (PLEASE SEE COMMENT #6). | | | | | | 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY | | | FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 60. SHT P-501 PIPING IN THE MEZZANINE CEILING FOR | | | RISERS SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN. | | | PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 61. SHTS P-500 & P-501 CLEANOUTS ARE REQUIRED AT THE | | | BASE OF EACH STACK PER SECTION 708.3.4. PLEASE SHOW ON | | | RISERS. | | | | | | 62. SHT P-502 SHOW 2 RISERS DESIGNATED RISER "E" PLEASE | | | CLARIFY. SECTION 106.1.1. | | | | | | 63. SHT P-502 SECOND RISER "E"THE S-1 SINK SHALL | | | DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM | | | FIXTURES. SECTION 909.1. | | | | | | 64. SHT P-503 FIVE HOSE BIBB LINES SHOWN ON THE FLOOR | | | PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 65. SHT P-504 THREE HOSE BIBB LINES SHOWN ON THE FLOOR | | | PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 66. SHT P-504 THE BRANCH LINE TO CW/18 DOES NOT REFLECT | | | THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 67. SHT P-504 THE BASE OF RISER CW/14A CONNECTION TO | | | THE WATER MAINS DOES NOT REFLECT THE FLOOR PLAN. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 68. SHT P-504 THE 1-1/4" HOT WATER BRANCH LINE DOES NOT | | | REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 69. SHT P-505 2 HOSE BIBB LINES SHOWN ON THE FLOOR PLAN | | | ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 70. SHT P-507 RISER "H" DOES NOT REFLECT THE FLOOR PLAN | | | PIPING FROM THE RISER AND TUBS ARE SHOWN ON THE FLOOR | | | PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 71. SHT P-600 CONDENSATE SHALL DRAIN SEPARATELY FROM | | | THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). | | | | | | 72. SHT P-600 CONDENSATE INFORMATION NOTE STATES "SEE | | | DWG P-103 FOR CONT". SHT P-103 WAS NOT SUBMITTED. SHT | | | 103A 2ND FLOOR WEST DOES NOT SHOW RISER. PLEASE | | | INDICATE WHERE INFORMATION CONTINUES. SECTION 106.1.1. | | | | | | 73. SHT P-600 RISERS STO/8 & STO/9 DO NOT REFLECT THE | | | FLOOR PLAN AT THE TERMINATION. (SEE SHT P-101A). PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 74. SHT P-600 CLEANOUTS REQUIRED PER SECTION 1101.8. | | | PLEASE SHOW ALL REQUIRED C/O'S ON PLANS. | | | | | | 75. SHT P-600 PDD CONNECTION TO RISER ST/8-ST/9 DOES | | | NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 76. SHT P-600 RISERS ST/10 & STO/10 DO NOT REFLECT THE | | | FLOOR PLAN AT THE OFFSET & LOCATION OF RISER STO/10. | | | (SEE SHT P-102A). PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR | | | PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR | | | ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12 | | | DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 79. SHT P-600 THE LOCATION OF STO/12 DOES NOT REFLECT | | | THE FLOOR PLAN.. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE | | | OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE | | | AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM | | | DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE | | | CORRELATE. SECTION 106.1.1. | | | | | | 81. SHT P-600 RISER STO/13 ALSO DOES NOT REFLECT THE | | | FLOOR PLAN. (SHT P-101A). PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | 82. SHT P-600 RISER STO/14 IS SHOWN TO THE SOUTH SIDE | | | OF ST/14 ON THE FLOOR PLAN. RISER DOES NOT REFLECT THE | | | FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 83. SHT P-600 RISERS ST/14 & STO/14 DO NOT REFLECT THE | | | FLOOR PLAN AS IT SHOWS THE RISERS THRU THE 5TH FLOOR | | | AND TO THE UPPER ROOF. THE FLOOR PLAN SHOWS THE ROOF | | | DRAINS AT THE 2ND LEVEL LOWER ROOF. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM | | | THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17). | | | | | | 85. SHT P-601 CLEANOUTS REQUIRED PER SECTION 1101.8. | | | PLEASE SHOW ALL REQUIRED C/O'S ON PLANS. | | | | | | 86. SHT P-601 THE PIPING AT THE BASE OF RISERS ST/6 - | | | ST/7 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. | | | SECTION 106.1.1. | | | | | | 87. SHT P-601 CONDENSATE NOTE REFERS TO DWG P--103A, | | | BUT NO RISER CONT. WAS FOUND. PLEASE INDICATE THE | | | LOCATION OF THE RISER DIAGRAMS. SECTION 106.1.2. | | | | | | 88. SHT P-601 THE PIPING OUT OF THE CATCH BASIN TO | | | RISERS ST/1 & ST/2 DOES NOT REFLECT THE FLOOR PLAN. | | | PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 89. A SEPARATE IRRIGATION PERMIT AND PLANS ARE | | | REQUIRED. THIS CAN BE SUBMITTED AFTER BUILDING PERMITS | | | ARE ISSUED BUT PRIOR TO COMMENCMENT OF IRR. WORK. | | | (INFORMATIONAL). | | | | | | 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING | | | INFORMATION IS REQUIRED: | | | | | | A. SUBMIT AN ISOMETRIC DRAWING THAT | | | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE | | | AND CORRESPONDING LENGTHS PER FBC-2004 | | | FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC | | | DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER | | | HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE | | | ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH | | | SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE | | | ENDS.PLEASE CORRELATE. SECTION 106.1.1. | | | | | | B. SHOW TYPE OF PIPING MATERIAL BEING | | | INSTALLED, ALL PIPE SIZES, (AND THE EDH | | | NUMBER OF CORRUGATED STAINLESS STEEL | | | TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE | | | SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE | | | INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE | | | 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6). | | | | | | C. TYPE OF GAS, (LP OR NATURAL). | | | | | | D. SHOW THE DISTANCE FROM THE POINT OF | | | DELIVERY, (METER), TO THE MOST REMOTE | | | OUTLET IN THE BUILDING AND/OR SYSTEM PER | | | FBC-2004 FUEL GAS CODE APPENDIX A - USE | | | OF CAPACITY TABLES A.3.1(4). | | | | | | E. SUBMIT CALCULATIONS FOR COMBUSTION | | | AIR (IF APPLICABLE) PER FBC-2004 FUEL | | | GAS CODE SECTION 304. | | | | | | F. INDICATE THE DELIVERY PRESSURE (PSI) | | | PER FBC-2004 FUEL GAS CODE SEC. 402.2. | | | NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602 | | | INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS | | | PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES | | | AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE | | | INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT | | | DELIVERY PRESSURE. | | | | | | G. SUBMIT A DETAIL SHOWING THE TYPE, | | | LOCATION, SIZE AND TERMINATION OF THE | | | GAS VENTS PER FBC-2004 FUEL GAS CODE | | | SECS. 502 THRU 505. | | | | | | H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS | | | EQUIPMENT TO VERIFY COMPLIANCE WITH | | | STANDARDS NFPA 54, NFPA 58, AND THE | | | FBC-2004 FUEL GAS CODE SEC 402.2. | | | | | | I. CLEARLY SHOW THE LOCATION AND CAP- | | | ACITY OF LP TANK(S), TYPE OF TANK (DOT | | | OR ASME), THE DISTANCE OF THE TANK FROM | | | THE BUILDING AND ADJACENT PROPERTY LINES | | | THE DISTANCE OF THE TANK FROM ALL SOUR- | | | CES OF IGNITION, OTHER CONTAINERS, BUILD | | | INGS, AND THE LOCATION OF ANY BUILDING | | | OPENINGS BELOW THE RELIEF VALVE OF THE | | | TANK PER NFPA 58, TABLE 3-2.2.2. | | | | | | J. CLEARLY INDICATE ON THE PLAN IF THE | | | LP TANK IS ABOVE OR BELOW GROUND, AND | | | SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES | | | PER NFPA 58. IF THE TANK | | | IS BELOW GROUND THE CONTAINER SHALL BE | | | SECURILY ANCHORED PER NFPA 58 SECTION | | | 3-2.2.7(H). | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED | | | LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL | | | HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
6 |
Status |
N |
Date |
2009-02-11 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2009-02-11 |
Time |
14:53 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2009-02-11 |
Time |
14:53 |
Sent To |
|
|
| Notes |
| 2009-02-11 14:54:29 | ZONING REVIEW: NOT REQUIRED | | | | | | ** REVISED M & P ONLY; PROJECT ELEVATIONS SHALL BE | | | MODIFIED TO INDICATE NEW LOUVER LOCATIONS. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
5 |
Status |
P |
Date |
2009-01-30 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2009-01-30 |
Time |
17:14 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2009-01-30 |
Time |
17:14 |
Sent To |
|
|
| Notes |
| 2009-01-30 17:15:42 | ZONING REVIEW: PASSED | | | | | | ** PLAN REVISIONS | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
4 |
Status |
P |
Date |
2008-10-27 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-10-27 |
Time |
09:13 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-10-27 |
Time |
09:13 |
Sent To |
|
|
| Notes |
| 2008-10-27 09:18:00 | ZONING REVIEW: PASSED WITH PROVISO: | | | | | | 1) ENGINEERING DEPT SHALL REVIEW AND CONFIRM NEW TRASH | | | PICK-UP CONFIGURATION PROPOSAL. | | | | | | 2) BIKE RACKS SHALL BE "U" MODEL, PER DISCUSSION WITH | | | CONTRACTOR'S REP AND APPROVED BY ARCHITECT. (ONE RACK | | | PER 40 VEHICULAR PARKING SPACES). | | | | | | 3) CREEPING FIG ALONG NORTH ELEVATION AGAINST ADJACENT | | | PARKING GARAGE MAY BE ELIMINATED, AS THERE WILL NOT BE | | | ENOUGH ROOM BETWEEN TWO BUILDINGS. | | | | | | 4) GATE AND WALL AT EAST END OF PROPERTY DOES NOT | | | APPEAR TO TURN BACK AND ENCLOSE PROPERTY. CONFIRM IT | | | WILL BE EXTEND NORTH TO SECURE AREA. | | | | | | 5) PLEASE COORDINATE TREE RELOCATION/REPLACEMENT WITH | | | ROBERT KUSSNER, LANDSCAPE PLANNER, AT 822-1435; WILL BE | | | REQUIRED PRIOR TO C/O. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
F |
Date |
2008-09-23 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-09-23 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-09-23 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2008-09-23 10:33:39 | ZONING REVIEW: FAILED | | | | | | ** BIKE RACK MODEL AND PLACEMENT ONLY | | | | | | 1) PLEASE INDICATE HOW PROPOSED RACK MEETS REQUIREMENT | | | (1 BIKE PARKING SPACE PER 20 CAR PARKING SPACES). | | | | | | 2) CITY-RECOMMENDED BIKE RACK MODELS ARE "INVERTED 'U'" | | | OR "HITCHING POST" TYPES. COPIES ATTACHED. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-04-29 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-04-29 |
Time |
10:20 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-04-29 |
Time |
10:20 |
Sent To |
|
|
| Notes |
| 2008-04-29 10:22:15 | ZONING REVIEW: PASSED WITH PROVISO | | | | | | 1) UPON RESUBMITTAL OR REVISION, PLEASE AMEND AC 101 | | | AND A 100A SUCH THAT THE CURB CUT AT LAKEVIEW DRIVE | | | MATCHES THE DIRECTIONAL DRIVEWAY INDICATED BY THE CIVIL | | | DRAWINGS. THEY DO NOT MATCH. | | | | | | 2) PLEASE PROVIDE FURTHER DETAIL ON THE | | | CANOPIES/AWNINGS PROPOSED FOR THE BUILDING ELEVATIONS. | | | THEY ARE NOT INCLUDED IN THIS PACKAGE. | | | | | | 3) NO GENERAL PLANTING DETAILS ARE INCLUDED. PLEASE ADD | | | TO REVISED DRAWINGS. | | | | | | MATT FLIS - 822-1445 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
mflis |
Date |
2008-01-16 |
Time |
15:09 |
Rev Time |
0.00 |
| Received By |
mflis |
Date |
2008-01-16 |
Time |
15:09 |
Sent To |
|
|
| Notes |
| 2008-01-16 15:24:54 | ZONING REVIEW: PASSED WITH PROVISO: | | | | | | UPON RESUBMITTAL OR REVISION, PLEASE ADDRESS THE | | | FOLLOWING: | | | | | | 1) ON ENGINEERING SHEET #4, PLEASE CHANGE ZONING | | | DESIGNATION TO READ "BUILDING TYPE III" INSTEAD OF | | | CC3. | | | 2) ON ENGINEERING SHEET #4, STANDARD AND VALET PARKING | | | SPACES SHOULD BE INDICATED AS 8'-6" WIDE INSTEAD OF | | | 9'-0" WIDE. | | | 3) PLEASE PROVIDE INFORMATION ON SCREENING OF ROOF-TOP | | | UNITS, PER SITE PLAN APPROVAL. EQUIPMENT SHOULD NOT BE | | | VISIBLE FROM THE STREET. | | | 4) PLEASE PROVIDE INFORMATION ON FLOOD LIGHTS (RE | | | FIXTURE ON E-505) FOR TOP LEVEL OF PARKING TO CONFIRM | | | FIXTURE TYPE WILL NOT BE CASTING SIGNIFICANT LIGHT OR | | | GLARE TO ADJACENT PROPERTIES. | | | 5) PLEASE INDICATE FOOTCANDLES LEVELS WITHIN PARKING | | | GARAGE AND TOP PARKING LEVEL. | | | 6) PLEASE CONFIRM DETAIL FOR "SCORE LINES" AND THAT | | | SCALE OF REVEAL IS SUFFICIENT TO BE VISIBLE AS A | | | ARCHITECTURAL ELEMENT IN THE BUILDING FACADE. | | | 7) BUILDING SECTIONS DO NOT PROVIDE ANY DETAIL AS TO | | | CONSTRUCTION OF CANOPY ELEMENTS. PLEASE ADD DETAILS, | | | INCLUDING MATERIALS FOR THESE ELEMENTS. | | | | | | | | | OTHER COMMENTS: | | | | | | * PROJECT IS SUBJECT TO APPROVALS AND CONDITIONS AS | | | PROVIDED IN THE SITE PLAN APPROVAL AND DAC APPROVAL. | | | | | | MATT FLIS - 822-1445 |
|
|