Plan Review Details - Permit 08010249
Plan Review Stops For Permit 08010249
Review Stop B BUILDING (STRUCTURAL)
Rev No 45 Status P Date 2009-04-22 Cont ID  
Sent By jwitmer Date 2009-04-22 Time 16:37 Rev Time 0.77
Received By jwitmer Date 2009-04-22 Time 16:36 Sent To PC
Notes
2009-04-22 16:37:55SUBMITTAL: PARAPET HANDRAIL AND INTERIOR LOBBY HANDRAIL

Review Stop B BUILDING (STRUCTURAL)
Rev No 44 Status P Date 2009-04-14 Cont ID  
Sent By jwitmer Date 2009-04-14 Time 15:29 Rev Time 0.77
Received By jwitmer Date 2009-04-14 Time 15:29 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 43 Status F Date 2009-03-16 Cont ID  
Sent By jwitmer Date 2009-03-16 Time 13:07 Rev Time 1.11
Received By jwitmer Date 2009-03-16 Time 13:07 Sent To PC
Notes
2009-03-16 13:26:20BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: ROOFTOP CAGES
  
 ACTION: DENIED
  
 1) THIS PROJECT IS A THRESHOLD BUILDING REQUIRING (3)
 ORIGINAL REPORTS TO BE SIGNED AND SEALED, NOT COPIES OF
 REPORTS.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 2) THE ENGINEERING REPORT REVISED 1-20-09 BY RAUL A.
 LESCANO P. E. DOES NOT SAY THAT HE IS THE P. E. WHO
 DESIGNED THIS SYSTEM BUT HE DID A SITE VISIT, IS MR.
 LESCANO THE DESIGNER OF THIS ENCLOSURE OR IS THIS A TO
 BE A PIER REVIEW OF SOMEONE ELSES WORK. IN EITHER CASE
 AGAIN THE INFORMATION IS COPIED AND NO ORIGINAL SIGNING
 AND SEALING OF DOCUMENTS FOR PUBLIC
 RECORD.61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED &
 SEALED BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER
 THE: NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER
 OR, THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 3) THE THIRD PROBLEM WITH THE DOCUMENTS SUBMITTED THE
 ENGINEER OF RECORD TOM BOGACKI COVER LETTER AGAAIN IS A
 PHOTOCOPY AND NONE OF THE THREE SUBMITTED ARE ORIGINALS
 WITH RAISED SEAL AND ORIGINAL SIGNATURES.
 61G15-23.002(2) FL. ADMIN. CODE. PLANS SIGNED & SEALED
 BY A PROFESSIONAL ENGINEER SHALL INCLUDE EITHER THE:
 NAME, ADDRESS AND LICENSE NUMBER OF THE ENGINEER OR,
 THE NAME AND LICENSE NUMBER OF THE ENGINEER AND THE
 NAME, ADDRESS AND CERTIFICATE OF AUTHORIZATION NUMBER
 OF THE ENGINEERING BUSINESS THROUGH WHICH THE ENGINEER
 IS PRACTICING (471.025 F.S. AND 471.023 F.S.).
  
 NOTE IF THE DOCUMENTS PROVIDED WERE ORIGINALS IN NATURE
 WITH RAISED SEAL AND SIGNATURES THEY WOULD OF PASSED
 THIS REVIEW.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 42 Status P Date 2009-01-23 Cont ID  
Sent By jwitmer Date 2009-01-23 Time 20:23 Rev Time 3.50
Received By jwitmer Date 2009-01-23 Time 20:23 Sent To  
Notes
2009-01-23 20:24:52BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISION# 7 REVIEW:
 ACTION: ARCHITECTURAL AND STRUCTURAL -OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 41 Status P Date 2008-12-12 Cont ID  
Sent By jwitmer Date 2008-12-12 Time 16:43 Rev Time 0.77
Received By jwitmer Date 2008-12-12 Time 16:43 Sent To PC
Notes
2008-12-12 16:44:56BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: WON DOOR SUBMITTAL# 081100-3
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 40 Status P Date 2008-12-12 Cont ID  
Sent By jwitmer Date 2008-12-12 Time 16:21 Rev Time 0.77
Received By jwitmer Date 2008-12-12 Time 16:21 Sent To PC
Notes
2008-12-12 16:40:25BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: FIRESTOPPING/ MEISNER ELECTRIC
 ACTION: REVIEWED/ SUBMITTAL 078400-3
  
 BUILDING PROVISO: THE DESIGNER OF RECORD SHALL
 REQUIREONE BRAND NAME MATERIAL, APPROVED FOR FIRE
 STOPPING PENETRATIONS, FOR WALLS, FLOOR CEILING
 ASSEMBLIES.
 WEST PALM BEACH THRESHOLD GUIDELINES COMMENT# 26.

Review Stop B BUILDING (STRUCTURAL)
Rev No 39 Status P Date 2008-12-11 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 14:14 Rev Time 0.77
Received By jwitmer Date 2008-12-11 Time 14:14 Sent To PC
Notes
2008-12-11 14:15:34BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:ACCURATE GLASS SHOP DRAWINGS
 ACTION: REVIEWED
  
 SUBMITTAL# 088000-12

Review Stop B BUILDING (STRUCTURAL)
Rev No 38 Status P Date 2008-12-11 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 14:13 Rev Time 0.77
Received By jwitmer Date 2008-12-11 Time 14:13 Sent To  
Notes
2008-12-11 14:14:08BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: WINDOW CALCULATIONS
 ACTION: REVIEWED
  
 SUBMITTAL# 088000-9

Review Stop B BUILDING (STRUCTURAL)
Rev No 37 Status P Date 2008-12-11 Cont ID  
Sent By jwitmer Date 2008-12-11 Time 14:11 Rev Time 0.77
Received By jwitmer Date 2008-12-11 Time 14:11 Sent To PC
Notes
2008-12-11 14:12:53BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SHOP DRAWING
 ACTION: REVIEWED
  
 SUBMITTAL# 088000-8-R1

Review Stop B BUILDING (STRUCTURAL)
Rev No 36 Status F Date 2008-11-24 Cont ID  
Sent By jwitmer Date 2008-11-24 Time 16:41 Rev Time 0.33
Received By jwitmer Date 2008-11-24 Time 16:41 Sent To PC
Notes
2008-11-24 16:47:03BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: ALUMINIUM SHOP DRAWINGS
 ACTION: DENIED
  
 1) SHOIP DRAWINGS ARE SIGNED AND SEALED WITH CUT AND
 PASTE SECTION ON VARIOUS SHEETS. W.P.B. ADMINISTRATIVE
 CODE 106.1.1
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 35 Status F Date 2008-11-24 Cont ID  
Sent By jwitmer Date 2008-11-24 Time 16:34 Rev Time 0.77
Received By jwitmer Date 2008-11-24 Time 16:34 Sent To B
Notes
2008-11-24 16:38:55BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL# 081100-3.
 ACTION: DENIED
  
 STRUCTURAL SHEETS FROM O'DONNELL, NACCARATO, MIGNOGNA &
 JACKSON, INC. ARE TO BE SIGNED AND SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)805-6731
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 34 Status P Date 2008-11-17 Cont ID  
Sent By jwitmer Date 2008-11-17 Time 15:30 Rev Time 7.50
Received By jwitmer Date 2008-11-17 Time 15:30 Sent To  
Notes
2008-11-17 15:32:05REVISION# 5 PROVISO: CALLED RODOLFO MISSING SHEET
 A-101A IN CITY SET OF REVISIONS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 33 Status F Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 16:26 Rev Time 0.22
Received By jwitmer Date 2008-11-07 Time 16:26 Sent To PC
Notes
2008-11-07 16:31:43BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: VENEER WALL YKK YCW 750
 ACTION: DENIED
  
 1609.6.2.2 COMPONENTS AND CLADDING THIS JOB IS
 CONSIDERED A THRESHOLD BUILDING AND WILL REQUIRE (3)
 SETS OF SHOP DRAWING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 32 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 16:23 Rev Time 0.77
Received By jwitmer Date 2008-11-07 Time 16:22 Sent To  
Notes
2008-11-07 16:25:59BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL 042200-3
 ACTION: REVIEWED
  
 SHAFT WALL IN STAIRWELLS SUBSTITUTION REQUEST FORM TO
 AERCON UL DESIGN # U920
 BUILDING PROVISO: PLANS ARE TO BE UPDATED TO REFLECT
 THE NEW WALL TYPE FOR STAIRWELL.

Review Stop B BUILDING (STRUCTURAL)
Rev No 31 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 14:32 Rev Time 0.77
Received By jwitmer Date 2008-11-07 Time 14:32 Sent To  
Notes
2008-11-07 14:34:05BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:SUBMITTAL# 089100-5
 ACTION:REVIEWED
  
 LOUVER NOA 07-1015.06

Review Stop B BUILDING (STRUCTURAL)
Rev No 30 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 14:22 Rev Time 0.77
Received By jwitmer Date 2008-11-07 Time 14:22 Sent To PC
Notes
2008-11-07 14:23:47BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL# 055100-5
 ACTION : REVIEWED
  
 STEEL STAIR SHOP DRAWINGS

Review Stop B BUILDING (STRUCTURAL)
Rev No 29 Status P Date 2008-11-07 Cont ID  
Sent By jwitmer Date 2008-11-07 Time 14:20 Rev Time 0.77
Received By jwitmer Date 2008-11-07 Time 14:20 Sent To PC
Notes
2008-11-07 14:22:21BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL 055100-1
 ACTION: REVIEWED
 STEEL STAIR CALCULATIONS
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 28 Status F Date 2008-10-23 Cont ID  
Sent By jwitmer Date 2008-10-23 Time 10:26 Rev Time 0.77
Received By jwitmer Date 2008-10-23 Time 10:26 Sent To PC
Notes
2008-10-23 10:48:52BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: EXTERIOR METAL STUD FRAMING
 SUBMITTAL# 092214-7
 ACTION: DENIED
  
 THE ENGINEER OF RECORD IS TO AFFIX A SHOP DRAWING STAMP
 OR A ORIGINAL COVER PAGE WITH INDEX OF ENGINEERING
 UNDER THIER REVIEW,
 NOTE THERE IS NO IDENTIFICATION AS TO THE ADDRESS NOR
 THE PERMIT NUMBER ON THE DOCUMENT LINKING THE DOCUMENT
 TO THE SHOP DRAWINGS.
 61G15-23.002/ 61G15-30.006
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 27 Status F Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 11:32 Rev Time 0.77
Received By jwitmer Date 2008-10-17 Time 11:32 Sent To PC
Notes
2008-10-17 11:44:37BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL# 092116-04 REV#1
 ACTION: DENIED
  
 1) THIS CONSTITUTES A REVISION AND SHOULD PAY REVISION
 FEES
 2) PLEASE IDENTIFY WALL TYPES THAT THE INSULATION IS
 CHANGING, PROVIDE PLANS INDICATING THE REVISION AND
 WALL TYPES, NOTE THE CHANGE WILL NEED TO ALSO REFLECT
 IN THE ENEERGY CALCULATIONS
 THE EXTERIOR WALLS ;
 TYPE 1C: INDICATE A 2 INCH INSULATION AND A R VALUE
 (H.SF.F/BTU OF 9.1
 TYPE 1C- DETAIL 9/512 ALSO INDICATES A 2 INCH
 INSULATION AND A R VALUE (H.SF.F/BTU) OF 10.6
  
 PLEASE SUBMIT NEW ENERGY CALS WITH THE DECREASED VALUES
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 26 Status F Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 11:15 Rev Time 0.77
Received By jwitmer Date 2008-10-17 Time 11:15 Sent To PC
Notes
2008-10-17 11:19:00BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: SUBMITTAL 089100.5
 ACTION: DENIED
  
 106.1.2 ADDITIONAL INFORMATION REQUIRED, 1609.6.2.2.
 ONLY A PRODUCT APPROVAL WAS SUBMITTED, NO INFORMATION
 AS TO THE LOCATION, SIZE NOR PRESSURES TO BE IMPOSED ON
 THIS PRODUCT.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 25 Status P Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 11:10 Rev Time 0.00
Received By jwitmer Date 2008-10-17 Time 11:10 Sent To PC
Notes
2008-10-17 11:12:06BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:SUBMITTAL: 055000-8
 ACTION: REVIEWED
  
 STEEL BOLLARD & BASE PLATE

Review Stop B BUILDING (STRUCTURAL)
Rev No 24 Status F Date 2008-10-17 Cont ID  
Sent By jwitmer Date 2008-10-17 Time 11:05 Rev Time 0.55
Received By jwitmer Date 2008-10-17 Time 11:05 Sent To PC
Notes
2008-10-17 11:08:20BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW:SUBMITTAL 05000-8
 ACTION: DENIED.
 THE ATTACHED PLANS INDICATING THE LOCATION OF THE
 BOLLARD ARE COPIES OF ORIGINAL PLANS, THESE PLANS ARE
 NOT SIGNED NOR SEALED.
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
 FL ADMIN CODE 61G16.003 ARCHITECTS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 23 Status F Date 2008-09-23 Cont ID  
Sent By jwitmer Date 2008-09-23 Time 15:58 Rev Time 7.55
Received By jwitmer Date 2008-09-23 Time 15:58 Sent To PC
Notes
2008-09-23 16:45:31BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 WINDOW SHOP DRAWING REVIEW:
 ACTION: DENIED
  
 1) SHEET 9 OF 12
 A) W2- NOTE DETAIL4/10 INDICATES NO ANCHORS REQUIREDAT
 CONTINIOUS JAMB WHERE AS DETAIL INDICATES ANCHOR
 SPACING ON SIDE JAMBS. DISCREPANCY 106.1.2 ADDITIONAL
 INFORMATION 1609..6
  
 B) W-2 ALSO INDICATS THAT THE JAMBS & MULLION ARE NOT
 REINFORCED, THE TRIBUTARY AREA FOR THE HORIZONTAL
 MULLION IS ROUGHLY 46.5"X72" SHEET 3 OF 7 MULLIONS W/O
 REINFORCEMENT INDICATE A -80.0 WHERE AS
 THE WINDOW INDICATES A NEGATIVE 89.
  
 C) W-2A IS THE SAME SIZE WINDOW WITH THE SAME SITUATION
 AS THE W-2 WINDOW.
  
 D) W-3A NO DESIGNATION AS TO MUTTINS.
  
 E) W-3A THE JAMB AND MULLION DETAIL INDICATES
 NON-REINFORCED WITH LOW PRESSURES FROM NOA SHEET 3 OF
 7.UN-REINFORCED JAMBS AND MULLIONS ARE GOOD TO 80 PSF
 THIS WINDOW IS INDICATED AS A -89.LOW PRESSURE
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 22 Status P Date 2008-09-18 Cont ID  
Sent By jwitmer Date 2008-09-18 Time 15:15 Rev Time 0.55
Received By jwitmer Date 2008-09-18 Time 15:15 Sent To PC
Notes
2008-09-18 15:16:51BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW: # 05-5000-15 SEPERATOR BEAM LOCATED
 WITHIN THE ELEVATOR SHAFT
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 21 Status N Date 2008-09-18 Cont ID  
Sent By jwitmer Date 2008-09-18 Time 13:58 Rev Time 0.22
Received By jwitmer Date 2008-09-18 Time 13:58 Sent To PC
Notes
2008-09-18 14:01:34BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: ELEVATOR SUBMITTALS
 ACTION: NONE ELEVATOR AND ASSOCIATED EQUIPMENT ARE
 REVIEWED BY BUREAU OF ELEVATOR SAFETY OF THE DEPARTMENT
 OF BUSSINESS AND PROFESSIONAL REGULATION SCOOPE 3001.1
 NOTE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 20 Status P Date 2008-09-18 Cont ID  
Sent By jwitmer Date 2008-09-18 Time 13:05 Rev Time 0.55
Received By jwitmer Date 2008-09-18 Time 13:05 Sent To PC
Notes
2008-09-18 13:40:18BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW:
 #093000-21 ULTRAFLEX 1 STANDARD POLYMER-ENRICHED TILE
 MORTER
 00-3000-5 PRECAST 4X4 CONCRETE SHOWER SILL
 ACTION: REVIEWED
  
 BUILDING PROVISO: THIS REVIEW IS FOR THE USE OF
 ULTRAFLEX 1 TO BE USED ON THE INSTALATIOJN OF THE
 PRECAST 4X4 INCH CONCRETE SHOWER SILL ONLY. THE
 CONTRACTOR HAS NOT PROVIDED WHAT TYPE OF MATERIALS WILL
 BE SUBMITTED FOR SOUND DEADENING. THE SUBFLOOR FOR THIS
 PRODUCT IS VERY LIMITED AS TO THE PRODUCT MUST COMPLY
 WITH 1207.3 STRUCTURAL-BORNE SOUND .
 1207.3 STRUCTURE-BORNE SOUND. FLOOR/CEILING ASSEMBLIES
 BETWEEN DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A
 PUBLIC OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE
 AN IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS
 THAN 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE
 WITH ASTM E 492.

Review Stop B BUILDING (STRUCTURAL)
Rev No 19 Status P Date 2008-09-18 Cont ID  
Sent By jwitmer Date 2008-09-18 Time 11:36 Rev Time 0.55
Received By jwitmer Date 2008-09-18 Time 11:35 Sent To PC
Notes
2008-09-18 11:39:41BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL # 055000-11 REVIEW: ELEVATOR HOIST BEAM
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 18 Status P Date 2008-09-18 Cont ID  
Sent By jwitmer Date 2008-09-18 Time 11:08 Rev Time 0.55
Received By jwitmer Date 2008-09-18 Time 11:08 Sent To PC
Notes
2008-09-18 11:14:51BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW # 078400-2
 ACTION: REVIEWED : TREMSTOPIA, SYSTEM # W-L-2420
  
 BUILDING PROVISO:
 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES FOR
 THRESHOLD INSPECTORS #26.
 ASSURE THAT THE DESIGNER HAS REQUIRED ON THE PLANS OR
 SPECIFICATIONS ONE MATERIAL,
 APPROVED FOR FIRE STOPPING PENETRATIONS, FOR WALLS AND
 CEILINGS.

Review Stop B BUILDING (STRUCTURAL)
Rev No 17 Status P Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 14:10 Rev Time 0.33
Received By jwitmer Date 2008-09-09 Time 14:10 Sent To PC
Notes
2008-09-09 14:11:383'-6" CORNER GAURDS- OK

Review Stop B BUILDING (STRUCTURAL)
Rev No 16 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 13:24 Rev Time 3.33
Received By jwitmer Date 2008-09-09 Time 13:24 Sent To PC
Notes
2008-09-09 13:44:12BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOGACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 SHOP DRAWING: STEEL RACKS @ ROOF
  
 1) PLEASE PROVIDE ADDITIONAL INFORMATION ON WHAT THIS
 SUBMITTAL IS TO BE USED FOR, IT APPEARS TO BE A
 SCREENING ENCLOSURE TO HIDE THE RTU ON THE TOP OF THE
 ROOF. IN DOING SO THIS WILL NEED TO UPDATE
 SHEETS A-105-A AND A105-B AS TO THIS WOULD BE A
 REVISION TO BE REVIEWED BY ZONING AND BUILDING.
  
 2) THE SECOND ISSUE IS THIS DETAIL INDICATES CHAIN-LINK
 BRACKETS BY OTHERS, BUT AGAIN IF FENCING IS TO BE
 APPLIED AS A SCREENING TYPE MATERIAL, IT WOULD ALSO
 NEED THE BLINDS INSERTED INTO EACH ROW CREATING A
 NON-VIEWABLE FENCING THAT WOULD NOT ALLOW WIND TO
 TRAVEL THROUGH, AND THERE IS NO INDICATION THAT THE
 ENGINEER OF RECORD THIS REVISION SINCE THE STRUCTURAL
 PLANS S106-A & S-106B ONLY INDICATE EMBEDS IN THE ROOF
 SLAB AND THE ACTUAL RTU STANDS WILL BE SUPPLIED LATTER
 AND REVIEWED AT THAT TIME.
  
 3) THE SHOP DRAWING STAMP IS NOT EVEN ON THIS DOCUMENT
 BUT A COPY ATTACHED TO ANOTHER PAGE. FL 61G-15-30.006
 (3) THE DELEGATED ENGINEER SHALL FORWARD THE DELEGATED
 ENGINEERING DOCUMENTS TO THE ENGINEER OF RECORD FOR
 REVIEW.
  
 4) SINCE THIS IS DOES NOT SHOW UP ON ANY
 ARCHITECTURALNOR STRUCTURAL SHEETS WHAT ARE THE WIND
 CRITERIA THIS AREA IS DESIGNED TOO?
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 5) IN REVIEWING THIS DOCUMENT WITH THE MECHANICAL PLAN
 REVIEWER, IT WOULD APPEAR THIS STRUCTURE WOULD BE MORE
 THAN A MERE FENCE ENCLOSURE THAT IS TO HIDE THE RTU
 UNITS, BUT IN ACTUALLITY THIS MAY BE A STRUCTURE TO
 HOLD THE ACTUAL CLADDING OR PORTIONS OF CLADDING OF THE
 ROOF TOP UNITS THAT MAY BLOW OF IN A HIGH WIND EVENT.
 JUNE 27/08 MECHANICAL PROVISO # 1 INDICATED THE NEED TO
 ILLUSTRATE COMPLIANCE WITH 301.13 FBCM AND ALTERNATE
 MEANS AND METHODS MAY BE ONE VEHICLE TO BE USED IF
 ENGINEERING OF THESE UNITS WAS NOT SUBMITTED AND
 REVIEWED AS CODE COMPLIANT. IN DOING SO ANY DOCUMENTS
 TO BE SUBMITTED AS ALTERNATE MEANS AND METHODS WILL
 NEED TO BE SUBMITTED IN WRITING WITH CALCULATIONS AND
 TO BE REVIEWED BY THE BUILDING OFFICAL. THE SAME ISSUES
 WILL OCCUR IF THIS STRUCTURE IS TO RESTRICT PORTIONS OF
 THE RTU CLADDING WIND WILL NOT BE ABLE TO TRAVEL
 THRUOGH, PROVIDE CALCULATIONS INDICATING COMPLIANCE
 WITH 301.13 FBCM.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 15 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 13:09 Rev Time 0.77
Received By jwitmer Date 2008-09-09 Time 13:09 Sent To B
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 14 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 12:15 Rev Time 0.67
Received By jwitmer Date 2008-09-09 Time 12:15 Sent To PC
Notes
2008-09-09 12:17:30BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 STEEL RACK @ ROOF

Review Stop B BUILDING (STRUCTURAL)
Rev No 13 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 12:02 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 12:02 Sent To PC
Notes
2008-09-09 12:06:49BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 STEEL STAIR SHOP DRAWING & LETTER:
 WITHIN THE LETTER FROM ONM& J IT STATES THAT" THE SHOP
 DRAWINGS WERE SIGNED AND SEALED BY THE ENGINEER
 RESPONSIBLE FOR THE STEELSTAIR SHOP DRAWINGS".
  
 PLANS, SPECIFICATIONS, REPORTS OR OTHER DOCUMENTS
 PREPARED BY THE DESIGN PROFESSIONAL AND BEING FILED FOR
 PUBLIC RECORD SHALL HAVE THE SIGNATURE AND SEAL OF THE
 DESIGN PROFESSIONAL AFFIXED TO THE DOCUMENT.
 FL ADMIN CODE 61G15-23.002 ENGINEERS
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 12 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 11:43 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 11:43 Sent To PC
Notes
2008-09-09 12:00:42BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 STRUCTURAL STEEL STAIR CALCULATIONS: 61G15-23.002(2)
 FL. ADMIN. CODE. A COVER SHEET OR INDEX SHEET FOR
 ENGINEERING SPECIFICATIONS MAY BE USED AND THAT SHEET
 MUST BE SIGNED IN RESPONSIBLE CHARGE OF THE PRODUCTION
 & PREPARATION OF EACH SECTION OF THE ENGINEERING
 SPECIFICATION WITH SUFFICIENT INFORMATION ON THE COVER
 SHEET OR INDEX.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 11 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 11:39 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 11:39 Sent To PC
Notes
2008-09-09 11:41:43BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 DECO-FIN PLEASE PROVIDE THE WIND CRITERIA THAT THIS
 STRUCTURAL STEEL ELEMENT WAS DESIGNED TOO.
 1603.1.4 WIND DESIGN DATA.
 THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL
 BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE
 DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE
 BUILDING:
 1. BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
  
 2. WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
  
 3. WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
  
 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5. COMPONENTS AND CLADDING. THE DESIGN WIND PRESSURES
 IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE SELECTION
 OF EXTERIOR COMPONENTS AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 10 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 11:20 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 11:20 Sent To B
Notes
2008-09-09 11:36:51BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 LOUVERS & MULLIONS:
  
 1) RULE 9B-72 REQUIRES PRODUCT APPROVALS THAT ARE
 LISTED WITH EITHER THE FLORIDA STATE WEBSITE OR ANOTHER
 APPROVED AGENCY SUCH AS UL OR MIAMI-DADE WITH THIRD
 PARTY QUALITY ASSURANCE PROGRAM IN EFFECTTHAT IS
 REGISTERED WITH THE STATE.
  
 2) 1609.1.4(5) LOUVERS. LOUVERS PROTECTING INTAKE AND
 EXHAUST VENTILATION DUCTS NOT ASSUMED TO BE OPEN THAT
 ARE LOCATED WITHIN 30 FEET (9144 MM) OF GRADE SHALL
 MEET REQUIREMENTS OF THE LARGE MISSILE TEST.
 IMPACT-RESISTANT COVERINGS SHALL BE TESTED AT 1.5 TIMES
 THE DESIGN PRESSURE (POSITIVE OR NEGATIVE) EXPRESSED IN
 POUNDS PER SQUARE FEET AS DETERMINED BY THE FLORIDA
 BUILDING CODE, BUILDING SECTION 1609 FOR WHICH THE
 SPECIMEN IS TO BE TESTED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 9 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 11:13 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 11:13 Sent To PC
Notes
2008-09-09 11:18:43BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 1) PLEASE PROVIDE THE LOCATION THIS SEPERATOR BEAM WILL
 BE INSTALLED WITHIN THE BUILDING. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 2) THE LEFT HAND DETAIL INDICATES (2) - 5/8" EXPANSION
 ANCHORS WHILE THE PLAN INDICATES FOUR? 106.1.2.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 11:04 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 11:04 Sent To PC
Notes
2008-09-09 11:07:39BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 1) EMBEDS- SHOP DRAWING DOES NOT PROVIDE THE LOCATION
 THIS EMBED WILL BE INSTALLED, NOR THE TYPE OF MATERIAL
 IT WILL BE CONSTRUCTED FROM NOR THE WELD SIZES FROM THE
 NELSON STUD TO PLATE MATERIAL.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 10:59 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 10:59 Sent To PC
Notes
2008-09-09 11:01:31BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEW
 ACTION: DENIED
  
 STEEL BOLLARD : PLEASE PROVIDE LOCATION THIS BOLLARD
 WILL BE INSTALLED. 106.1.2 ADDITIONAL INFORMATION
 REQUIRED.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-09-09 Cont ID  
Sent By jwitmer Date 2008-09-09 Time 10:50 Rev Time 0.55
Received By jwitmer Date 2008-09-09 Time 10:50 Sent To PC
Notes
2008-09-09 10:58:02BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 SUBMITTAL REVIEWS
 ACTION: DENIED
  
 1) SUBMITTALS BROUGHT IN SHOULD BE BROKE OUT TO THE
 CORRECT TRADES, NOT BUNCHED TOGETHER :
 A) DUMPSTER GATE WILL BE REVIEWED BY ENGINEERING NOT
 BUILDING
  
 B) BIKE RACK IS ZONING.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-08-29 Cont ID  
Sent By jwitmer Date 2008-08-29 Time 13:54 Rev Time 0.77
Received By jwitmer Date 2008-08-29 Time 13:54 Sent To PC
Notes
2008-08-29 13:56:39BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW SUBMITTAL #233713 -4 REVISION# 1 ELEVATOR LOUVER
 ACTION: REVIEWED

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-21 Cont ID  
Sent By lmartine Date 2008-07-21 Time 14:06 Rev Time 0.00
Received By lmartine Date 2008-07-21 Time 14:06 Sent To  
Notes
2008-07-21 14:41:23THE PREVIOUS COMMENT WAS PROCESSED IN ERROR, PLEASE
 DISREGUARD,L.MARTINEZ#6710
2008-07-21 14:07:44ANCHORING DETAILS AT ROOF TOP UNITS REVISIONOK
 LM

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By jwitmer Date 2008-06-25 Time 16:40 Rev Time 5.55
Received By jwitmer Date 2008-06-25 Time 16:40 Sent To  
Notes
2008-06-25 16:40:08BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 ARCH: PFVS/ GREGORY R PORTMAN
 TEL: (404)503- 5000
  
 STRUC: OMNJ/ THOMAS M BOG ACKI
 TEL: (561)835-9994
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: REVIEWED
  
 1) BUILDING PROVISO: EXTERIOR LIGHT GAUGE METAL FRAMING
 TO BE SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED
 AND APPROVED BY THE DESIGNER OF RECORD , STAMPED
 APPROVED.
  
 2) COMPACTOR SCISSOR LIFT SUBMIT SHOP DRAWINGS AND
 MANUFACTURER'S SPECIFICATION WITHIN 90 DAYS OF PERMIT
 ISSUANCE.
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-24 Cont ID  
Sent By rbrown Date 2008-05-24 Time 12:12 Rev Time 0.00
Received By rbrown Date 2008-05-24 Time 12:12 Sent To  
Notes
2008-05-24 12:16:32BUILDING PLAN REVIEW
 *******DENIED*******
 ROBERT BROWN(561) 805 6652
 E-MAIL: [email protected]
  
 FBC = FLORIDA BUILDING CODE 2004 AS AMENDED/REVISED
 FBC*= FLORIDA BUILD'G CODE (CITY AMEND)
 F.S.= FLORIDA (STATE) STATUTE
  
 FOR CONSISTENCY, THE FOLLOWING COMMENTS ARE NUMBERED AS
 PER THE BUILDING PLAN REVIEW OF 2/25/08:
  
 3B)FBC 715.3SHEET A-611,FIRE-RATED DOORS ON THE
 EXIT ACCESS CORRIDOR SERVING THE CONFERENCE ROOM(S).
 DOORS 127 AND 153 ARE NOT SHOWN AS FIRE-RATED ON DOOR
 SCHEDULE SHEET A-611.REVISE THE DOOR SCHEDULE.
  
 3C)FBC 715.3SHEET A-101A AND SHEET A-611,
 FIRE-RATED DOORS REQUIRED IN OCCUPANCY SEPARATION WALL
 BETWEEN PARKING GARAGE AND LOBBY.DOOR 131 IS NOT
 SHOWN AS FIRE-RATED ON DOOR SCHEDULE SHEET A-611.
 REVISE THE DOOR SCHEDULE.
  
 3E)FBC 302.3.2SHEET A-102B (AND CORRESPONDING LIFE
 SAFETY SHEET G-007) AND SHEET A-103B.ON SHEET A-102B
 (AND CORRESPONDING LIFE SAFETY SHEET G-007), THE
 MEZZANINE LEVEL WALL ON GRID 2 BETWEEN GRIDS A AND B.4
 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR FIRE-RATED
 OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE PARKING
 GARAGE AND EMERGENCY ELECTRICAL ROOM.AMEND SHEET
 A-102B.ALSO, ON SHEET A-103B, THE SECOND FLOOR LEVEL
 WALL BETWEEN THE PARKING GARAGE AND THE GUEST LAUNDRY
 NEAR GRID B/1.2 IS SHOWN AS 1 HOUR FIRE-RATED.2 HOUR
 FIRE-RATED OCCUPANCY SEPARATION IS REQUIRED BETWEEN THE
 PARKING GARAGE AND THE VESTIBULE AND ELECTRICAL ROOM.
 AMEND SHEET A-103B.
  
 3M) FBC 1012.1SHEET A-702, STAIR #2 - ROOF LEVEL
 PLAN.STAIR ACCESS TO THE ROOF HAS BEEN PROVIDED BUT
 THE GUARDRAIL DOES NOT CONTINUE TO THE SOUTH WALL.THE
 LANDING SHALL HAVE GUARDING AGAINST FALLING.AMEND
 SHEET A-702.
  
 4I) FBC* 106.1.2SHEET AC-102.COMPACTOR SCISSOR
 LIFT.SUBMIT SHOP DRAWINGS AND MANUFACTURER'S
 SPECIFICATION WITHIN 90 DAYS OF PERMIT ISSUANCE.
  
 5B) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN
 PARKING GARAGE OCCUPANCY SEPARATION WALL.DOORS M004,
 M005A, M013 ARE SHOWN AS 45 MINUTE OR 20 MINUTE
 FIRE-RATED ON DOOR SCHEDULE SHEET A-611.THESE DOORS
 SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.REVISE THE
 DOOR SCHEDULE.ALSO, DOOR M005B IS SHOWN AS NON-RATED.
 IT IS AN ELEVATOR LOBBY DOOR AND SHALL BE A MINIMUM OF
 20 MINUTE FIRE-RATED.REVISE THE DOOR SCHEDULE.
  
 6B) FBC 707.2SHEET A-102B.CHASES AND PARTITION
 WALLS ABOVE ROOMS 104-108.CONTRARY TO THE COMMENT
 RESPONSE LETTER, WALL TYPE TAGS HAVE NOT BEEN ADDED TO
 THE CHASES CALLING THEM OUT AS 2 HOUR FIRE-RATED
 CHASES.ALSO, THE WALL TYPE TAGS ON THE PARTITIONS
 SEPARATING THE ROOMS ON SHEET A-102B WOULD CLARIFY THE
 INTENTION AT THIS LEVEL.
  
 8D) FBC 707.4SHEET A-103A, DOOR 245 TO THE LINEN
 SHAFT TERMINATION ROOM IS SHOWN ON DOOR SCHEDULE SHEET
 A611 AS 45 MINUTE FIRE-RATED.THE DOOR SHALL BE A
 MINIMUM OF 90 MINUTE FIRE-RATED.ALSO, THE WALL
 BETWEEN THE TERMINATION ROOM AND THE VENDING/ICE ROOM
 DOES NOT HAVE A WALL TYPE TAG TO SHOW THE REQUIRED
 FIRE-RATING.AMEND SHEET A-103A.
  
 9A) FBC 715.3SHEET A-611,FIRE-RATED DOORS IN
 PARKING GARAGE OCCUPANCY SEPARATION WALL.DOOR 237 IS
 20 MINUTE FIRE-RATED ON DOOR SCHEDULE SHEET A-611.
 THIS DOOR SHALL BE A MINIMUM OF 90 MINUTE FIRE-RATED.
 REVISE THE DOOR SCHEDULE.
  
 11C) FBC 707.2SHEET A-104B.CHASES IN THE ELECTRICAL
 ROOM 302/402/502 AND IN THE PARTITIONS BETWEEN HOTEL
 ROOMS.CONTRARY TO THE COMMENT RESPONSE LETTER, WALL
 TYPE TAGS HAVE NOT BEEN ADDED TO THE CHASE IN THE
 ELECTRICAL ROOM.ALSO, THERE ARE NO WALL TYPE TAGS ON
 THE CHASES IN THE PARTITION WALLS SEPARATING HOTEL
 ROOMS.
  
 20) PROVISO:EXTERIOR LIGHT GAUGE METAL FRAMING TO BE
 SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE
 DESIGNER OF RECORD, APPROVED AND STAMPED.
  
 21) PROVISO:FIN WALL SHOWN ON SHEET A-511, DETAIL 9.
 THE STEEL FRAME AND "CURTAIN WALL" FOR THIS DECORATIVE
 ELEMENT OF THE BUILDING SHALL BE SUBMITTED AS SHOP
 DRAWINGS AFTER BEING REVIEWED BY THE DESIGNER OF
 RECORD, APPROVED AND STAMPED.
  
 22D) MULLION PRODUCT APPROVAL.IT IS NOTED THAT THE
 MULLION LENGTHS HAVE BEEN IDENTIFIED BY HIGHLIGHTER PEN
 ON THE PRODUCT APPROVAL.PLEASE NOTE THAT WE REQUIRE
 THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS, ETC. IN
 INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP WHEN THE
 DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF THE
 PROJECT UNDER THE MANDATORY RECORD RETENTION PROGRAM.
 THIS APPLIES TO ALL IDENTIFICATION MARKING ON ALL
 PRODUCT APPROVALS AND OTHER DOCUMENTS.
  
 22I)PRE-ENGINEERED A/C EQUIPMENT STANDS.NO PRODUCT
 APPROVAL OR COMMENT RESPONSE WAS SUBMITTED TO ADDRESS
 THE COMMENT REQUIRING SUBMITTAL OF PRODUCT APPROVAL
 DOCUMENTATION FOR PRE-ENGINEERED A/C EQUIPMENT STANDS.
  
 22J) CARLISLE ROOFING PRODUCT APPROVAL.IT IS NOTED
 THAT THE ROOFING PRODUCT APPROVAL DOCUMENTS HAVE BEEN
 MARKED UP WITH HIGHLIGHTER PEN.PLEASE NOTE THAT WE
 REQUIRE THAT SUCH IDENTIFICATION BE BY CIRCLES, ARROWS,
 ETC. IN INK AS THE HIGHLIGHTER PEN WILL NOT SHOW UP
 WHEN THE DOCUMENTS ARE DIGITALLY SCANNED AT THE END OF
 THE PROJECT UNDER THE MANDATORY RECORD RETENTION
 PROGRAM.THIS APPLIES TO ALL IDENTIFICATION MARKINGS
 ON ALL PRODUCT APPROVALS AND OTHER DOCUMENTS.
  
 30A)FBC 903.2.7FIRE SPRINKLERS.CONTRARY TO THE
 COMMENT RESPONSE LETTER, THE REVISED FIRE PROTECTION
 PLANS DO NOT SHOW FIRE SPRINKLER COVERAGE IN THE
 ELEVATOR SHAFT ABOVE THE SECOND FLOOR LEVEL.SEE
 FP-204A AND FP-205A (BOTH REVISION B, SIGNED AND SEALED
 ON 4/15/08).
  
 30B)THERE IS STILL NO SHEET FP-205B.IF THIS IS
 INTENTIONAL, IT WOULD BE MORE CLEAR IF SHEET FP-205A
 HAD A NOTE TO THAT EFFECT RATHER THAN A "MATCHLINE".
  
  
 **QUOTE PERMIT# ON ALL CORRESPONDENCE**
  
 END OF REVIEW COMMENTS
 THE CODE REFERENCES GIVE ADDITIONAL INFO TELEPHONE:
 (561) 805 6652ROBERT BROWN
 E-MAIL: [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-02-25 Cont ID  
Sent By jwitmer Date 2008-02-25 Time 12:22 Rev Time 8.88
Received By jwitmer Date 2008-02-25 Time 12:22 Sent To  
Notes
2008-02-25 12:23:54BUILDING PLAN REVIEW
 PERMIT: 08010249
 ADD: 295 LAKEVIEW AVE.
 CONT: KAST CONSTRUCTION
 TEL: (561)718-6141
 E-MAIL: [email protected]
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL. PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL.106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D) INFORMATIONAL. PLANS SUBMITTED FOR PERMIT (FIRST
 TIME REVIEW) AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO
 THE 2004 FBC BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2) W P B ADMINISTRATIVE CODE 108.2 SCHEDULE OF PERMIT
 FEES. ON BUILDINGS, STRUCTURES, ELECTRICAL, GAS,
 MECHANICAL, AND PLUMBING SYSTEMS OR ALTERATIONS
 REQUIRING A PERMIT, A FEE FOR EACH PERMIT SHALL BE PAID
 AS REQUIRED, IN ACCORDANCE WITH THE SCHEDULE
 ESTABLISHED BY THE APPLICABLE GOVERNING AUTHORITY.
  
 108.3*BUILDING PERMIT VALUATION.
 IF, IN THE OPINION OF THE BUILDING OFFICIAL, THE
 CLAIMED VALUATION OF BUILDING, ALTERATION, STRUCTURE,
 ELECTRICAL, GAS, MECHANICAL, OR PLUMBING SYSTEMS
 APPEARS TO BE UNDER ESTIMATED ON THE APPLICATION, THE
 PERMIT SHALL BE DENIED.FOR PERMITTINGPURPOSES,
 VALUATION OF BUILDINGS AND SYSTEMS SHALL BE TOTAL
 REPLACEMENT PURPOSES, VALUATION OF BUILDINGS AND
 SYSTEMS SHALL BE THE TOTAL REPLACEMENT VALUE TO INCLUDE
 STRUCTURAL, ELECTRICAL, PLUMBING, MECHANICAL, INTERIOR
 FINISHES, NORMAL SITE WORK (EXCAVATION AND BACKFILL FOR
 BUILDINGS), ARCHITECTURAL AND DESIGN FEES, MARKETING
 COST, OVERHEAD AND PROFIT; EXCLUDING ONLY LAND VALUE.
 VALUATION REFERENCES MAY INCLUDE THE LATEST PUBLISHED
 DATA OF NATIONAL CONSTRUCTION COST ANALYSIS SERVICES
 (MARSHALL-SWIFT, MEANS, ETC) WITH REGIONAL ADJUSTMENTS
 FOR LOCATION AS PUBLISHED BY THE INTERNATIONAL CODE
 CONGRESS.
  
 ICC TOTAL VALUATION FOR PROJECT IS $18,616,066.00
  
 MINUS VIBRO-FLOTATION& STRUCTURAL-3,941,840.00
 VALUATION FOR THIS PERMIT $
 14,674,226.00
  
 FEES DUE THIS PERMIT
 $163,439.36
 PAID TO DATE
 $45,493.17
 FEE BALANCE
 $117,946.19
 SEE FEE BALANCE SHEET ATTACHMENT.
  
 3) SHEET A-101A:
 3A) WHEN THE CONFERENCE ROOMS 110, 111 & 117 ARE OPENED
 INTO ONE LARGE CONFERENCE ROOM THE OCCUPANT LOAD WOULD
 BE 68 REQUIRING 2 EXITS. WHEN AN ASSEMBLY OCCUPANCY IS
 OVER 30 OCCUPANTS THE EXIT ACCESS CORRIDORS ARE
 REQUIRED TO BE FIRE RATED 1 HOUR EVEN WITH FIRE
 SPRINKLERS PLEASE SEE TABLE 1016.1.
  
 3B) THE OTHER CONCERN IS WITH THE RATING OF THE
 CORRIDOR, PLEASE REVIEW 1016.5 CONTINUITY OF CORRIDORS
 AND THE FIRE RATING INTO THE LOBBY AND RECEPTION AREAS.
 THIS WILL ALSO EFFECT THE DOOR RATINGS IN TABLE 715.3,
 PROTECTION OF OPENINGS.
  
 3C) THE FIRST FLOORDOORS CAN NOT BE CHECKED IN THE
 DOOR SCHEDULE SHEET A-611, THE NUMBERING SEQUENCE IS SO
 FAR OVER INTO THE LEFT MARGIN OF THE SHEET THAT THE
 NUMBERING SEQUENCE COLUMN IS BOUND BY THE STAPLES,
 PLEASE REPRINT THIS SHEET AND ALLOW FOR BINDING OF
 PLANS TOGETHER. 106.1.1 INFORMATION ON CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF WORK PROPOSED AND
 SHOW IN DETAIL THAT IT CONFORMS TO THE PROVISIONS OF
 THIS CODE.
  
 3D) THE EXTERIOR NORTH WALL OF THE BUILDING INDICATES
 WALL TAGS OF 1 HOUR RATING, PLEASE REVIEW TABLE 602 , <
 5?-0? REQUIRES A 3 HR RATED WALL FOR THESE
 OCCUPANCIES:
 ASSEMBLY, BUSINESS OR RESIDENCE. PLEASE CORRECT PLAN.
  
 3E) ADDITIONAL INFORMATION REQUIRED, 106.1.2. OCCUPANCY
 SEPARATION, WALL TAGS ARE MISSING ON THE COMMON PARKING
 GARAGE AND THE OTHER OCCUPANCIES, PLEASE SEE
 TABLE302.3.2.
  
 3F) PLEASE REVIEW THE ELEVATOR WALLS FOR WALL
 IDENTIFICATION TAGS INDICATING THE RATING FOR SHAFTS,
 SEE 707.4.
  
 3G) THE MAIN ENTRY DOOR 131 APPEARS TO BE A PASSENGER
 LOADING ZONE WITH A VALET SERVICE AND LUGGAGE AREA. THE
 PLANS DO NOT INDICATE A DROPPED CURB NOR A PASSENGER
 LOADING ZONE.
 11-4.1.2(5)?. ALSO SEE 11-4.2.9.5 DETECTABLE WARNING
 DEVISES.
  
 3H) THE DISABLED PARKING SPACE, WEST END OF, INDICATES
 A RAMP NO INFORMATION ON HEIGHT OF RAMP, CHANGE IN
 GRADE SEE 11-4.8(1-6).
  
 3I) RESTROOMS 112 & 113 ARE INDICATED AS DETAIL# 2
 SHEET A-403, PLEASE CORRECT TO A-402.
  
 3J) RESTROOMS 112 & 113 PLEASE PROVIDE IN DETAIL THE
 CLEAR WIDTH OF THE ACCESSIBLE STALL DOOR, PLEASE SEE
 FIGURE 30E.
  
 3K) 106.1.2 ADDITIONAL INFORMATION REQUIRED, WHAT IS
 THE PURPOSE OF THE E-ROOM?
  
 3L) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3
  
 3M) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN
 BUILDINGS 4 STORIES AND MORE, 1009.12..
  
 3N) THERE APPEARS TO BE A RAMP IN FRONT OF DOOR# 114,
 THIS RAMP DOES NOT PROVIDE THE MAXIMUM ALLOWABLE SLOPE
 INFORMATION, HANDRAILS OR BOTTOM LANDING INFORMATION,
 PLEASE SEE 11-4.8.
  
 3O)THIS PLAN INDICATES THE USE OF AN EMERGENCY
 GENERATOR PLEASE PROVIDE ADDITIONAL INFORMATION ON THE
 GENERATOR AND FUEL SUPPLY TANK. QUANTITY OF FUEL THAT
 IS TO BE STORED ON SITE AND TYPE OF VAULT. DOES THIS
 FUEL TANK HAVESECONDARY CONTAINMENT?
  
 4) SHEET A-101B
 4A) THE NORTH AND EAST PROPERTY LINE WALLS HAVE WALL
 IDENTIFICATION TAGS 1-B, PLEASE SEE
 TABLE 602 FOR WALLS LOCATED LESS THAN 5?-0? FROM THE
 PROPERTY LINE. TABLE 602 INDICATES
 A 3HOUR WALL.
  
 4B) PLEASE LOOK AT THE DOOR # 149 IN THE DOOR SCHEDULE,
 SCHEDULE INDICATES NO FIRE RATING,
 1016.1 ANDTABLE 302.3.2 OCCUPANCY SEPARATION, OPENING
 PROTECTIVE TABLE 715.3 .
  
 4C) RAMP FROM DOOR# 149 TO THE EXTERIOR, THE PLANS ARE
 MISSING THE TOP TURNING RADIUS.
 PLEASE SEE 11-4.8.4(3).
  
 4D) RAMP FROM DOOR # 149 IS MISSING THE HANDRAILS
 REQUIRED BOTH SIDES11-4.8.5.
  
 4E) RAMP BY DOOR 149 DOES NOT INDICATE THE BOTTOM
 LANDING, 11-4.8.4(2).
  
 4F) RAMP BY DOOR# 149 PLEASE PROVIDE THE CLEAR
 DIMENSION AT THE BOTTOM OF THE RAMP FROM COLUMN TO
 COLUMN. 11-4.8.3 WHEN PART OF A MEANS OF EGRESS MINIMUM
 OF44? CLEAR.
  
 4G) RAMP BY DOOR# 149 INDICATES A SLOPE OF 8% PLEASE
 SEE 11-4.8.2 THE MAXIMUM SLOPE OF A RAMP IN NEW
 CONSTRUCTION SHALL BE 1 TO 12.
  
 4H)EAST SIDE OF THE BUILDING ROOM 103 THE EMERGENCY
 GENERATOR ROOM INDICATES OPENINGS IN THE WALL, PLEASE
 SEE TABLE 602 LESS THAN FIVE FOOT FROM THE PROPERTY
 LINE, NO OPENINGS.
  
 4I) COMPACTOR DETAIL FOUND ON SHEET AC-102 DETAIL 9
 INDICATES THE USE OF A SCISSOR LIFT, PLEASE PROVIDE
 ADDITIONAL INFORMATION.106.1.2.
  
 4J) PLEASE PROVIDE STAIR IDENTIFICATION 1009.5.3
  
 4K) PLEASE REVIEW STAIR ACCESS TO ROOF BUILDINGS IN
 BUILDINGS 4 STORIES AND MORE, 1009.12..
  
  
 5)SHEET A-102A
 5A) PLEASE PROVIDE AREA CALCULATIONS HOW THIS LEVEL
 CLASSIFIES AS A MEZZANINE?505.2 AREA LIMITATION.THE
 AGGREGATE AREA OF A MEZZANINE OR MEZZANINES WITHIN A
 ROOM SHALL NOT EXCEED ONE-THIRD OF THE AREA OF THAT
 ROOM OR SPACE IN WHICH THEY ARE LOCATED.
  
 5B)DOORS ON THE A-102A & A-102B FLOOR PLANS DO NOT
 SHOW UP ON THE DOOR SCHEDULE
 SHEET A-611, PLEASE CORRECT, THIS SHEET CAN NOT BE
 CHECKED FOR OPENING PROTECTIVES
 TABLE 715.3.
  
 5C) THIS COMMENT WILL NOT BE REPEATED FOR EVERY CASE
 BOTH SHEET A-102A AND A-102B THE NORTH AND EAST
 PROPERTY LINES ARE LESS THAN 5?-0? FROM THE PROPERTY
 LINE REQUIRING 3 HR FIRE RATING. SEE TABLE 602.
  
 5D) THERE IS A ROOM NOT IDENTIFIED, DOOR 155A LEADS
 INTO THIS AREA. PLEASE PROVIDE ADDITIONAL INFORMATION
 106.1.2.
  
 5E) ADDITIONAL INFORMATION REQUIRED 106.1.2. ON SHEET
 A-101A THERE ARE ROOMS 118-123
 THE NEXT LEVEL UP (SHEET A-102A) THE PLAN INDICATES
 CEILING BELOW BUT THERE IS NO CUT SECTIONS OF THIS AREA
 INDICATING HEIGHT OF THE CEILING OR MATERIAL. PLEASE
 PROVIDE HEIGHT OF THE CEILING AND STRUCTURAL COMPONENTS
 OF THIS SYSTEM.
  
 6) A-102B
 6A) THE ROOMS BELOW (105-108) ARE INDICATED AS CEILING
 BELOW, PLEASE PROVIDE A CUT SECTION THROUGH INDICATING
 TYPE OF CEILING, HEIGHT OF CEILING AND TYPE OF
 STRUCTURAL COMPONENTS. 106.1.2.
  
 6B) IN THE SAME ROOMS MENTIONED ABOVE THE PLANS APPEAR
 TO HAVE (3) CHASES IN THE CENTER OF THIS AREA? PROVIDE
 MORE DETAILS AND FIRE RATINGS. 106.1.2. ? 712.4.
  
 6C) THERE IS A CONCRETE WALL ON GRID LINE B.4 BETWEEN
 COLUMN LINE 2-3. THIS SHOULD BE A GUARD RAIL AS WELL AS
 VEHICLE BARRIER, PLEASE PROVIDE COMPLIANCE WITH
 1607.7.3
  
 6D) THE OTHER AREA OF CONCERNS WITH GUARDS WOULD BE THE
 DROP OFF EDGE WHERE THE RAMP RISES AND OR FALLS TO THE
 NEXT LEVEL. PLEASE PROVIDE COMPLIANCE WITH 1607.7.3.
  
 6E) THE NORTHEAST CORNER OF THE GARAGE THERE APPEARS TO
 BE A SHAFT BUT NO WALL TAGS.
 707.4.
  
 6F) CORRIDOR M114 IS INDICATED AS A 1 HR RATED WALL
 WITH NO DOORS SEPARATING THE GARAGE FROM THE CORRIDOR.
 106.1.2.
  
 7) SHEET A-103A:
 7A) EXIT WAY# 230 IS INDICATED AS NON RATED WALLS, THE
 MECHANICAL SHEETS INDICATE FIRE DAMPERS, SEE TABLE
 1016.1 FOR FIRE RATINGS.
  
 8) SHEET A-103A
 8A) ELEVATOR LOBBY 240, THIS COMMENT WILL STAND FOR ALL
 FLOORS WITH R1 TYPE OCCUPANCY.
 PLEASE SEE REQUIRED 1 HOUR RATING & OPENING PROTECTION,
 707.14.1, TABLE 1016.1 AND THE CODE COMMENTARY FOR
 REQUIREMENTS FOR A 1 HR FIRE RATING, THIS COMMENT WILL
 STAND FOR ALL COMMON FLOORS.
  
 8B)STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN
 THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE
 STAIRS FROM THE ELECTRIC ROOM PLEASE IDENTIFY WALL TYPE
 AND HOURLY RATING, 707.4 THIS COMMENT WILL STAND FOR
 THE COMMON FLOORS.
  
 8C) STAIR TOWER# 2 INDICATES TWO METAL STUD WALLS IN
 THE INTERIOR OF THE STAIR TOWER ONE SEPARATES THE
 STAIRS FROM WHAT APPEARS TO BE A SHAFT WITHIN THE STAIR
 TOWER, PLEASE IDENTIFY WALL TYPE AND HOURLY RATING,
 707.4. THIS COMMENT WILL STAND FOR ALL COMMON FLOORS.
  
 8D) LAUNDRY ROOM 235 DOES NOT HAVE A TERMINATION ROOM
 AS REQUIRED IN 707.13.4.THE TERMINATION ROOM SHALL
 HAVE OPENING PROTECTION NOT LESS THAN ? HOURS AND BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
  
 8E) LAUNDRY ROOM ITSELF WOULD NORMALLY ONLY REQUIRE THE
 WALLS TO BE SMOKE RATED, AS THE WALLS THAT ARE SHARED
 BY THE TRAINING AND HOUSE KEEPING ROOMS, PLEASE NOTE
 THAT NON OF THE NON-RATED WALL TYPES ARE SPECIFIED AS
 SMOKE PARTITIONS SEE SECTION 710. IN THIS CASE THE
 LAUNDRY ROOM WALLS THAT ARE COMMON TO THE EXIT ACCESS
 CORRIDOR WILL NEED TO BE 1 HR FIRE RATING BECAUSE OF
 THE R1 OCCUPANCY, TABLE 1016.1.
  
 8F) DOOR 230A IS STILL PART OF THE 1 HR RATED EXIT
 ACCESS CORRIDOR THAT LEADS TO THE VERTICAL EXIT
 STAIRWELL, THE DOOR SCHEDULE INDICATES THIS DOOR NOT
 RATED, PLEASE CORRECT, TABLE 1016.1/ TABLE 715.3
 OPENING PROTECTIVE.
  
 8G) DOOR 230A APPEARS TO BE MISSING THE REQUIRED 18? ON
 THE PULL, LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 8H) LAUNDRY ROOM PLAN IS MISSING THE THROUGH
 PENETRATIONS (2-LOUVERS) IN THE RATED WALL
 COMMON WITH THE GARAGE. OPENING PROTECTION IS REQUIRED,
 SEE TABLE 715.3.
  
 8I) BETWEEN UNITS THERE ARE QUITE A FEW WALLS THAT DO
 NOT HAVE WALL IDENTIFICATION TAGS,
 SEE 1207.2. THIS COMMENT WILL STAND FOR ALL
 SHEETS.
  
 9) SHEET A-103B:
 9A) DOOR# 237APPEARS TO BE MISSING THE REQUIRED 18?
 ON THE PULL, LATCH SIDE OF THE DOOR.
 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. MINIMUM
 MANEUVERING CLEARANCES AT DOORS THAT ARE NOT AUTOMATIC
 OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. 25. THE
 FLOOR OR GROUND AREA WITH IN THE REQUIRED CLEARANCES
 SHALL BE CLEAR & LEVEL.
  
 9B) LAUNDRY ROOM 238 INDICATES ON THE MECHANICAL SHEETS
 DRYER EXHAUST PENETRATINGA 1HR FIRE RATED WALL
 INDICATE OPENING PROTECTION, TABLE 715.3.
  
  
  
 10) A-104A COMMON TO THE 3RD, 4TH & 5TH FLOORS.
 10A) ROOM# 450 VENDING / ICEAND ROOM 451LINEN ROOM
 THIS COMMON WALL IS PART OF THE
 1 HR RATED CORRIDOR IS MISSING WALL TAG, TABLE 715.3.
  
 10B) THE LAUNDRY ROOM DOOR IS ALSO THE LAUNDRY CHUTE
 ACCESS DOOR REQUIRING A ? HR OPENING PROTECTIVE AND BE
 SELF-CLOSING OR AUTOMATIC-CLOSING UPON THE DETECTION OF
 SMOKE.
 IS FOR ALL COMMON FLOORS. NOT 20 MINUTE AS INDICATED IN
 THE DOOR SCHEDULE, PLEASE CORRECT& SEE 707.13.4. THIS
 COMMENT IS FOR ALL COMMON FLOORS.
  
 10C)THE LAUNDRY ROOM ACCESS ROOM ALSO IS MISSING THE
 WALL RATINGS OF BOTH SHAFT ENCLOSURES IN THIS ROOM.
 707.4. SHAFTS. THIS COMMENT IS FOR ALL COMMON FLOORS.
  
 10D)BETWEEN UNITS 433 & 436 AT THE SHOWER LOCATIONS
 THE PLANS INDICATE A WALL TAG
 ?OC? NON-RATED WALL. 708.1(2) , 708.3 & 708.4.
  
 10E) THE UNIDENTIFIED ROOM JUST LEFT OF STAIR TOWER# 2
 HAS A 25X45 MECHANICAL CHASE, THE SHAFT WALLS ARE NOT
 IDENTIFIED WITH WALL TAGS. SEE 707.4.
  
 10F) PLEASE IDENTIFY THE USAGE OF ROOM LISTED ABOVE.
 106.1.2.
  
 11) SHEET A-104B COMMON TO 3RD, 4TH & 5TH FLOORS.
 11A) THIS SHEET THERE ARE NO WALL TAGS IDENTIFYING WALL
 RATINGS. TABLE 1016.1, 708.1(2), 708.3 & 708.4.
  
 11B) STAIR TOWER# 1 INDICATES A SHAFT LOCATED WITHIN
 THE STAIR TOWER, SEE 707.4 & 1019.1.2.
  
 11C) PLANS INDICATE A CHASE OR SHAFT IN THE ELECTRIC
 ROOM 402, PLEASE SEE 707.4.
  
 11D)THE EAST ELECTRICAL ROOM AND STORAGE ROOM DOORS
 AND HALLWAY DOOR DO NOT HAVE IDENTIFICATION TAGS, FIRE
 RATINGS? THIS IS A 1HR FIRE RATED CORRIDOR. TABLE
 1016.1. THE CORRIDOR WIDTH IN THE UPPER DETAIL IS NOT
 PROVIDED?CONSIDER DOOR WIDTH VERSES CORRIDOR WIDTH.
 1005.2DOOR ENCROACHMENT.
  
 12) SHEET A-105A:
 12A) NO ROOF ACCESS SEE COMMENT (3M) FOR STAIR ACCESS
 TO ROOF. 1009.12.
  
 13) SHEET A-105B:
  
 13A) THE STAIRWELL# 2 IS NOT DEPICTED AS GOING THROUGH
 TO THE ROOF LEVEL,SEE 1009.12.
  
  
 13B) THERE IS NO ROOF PLAN OF STAIR# 2 INDICATING THAT
 DOES GO TO THE ROOF AND DOOR TO THE
 ROOF LEVEL, THE DOOR SCHEDULE ALSO WILL NEED TO REFLECT
 THIS DOOR AND FIRE RATING, 106.1.2,
 & TABLE 715.3 OPENINGPROTECTION.
  
 14) SHEET A-202, A-203 & A-204 ALL FAIL TO INDICATE THE
 STAIRWELL# 2 CONTINUING THROUGH TO THE ROOF LEVEL.
 ADDITIONAL INFORMATION REQUIRED, 106.1.2 & 1009.12.
  
 15) SHEET A-307 DETAIL# 2 ON THE MEZZANINE AND 2ND
 FLOOR LEVELS INDICATE WHAT APPEARS TO BE CONCRETE KNEE
 WALLS WHERE IS THIS CUT SECTION TAKEN, SHEETS A-102A,
 A-102B, A-103A
 & A103B ALL INDICATE A 1HOUR RATED BLOCK WALL?
 ADDITIONAL INFORMATION REQUIRED 106.1.2.
  
 16)SHEET A-402 BUFFET PLEASE INDICATE COMPLIANCE WITH
 11-5.2, 11-5.4&11.5.5.
  
 17)SHEET A-428 INDICATES THE USE OF A FIRE SHUTTER AT
 THE ELEVATOR LOBBYPLEASE PROVIDE INFORMATION ON THE
 RATING OF FIRE SHUTTER AND COMPLIANCE WITH 715.3.9.
  
 18) SHEET A-429, A-430 &A-431 BOTH FAIL TO INDICATE
 OPENING PROTECTION AT THE ELEVATOR LOBBY.PLEASE SEE
 707.14.1.
  
 19) SHEET AR 401 DETAIL 3 INDICATES THE USE OF ACRYLIC
 PANELS PLEASE PROVIDE THE AREA WHERE THIS CEILING WILL
 TAKE PLACE AND HOW IT WILL BE HUNG? PLEASE PROVIDE THE
 SMOKE DEVELOPMENT AND FLAME SPREAD FOR THIS PRODUCT IN
 THIS APPLICATION. TABLE 803.5 & 803.1.
  
 20)PROVISO: EXTERIOR LIGHT GAUGE METAL FRAMING TO BE
 SUBMITTED AS SHOP DRAWINGS AFTER BEING REVIEWED BY THE
 DESIGNER OF RECORD REVIEW AND APPROVAL.
  
 21)A-511 FIN WALL DETAIL# 9 INDICATES THAT THE
 FINWALL FRAME IS TO BE ATTACHED TO THE STRUCTURE PER
 NOA REQUIREMENTS,THERE IS NO FIN WALL LISTED UNDER
 EITHER MIAMI-DADE OR
 THE FLORIDA STATE WEB SITE.THE PRODUCT TESTING REPORT
 WILL NEED TO HAVE THIS TYPE WINDOW APPLICATION TESTED
 AND SHOW THE REQUIRED ANCHORAGE.
 1714.5.4.1. WINDOW AND DOOR ASSEMBLIES SHALL BE
 ANCHORED IN ACCORDANCE WITH THE PUBLISHED
 MANUFACTURER?S RECOMMENDATIONS TO ACHIEVE THE DESIGN
 PRESSURE SPECIFIED. SUBSTITUTE ANCHORING SYSTEMS USED
 FOR SUBSTRATES NOT SPECIFIED BY THE FENESTRATION
 MANUFACTURER SHALL PROVIDE EQUAL OR GREATER ANCHORING
 PERFORMANCE AS DEMONSTRATED BY ACCEPTED ENGINEERING
 PRACTICE.
  
 22)1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE
 DEBRIS REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
  
 FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES,
 3 IF THRESHOLD OR RESIDENT INSPECTOR OF PRODUCT TESTING
 REPORTS, MISSING REPORTS ARE AS FOLLOWS:
 22A) STOREFRONT UNITS- OK COMPLIED
 22B) FIXED WINDOWS- TRACO WINDOWS DID NOT MEET THE -89
 IN END ZONES
 22B) HORIZONTAL SLIDING UNITS TRACO- CIRCLE GLAZING
 TYPE FOR PRESSUES
 22C) FINWALL WINDOW SYSTEMS- NO REPORT SUBMITTED
 22D) MULLIONS- PGT MULLIONS CIRCLE MULLION LENGTHS TO
 BE USED/ FOR PRESSURES
 22E) WALL LOUVERS- OK REVIEWED
 22F)EXTERIOR HOLLOW METAL DOORS, SINGLE & PAIR OF
 DOORS
 22G) EXTERIOR AUTOMATIC SLIDING DOORS- OK REVIEWED
 22H) EXTERIOR GLAZED SWING DOORS- OK COMPLIED
 22I)PRE-ENGINEERED A/C STANDS- NO REPORT SUBMITTED
 22J) ROOFING ASSEMBLIES- CARLISLE REPORT, REQUIRES
 SHOP DRAWINGS AND AN APPROVED ROOFING
 CONTRACTOR TO BE SIGNED ON.
  
 23) FOR FLAT ROOF THESE ARE THE MOST COMMON MISTAKES IN
 SUBMITTING ROOFING REPORTS
 _XX__ THE SUB-SYSTEM PROVIDED IN THE REPORT IS NOT
 HIGHLIGHTED.
 __XX__ THE SUB-SYSTEM PICKEDHAS A LOWPRESSURE FOR
 ZONE _2&3__ .
 __XX_ THE SYSTEM PROVIDED STATES LIMITATION# 7, SHOULD
 THE FASTENER RESISTANCE BE LESS THAN THATREQUIRED, AS
 DETERMINED BY THE BUILDING OFFICIAL, A REVISED FASTENER
 SPACING, PREPARED , SIGNED AND SEALED BY A FLORIDA
 REGISTEREDPROFESSIONAL ENGINEER, REGISTERED
 ARCHITECT OR REGISTERED ROOFCONSULTANT MAY BE
 SUBMITTED.
 __XX_ THE SYSTEM PROVIDED INDICATES LIMITATION# 9, NO
 ENHANCED FASTENING ALLOWED.
  
 24)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 25) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 26) S-207 EAST ELEVATION PRESSURES ARE NOT PROVIDED FOR
 WALL LOUVER AT EAST LOWER LEFT
 ELEVATION.
  
 27) NOTE: AWNINGS REQUIRE A SEPARATE PERMIT. WILL NOT
 BE PART OF THIS REVIEW.
  
 28)SHEET A-711/ ELEVATORS:
 28A)BUILDINGS 4 STORIES IN HEIGHT, AT LEAST ONE
 ELEVATOR SHALL BE PROVIDED FOR FIRE DEPARTMENT
 EMERGENCY ACCESS TO ALL FLOORS. SUCH ELEVATOR CARS
 SHALL BE OF SUCH SIZE AND ARRANGEMENT TO ACCOMMODATE A
 24-INCH BY 76-INCH AMBULANCE STRETCHER IN THE
 HORIZONTAL, OPEN POSITION AND SHALL BE IDENTIFIED BY
 THE INTERNATIONAL SYMBOL FOR EMERGENCY MEDICAL SERVICES
 (STAR OF LIFE).
  
 28B)THERE IS NO FIRE ALARM PLANS AND THE ELECTRICAL
 PLANS DO NOT INDICATE THE USE OF SMOKE DETECTORS IN
 EACH LEVEL OF THE ELEVATOR LOBBIES NOR IN THE MACHINE
 ROOM. PLEASE SEE 3002.8.
 ALSO SEE THE REQUIREMENTS FOR IF HOIST-WAY IS OR IS NOT
 FIRESPRINKLED.
  
 28C)PLEASE SEE REQUIREMENTS FOR ELEVATOR VENTING FOR
 R! OCCUPANCIES 3 STORIES AND GREATER.3004.2 LOCATION
 OF VENTS
 3004.3 AREA OF VENTS
  
 29) SHEET A-513:
 29A) PLANS FAIL TO INDICATE THE USE OF FIRE SPRINKLERS
 AS REQUIRED IN 707.13.6 & 903.2.10.2.
  
 29B) PLANS INDICATE 2 SHAFTS IN THIS PLAN BOTH
 INDICATING THEY ARE 2 HR CONSTRUCTION, PLEASE PROVIDE
 AN ASSEMBLY NUMBER FORTHESE SHAFTS. 707.4.
  
 30) FP-205:
 30A) FP-205A IS THE FIRE SPRINKLER PLAN FOR THE ROOF
 LEVEL WEST PORTION OF THE BUILDING, NO INFORMATION IF
 FIRE SPRINKLERS WILL BE IN THE ELEVATOR SHAFT.
  
 30B) FP-205B THIS SHEET IS MISSING TOTALLY, STAIRWELL
 AND STANDPIPE THAT PROVIDES ROOF ACCESS.
  
 31) PLEASE COORDINATE PLANS BETWEEN A-101A AND FP-201 A
 DOOR 114 ON THE FP SWINGS AGAINST THE EGRESS FLOW, SEE
 1008.1.2.
  
 32) PLEASE PROVIDE FIRE ALARM INFORMATION 907.2.10.1.1.
 / 106.3.5.1.1(5) & (6) EARLY WARNING SYSTEMS. WILL ALSO
 REQUIRE A SEPARATE PERMIT AND REVIEW NOT UNDER THIS
 PERMIT.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  
  

Review Stop E ELECTRICAL
Rev No 33 Status P Date 2009-05-20 Cont ID  
Sent By dwise Date 2009-05-20 Time 19:59 Rev Time 0.00
Received By dwise Date 2009-05-20 Time 19:59 Sent To FIRE
Notes
2009-05-20 20:00:28ASKING FOR FIRE TO CONFIRM THAT THEY REQUESTED/APPROVED
 RELOCATION AND REMOVAL OF EXIT SIGNAGE AND WALL PACKS.

Review Stop E ELECTRICAL
Rev No 32 Status F Date 2009-05-18 Cont ID  
Sent By dwise Date 2009-05-18 Time 08:58 Rev Time 0.00
Received By dwise Date 2009-05-12 Time 08:58 Sent To  
Notes
2009-05-18 09:00:32HOLDING FOR CORRECTIONS TO PLANS. REVISIONS CLOUDED BY
 HAND NOT SIGNED BY DESIGN PROFESSIONAL. SPOKE WITH EOR,
 WILL OVERNIGHT CLOUDED "AS-BUILT" ELECTRICAL REVISIONS
 DIRECTLY TO ME. DBW

Review Stop E ELECTRICAL
Rev No 31 Status P Date 2009-02-17 Cont ID  
Sent By dpalmer Date 2009-02-17 Time 14:13 Rev Time 0.00
Received By dpalmer Date 2009-02-17 Time 14:13 Sent To PC
Notes
2009-02-17 14:16:05REVISED COORDINATION STUDY AND SHORT CIRCUIT
 CALCULAITONS. OK.
  
 OK FOR TCO AND STILL NEED FINAL REVISED PLANS AND
 ENERGY CALCULATIONS BEFORE FINAL.

Review Stop E ELECTRICAL
Rev No 30 Status F Date 2009-02-16 Cont ID  
Sent By dpalmer Date 2009-02-16 Time 10:47 Rev Time 3.00
Received By dpalmer Date 2009-02-16 Time 10:47 Sent To PC
Notes
2009-02-16 10:47:30** DENIED REVIEW **
  
 ** REVISIONS
  
  
 1) NOTE: ALL SUBMITTED REPORTS FOR COORDINATION STUDY
 AND SHORT CIRCUIT CALCULATIONS NEED TO BE SIGNED, DATED
 AND SEALED BY THE ENGINEER OF RECORD.
 FAC 61G15-23.002
 FS 471.023
  
 2) NOTE: THE COORDINATION STUDY NEEDS TO INCLUDE ALL
 EQUIPMENT/PANELS/MAIN BREAKERS AND CONDUCTORS FOR LIFE
 SAFETY (700 SYSTEMS) AND LEGALLY REQUIRED (701)
 SYSTEMS. 700.27,701.18 AND 240.12. THIS IS IMPERATIVE
 FOR THESE SYSTEMS TO COORDINATE. AT ANY GIVEN POINT THE
 LACK OF COORDINATION COULD RESULT IN A LOSS OF AN
 ENTIRE PANEL, MULTIPLE PANELS OR AN ENTIRE EMERGENCY OR
 LEGALLY REQUIRED SYSTEM.
 PLEASE SEE THE FOLLOWING ITEMS WHICH COULD NOT BE FOUND
 IN THE COORDINATION STUDY. THERE WILL BE COMMENTS BELOW
 ALSO WITH RESPECT TO THE SHORT CIRCUIT CALCULATIONS AND
 ANALYSIS.
  
 A) PLEASE SEE PANEL ELSW2 IS NOT LOCATED IN THE
 COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION
 ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION.
  
 B) PLEASE SEE PANEL EMLW2 IS NOT LOCATED IN THE
 COORDINATION STUDY. I COULD NOT LOCATE ANY INFORMATION
 ON THIS PANEL, OCP OR CONDUCTOR CONTRIBUTION.
  
 C) PLEASE BE SURE TO INCLUDE THE LARGEST CIRCUIT
 CONTRIBUTION IS INCLUDED ON BOTH OF THESE PANELS.
  
 D) MSB IS NOTED AS MDP. (SAME HOWEVER ONLY MISPRINTED
 FOR IDENTIFICATION).
  
 E) PLEASE INCLUDE CONDUCTOR CONTRIBUTION FOR ALL
 EQUIPMENT. THE CONDUCTORS ARE NOTED FOR EDPLS, TLSE2
 FEEDER, CONDUCTORS FOR ELSE2 AND FIRE PUMP. HOWEVER
 WHERE ARE THE OTHERS?
  
 F) PLEASE ALSO SEE MISSING TLSW-2.
  
 3) NOTE: PLEASE BE SURE THE SHORT CIRCUIT CALCULATIONS
 SCHEDULE ALSO COORDINATES WITH THE IDENTIFICATION OF
 ALL EQUIPMENT ON THE STUDY AND THE PLANS. THE SHORT
 CIRCUIT CALCULATIONS WILL BE NOTED AS SCC FOR THE
 REMAINDER OF THESE COMMENTS. SAME CODE SECTIONS AS
 NOTED ABOVE.
  
 FOR EXAMPLE: THE LIST OF PANELS AND EQUIPMENT ON THE
 THIRD PAGE OF THE SCC IN INDICATES AN ELSE3, YET THERE
 IS NO SUCH EQUIPMENT NOTED ON PLANS OR COORDINATION
 STUDY.
 THE RISER AT THE BACK OF THE SCC ALSO DOES NOT INCLUDE
 THIS ELSE3 PANEL. IF THIS IS REALLY THE ELSW2 PANEL,
 PLEASE ADJUST BOTH THE SCC AND THE SCC RISER.
  
 FOR EXAMPLE: THE LIST ON THIS SAME PAGE THREE OF THE
 SCC DOES NOT LIST EMLW2. THE RISER ON THE BACK OF THE
 SCC DOES INCLUDE THIS EMLW2 PANEL.
  
  
 **THE COMMENTS ABOVE IN NOTE #2 ALREADY GIVE THE NOTE
 WITH RESPECT TO THE COORDINATION STUDY MISSING THE
 ELSW2 AND EMLW2.
  
 4) NOTE: PLEASE IDENTIFY RECEPTACLES NOTED ON PANEL
 SCHEDULE EMLW2 FOR CIRCUITS 15, 17 /19. THE SCHEDULE
 INDICATES REC HOWEVER THE INFORMATION ON THE RISER
 ACTUALLY SHOWS THESE AS CIRCUITS TO THE GENERATOR. THE
 OCP FOR CIRCUIT 17/19 SEEMS TO BE A LARGER BREAKER OR
 CIRCUIT WHICH WILL BE A REVISED PORTION OF THE STUDY.
 THIS NEEDS TO BE VERIFIED BEFORE REVISED THE
 COORDINATION STUDY.
 408.4
 FBC 106.1.1, 106.5 FOR CLARITY, COORDINATION OF RECORD
 PLANS.
  
 5) NOTE: IT IS IMPORTANT TO KNOW AS THERE ARE SEVERAL
 CHANGES WITH RESPECT TO PLANS FROM AIC RATINGS,
 CONDUCTORS ETC FROM PREVIOUS PLANS A NEW ELECTRICAL
 INSPECTION WILL BE REQUIRED BEFORE THE TCO.
  
  
 6) NOTE: SHEETS E-102A, 102B, 103A ,203 AND 204 ARE OK.
 THESE SHEETS RETAINED FOR FILE.
 THE OTHER SHEETS SUCH AS RISER, AND PANEL SCHEDULE
 SHEETS NEED TO BE BROUGHT BACK IN IF THEY ARE NOT
 REVISED.
  
 *** ALL COMMENTS WERE GONE OVER WITH THE ENGINEER OF
 RECORD. THE ORIGINAL COMMENTS E-MAILED TO THE ENGINEER
 HAVE BEEN ADJUSTED FOR THESE POSTED NOTES. ONE COMMENT
 WAS REMOVED AS THE PRINTED SHEET WAS NOT EASILY
 READABLE AND ENGINEER CLARIFIED INFORMATION. THE
 COMMENT #4 ABOVE WAS REVISED ALSO FOR MORE INFORMATION
 AND COORDINATION NEEDED.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 29 Status F Date 2009-02-12 Cont ID  
Sent By dpalmer Date 2009-02-12 Time 18:03 Rev Time 0.00
Received By dpalmer Date 2009-02-12 Time 18:03 Sent To  
Notes
2009-02-12 18:03:44** DENIED REVIEW **
  
 REVISION #9
  
 1) NOTE: PLANS SUBMITTED WERE FOR REVISION #9 WHICH WAS
 FOR NEW SUPPLY FAN AND EXHAUST FANS ADDED. IN THE
 REVIEW OF PAGE E-502 A REVISION #8 WAS LOCATED ON PANEL
 SCHEDULE ELSW2 FOR CO CONTROL PANEL. HOWEVER A REVISION
 #8 WAS NEVER SUBMITTED AND THE REVISED PLANS SHOWING
 REVISIONS UP THROUGH REVISION #9 DOES NOT SHOW OR
 INDICATE THIS NEW CO PANEL.
 AS PLANS FOR ALL REVISED PANELS SHOWING ALL REVISED
 LOADS WERE NOT SUBMITTED THESE OTHER ITEMS COULD NOT BE
 REVIEWED.
 SPOKE TO KAST CONSTRUCTION REPRESENTATIVE ON THE PHONE
 AND REVISED ELECTRICAL SHEETS FOR FANS WILL NOT BE
 NEEDED AT THIS TIME. FIELD INSPECTION WAS DONE AND FANS
 ARE ALREADY TESTED BY INSPECTORS. THIS IS ALSO TO BE
 VERIFIED WITH THE ELECTRICAL INSPECTOR.
 THESE WILL BE PART OF REVISIONS TO BE SUBMITTED ON
 2/13/09.
  
 ** A CALLED BY PLACED TO TLC ENGINEERS @ 5:55PM TO GO
 OVER COMMENTS. A MESSAGE WAS LEFT ON VOICE MAIL BRIEFLY
 EXPLAINING THESE ITEMS AND TO RETURN PHONE CALL TO THIS
 OFFICE.
  
 2) NOTE: PLEASE BE SURE TO COORDINATE ALL REVISED
 SHEETS TO DATE WHEN SUBMITTING REVISED PLANS AND
 COORDINATION STUDY FOR REVIEW.
  
  
 ** IMPORTANT **
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 28 Status F Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 12:00 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:40 Sent To PC
Notes
2009-01-31 12:01:03*** DENIED***
  
  
 1) NOTE: THE LOCATION NOTES OF T-STAT DEVICE E528 ON
 ENLARGE GUEST ROOM LIGHTING CONTROLS PLANS NEED TO BE
 UPDATED OR REMOVED. THE NOTES STATE THE DEVICE BY THE
 DOOR DOES NOT PROVIDE COVERAGE AND NOTES AN ADDITIONAL
 DEVICE IS NEEDED FOR FULL COVERAGE. AFTER A PHONE
 MEETING WITH ELECTRICAL DESIGNERS AS WELL AS THE
 LIGHTING SYSTEM MANUFACTURE IT WAS STATED THE SWITCH
 DEVICES AT BED LOCATIONS ALSO ACT AS AN OVER RIDE
 WHETHER OR NOT THE T-STAT/E528 DEVICE SENSES AN
 OCCUPANT OR NOT.
 THE NOTES ON THESE SHEETS WILL BE UPDATED.
 13-415.1.ABC.1, NFPA-101 7.8
  
 2) NOTE: AS NOTED ON PREVIOUS SUBMITTAL REVIEW OF POOL
 HEATER THIS UNIT IS NOT LISTED ON THE INPUT DATA REPORT
 OF THE SUBMITTED CALCULATIONS.
 13-412, 13-400.A.3
 THERE ARE OTHER ITEMS WITH THE SUBMITTED CALCULATIONS
 WHICH ARE NOT COORDINATING WITH PLANS. FIXTURE TYPE T
 APPEARS TO BE OVER ALONG WITH M HOWEVER OTHER FIXTURES
 AS R/RE APPEAR TO BE A LITTLE UNDER.
 PLEASE VERIFY EXTERIOR LIGHTING AS INSTALLED IN THE
 FIELD WITH WHAT IS SHOWN ON PLANS AND IN THE
 IDR.13-415.2.ABC.1.3
  
 3) NOTE: AS NOTED IN PREVIOUS SUBMITTED THERE ARE NOTES
 PERTAINING TO THE AIC RATINGS OF SOME PANELS/BREAKERS
 INSTALLED AND NOTED ON SHOP DRAWINGS. THESE ITEMS NEED
 TO BE CONFIRMED THEY HAVE BEEN CORRECTED AND NOT
 CHANGED ANY BREAKERS ETC FROM THE PREVIOUS COORDINATION
 STUDY SUBMITTED.
 ANY CHANGES WITH A LOWER RATING WHICH WOULD AFFECT THE
 COORDINATION OF ANY LIFE SAFETY OR LEGALLY REQUIRED
 SYSTEM WOULD NEED TO BE ADDRESSED AT THIS TIME.
 240.12, 700.27, 701.18
  
 4) NOTE: THE FIXTURE ON THE SECOND LEVEL PARAPET WALL
 MAY BE OVER THE ACTUAL PROPERTY LINE IF MOUNTED ON THE
 NORTH WALL. PLEASE VERIFY.
  
 5) NOTE: PLEASE BE SURE TO REVISE ALL CIRCUITING,
 EQUIPMENT AND ITEMS ADDED FOR POOL PANEL. AN EXAMPLE IS
 THE NEW SUBMITTAL FOR ELECTRIC POOL HEATER WHICH IS NOT
 ON PANEL PL.
 PLEASE REVISE ALL LOADS ETC.
 220,408,310.16,240.4 ETC
 FBC 106.5, 106.1.1 FOR COORDINATION AND CLARITY OF
 RECORD PLANS.
  
  
  
 ** ONCE NOTES FOR SUBMITTALS AND ITEMS ABOVE HAVE BEEN
 ADDRESSED SOME SHEETS IN SETS MAY NOT NEED TO BE
 REVISED. SHEETS WHICH DO NOT NEED REVISIONS SHOULD BE
 BROUGHT BACK IN WITH OTHER REVISED ITEMS.
  
  
 FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 27 Status F Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:40 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:26 Sent To PC
Notes
2009-01-31 10:40:39*** DENIED***
  
 POOL PAK HEATER
  
 1) NOTE: THE SUBMITTAL FOR THIS ITEM WAS NOT STAMPED OR
 REVIEWED BY THE ELECTRICAL ENGINEERING FIRM/DESIGNER OF
 RECORD. COMMENTS WILL ALSO BE MADE AT THIS HEATING UNIT
 IS NOT INCLUDED WITH THE SUBMITTED ENERGY CALCULATIONS.
 FBC13-412, 13-412.1.ABC.3 EQUIPMENT PERFORMANCE
 STANDARDS.
 THE SPECS SUBMITTED CONTAIN IDENTIFICATION OF MULTIPLE
 VOLTAGES. SOME SHEETS HAVE SOME HAND DRAWN CORRECTIONS
 AND OTHER SHEETS STILL HAVE 460/480V CIRCLED. PLEASE
 COORDINATE THESE ITEMS
 PLEASE SEE 13-412.1.ABC.3. WHERE DO THE SUBMITTED
 DOCUMENTS SHOW ANY INFORMATION OR COMPLIANCE WITH THIS
 TABLE FOR MINIMUM REQUIREMENTS?
  
 FBC 106.1.1 FOR COORDINATION AND CLARITY WITH PLANS.
  
  
  
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 26 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:20 Sent To PC
Notes
2009-01-31 10:24:57*** NOTED ***
  
 GROUNDING AND BONDING FITTINGS AND CONNECTORS.
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
 DEVICES AS SHOWN ARE OK
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 25 Status F Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:18 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:13 Sent To PC
Notes
2009-01-31 10:20:23*** NOTED ***
  
 CABLES, WIRE NUTS, WIRE CONNECTORS ETC
  
 1) NOTE: THE SUBMITTAL CONTAINS NOTES FROM THE
 ENGINEERING FIRM WHICH STATES MC CABLE WAS NOT
 SPECIFIED. THE INSTALLATION AND USE IS BY DESIGN,
 LOCATIONS BY NEC AND CONTRACTOR.
 THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED OR
 NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR THESE
 TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN
 WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 24 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:10 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:08 Sent To PC
Notes
2009-01-31 10:12:58*** NOTED ***
  
 BROAD BAND SYSTEM, FITTINGS AND CABLES
  
 1) NOTE: THE PRODUCRT DATA SUBMITTED FOR TYPE OF CABLE
 DOES INDICATE IF PLENUM RATED. THE INSTALLATION IN
 FILED MAY BE INSTALLED IN CONDUIT. THIS SHALL BE FEILD
 VERIFIED FOR TYPE OF CABLE AND METHOF OF INSTALLATION.
  
 2) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 23 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:07 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:06 Sent To PC
Notes
2009-01-31 10:08:05*** NOTED ***
  
 SLEEVE SEALS
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 22 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 10:03 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 10:00 Sent To PC
Notes
2009-01-31 10:03:56*** NOTED ***
  
 HANGERS AND SUPPORTS
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 21 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:59 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:56 Sent To PC
Notes
2009-01-31 10:00:36*** NOTED ***
  
 RACEWAYS AND BOXES
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 20 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:40 Sent To PC
Notes
2009-01-31 09:44:38*** NOTED ***
  
 ENCLOSED SAFETY SWITCHES
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 19 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:38 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:36 Sent To PC
Notes
2009-01-31 09:38:31*** NOTED ***
  
 TRANSFORMERS
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 18 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:32 Sent To PC
Notes
2009-01-31 09:34:44*** NOTED ***
  
 STRUCTURED CABLING SYSTEM
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUESTS FOR
 THESE TO BE PART OF SUBMITTALS FOR RECORD PLANS PLEASE
 RETURN WITH ANY CORRECTIONS AS NOTED BY THE ENGINEERING
 FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 17 Status F Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:23 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:18 Sent To PC
Notes
2009-01-31 09:29:12*** NOTED ***
  
 SWITCH BOARD
  
 1) NOTE: THE SUBMITTAL FOR THE SWITCH BOARD WOULD NEED
 TO CORECTED AS NOTED BY THE ENGINEERING FIRM. THE
 SUBMITTAL IS NOT REQUIRED HOWEVER MAY BE PART OF THE
 RECORD PLANS IF CORRECTED AS NOTED. THE PLANS SHOWS THE
 SAME INFORMATION.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 16 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:16 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:15 Sent To PC
Notes
2009-01-31 09:16:51*** NOTED ***
  
 IDENTIFICATION METHODS/IDENTIFICATION
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUEST TO BE
 PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN WITH
 ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 15 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:12 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:12 Sent To PC
Notes
2009-01-31 09:13:12*** NOTED ***
  
 TRANSIENT VOLTAGE SURPRESSORS
  
 1) NOTE: THE SUBMITTAL FOR THESE ITEMS ARE NOT REQUIRED
 OR NEEDED BY THIS OFFICE. IF CONTRACTOR REQUEST TO BE
 PART OF SUBMITTALS FOR RECORD PLANS PLEASE RETURN WITH
 ANY CORRECTIONS AS NOTED BY THE ENGINEERING FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 14 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:03 Sent To PC
Notes
2009-01-31 09:07:43*** NOTED ***
  
 MOTOR CONTROLLERS
  
 1) NOTE: THE SUBMITTAL FOR THE MOTOR CONTROLERS DEVICES
 ARE NOT REQUIRED OR NEEDED BY THIS OFFICE. IF
 CONTRACTOR REQUEST TO BE PART OF SUBMITTALS FOR RECORD
 PLANS PLEASE RETURN WITH ANY CORRECTIONS AS NOTED BY
 THE ENGINEERING FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 13 Status N Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 09:03 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 09:01 Sent To PC
Notes
2009-01-31 09:03:38*** NOTED ***
  
 WIRING DEVICES
  
 1) NOTE: THE SUBMITTAL FOR WIRING DEVICES ARE NOT
 REQUIRED OR NEEDED BY THIS OFFICE. IF CONTRACTOR
 REQUEST TO BE PART OF SUBMITTALS FOR RECORD PLANS
 PLEASE RETURN WITH ANY CORRECTIONS AS NOTED BY THE
 ENGINEERING FIRM.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 12 Status F Date 2009-01-31 Cont ID  
Sent By dpalmer Date 2009-01-31 Time 08:58 Rev Time 0.00
Received By dpalmer Date 2009-01-31 Time 08:41 Sent To PC
Notes
2009-01-31 08:58:31*** DENIED ***
  
 PANEL BOARD/ BREAKERS SUBMITTAL.
  
 1) NOTE: PLEASE CORRECT THE SUBMITTALS AS NOTED BY THE
 ENGINEERING FIRM. THERE ARE SEVERAL ITEMS WHICH DO NOT
 COORDINATE WITH PLANS. IF AIC RATINGS ARE BEING REVISED
 ON THE ACTUAL EQUIPMENT INSTALLED IN FIELD THEN IT WILL
 BE REQUIRED TO REVISE THE COORDINATION STUDY.
 THE RATINGS ON EMERGENCY EQUIPMENT, PANELS AND BREAKERS
 PER 240.12, 700.27, AND 701.18 ARE REQUIRED AS A LIFE
 SAFETY REQUIREMENT.
 ** IMPORTANT**
 THERE ARE OTHER ITEMS ON THE SUBMITTALS WHICH ARE NOT
 NOTED BY ENGINEERING FIRM WHICH DO NOT COORDINATE WITH
 PLANS. AN EXAMPLE IS THE RATINGS OF BREAKERS IN SOME
 PANELS. ONE WOULD BE THE PLANS ON REV #7 SUBMITTED
 CONTAINS A 2-POLE 80AMP BREAKER ON PANEL HP2LW (SECT 1)
 FOR AHU #6, HOWEVER THE ITEM #16 FOR THIS SAME PANEL ON
 SUBMITTALS DOES NOT INDICATE THIS BREAKER.
 THIS IS ONE EXAMPLE ONLY.
  
 FBC 106.1.1 FOR COORDINATION WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 11 Status F Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 19:20 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 19:20 Sent To PC
Notes
2009-01-29 19:20:38*** DENIED ***
  
 1) NOTE: LIGHTING SUBMITTALS FOR INTERIOR LIGHTING IN
 GUEST ROOMS CONTAINS GENERAL NOTES WITH RESPECT TO THE
 INNCOM LIGHTING SYSTEM.
 THE GENERAL NOTES STATES THE T-STAT E528 DEVICE WILL
 NOT PROVIDE SUFFICIENT COVERAGE FOR THE CONTROL OF
 LIGHTING IN ROOMS BASED ON THE LOCATION AS SHOWN. THE
 NOTE ALSO STATES AN ADDITIONAL K594 DEVICE WOULD BE
 REQUIRED FOR FULL COVERAGE. THE DEVICE SCHEDULE HOWEVER
 DOES NOT CONTAIN ANY ADDITIONAL DEVICE FOR REQUIRED
 COVERAGE.
 THE LIGHTING SUBMITTAL SUBMITTED BY THE CONTRACTOR DOES
 HOWEVER INDICATE THE T-STAT E528 DEVICE IN A DIFFERENT
 LOCATION WHICH IS MORE CENTRAL TO ROOM. PLEASE
 COORDINATE THE ELECTRICAL PLANS AS THESE ARE THE FINAL
 DESIGN DOCUMENTS FOR THE ROOM.
 IF AN OCCUPANT IS LOCATED IN BED AREA AND THE T-STAT
 WHICH IS LOCATED AT THE DOOR DOES NOT PROVIDE COVERAGE
 THEN AN OCCUPANT WOULD NOT BE ABLE TO TURN LIGHTING FOR
 EGRESS AROUND THE GUEST ROOM OR EGRESS OUT OF THE ROOM.
 FBC 13-415.1.ABC.1.3, NFPA-101 7.8
  
 FBC 106.1.1 FOR COORDINATION WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 10 Status P Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 18:31 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 18:31 Sent To PC
Notes
2009-01-29 18:32:25LIGHTING CONTROLS SUBMITTAL. OK. STAMPED AND RETAINED
 ONE COPY FOR FILE.

Review Stop E ELECTRICAL
Rev No 9 Status P Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 17:48 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 17:48 Sent To PC
Notes
2009-01-29 17:51:43SUBMITTAL FOR GENERATOR AND ATS DEVICES.
 REDLINED THE *EMERGENCY DISCONNECT* IN SUBMITTED. THE
 GLASS TYPE SHUNT TRIP IS NOT A RATED DISCONNECT. THE
 DISCONNECTTING MEANS RATED FOR THE LOAD SERVED IS
 LOCATED ON RISER. SHOWN ON EMDP,EDPLS AND EACH BREAKER
 ON THE GENERATOR. THIS GLASS BREAK TYPE OF BUTTON IS IN
 ADDITION TO THE RATED DISCONNECTS AS SHOWN.
 230.76,230.79,225.39 ETC

Review Stop E ELECTRICAL
Rev No 8 Status F Date 2009-01-29 Cont ID  
Sent By dpalmer Date 2009-01-29 Time 17:26 Rev Time 0.00
Received By dpalmer Date 2009-01-29 Time 07:30 Sent To  
Notes
2009-01-29 17:26:46*** DENIED ***
  
 1) NOTE: LIGHTING SUBMITTALS FOR INTERIOR LIGHTING HAS
 SEVERAL FIXTURES WHICH WERE REJECTED BY THE ENGINEERING
 FIRM OF RECORD. IF THE LIGHTING SUBMITTALS ARE NOT THE
 SAME AS PLANS THESE ARE ALSO REJECTED BY THIS OFFICE AS
 THEY DO NOT COORDINATE WITH THE SUBMITTED PLANS. PLEASE
 ALSO BE SURE ANY LIGHTING SUBMITTALS CONTAIN A LISTING
 FROM A NRTL. SOME OF THE FIXTURES DO INDICATE A LISTING
 HOWEVER NOT ALL. AN EXAMPLE OF THIS IS TYPE BR.
 110.3
 FBC 106.1.1 FOR COORDINATION WITH PLANS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 7 Status F Date 2008-11-07 Cont ID  
Sent By dpalmer Date 2008-11-07 Time 10:12 Rev Time 0.00
Received By dpalmer Date 2008-11-07 Time 10:11 Sent To  
Notes
2008-11-07 10:12:41** DENIED REVISIONS **
  
 ** A CALLED WAS PLACED TO ENGINEER ON 11/6/08 IN THE
 AFTERNOON HOWEVER HE WAS OUT OF THE OFFICE. SOME OF
 THESE ITEMS WILL NEED TO BE GONE OVER.
  
 ** THANK YOU FOR NARRATIVE ON REVISIONS. IT IS MOST
 HELPFUL.
  
 1) NOTE: NOTED FOR INFORMATION. AS THERE ARE SEVERAL
 LIGHTING FIXTURES ADDED AND INCLUDING REVISIONS OF THE
 TYPES OF LIGHTING FIXTURES, PER FBC 13-415.2,
 13-415.2.ABC.1.1,.1.2, .1.3 AND 13-400.3A COMPLETED
 REVISED ENERGY CALCULATIONS WILL BE REQUIRED. THIS
 SHOULD BE SUBMITTED ONCE ALL KNOWN COMPONENTS TO
 BUILDING ARE COMPLETED.
  
 2) NOTE: PLEASE KNOW FOR ITEMS SUCH AS CAMERAS AND
 OTHER LOW VOLTAGE WHICH WAS NOT PART OF ORIGINAL PLANS
 NEED TO BE PERMITTED. THE VALUE FOR THESE ITEMS IN THE
 SCOPE OF WORK NEEDS TO BE APPLIED TO LOW VOLTAGE
 PERMITS REQUIRED.
 105.1, 108.3.
 NEC 800
  
 ** AS OF THIS REVIEW ONLY THE LOW VOLTAGE FOR DATA AND
 CATV HAS BEEN APPLIED FOR AND PERMITTED.
  
 3) NOTE: PLEASE SUBMIT COMPLETED LIGHTING CONTROL PANEL
 SCHEDULES. FOR EXAMPLE: POOL AREA LIGHTING IS ONE AREA
 NOTED WHICH MENTIONS TO WIRE THROUGH LIGHTING CONTROL
 PANEL HOWEVER THE PANELS SUBMITTED DO NOT INDICATE
 THIS. THIS IS ONE EXAMPLE ONLY..
 13-415.1.ABC.1.1, .1.2, .1.3.
  
 4) NOTE: INFORMATION IS NEEDED FOR NEW WAP ( WIRELESS
 ACCESS POINTS) ADDED TO PLANS. THE PLANS SPECIFICALLY
 CALL OUT FOR *RECEPTACLES*. THIS LENDS TO THESE BEING
 INSTALLED IN THE HALLWAYS WITH EQUIPMENT WHICH WILL BE
 PLUGGED IN. THESE WOULD BE REQUIRED TO BE INSTALLED
 BELOW THE CEILING HANGING IN THE HALLWAY.
 PLEASE SEE 400.8. THE FOLLOWING HAS BEEN EXTRACTED FROM
 THE CODE FOR REVIEW.
 **400.8
 USES NOT PERMITTED
 UNLESS SPECIFICALLY PERMITTED IN 400.7, FLEXIBLE CORDS
 AND CABLES SHALL NOT BE USED FOR THE FOLLOWING:
 (1) AS A SUBSTITUTE FOR THE FIXED WIRING OF A STRUCTURE
 (2) WHERE RUN THROUGH HOLES IN WALLS, STRUCTURAL
 CEILINGS, SUSPENDED CEILINGS, DROPPED CEILINGS, OR
 FLOORS
 (3) WHERE RUN THROUGH DOORWAYS, WINDOWS, OR SIMILAR
 OPENINGS
 (4) WHERE ATTACHED TO BUILDING SURFACES
 EXCEPTION TO (4): FLEXIBLE CORD AND CABLE SHALL BE
 PERMITTED TO BE ATTACHED TO BUILDING SURFACES IN
 ACCORDANCE WITH THE PROVISIONS OF 368.56(B)
 SECTION 368.56(B) PROVIDES THE REQUIREMENTS FOR THE
 INSTALLATION OF FLEXIBLE CORDS INSTALLED AS BRANCHES
 FROM BUSWAYS.
 (5) WHERE CONCEALED BY WALLS, FLOORS, OR CEILINGS OR
 LOCATED ABOVE SUSPENDED OR DROPPED CEILINGS
 (6) WHERE INSTALLED IN RACEWAYS, EXCEPT AS OTHERWISE
 PERMITTED IN THIS CODE
 THE FLEXIBLE CORDS AND CABLES REFERRED TO IN ARTICLE
 400 ARE NOT LIMITED TO USE WITH PORTABLE EQUIPMENT.
 THEY MAY NOT BE USED, HOWEVER, AS A SUBSTITUTE FOR THE
 FIXED WIRING OF A STRUCTURE OR WHERE CONCEALED BEHIND
 BUILDING WALLS, FLOORS, OR CEILINGS (INCLUDING
 STRUCTURAL, SUSPENDED, OR DROPPED-TYPE CEILINGS). SEE
 240.5, 590.4(B), AND 590.4(C) FOR THE USES OF
 MULTICONDUCTOR FLEXIBLE CORDS FOR FEEDER AND
 BRANCH-CIRCUIT INSTALLATIONS AND FOR OVERCURRENT
 PROTECTION REQUIREMENTS FOR FLEXIBLE CORD. SEE 410.30
 FOR CORD-CONNECTED LUMINAIRES.
 (7) WHERE SUBJECT TO PHYSICAL DAMAGE
 **
 PLEASE REVISE PLANS ACCORDINGLY AND SUBMIT INFORMATION.
  
 5) NOTE: PLEASE SEE THE LIGHTING ON PLANS AS NOTED ON *
 PROVISO * ISSUED WHEN PERMIT WAS ISSUED HAS NOT BEEN
 ADDRESSED. PLEASE SEE E201 AS SOME OF THE LIGHTING
 STILL NOT COORDINATE WITH THE LIGHTING ON THE ROOM
 LAYOUT PLANS FOR LIGHTING CONTROLS ON E 203,204 ETC.
 EXAMPLES ON THREE PREVIOUS REVIEWS WERE GIVEN AND THEY
 WILL BE GIVEN AGAIN. SEE KING ACCESSIBLE, AND DOUBLE
 QUEEN ACCESSIBLE ETC.
 13-415.1.ABC.1.1, .1.2, .1.3
 FBC 106.1.1 FOR CLARITY, COORDINATION OF PLANS.
 *** CALL TO GO OVER THESE AS THEY CAN BE POINTED OUT.
  
 6) NOTE: THE FOLLOWING SHEETS SIGNED, DATED AND SEALED
 OCT 9TH APPEAR TO BE OK AT THIS TIME HOWEVER BASED ON
 THE COMMENTS ABOVE THE OTHER SHEETS IN SETS MAY ALL
 NEED REVISIONS. THE FOLLOWING SHEETS IF NO CHANGES ARE
 MADE WILL BE STAMPED ONCE RESUBMITTED AND NO
 CORRECTIONS ARE NEEDED.
 PLEASE CALL TO GO OVER IF NEEDED. NO REVISION FEE WILL
 BE CHARGED FOR THESE SHEETS WHEN BRINGING BACK
 CORRECTED PLANS AS LONG AS NO CHANGES ARE MADE.
 107A, 107B, 205,301,302, AND 403. THESE SHEETS DO NOT
 APPEAR TO NEED REVISIONS AT THIS TIME ALTHOUGH THAT MAY
 CHANGE.
  
  
  
  
  
  
  
  
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 6 Status N Date 2008-11-04 Cont ID  
Sent By dpalmer Date 2008-11-04 Time 11:54 Rev Time 0.00
Received By dpalmer Date 2008-11-04 Time 11:54 Sent To FIRE
Notes
2008-11-04 11:55:31FIRE ALARM SUBMITTAL NOT REVIEWED.
 NOT SIGNED BY ENGINEER OF RECORD.
 SENT TO FIRE.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-07-24 Cont ID  
Sent By dpalmer Date 2008-07-24 Time 16:26 Rev Time 0.00
Received By dpalmer Date 2008-07-24 Time 16:26 Sent To  
Notes
2008-07-24 16:26:47** PROVISO **
  
 ** PLEASE SEE THE FOLLOWING ITEMS NEED TO BE REVISED
 AND SUBMITTED FOR REVIEW WITH IN 30DAYS OF ISSUANCE OF
 PERMIT. IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 1) NOTE: CARBON MONOXIDE DETECTORS REQUIRED PER RULE
 9B-3.0472IN UNITS.
  
 2) NOTE: PLEASE SEE LIGHTING SHOWN AND IDENTIFIED ON
 SHEET E-201 NEEDS TO COORDINATE WITH THE LIGHTING SHOWN
 ON GUEST ROOMS. EXAMPLES OF ENLARGED KING, ACCESSIBLE
 KING AND DOUBLE QUEEN WERE GIVEN ON PREVIOUS REVIEW.
 PLEASE SEE THE FIXTURES SHOWN ON E-201 ARE WALL SCONCES
 BASED ON FIXTURE IDENTIFICATION AND FIXTURE LEGEND. THE
 GUEST ROOM LIGHTING CONTROL PLANS CALL FOR SCONCES IN
 MANY LOCATIONS FOR GR1, GR2, GR3 ETC HOWEVER PLEASE SEE
 SOME OF THESE ON THE GUEST ROOM LIGHTING CONTROL PLANS
 ARE CALLING FOR *LAMPS* WITH SENSORS. TABLE LAMPS WITH
 SENSORS ARE NOT THE SAME AS WALL SCONCES WITH A
 LIGHTING CONTROL SYSTEM.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 16:20 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 16:20 Sent To  
Notes
2008-07-18 16:20:59* DENIED 4TH REVIEW**
  
  
  
 1) NOTE: PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS>
 PLEASE SEE COMPLIANCE SUMMARY ON SHEET 2 WHICH APPEARS
 TO DROP THE 7TH DIGIT FROM THE CRITERIA. CALLED AND
 SPOKE TO JIM MULLENS FROM TLC AND THEY WILL WORK ON
 TRYING TO FIX THIS.
 13-400.3.A.
  
 2) NOTE: PLEASE SEE ONE SET OF PLANS IS MISSING E201.
 NEED THREE COMPLETE SETS.
 FBC 106.1
  
 3) NOTE: PLEASE SEE THE LIGHTING SHOWN ON E-201 DOES
 NOT COORDINATE WITH THE LIGHTING WHICH IS NOW SHOWN ON
 SHEETS E 203,204,ETC.
 FOR EXAMPLE:
 PLEASE SEE ENLARGED KING, ACCESSIBLE KING, DOUBLE
 QUEEN.
 13-415.1.ABC.1.1, .1.2
  
 4) NOTE: PLEASE KNOW THE M FIXTURES ON PHOTO-METRICS
 ARE STILL SHOWN. THESE CAN BE REDLINED OFF THE PLANS.
  
 5) NOTE: SMOKE/CARBON MONOXIDE DETECTORS WERE NOT
 REVISED. WILL BE PART OF PROVISO.
  
 ** PLACED CALL TO CONTRACTOR REP AND LEFT MESSAGE.
  
 ** PLACED CALL TO ENGINEER WHICH IS ON VACATION.
 ENGINEER OF RECORD WILL CALL BACK TO WORK OUT ITEMS ON
 PLANS FOR NEW SHEETS.
  
  
  
  
 IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-30 Cont ID  
Sent By dpalmer Date 2008-06-30 Time 15:22 Rev Time 0.00
Received By dpalmer Date 2008-06-30 Time 15:22 Sent To  
Notes
2008-06-30 15:23:07** DENIED THIRD REVIEW **
  
 PLEASE SEE SOME COMMENTS FROM THE PREVIOUS REVIEWS ARE
 IN NEED OF ADDRESSING.
 PLEASE SEE SOME COORDINATION OF OTHER COMMENTS BELOW
 WITH SUPPORTING DOCUMENTS.
  
 1) NOTE: THE PREVIOUS REVIEWS REQUESTED FOR SUBMITTALS
 OF MANUFACTURES SPECS/CUT SHEETS FOR THE ATS,
 GENERATOR, FIRE PUMP AND FIRE PUMP CONTROLLER.
 THE RESPONSE MENTIONS TO SEE SPECS IN THE SUBMITTAL
 BOOKS. PLEASE BE SURE TO COORDINATE SUBMITTALS. FOR
 EXAMPLE:
 PLEASE SEE THERE ARE TWO SUBMITTALS FOR FIRE PUMP: ONE
 SHOWS AURORA, THE OTHER SHOWS MORSE FAIRBANKS. PLEASE
 SEE THERE ARE TWO SUBMITTALS FOR THE FIRE PUMP
 CONTROLLER: ONE SHOWS METRON WHICH DOES NOT INDICATE
 ANY LISTING AND THE OTHER IS A HUBBELL FOR FIRE PUMP
 AND JOCKEY PUMP WHICH DOES SHOW LISTING.
 PLEASE SEE THE ATS SPECS: ONE SHOWS AN ASCO AND THE
 OTHER A CATERPILLAR.
 PLEASE SEE THE GENERATOR SPACES: ONE SHOWS AN ONAN AND
 THE OTHER A CATERPILLAR.
  
 ** PLEASE REMOVE THE DOCUMENTS FORREVIEW AND RECORD
 PLANS. PLEASE BE SURE THE FINAL SPECS DO CONTAIN THE
 LISTING. IF THIS WERE THE ONLY COMMENT A REPRESENTATIVE
 WOULD BE ABLE TO CORRECT IN OFFICE.
 110.3, 90.7, 695 OF NFPA-70, CHAPTER 9 AND 10.
 FBC 106.1.1 FOR CLARITY OF CONSTRUCTION DOCUMENTS.
  
 2) NOTE: PLEASE SEE THE SUBMITTED COORDINATION STUDY
 WHICH WAS PREVIOUSLY REQUESTED. THE INFORMATION ON THE
 STUDY DOES NOT COORDINATE WITH THE SUBMITTED ELECTRICAL
 PLANS. PLEASE SEE SOME EXAMPLES GIVEN.
  
 FOR EXAMPLE:
 PLEASE SEE THE RISER WHICH SHOWS 1-SET OF 3/0 FROM
 GENERATOR TO FIRE PUMP YET THE COORDINATION STUDY SHOWS
 2-SETS OF 4/0.
  
 FOR EXAMPLE:
 PLEASE SEE THE RISER SHOWS 225 FOR ATS-LS, YET THE
 COORDINATION STUDY SHOWS 250AMPS.
  
 FOR EXAMPLE:
 PLEASE SEE THERE IS NO NORMAL FEED TO THE FIRE PUMP.
  
 FOR EXAMPLE:
 PLEASE SEE THE BREAKER OR RISER FOR FIRE PUMP ON THE
 GENERATOR IS SHOWN AS 450AMPS, YET THE COORDINATION
 STUDY SHOWS BREAKER AT 600AMPS.
  
 ** THESE ARE SOME EXAMPLES.
  
 ** PLEASE BE AWARE THAT THESE MUST BE SIGNED, DATED AND
 SEALED BY THE DESIGNER OF RECORD. THESE WERE NOT
 SIGNED, DATED OR SEALED.
 FAC61G15-23.002, 61G15-33.0002, FS 471.025
 NEC 240.12
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO
 *MINIMUM* LIGHTING REQUIRED FOR LIFE SAFETY. PLEASE SEE
 NFPA-101 7.8.1.3, 7.8, 7.9, 7.9.2
 AS THE MINIMUM LEVELS FOR WALK AREAS (NOT STAIRS) IS
 REQUIRED TO BE 1FT CANDLE UNDER NORMAL AS WELL AS 1FT
 CANDLE UNDER EMERGENCY. THERE ARE SOME EXAMPLES GIVEN
 WHICH THE LIGHTING LEVELS ARE AS LOW HALF THE *MINIMUM*
 REQUIRED BY THE LIFE SAFETY CODE.
  
 FOR EXAMPLE:
 PLEASE SEE E-101C AND E-101D CORRIDOR #149 WHICH SHOWS
 .04 FT CANDLES YET THE MINIMUM NEEDS TO BE A MINIMUM OF
 1FT CANDLE.
  
 FOR EXAMPLE:
 PLEASE SEE 603C, 603DAS THE LIGHTING IN AREAS 237,
 242 AND 230 ARE ALL BELOW THE 1FT CANDLE MINIMUM FOR
 EMERGENCY EGRESS. THESE LEVELS ARE SHOWN AS .5 IN
 CORRIDOR 237, .5 IN CORRIDOR 242 AND .6 INEGRESS PATH
 230.
  
 ** THESE ARE EXAMPLES GIVEN AS A BENEFIT TO DESIGN
 TEAM.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO ALL LIGHTING ON PLANS AND THE NEED FOR
 COORDINATION WITH THE SUBMITTED FLA-COM ENERGY
 CALCULATIONS.
 PLEASE SEE SECTIONS, 13-415.2, 13-415.2.ABC.1.1, .1.2
 AND .1.3.
 THIS IS TO INCLUDE ALL INTERIOR AND EXTERIOR LIGHTING.
 SOME EXAMPLES WILL BE GIVEN BELOW. THESE ARE GIVEN AS A
 BENEFIT ONLY.
  
 FOR EXAMPLE:
 PLEASE SEE THE EXTERIOR LIGHTS SUCH AS THE *M* FIXTURES
 SHOWN ON PLANS ON THE SOUTH SIDEWALK YET THESE ARE NOT
 IN ANY EXTERIOR OR INTERIOR LIGHTING IN THE INPUT DATA
 REPORTS.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR ELEVATOR LOBBY MISSING THE SAS
 FIXTURE IN THE IDR. PLEASE ALSO SEE THE SAME ARE FOR
 THE *SP* FIXTURE COUNT.
 ** THIS SAME AREA ON THE METHOD OF CONTROLS INDICATES
 OCCUPANCY SENSORS YET NO OCCUPANCY SENSORS ARE SHOWN ON
 PLANS. THIS APPEARS TO BE AN ERROR IN THE CHOICE OF
 LIGHTING CONTROLS OPTION.
  
 FOR EXAMPLE:
 PLEASE SEE THE INTERIOR LIGHTING IN THE GUEST ROOMS
 NEED TO COORDINATE WITH THE INPUT DATA REPORT. THE
 LIGHTING PLANS ON E-201 AND E-205 ARE NOT THE SAME. IN
 FACT SOME EXAMPLES OF THIS WILL BE GIVEN.
  
 FOR EXAMPLE:
 PLEASE SEE THE KING SUITES.E-201 SHOWS A TOTAL OF 11
 FIXTURES YET THE OTHER LIGHTING PLANS FOR CONTROLS ON
 E-205 SHOW ONLY 8 FIXTURES.
 IN EITHER CASE THE IDR OF THE SUBMITTED ENERGY
 CALCULATIONS ONLY SHOW 7 FIXTURES.
 ** PLEASE LOOK AT LIGHTING PLANS FOR TYPES OF FIXTURES
 AS THERE IS THE DIFFERENCE OF 4 FIXTURES IN EACH OF
 THESE ALONE.
 COORDINATE TYPES OF FIXTURES. (WALL SCONCES ETC)
  
 FOR EXAMPLE:
 PLEASE SEE THE ENLARGED KING ACCESSIBLE UNIT: THIS
 SHOWS DIFFERENT FIXTURES ON E-201 COMPARED TO FIXTURES
 ON E-205. ALL OF THESE UNITS ALSO SHOW A LOWER NUMBER
 OF FIXTURES ON THE IDR. IT IS NOT JUST ONE FIXTURE
 TOTAL, IT IS ONE FIXTURE FOR EACH UNIT.
 ** PLEASE ALSO COORDINATE TYPES OF FIXTURES. (WALL
 SCONCES)
  
 ** THESE WERE S FEW EXAMPLES GIVEN AS A BENEFIT TO
 DESIGN TEAM. THIS IS NOT ALL FIXTURES AS THERE ARE
 OTHERS FOR OTHER UNITS WHICH E201 DOES NOT COORDINATE
 WITH E-205.
  
 5) NOTE: PLEASE BE AWARE OF NEW FLORIDA ADMINISTRATIVE
 CODE RULE 9B-3.0472. THIS REQUIRES ALL BUILDING PERMITS
 ISSUED AFTER JULY 1ST TO CONTAIN CO SENSORS WHEN
 MEETING THE PROVISIONS AND DEFINITIONS AS FOLLOWS.
 PLEASE SEE THIS RULING BECAME IN AFFECT AFTER ADOPTION
 OF FS 553.885.
 ** THIS CAN BE A PROVISO TO ADJUST ALL DEVICES ON PLANS
 HOWEVER PLANS ARE GOING BACK FOR CORRECTIONS AT THIS
 TIME.
  
  
 **********
  
 (1) DEFINITIONS: FORPURPOSES OF THIS RULE, THE
 FOLLOWING DEFINITIONS SHALL APPLY:
 (A) CARBON MONOXIDE ALARM. A DEVICE FOR THEPURPOSE OF
 DETECTING CARBON MONOXIDE, THAT PRODUCES A DISTINCT
 AUDIBLE ALARM,AND IS LISTED OR LABELED WITH THE
 APPROPRIATE STANDARD, EITHER ANSI/UL 2034 -96,
 STANDARD FOR SINGLE AND MULTIPLE STATION CO ALARMS,
 INCORPORATED HEREIN BYREFERENCE, OR UL 2075 - 04, GAS
 AND VAPOR DETECTOR SENSOR, INCORPORATED HEREINBY
 REFERENCE, IN ACCORDANCE WITH ITS APPLICATION. BOTH
 DOCUMENTS MAY BE OBTAINEDBY WRITING TO: CODES AND
 STANDARDS SECTION, DEPARTMENT OF COMMUNITY AFFAIRS,
 2555 SHUMARD OAK BOULEVARD, TALLAHASSEE, FLORIDA
 32399-2100.
  
 (B) FOSSIL FUEL. COAL, KEROSENE,OIL, FUEL GASES, OR
 OTHER PETROLEUM OR HYDROCARBON PRODUCT THAT EMITS
 CARBONMONOXIDE AS A BY-PRODUCT OF COMBUSTION.
  
 (2) EVERY BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED ON OR AFTER 7/1/08 AND HAVING A
 FOSSIL-FUEL-BURNINGHEATER OR APPLIANCE, A FIREPLACE,
 OR AN ATTACHED GARAGE SHALL HAVE ANOPERATIONAL CARBON
 MONOXIDE ALARM INSTALLED WITHIN 10 FEET OF EACH ROOM
 USED FORSLEEPING PURPOSES.
  
 (3) IN NEWCONSTRUCTION, ALARMS SHALL RECEIVE THEIR
 PRIMARY POWER FROM THE BUILDING WIRINGWHEN SUCH
 WIRING IS SERVED FROM THE LOCAL POWER UTILITY. SUCH
 ALARMS SHALL HAVEBATTERY BACK UP.
  
 (4)COMBINATION SMOKE/CARBON MONOXIDE ALARMS SHALL BE
 LISTED OR LABELED BY ANATIONALLY RECOGNIZED TESTING
 LABORATORY.
 SPECIFIC AUTHORITY 553.885(2) FS. LAW IMPLEMENTED
 553.72, 553.73(2), (3), (7), (9), 553.885(2) FS.
 HISTORY,NEW 11-18-07.
  
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-02 Cont ID  
Sent By dpalmer Date 2008-05-02 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2008-05-02 Time 16:07 Sent To  
Notes
2008-05-02 16:08:01** DENIED 2ND REVIEW **
  
 ** PLEASE SEE SOME NOTES FROM PREVIOUS REVIEW ARE STILL
 IN NEED OF ADDRESSING.
 **PLEASE ALSO KNOW THERE ARE SEVERAL NEW COMMENTS DUE
 TO DOCUMENTS SUBMITTED ALONG WITH NEW COMMENTS DUE TO
 SOME NEW CODE INFORMATION.
  
 1) NOTE: PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND
 ALL SUPPORTING DOCUMENTS FOR REVIEW AND STAMPING.
 PLEASE KNOW ONLY TWO BINDERS WITH RESPONSES, SPECS,
 PRODUCT APPROVAL ETC WERE SUBMITTED. THREE DIVISION
 SPEC BOOKS WERE SUBMITTED AND THREE SETS OF PLANS
 HOWEVER ONLY TWO OTHER BOOKS AS MENTIONED.
 THIS IS A THRESHOLD PROJECT.
 FBC 106.1, ETC FOR ADDITIONAL INFORMATION AND
 COORDINATION.
  
 2 NOTE: PLEASE SUBMIT ENERGY CALCULATIONS WHICH
 COORDINATE WITH THE SUBMITTED PLANS. TWO DAYS AFTER
 PLANS WERE RE-SUBMITTED ON APRIL 17TH, THIS REVIEW WAS
 SPEAKING TO ELECTRICAL ENGINEER OF RECORD. THE ENERGY
 CALCULATIONS WERE STILL BEING COMPLETED. THIS REVIEW
 WAS TOLD THE REVISED CALCULATIONS WOULD BE IN THIS
 OFFICE WITHIN A COUPLE OF DAYS. ONE WEEK LATER THE
 CALCULATIONS WERE NOT SUBMITTED. THIS REVIEWER SPOKE
 WITH KAST CONSTRUCTION PROJECT COORDINATOR WITH RESPECT
 TO THE CALCULATIONS WHICH HAD NOT YET BEEN SUBMITTED.
 THE REVIEW WAS PUSHED BACK PAST OTHER PROJECTS IN DATED
 ORDER WAITING FOR THE CALCULATIONS TO BE SUBMITTED.
 PLEASE KNOW AS OF THIS REVIEW DATE 5/2/08 NO REVISED
 ENERGY CALCULATIONS WERE SUBMITTED. THE REVISED
 CALCULATIONS WILL BE REVIEWED ON THE NEXT RE-SUBMITTAL
 OF PLANS.
 *** IMPORTANT ***
 PLEASE BE SURE *ALL* INFORMATION ON PLANS INCLUDING
 LIGHTING, MECHANICAL, BUILDING COMPONENTS ETC ARE
 PLACED INTO THE CALCULATIONS. THIS IS ONE OF THE MAIN
 REASONS PLANS ARE REJECTED FOR NON-CODE COMPLIANCE.
 PLEASE BE SURE TO SEE 13-400.3.A, 13-415.2,
 13-415.2.ABC.1.1, .1.2, .1.3.
 PLEASE SEE 13-411, 13-412 ETC.
 COMPLIANCE FOR CHAPTER 13 AND LIGHTING AND OTHER
 EFFICIENCIES OF THIS BUILDING HAS NOT BEEN MET AND
 PERMIT SHALL NOT BE ISSUED.
 RESPONSE LETTER MENTIONS IN MORE THAN ONE LOCATION TO
 SEE SECTION 7 AND TAB 11 FOR CALCULATIONS HOWEVER THESE
 ARE EMPTY.
  
 3) NOTE: PLEASE GO THROUGH ALL LIGHTING FIXTURES ON THE
 FIXTURE LEGEND. THERE ARE STILL FIXTURES WHICH DO NOT
 SEEM TO BE ACCURATE. AN EXAMPLE OF FIXTURE *SZ* ON
 PREVIOUS REVIEW WAS GIVEN HOWEVER THIS SAME FIXTURE IS
 STILL SHOWN W/ 200VA?
 MANY OF THESE ITEMS CAN NOT BE VERIFIED DUE TO COMMENT
 #2 ABOVE.
 PLEASE COORDINATE ALL.
 FBC 13-415.2, 106.1.2, 106.13.5.1.2
  
 4) NOTE: PLEASE SEE THE INFORMATION ON THE FIRE PUMP
 CONTROLLER SPECS/MANUFACTURES CUT SHEETS IS STILL IN
 QUESTION. THIS WAS BROUGHT UP IN MEETING HELD BEFORE
 PLANS WERE SUBMITTED OF SOME OF THE INFORMATION FOR
 NFPA-20 COMPLIANCE WAS STILL NOT SHOWN ON SPECS/CUT
 SHEETS. THE RESPONSE IN MEETING WAS THAT NEW SPECS/CUT
 SHEETS WOULD BE OBTAINED AND SUBMITTED IN THE BINDERS.
 THIS WAS NOT DONE.
 CAN NOT VERIFY SEVERAL ITEMS FROM NFPA-20.
 PLEASE SEE NO ISOLATION SWITCH, MAIN DISCONNECT ETC
 PLEASE SEE NO NRTL WAS INDICATED ON THESE SAME SHEETS.
 PLEASE SEE NEC 695, 110.3, 90.7
 PLEASE SEE NFPA-20, CHAPTERS 9 AND 10. PLEASE SEE THE
 BELOW IS TEXT EXTRACTED FROM NFPA-20 WHICH WILL GIVE
 SOME EXAMPLES WHICH THIS OFFICE NEEDS TO VERIFY IF THIS
 EQUIPMENT IS MEETING *MINIMUM* CODE COMPLIANCE.
  
 **10.3 CONSTRUCTION.
 10.3.1 EQUIPMENT. ALL EQUIPMENT SHALL BE SUITABLE FOR
 USE IN LOCATIONS SUBJECT TO A MODERATE DEGREE OF
 MOISTURE, SUCH AS A DAMP BASEMENT.
 10.3.2 MOUNTING. ALL EQUIPMENT SHALL BE MOUNTED IN A
 SUBSTANTIAL MANNER ON A SINGLE NONCOMBUSTIBLE
 SUPPORTING STRUCTURE.
 10.3.3 ENCLOSURES.
 10.3.3.1* THE STRUCTURE OR PANEL SHALL BE SECURELY
 MOUNTED IN, AS A MINIMUM, A NATIONAL ELECTRICAL
 MANUFACTURERS ASSOCIATION (NEMA) TYPE 2, DRIPPROOF
 ENCLOSURE(S).
 10.3.3.2 WHERE THE EQUIPMENT IS LOCATED OUTSIDE, OR
 WHERE SPECIAL ENVIRONMENTS EXIST, SUITABLY RATED
 ENCLOSURES SHALL BE USED.
 10.3.3.3 THE ENCLOSURE(S) SHALL BE GROUNDED IN
 ACCORDANCE WITH NFPA 70, NATIONAL ELECTRICAL CODE,
 ARTICLE 250.
 10.3.4 CONNECTIONS AND WIRING.
 10.3.4.1 ALL BUSBARS AND CONNECTIONS SHALL BE READILY
 ACCESSIBLE FOR MAINTENANCE WORK AFTER INSTALLATION OF
 THE CONTROLLER.
 10.3.4.2 ALL BUSBARS AND CONNECTIONS SHALL BE ARRANGED
 SO THAT DISCONNECTION OF THE EXTERNAL CIRCUIT
 CONDUCTORS WILL NOT BE REQUIRED.
 10.3.4.3 PROVISIONS SHALL BE MADE WITHIN THE CONTROLLER
 TO PERMIT THE USE OF TEST INSTRUMENTS FOR MEASURING ALL
 LINE VOLTAGES AND CURRENTS WITHOUT DISCONNECTING ANY
 CONDUCTORS WITHIN THE CONTROLLER.
 10.3.4.4 MEANS SHALL BE PROVIDED ON THE EXTERIOR OF THE
 CONTROLLER TO READ ALL LINE CURRENTS AND ALL LINE
 VOLTAGES WITHIN "5 PERCENT OF FULL SCALE.
 10.3.4.5 CONTINUOUS-DUTY BASIS.
 10.3.4.5.1 UNLESS THE REQUIREMENTS OF 10.3.4.5.2 ARE
 MET, BUSBARS AND OTHER WIRING ELEMENTS OF THE
 CONTROLLER SHALL BE DESIGNED ON A CONTINUOUS-DUTY
 BASIS.
 10.3.4.5.2 THE REQUIREMENTS OF 10.3.4.5.1 SHALL NOT
 APPLY TO CONDUCTORS THAT ARE IN A CIRCUIT ONLY DURING
 THE MOTOR STARTING PERIOD, WHICH SHALL BE PERMITTED TO
 BE DESIGNED ACCORDINGLY.
 10.3.4.6 A FIRE PUMP CONTROLLER SHALL NOT BE USED AS A
 JUNCTION BOX TO SUPPLY OTHER EQUIPMENT.
 10.3.4.7 ELECTRICAL SUPPLY CONDUCTORS FOR PRESSURE
 MAINTENANCE (JOCKEY OR MAKE-UP) PUMP(S) SHALL NOT BE
 CONNECTED TO THE FIRE PUMP CONTROLLER.
 10.3.5 PROTECTION OF AUXILIARY CIRCUITS. CIRCUITS THAT
 ARE NECESSARY FOR PROPER OPERATION OF THE CONTROLLER
 SHALL NOT HAVE OVERCURRENT PROTECTIVE DEVICES CONNECTED
 IN THEM.
 10.3.6* EXTERNAL OPERATION. ALL SWITCHING EQUIPMENT FOR
 MANUAL USE IN CONNECTING OR DISCONNECTING, OR STARTING
 OR STOPPING, THE MOTOR SHALL BE EXTERNALLY OPERABLE.
 10.3.7 ELECTRICAL DIAGRAMS AND INSTRUCTIONS. 10.3.7.1
 AN ELECTRICAL SCHEMATIC DIAGRAM SHALL BE PROVIDED AND
 PERMANENTLY ATTACHED TO THE INSIDE OF THE CONTROLLER
 ENCLOSURE.
 10.3.7.2 ALL THE FIELD WIRING TERMINALS SHALL BE
 PLAINLY MARKED TO CORRESPOND WITH THE FIELD CONNECTION
 DIAGRAM FURNISHED.
 10.3.7.3* COMPLETE INSTRUCTIONS COVERING THE OPERATION
 OF THE CONTROLLER SHALL BE PROVIDED AND CONSPICUOUSLY
 MOUNTED ON THE CONTROLLER.
 10.3.8 MARKING.
 10.3.8.1 EACH MOTOR CONTROL DEVICE AND EACH SWITCH AND
 CIRCUIT BREAKER SHALL BE MARKED TO PLAINLY INDICATE THE
 NAME OF THE MANUFACTURER, THE DESIGNATED IDENTIFYING
 NUMBER, AND THE ELECTRICAL RATING IN VOLTS, HORSEPOWER,
 AMPERES, FREQUENCY, PHASES, AND SO FORTH, AS
 APPROPRIATE.
 10.3.8.2 THE MARKINGS SHALL BE SO LOCATED AS TO BE
 VISIBLE AFTER INSTALLATION.
 10.4 COMPONENTS.
 10.4.1* VOLTAGE SURGE ARRESTER.
 10.4.1.1 UNLESS THE REQUIREMENTS OF 10.4.1.3 OR
 10.4.1.4 ARE MET, A VOLTAGE SURGE ARRESTER COMPLYING
 WITH ANSI/IEEE C62.1, IEEE STANDARD FOR GAPPED
 SILICON-CARBIDE SURGE ARRESTERS FOR AC POWER CIRCUITS,
 OR C62.11, IEEE STANDARD FOR METAL-OXIDE SURGE
 ARRESTERS FOR ALTERNATING CURRENT POWER CIRCUITS (>1
 KV), SHALL BE INSTALLED FROM EACH PHASE TO GROUND. (SEE
 10.3.2.)
 10.4.1.2 THE SURGE ARRESTER SHALL BE RATED TO SUPPRESS
 VOLTAGE SURGES ABOVE LINE VOLTAGE.
 10.4.1.3 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2
 SHALL NOT APPLY TO CONTROLLERS RATED IN EXCESS OF 600
 V. (SEE SECTION 10.6.)
 10.4.1.4 THE REQUIREMENTS OF 10.4.1.1 AND 10.4.1.2
 SHALL NOT APPLY WHERE THE CONTROLLER CAN WITHSTAND
 WITHOUT DAMAGE A 10 KV IMPULSE IN ACCORDANCE WITH
 ANSI/IEEE C62.41, IEEE RECOMMENDED PRACTICE FOR SURGE
 VOLTAGES IN LOW-VOLTAGE AC POWER CIRCUITS.
 10.4.2 ISOLATING SWITCH.
 10.4.2.1 GENERAL.
 10.4.2.1.1 THE ISOLATING SWITCH SHALL BE A MANUALLY
 OPERABLE MOTOR CIRCUIT SWITCH OR A MOLDED CASE SWITCH
 HAVING A HORSEPOWER RATING EQUAL TO OR GREATER THAN THE
 MOTOR HORSEPOWER.
 10.4.2.1.2* A MOLDED CASE SWITCH HAVING AN AMPERE
 RATING NOT LESS THAN 115 PERCENT OF THE MOTOR RATED
 FULL-LOAD CURRENT AND ALSO SUITABLE FOR INTERRUPTING
 THE MOTOR LOCKED ROTOR CURRENT SHALL BE PERMITTED.
 10.4.2.1.3 A MOLDED CASE ISOLATING SWITCH SHALL BE
 PERMITTED TO HAVE SELF-PROTECTING INSTANTANEOUS
 SHORT-CIRCUIT OVERCURRENT PROTECTION, PROVIDED THAT
 THIS SWITCH DOES NOT TRIP UNLESS THE CIRCUIT BREAKER IN
 THE SAME CONTROLLER TRIPS.
 10.4.2.2 EXTERNALLY OPERABLE. THE ISOLATING SWITCH
 SHALL BE EXTERNALLY OPERABLE.
 10.4.2.3* AMPERE RATING. THE AMPERE RATING OF THE
 ISOLATING SWITCH SHALL BE AT LEAST 115 PERCENT OF THE
 FULL-LOAD CURRENT RATING OF THE MOTOR.
 10.4.2.4 WARNING.
 10.4.2.4.1 UNLESS THE REQUIREMENTS OF 10.4.2.4.2 ARE
 MET, THE FOLLOWING WARNING SHALL APPEAR ON OR
 IMMEDIATELY ADJACENT TO THE ISOLATING SWITCH: WARNING
 DO NOT OPEN OR CLOSE THIS SWITCH WHILE
 THE CIRCUIT BREAKER (DISCONNECTING MEANS)
 IS IN CLOSED POSITION.
 10.4.2.4.2 INSTRUCTION LABEL. THE REQUIREMENTS OF
 10.4.2.4.1 SHALL NOT APPLY WHERE THE REQUIREMENTS OF
 10.4.2.4.2.1 AND 10.4.2.4.2.2 ARE MET. 10.4.2.4.2.1
 WHERE THE ISOLATING SWITCH AND THE CIRCUIT BREAKER ARE
 SO INTERLOCKED THAT THE ISOLATING SWITCH CAN BE NEITHER
 OPENED NOR CLOSED WHILE THE CIRCUIT BREAKER IS CLOSED,
 THE WARNING LABEL SHALL BE PERMITTED TO BE REPLACED
 WITH AN INSTRUCTION LABEL THAT DIRECTS THE ORDER OF
 OPERATION.
 10.4.2.4.2.2 THIS LABEL SHALL BE PERMITTED TO BE PART
 OF THE LABEL REQUIRED BY 10.3.7.3.
 10.4.2.5 OPERATING HANDLE.
 10.4.2.5.1 UNLESS THE REQUIREMENTS OF 10.4.2.5.2 ARE
 MET, THE ISOLATING SWITCH OPERATING HANDLE SHALL BE
 PROVIDED WITH A SPRING LATCH THAT SHALL BE SO ARRANGED
 THAT IT REQUIRES THE USE OF THE OTHER HAND TO HOLD THE
 LATCH RELEASED IN ORDER TO PERMIT OPENING OR CLOSING OF
 THE SWITCH.
 10.4.2.5.2 THE REQUIREMENTS OF 10.4.2.5.1 SHALL NOT
 APPLY WHERE THE ISOLATING SWITCH AND THE CIRCUIT
 BREAKER ARE SO INTERLOCKED THAT THE ISOLATING SWITCH
 CAN BE NEITHER OPENED NOR CLOSED WHILE THE CIRCUIT
 BREAKER IS CLOSED.
 10.4.3 CIRCUIT BREAKER (DISCONNECTING MEANS). 10.4.3.1*
 GENERAL.
 10.4.3.1.1 THE MOTOR BRANCH CIRCUIT SHALL BE PROTECTED
 BY A CIRCUIT BREAKER THAT SHALL BE CONNECTED DIRECTLY
 TO THE LOAD SIDE OF THE ISOLATING SWITCH AND SHALL HAVE
 ONE POLE FOR EACH UNGROUNDED CIRCUIT CONDUCTOR.
 10.4.3.1.2 WHERE THE MOTOR BRANCH CIRCUIT IS
 TRANSFERRED TO AN ALTERNATE SOURCE SUPPLIED BY AN
 ON-SITE GENERATOR AND IS PROTECTED BY AN OVERCURRENT
 DEVICE AT THE GENERATOR (SEE 9.6.5), THE LOCKED ROTOR
 OVERCURRENT PROTECTION WITHIN THE FIRE PUMP CONTROLLER
 SHALL BE PERMITTED TO BE BYPASSED WHEN THAT MOTOR
 BRANCH CIRCUIT IS SO CONNECTED.
 10.4.3.2 MECHANICAL CHARACTERISTICS. THE CIRCUIT
 BREAKER SHALL HAVE THE FOLLOWING MECHANICAL
 CHARACTERISTICS:
 (1)IT SHALL BE EXTERNALLY OPERABLE. (SEE
 10.3.6.)
  
 (2)IT SHALL TRIP FREE OF THE HANDLE.
 (3)A NAMEPLATE WITH THE LEGEND "CIRCUIT BREAKER "
 DISCONNECTING MEANS" IN LETTERS NOT LESS THAN 10 MM (
 IN.) HIGH SHALL BE LOCATED ON THE OUTSIDE OF THE
 CONTROLLER ENCLOSURE ADJACENT TO THE MEANS FOR
 OPERATING THE CIRCUIT BREAKER.
  
 10.4.3.3* ELECTRICAL CHARACTERISTICS.
 10.4.3.3.1 THE CIRCUIT BREAKER SHALL HAVE THE FOLLOWING
 ELECTRICAL CHARACTERISTICS:
 (1)A CONTINUOUS CURRENT RATING NOT LESS THAN 115
 PERCENT OF THE RATED FULL-LOAD CURRENT OF THE MOTOR (2)
 OVERCURRENT-SENSING ELEMENTS OF THE NONTHERMAL TYPE
 (3)INSTANTANEOUS SHORT-CIRCUIT OVERCURRENT
 PROTECTION
 (4)*AN ADEQUATE INTERRUPTING RATING TO PROVIDE
 THE SUITABILITY RATING 10.1.2.2 OF THE CONTROLLER (5)
 CAPABILITY OF ALLOWING NORMAL AND EMERGENCY STARTING
 AND RUNNING OF THE MOTOR WITHOUT TRIPPING (SEE
 10.5.3.2.)
 (6)AN INSTANTANEOUS TRIP SETTING OF NOT MORE THAN
 20 TIMES THE FULL-LOAD CURRENT
  
 10.4.3.3.2* CURRENT LIMITERS, WHERE INTEGRAL PARTS OF
 THE CIRCUIT BREAKER, SHALL BE PERMITTED TO BE USED TO
 OBTAIN THE REQUIRED INTERRUPTING RATING, PROVIDED ALL
 THE FOLLOWING REQUIREMENTS ARE MET:
 (1)THE BREAKER SHALL ACCEPT CURRENT LIMITERS OF
 ONLY ONE RATING.
 (2)THE CURRENT LIMITERS SHALL HOLD 300 PERCENT OF
 FULL-LOAD MOTOR CURRENT FOR A MINIMUM OF 30 MINUTES.
 (3)THE CURRENT LIMITERS, WHERE INSTALLED IN THE
 BREAKER, SHALL NOT OPEN AT LOCKED ROTOR CURRENT. (4)
 A SPARE SET OF CURRENT LIMITERS OF CORRECT RATING SHALL
 BE KEPT READILY AVAILABLE IN A COMPARTMENT OR RACK
 WITHIN THE CONTROLLER ENCLOSURE.
  
 10.4.4 LOCKED ROTOR OVERCURRENT PROTECTION. 10.4.4.1
 THE ONLY OTHER OVERCURRENT PROTECTIVE DEVICE THAT SHALL
 BE REQUIRED AND PERMITTED BETWEEN THE ISOLATING SWITCH
 AND THE FIRE PUMP MOTOR SHALL BE LOCATED WITHIN THE
 FIRE PUMP CONTROLLER AND SHALL POSSESS THE FOLLOWING
 CHARACTERISTICS:
 (1)FOR A SQUIRREL-CAGE OR WOUND-ROTOR INDUCTION
 MOTOR, THE DEVICE SHALL BE AS FOLLOWS:
  
 (A)OF THE TIME-DELAY TYPE HAVING A TRIPPING TIME
 BETWEEN 8 SECONDS AND 20 SECONDS AT LOCKED ROTOR
 CURRENT
 (B)CALIBRATED AND SET AT A MINIMUM OF 300 PERCENT
 OF MOTOR FULL-LOAD CURRENT
 (2)FOR A DIRECT-CURRENT MOTOR, THE DEVICE SHALL
 BE AS FOLLOWS:
  
 (A)OF THE INSTANTANEOUS TYPE
 (B)CALIBRATED AND SET AT A MINIMUM OF 400 PERCENT
 OF MOTOR FULL-LOAD CURRENT
 (3)*THERE SHALL BE VISUAL MEANS OR MARKINGS
 CLEARLY INDICATED ON THE DEVICE THAT PROPER SETTINGS
 HAVE BEEN MADE.
 (4)IT SHALL BE POSSIBLE TO RESET THE DEVICE FOR
 OPERATION IMMEDIATELY AFTER TRIPPING, WITH THE TRIPPING
 CHARACTERISTICS THEREAFTER REMAINING UNCHANGED. (5)
 TRIPPING SHALL BE ACCOMPLISHED BY OPENING THE CIRCUIT
 BREAKER, WHICH SHALL BE OF THE EXTERNAL MANUAL RESET
 TYPE.
  
 10.4.4.2 WHERE THE MOTOR BRANCH CIRCUIT IS TRANSFERRED
 TO AN ALTERNATE SOURCE SUPPLIED BY AN ON-SITE GENERATOR
 WHOSE CAPACITY IS 225 PERCENT OR LESS OF THE CAPACITY
 OF THE FIRE PUMP MOTOR AND IS PROTECTED BY AN
 OVERCURRENT DEVICE AT THE GENERATOR (SEE 9.6.5), THE
 LOCKED ROTOR OVERCURRENT PROTECTION WITHIN THE FIRE
 PUMP CONTROLLER SHALL BE PERMITTED TO BE BYPASSED WHEN
 THAT MOTOR BRANCH CIRCUIT IS SO CONNECTED.
  
 ** IT WAS MENTIONED IN THE PREVIOUS MEETING THIS WAS
 NOT NEEDED HOWEVER BASED ON ONLY SOME SECTIONS OF THE
 EXTRACTED CODE IT CAN BE SEEN THIS OFFICE WILL REVIEW
 THESE DOCUMENTS ONCE SUBMITTED.
 PLEASE SUBMIT.
 FBC 106.1.2.
  
 5) NOTE: PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS
 FOR THE GENERATOR AND TRANSFER SWITCHES.
 NFPA-110, NFPA-70, 110.3, 90.7 ETC
 FBC 106.1.2FOR ADDITIONAL INFORMATION/COORDINATION.
  
 6) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH MENTIONED THE
 METER FOR 700S OLIVE WAS NOT TO BE LOCATED ON THIS
 BUILDING. ONE REVISED SITE SHEET DOES SHOW THE
 METER/SERVICE LOCATED OVER AT THE ACTUAL ADDRESS.
 PLEASE SEE THE RESPONSE LETTER EVEN MENTIONS THE PLANS,
 SPECIFICALLY SHEET E-101B WAS REVISED TO RELOCATE.
 PLEASE SEE THE SHEET MENTIONED IN RESPONSE LETTER STILL
 SHOWS THIS METER FOR 700 S OLIVE STILL LOCATED ON
 PLANS.
 PLEASE REMOVE AND UPDATE PLANS.
 FBC 106.1.2 FOR COORDINATION.
  
 7) NOTE: PLEASE KNOW IN THE PREVIOUS MEETING HELD ABOUT
 ONE MONTH BEFORE THIS REVIEW IT WAS MENTIONED A
 POSSIBLE *PROVISO* FOR CODE COMPLIANCE FOR SELECTIVE
 COORDINATION. THE EQUIPMENT FOR THIS PROJECT SHOULD BE
 IN ORDER STATUS WITHIN SHORT FASHION. PLEASE KNOW THIS
 INFORMATION WILL BE REQUIRED WITHIN 30DAYS.
 THESE PLANS WILL BE BACK OUT FOR CORRECTIONS AND
 SELECTIVE COORDINATION MAY BE SUBMITTED WITH REVISED
 PLANS.
 240.12
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE LIGHTING CONTROLS FOR FBC AND
 CHAPTER 13 STILL HAVE SOME ITEMS TO RESOLVE.
 13-415.1.ABC.1.1, .1.2, .1.3 AND .1.4.
  
 A) PLEASE CLARIFY WHERE MAXIMUM TIMES FOR OCCUPANCY
 DEVICES ARE LOCATED ON PLANS. THE WORDING IN THE
 RESPONSE LETTER FOR ROOMS AND OTHER DEVICES DO STATE
 PERMISSIBLE TIMES ALLOWED BY THE CODE HOWEVER THESE
 SHOULD BE STATED ON PLANS.
 PLEASE SEE THE SYMBOLS FOR SOME OF THESE DEVICES ON
 PLANS COULD NOT BE LOCATED ON SYMBOL LEGEND.
 FOR EXAMPLE:
 OC DEVICE IN MANY ROOMS ARE NOT ON SYMBOL LEGEND.
 PLEASE SEE THE NEW ITEMS FOR THE UNITS/GUEST ROOMS
 APPEAR TO BE OK, HOWEVER TWO QUESTIONS FOR THIS
 PROPOSED SYSTEM EXIST.
 PLEASE GIVE SYSTEM FUNCTION ON PLANS. THE RESPONSE
 LETTER IS NOT PART OF THE RECORD PLANS FOR CODE
 COMPLIANCE. THIS WILL INCLUDE MAXIMUM TIMES. PLEASE
 CLARIFY HOW THE PHONE LINE CONNECTION WORKS WITH SYSTEM
 FROM DESK/SYSTEM.
 PLEASE VERIFY THAT BASED ON THE NEW *LOAD CENTER* NOW
 ON PLANS THAT THIS PANEL/EQUIPMENT DOES NOT CONTAIN ANY
 OVER CURRENT PROTECTION. PLEASE SEE 110.26, 408.1,
 240.24 AS NO OVER CURRENT PROTECTION DEVICES SHALL BE
 LOCATED IN CLOTHES CLOSETS.
  
 B) PLEASE VERIFY AND SHOW DETAIL ON HOW *ALL* OUTSIDE
 LIGHTS COMPLY FOR CONTROLS AS REQUIRED PER .1.4. PLANS
 DO CONTAIN AN OCTAGONAL NOTE #5 FOR SOME FIXTURES ON
 THE OUTSIDE OF THE STRUCTURE HOWEVER NOT FOR ALL. WILL
 ALL LIGHTS BE CONTROLLED BY PHOTO-SENSOR ON ROOF? WILL
 THE STREET LEVEL NOT BE DARKER THAN THE ROOF LEVEL?
 WILL THE LIGHTS BE CONTROLLED BY AN ASTRONOMICAL TIME
 CLOCK? IF SO PLEASE SEE MINIMUM TIMES FOR BATTERY BACK
 UP OF PROGRAMMING SHALL BE 10HRS.
 PLEASE SEE OTHER LIGHTS FOR EXAMPLE CIRCUITHP2LW1-36
 WHICH IS NOT CLEAR ON HOW THESE MEET EITHER CONTROL.
  
 C) PLEASE SEE THE LIGHTING CONTROL DEVICES (SWITCHES)
 SHOWN ON LIGHTING SUBMITTALS IN BINDERS DO NOT
 COORDINATE WITH THE LIGHTING CONTROLS AS SHOWN ON
 PLANS.
 PLEASE REVISE PLANS FOR CODE COMPLIANCE. PLANS WILL BE
 THE RECORD SET OF DOCUMENTS NOT THESE SEPARATE
 SUBMITTALS.
  
 9) NOTE: PLEASE SEE ELEVATOR MACHINE ROOM LIGHTING
 CIRCUIT AS THIS IS REQUIRED TO BE DEDICATED PER 620.23.
 PLEASE SEE PANEL SCHEDULE FOR ELSW2-18 WHICH MENTIONS
 *MEZZANINE LIGHTING*.
  
 10) NOTE: PLEASE SEE EQUIPMENT IN GUEST LAUNDRY ROOM.
 PLEASE SEE DRYERS WHICH ARE SHOWN AS 30AMPS ON
 EQUIPMENT SCHEDULE YET THE PANEL SCHEDULES SHOW
 50AMPS.
 PLEASE COORDINATE.
 FBC 106.1.2
 NEC 408.4, 240.4 ETC
  
 11) NOTE: PLEASE VERIFY THE RECEPTACLES ON THESE SAME
 DRYERS IN GUEST LAUNDRY ROOM AS THE PLANS INDICATE A
 RECEPTACLE SYMBOL AND BASED ON SYMBOL LEGEND THESE ARE
 PLUG IN UNITS. HOWEVER PLEASE SEE EQUIPMENT SCHEDULE
 FOR THESE SAME UNITS AS THIS STATES THESE ARE
 HARDWIRED.
 PLEASE COORDINATE.
 PLEASE ALSO KNOW AS PER 422.31 IF THESE ARE HARDWIRE
 UNITS, DISCONNECTS WILL BE REQUIRED.
  
 12) NOTE: PLEASE SEE NEC 700, 701 AND 702.
 PLEASE KNOW LOADS CONSIDERED LIFE SAFETY SHALL BE THE
 ONLY LOADS ON ATS0LS. PLEASE KNOW OTHER LOADS
 CONSIDERED UNDER LEGALLY REQUIRED OR OPTIONAL STAND-BY
 IS NOT PERMITTED ON THE SAME ATS, PANELS OR EQUIPMENT.
 PLEASE SEE THE SAME GOES FOR THE LEGALLY REQUIRED ITEMS
 (LOADS ON WITHIN 60 SECONDS) AND LOADS REQUIRED BY
 CODES, ETC SHALL NOT CONTAIN LIFE SAFETY LOADS OR
 OPTIONAL STAND-BY LOADS.
 FOR EXAMPLE;
 PLEASE SEE ITEMS SUCH AS DATA RECEPTACLES, SMOKE
 DAMPERS ETC SHALL NOT BE ON THE LS SYSTEMS.
 PLEASE SEE THESE ITEMS ABOVE WOULD ACTUALLY BE ON TWO
 SYSTEMS.
 SMOKE DAMPERS WOULD BE LEGALLY REQUIRED AND DATA
 RECEPTACLES WOULD BE OPTIONAL STAND-BY.
 PLEASE EXPLAIN WHY THE RECEPTACLE IN THE GUEST LAUNDRY
 ROOM #238 WOULD BE ON THE LS SYSTEM? ( ELSE2-9)? PLEASE
 SEE ITEMS SUCH AS GENERATOR OIL PUMP WOULD NEED TO BE
 ON THE LS SYSTEM AS THIS IS CRITICAL FOR THE RUNNING OF
 THE GENERATOR WHICH IS LIFE SAFETY. PLEASE COORDINATE
 ALL. PLEASE CONTACT THIS OFFICE TO GO OVER ITEMS.
 AT THIS POINT AN OPTIONAL STAND-BY ATS WILL BE REQUIRED
 AS THERE ARE SEVERAL ITEMS WHICH CAN NOT BE CONSIDERED
 LIFE SAFETY OR LEGALLY REQUIRED BY CODE.
 700.9, 701.10, 702.9 ETC
  
 13) NOTE: PLEASE SEE THE PHOTO-METRIC LEVELS ON ALL
 EGRESS AREAS AS PREVIOUSLY REQUESTED NEED TO BE
 COMPLETED.
 PLEASE SEE SOME AREAS LIKE THE GARAGE DOES NOT HAVE THE
 LIGHTING LEVELS COMPLETED.
 THIS CAN BE SEEN ON E-603C, 603D FOR ONE EXAMPLE.
 PLEASE SEE THE LIGHTING LEVELS ARE NOT SHOWN ON ANY
 TABLES SO THE AVERAGE IS NOT STATED, SHOWN ETC. FOR
 EXAMPLE:
 PLEASE SEE ONE LOCATION WHICH THERE IS QUESTION ON WHAT
 FIXTURES WERE USED AND APPEARS LEVELS DO NOT MEET
 MINIMUM REQUIRED BY CODE IS THE EGRESS EXIT ACCESS
 HALLWAY JUST TO THE WEST OF THE DRIVE ON THE SOUTH SIDE
 OF THE BUILDING.
 THIS HALLWAY CONTAINS ME FIXTURES ALONG WITH WALL
 MOUNTED BATTERY BACK UP LIGHTS.
 IF THE NORMAL LEVEL FIGURES THESE ME FIXTURES AND THESE
 FIXTURES ARE BATTERY BACK UP BASED ON THE FIXTURE
 LEGEND HOW IS IT THE LIGHTING LEVELS GO DOWN AS MUCH AS
 SHOWN? NORMAL LEVEL SHOWS IN EXCESS OF 20 FC, YET UNDER
 EM, IT APPEARS TO BE LESS THAN 1 FC.
 PLEASE VERIFY THIS ALONG WITH THE LEVEL SHOWN.
 FOR EXAMPLE:
 PLEASE SEE POOL AREA EGRESS PATHS WHICH DO NOT MEET
 MINIMUM LEVELS PER LIFE SAFETY CODE UNDER EMERGENCY
 CONDITIONS.
 PLEASE SEE MINIMUM LEVELS NEED TO BE SHOWN ON ALL
 SHEETS ON TABLE FOR AREAS.
 *** IMPORTANT ***
 IT IS IMPORTANT TO KNOW THAT THESE ARE TWO EXAMPLES
 ONLY. THIS IS GIVEN AS A BENEFIT ONLY AND IS IN NO WAY
 AN EXHAUSTED LIST OF ALL POSSIBLE AREAS IN QUESTION.
 PLEASE SEE 2003 NFPA-101 7.8, 7.9, 7.8.1.3, 7.9.2.2
  
 14) NOTE: PLEASE SEE THE PREVIOUS REVIEW WHICH
 REQUESTED THE PHOTO-METRIC LEVELS FOR SWIMMING POOL
 AREA BE SUBMITTED TO THE PALM BEACH COUNTY HEALTH
 DEPARTMENT FOR REVIEW AND STAMPING. THE RESPONSE
 MENTIONS THIS WILL BE DONE, HOWEVER BASED ON THE
 SUBMITTED PLANS NO REVIEW STAMPS FROM THE ABOVE
 MENTIONED PBCHD WAS LOCATED ON SAID PLANS.
 THIS IS AND WILL BE REQUIRED.
  
 15) NOTE: PLEASE KNOW AS NOTED PREVIOUSLY ON NOTES, PER
 PLANS AND RESPONSE LETTER: *ALL* ACCESS CONTROLS
 SYSTEMS SHALL BE UNDER SEPARATE PERMIT AND COMPLETED
 PLANS, SIGNED, DATED AND SEALED BY A FLORIDA LICENSED
 PE. IF THIS INFORMATION IS INCLUDED ON THESE PLANS THIS
 WILL NOT BE REQUIRED.
 ** THIS NOTED ONLY FOR INFORMATIONAL PURPOSE.
  
 16) NOTE: PLEASE KNOW THE LS1 FIXTURES WHICH APPEAR AS
 STREET POLE LIGHTS WILL NOT BE PART OF THIS BUILDING
 PLANS, PERMITS, CONTROLS ETC. IF THESE ARE LOCATE DIN
 THE RIGHT OF WAY THESE WILL BE FED FROM RIGHT OF WAY
 POWER AND WILL NOT BE PART OF THE BUILDING. THIS IS IN
 CONFLICT HOWEVER WITH THE NOTE #5 ON SHEET E101C AS
 THESE MENTION TO BE CONTROLLED BY RELAY
 PANEL/PHOTO-SENSOR.
 PLEASE VERIFY THIS AT THIS TIME AS THIS WILL AFFECT
 ENERGY CALCULATIONS, LOAD CALCULATIONS, CONTROLS,
 PERMITTING ETC.
 FBC 106.1.2
  
 17) NOTE: PLEASE SEE NOTICE TO FS 553.80(2)(B) IS BEING
 GIVEN AT THIS TIME AS THERE ARE SOME CODE COMPLIANCE
 COMMENTS REPEATED THE SECOND TIME.
 PLEASE KNOW THIS IS ONLY A NOTICE GIVEN AT THIS TIME.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-02-06 Cont ID  
Sent By dpalmer Date 2008-02-06 Time 15:42 Rev Time 0.00
Received By dpalmer Date 2008-01-29 Time 08:06 Sent To  
Notes
2008-02-06 15:42:19 
  
 ** DENIED REVIEW **
  
 HYATT HOTEL
 295 LAKEVIEW AVE.
  
 1) NOTE: PLEASE BE SURE ALL OF THE FOLLOWING RELEVANT
 CODES ARE STATED ON PLANS. AT THIS POINT IN TIME SOME
 ARE ALREADY SHOWN ON SOME SHEETS HOWEVER NOT ALL. THE
 FOLLOWING WILL NEED TO BE PART OF ARCHITECTURAL,
 ELECTRICAL AND FIRE PROTECTION PLANS WHICH WERE NOT YET
 SUBMITTED
 2005 NFPA-70
 2003 NFPA-101
 2003 NFPA-20
 2002 NFPA-110
 FBC 2004 W/2007 REVISIONS.
  
 ** PLEASE BE AWARE PLANS NOTE JURISDICTION AS *PALM
 BEACH COUNTY * AS WELL AS CITY OF WEST PALM BEACH. THIS
 IS ONLY LOCATED IN THE CITY OF WEST PALM BEACH.
  
  
 2) NOTE: PLEASE KNOW AS THERE WERE SOME ITEMS NOT
 SUBMITTED FOR REVIEW A COMPLETE AND FULL REVIEW COULD
 NOT BE DONE. PLEASE ALSO SEE NOTES BELOW WITH RESPECT
 TO FBC AND CHAPTER 13.
 PLEASE SUBMIT THREE COMPLETE SETS OF PLANS AND ALL
 DOCUMENTATION.
 PLEASE SUBMIT FIRE SPRINKLER PLANS. WHILE THESE WILL BE
 UNDER SEPARATE PERMIT AND REVIEWED BY OTHER TRADES AS
 WELL, THE BASE SET OF BUILDING PLANS AS IT IS REQUIRED
 TO BE SPRINKLED WILL BE REQUIRED TO SHOW A BASE
 DESIGNED SYSTEM.
 PLEASE SEE COMMENTS FROM OTHER TRADES SUCH AS
 MECHANICAL FOR SYSTEMS WHICH ARE NOT COMPLETE FOR
 ELECTRICAL CONNECTIONS AS WELL AS MECHANICAL. (EXAMPLE:
 GARAGE VENTILATION, ETC)
 AT THIS TIME CROSS REFERENCE AND REVIEW OF FIRE
 EQUIPMENT AND OTHER SYSTEMS CAN NOT BE COMPLETED. FBC
 106.1.2, 106.3.5.1.2 ETC ADMIN SECTION.
 FBC MECHANICAL CODE, FIRE CODE NFPA-1, LIFE SAFETY 101
 ETC.
 FS 633
  
 3) NOTE: PLEASE SEE THE NEW BUILDING IS SHOWING THE
 SERVICE METER FOR 700 S OLIVE LOCATED ON THE SIDE OF
 THIS BUILDING WHICH IS NOT PERMITTED. THE FPL VAULT
 AREA IS REQUIRED TO HAVE AN FPL EASEMENT ALONG WITH ANY
 UNDERGROUND EASEMENTS TO RE-FEED THE EXISTING BUILDING
 LOCATED ON THE NORTH SIDE OF PROPERTY. THE METERING
 DEVICE(S) WOULD BE LOCATED ON THE PROPERTY OF 700 S.
 OLIVE.
 PLEASE RELOCATE.
  
 4) NOTE: PLEASE CONTACT FPL WITH RESPECT TO ELECTRICAL
 PERMITTED INSIDE THEIR VAULT AREA. PLANS SHOW LIGHTING,
 EXIT SIGNS, AND RECEPTACLES WHICH BY THE FPL STANDARDS
 AND GUIDES IS NOT PERMITTED.
 THIS IS KNOWN TO THIS OFFICE AND IS BEING GIVEN FOR
 INFORMATIONAL PURPOSE TO REVISE PLANS AT THIS TIME.
  
 5) NOTE: PLEASE SEE POSSIBLE COMMENTS FROM BUILDING
 TRADE WITH RESPECT TO ANY EGRESS STAIRS OR HALLWAY DOOR
 SWINGS. THIS IS NOT AN ELECTRICAL ISSUE HOWEVER WOULD
 AFFECT THE ELECTRICAL PLANS. THIS IS FOR INFORMATION
 ONLY AND NOT A REVIEW COMMENT FOR CODE COMPLIANCE.
  
 6) NOTE: PLEASE SEE 240.12 AND SUBMIT A SELECTIVE
 COORDINATION STUDY FOR LIFE SAFETY AND LEGALLY REQUIRED
 EQUIPMENT. THIS IS ALSO REQUIRED UNDER NFPA-110 6.5.2,
 6.5.3 ETC
  
 7) NOTE: PLEASE SUBMIT COMPLETED PLANS AND SUPPORTING
 DOCUMENTS FOR FBC REQUIRED CHAPTER 13 COMPLIANCE.
 PLEASE SEE SUB SECTIONS BELOW ARE BROKEN UP FOR CHAPTER
 13. PLEASE SEE REFERENCES IN NOTES BELOW TO THE INPUT
 DATA REPORT WILL BE ABBREVIATED AS IDR.
  
 A) ** PLEASE SUBMIT COMPLETE ENERGY CALCULATIONS PER
 FBC 13-400.3.A, AND 13-415.2. PLEASE SEE THERE ARE
 SEVERAL ITEMS WHICH ARE IN NEED OF ADDRESSING. PLEASE
 SEE SEVERAL EXAMPLES WILL BE GIVEN BUT IS IN NO WAY ALL
 ITEMS FOUND:
 PLEASE SEE THE METHOD OF CONTROL IS ALL BEING SHOWN AS
 *MANUAL ON/OFF* WHICH IS NOT POSSIBLE WHEN AUTOMATED
 SYSTEMS ARE REQUIRED ON MOST.
 PLEASE SEE THE EXTERIOR LIGHTING ON THE IDR SHOWS A
 TOTAL OF ONLY 9 FIXTURES. HOW IS THIS POSSIBLE WHEN THE
 PLANS SHOW MANY MORE FIXTURES THAN THIS?
 PLEASE SEE NO LIGHTING FOR GARAGE AREAS ARE SHOWN
 FIGURED INTO THE IDR. HOW IS THIS POSSIBLE? THIS
 ACCOUNTS FOR HUNDREDS OF FIXTURES. 13-415.2.ABC.1.3
 PLEASE SEE NO BREAK UP FOR TRACK LIGHTING. THIS IS
 NOTED SPECIFICALLY AS THIS IS A COMMON ISSUE.
 13-415.2.ABC.1.2
 PLEASE SEE 13-415.2,
 ** PLEASE CALL TO GO OVER THE LIGHTING CALCULATIONS IS
 THERE ARE ANY QUESTIONS.
  
 B) ** PLEASE SEE THE SUBMITTED ENERGY CALCULATIONS IN
 FACT CONTAIN A RAISED SEAL OVER A PHOTO-COPIED
 SIGNATURE ON ALL SETS SUBMITTED. THIS IS ALSO THE CASE
 FOR THE MECHANICAL CALCULATIONS ALSO ATTACHED TO THE
 ENERGY CALCULATIONS.
 PLEASE SEE FLORIDA STATUTES 471.025 AND FLORIDA
 ADMINISTRATIVE CODE 61G15-23.002 WHICH REQUIRES AN
 *ORIGINAL* SIGNATURE AND DATE ON ALL DOCUMENTS. THIS
 COMMENT IF ALL TRADES AND FOR ALL DOCUMENTS WHETHER OR
 NOT COMMENT IS MADE BY OTHER REVIEW TRADES.
 FBC 13-103.1.1.1
  
 C) ** PLEASE BE SURE THE OWNER AGENT IS SIGNED ON THE
 CERTIFICATION SHEETS ONCE NEW METHOD *A* CALCULATIONS
 ARE COMPLETE BEFORE RESUBMITTING PLANS. 13-103.1
  
 D) ** PLEASE SEE THERE ARE SEVERAL FIXTURE WATTAGES ON
 THE IDR FOR INTERIOR LIGHTING WHICH DOES NOT CORRELATE
 WITH THE SAME FIXTURE WATTAGES ON THE FIXTURE LEGEND
 SUBMITTED ON PLANS. THERE ARE SOME EXAMPLES BUT IN NO
 WAY ALL.
 PLEASE SEE LS-2 70W AND 200W,
 PLEASE SEE IDR WITH 75W FIXTURES AND NONE ON PLANS.
 PLEASE SEE R, RE NO 250W ON IDR,
 PLEASE SEE SH WHICH SHOWS A 120W MR-16, (HOW IS THIS
 POSSIBLE?)
 PLEASE SEE SZ SHOWS 200VA ON FIXTURE LEGEND FOR MR-16?
 PLEASE SEE SAXE WHICH SHOWS 75W T-8 WITH A TOTAL OF
 150VA? (HOW IS THIS POSSIBLE?)
 PLEASE SEE GR2 AND GR3 WHICH SHOWS 2-17W BULBS WHICH IS
 SHOWING A TOTAL OF 13WATTS. HOW IS THIS POSSIBLE? (2X17
 IS 34)
  
 THESE ARE SOME EXAMPLES HOWEVER NOT ALL ITEMS. THIS
 OFFICE CAN NOT EMPHASIZE ENOUGH TO PLEASE MAKE SURE ALL
 LIGHTING WHICH IS SHOWN ON PLANS COORDINATES WITH NOT
 ONLY THE FIXTURE LEGEND BUT MORE IMPORTANTLY THE INPUT
 DATA REPORT AND INFORMATION INSERTED INTO THE ENERGY
 CALCULATIONS.
  
 E) ** PLEASE SUBMIT MORE INFORMATION ON PROPOSED
 LIGHTING CONTROLS FOR COMMONS AREAS. THE INFORMATION
 SUBMITTED NEEDS TO PROVIDE MORE DETAILS ON TIMES, OVER
 RIDE DEVICES AND LOCATIONS. PLANS SHOW LIGHTING CONTROL
 PANELS IN MANY LOCATIONS HOWEVER NO OVER RIDE DEVICES
 AS REQUIRED PER THE FBC COULD BE LOCATED FOR MOST
 AREAS.
 PLEASE SE E13-415.1.ABC.1.1, .1.2 AND .1.3
 PLANS SHOWS LIGHTING CONTROL PANELS/DIMMING PANELS ON
 MOST FIXTURES YET COULD NOT LOCATE MORE DETAILED
 INFORMATION ON HOW COMMON AREAS ARE BEING CONTROLLED BY
 DIMMING PANELS. (SEE COMMENTS WITH RESPECT TO EGRESS
 LIGHTING)
  
 F) ** PLEASE INDICATE ALL MAXIMUM TIMES ON ALL
 OCCUPANCY SENSORS SHOWN ON PLANS AND OVER RIDES PER
 13-415.1.ABC.1.1, .1.2.
 PLEASE SEE THERE ARE SYMBOLS ON PLANS WHICH ARE NOT
 REFLECTED ON SYMBOL LEGEND OR ON LIGHTING CONTROL
 DETAIL SHEETS.
  
 G) ** PLEASE SUBMIT MORE DETAILS AND COMPLETE
 INFORMATION FOR GUEST ROOM CONTROLS. THE PLANS MAKE
 NOTE OF SOME SORT OF SYSTEM ON E201 YET NOT ENOUGH FOR
 REVIEW. 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 H) ** PLEASE SEE 13-413.1.ABC.2, .2.1 AND .2.2 FOR
 REQUIRED NOTES TO BE PLACED ON PLANS.
  
 I) ** PLEASE SEE THE SQUARE FOOTAGE ON ENERGY
 CALCULATIONS NEEDS TO COORDINATE WITH THE PLANS.
  
 J) ** PLEASE CLARIFY THE TYPE OF OCCUPANCY SENSOR
 DEVICE WHICH IS LOCATED IN BATHROOMS. PLEASE VERY
 FAILSAFE ON OR MULTIPLE SENSING. MAY NOT ONLY BE MOTION
 SENSING DEVICE ON BATHROOMS MORE THAN SINGLE POINT
 USE.
  
 ** PLEASE SEE ALL OF CHAPTER 13 FOR ELECTRICAL AND
 OTHER TRADES. THE ABOVE NOTES ARE EXAMPLES OF ITEMS AND
 AREAS OF CONCERN.
  
 8) NOTE: PLEASE INCLUDE COLOR CODING FOR 277/480V
 SYSTEMS AS BROWN, PURPLE, AND YELLOW.
 THE NEC DOES NOT PROVIDE COLOR CODING FOR THESE
 SYSTEMS. THESE SYSTEMS OF THIS SAME VOLTAGE IN THIS
 COUNTY AND CITY UNDER THE PREVIOUS ADOPTED TECHNICAL
 AMENDMENTS FOR SEVERAL DECADES HAS HAD THIS SAME COLOR
 CODING AND IN THE INTEREST OF SAFETY AND AS WELL AS
 CONSISTENCY THIS AHJ REQUIRES THE ABOVE COLORING. 90.4
 FBC 106.1.2
  
 9) NOTE: PLEASE SUBMIT FIRE PUMP CONTROLLER
 MANUFACTURES SPECS AND CUT SHEETS WHICH REFLECT A
 LISTING FROM A NRTL. (NATIONALLY RECOGNIZED TESTING
 LABORATORY).
 110.4, 659.4, 90.7
 NFPA-20 CHAPTER 9 (ALL AS THERE ARE TOO MANY TO LIST)
 AND 10 ETC. 10.4.3.3.1, 10.4.4, ETC
 PLEASE PROVIDE INFORMATION ON ROUTING OF CONDUITS FROM
 FPL VAULT TO THE FIRE PUMP CONTROLLER AND FIRE PUMP.
 PLEASE SHOW ON PLANS AS WELL AS PROTECTIONS OF THE
 INSTALLATIONS DEPENDING ON DESIGN.
 AT THIS TIME AS INFORMATION WAS NOT CLEAR OR SUBMITTED
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 10) NOTE: PLEASE SUBMIT MINIMUM FUEL TIMES ON THE
 GENERATOR FOR BACK UP OF FIRE PUMP AND OTHER LIFE
 SAFETY AND LEGALLY REQUIRED SYSTEMS.
 NFPA-70, 700, 701, NFPA-110, CHAPTER 7, 7.9, NFPA-20
 9.6.2.2
 PLEASE ACTUALLY INDICATE THE ELEVATION OF THE
 EQUIPMENT. THE PLANS STATE A NOTE TO BE ABOVE THE 100
 YEAR STORM SURGE LEVEL, HOWEVER PLEASE INDICATE WHERE
 AND/OR WHAT THAT LEVEL IS. PLEASE SEE NFPA-110 7.2.3 **
 PLEASE SEE ANY COMMENTS FROM OTHER TRADES WITH RESPECT
 TO LOCATION OF GENERATOR, EXHAUST, MAKE UP AIR ETC.
  
 11) NOTE: PLEASE SEE NFPA-110 7.3.3 WHICH REQUIRES A
 MINIMUM OF 30FT CANDLES OF LIGHTING IN ROOM. PLEASE BE
 SURE TO INCLUDE THIS ON PLANS OR ON THE LIGHTING
 PHOTO-METRICS. (PLEASE SEE OTHER COMMENTS WITH RESPECT
 TO PHOTO-METRICS).
  
 12) NOTE: PLANS SHOW A NOTE WITH RESPECT TO FIRE ALARM
 DEVICES AND MINIMUM LEVELS, HOWEVER PLEASE SEE
 11-4.28.1, .2 AND .3. PLEASE BE SURE ALL MINIMUM LEVELS
 ARE SHOWN.
  
 13) NOTE: PLEASE KNOW EVEN AS MANY LOW VOLTAGE
 SYSTEMS/ITEMS ARE SHOWN ON PLANS, SEPARATE PERMITS WILL
 BE REQUIRED. PLEASE KNOW ANY INSTALLED LOW VOLTAGE
 SYSTEMS WHICH ARE NOT COMPLETED ON THESE PLANS WILL
 REQUIRE SEPARATE PLANS.
 FIRE ALARM SYSTEM IS SEPARATE PERMIT AND PLANS. PLEASE
 KNOW THE LIGHTNING PROTECTION SYSTEM AS NOTED ON PLANS
 WILL REQUIRE SEPARATE PLANS AND PERMIT.A COMPLETE
 SYSTEM IS NOT SHOWN.
 ** THIS IS PROVIDED FOR INFORMATION AT THIS TIME.
  
 14) NOTE: PLEASE SUBMIT MORE INFORMATION ON ACCESS
 CONTROLS AS SHOWN ON PLANS. PLEASE SHOW AND INDICATE
 HOW THE EGRESS PATHS ARE AFFECTED IN THE EVENT OF NOT
 ONLY POWER FAILURE BUT ALSO IN AN EMERGENCY. PLEASE SEE
 THE DETAIL SHOWN ON SHEET E-406 DOES NOT PROVIDE ENOUGH
 INFORMATION AT THIS TIME.
 PLEASE SEE NFPA-101 7.5.1,7.5.2, 7.1.9, 7.2.1.6.2 ETC
 PLEASE PROVIDE FAIL SAFE OPERATIONS AND BE AWARE OF
 REVIEW FROM FIRE MARSHAL.
 PLEASE SUBMIT INFORMATION ON GATE OPERATIONS IN THE
 SAME SCENARIO AS STATED ABOVE.
  
 15) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR ALL
 EGRESS PATHS UNDER NORMAL AND EMERGENCY CONDITIONS.
 THIS SHOULD INCLUDE GARAGE AREAS, GENERATOR ROOM
 PREVIOUSLY NOTED ABOVE, ALL STAIR LOCATIONS. PLEASE
 KNOW THE STAIR POINT BY POINT DOES NOT SHOW ALL AREAS
 OF THE STAIR WALKING SURFACES AS AN AVERAGE UNDER EACH.
 PLEASE CLARIFY WHY HOW THE SAME AMOUNT OF FIXTURES ARE
 SHOWING LESS LIGHTING UNDER EMERGENCY CONDITION. IS THE
 BATTERY BACK UP BALLAST BASED ON LOWER LUMENS BACK UP?
 PLEASE ALSO PROVIDE MINIMUM LEVELS FOR ELEVATOR PIT PER
 620.23 ( PLEASE SEE NEC WHICH REFERENCES MINIMUM LEVELS
 PER ASME A17.1-2004 WHICH REFLECT SAFETY CODE FOR
 ELEVATORS AND ESCALATORS.
 ** MOST IMPORTANT, WILL BUILDING REMAIN *OCCUPIED*
 UNDER GENERATOR POWER PAST THE MINIMUM LEVELS FOR
 FUEL?
  
 WILL THE FAILURE OF THE SINGLE MAIN BREAKER ON THE
 EMERGENCY PANEL OR GENERATOR LEAVE NO EGRESS LIGHTING
 IN AREAS?
 PLEASE KNOW WHEN A BUILDING IS OCCUPIED AND UNDER
 GENERATOR POWER AND AN EMERGENCY EVENT OF SOME NATURE
 OCCURS, THE FAILURE OF THE GENERATOR, MAIN BREAKER ETC
 WILL LEAVE ANY EGRESS AREA IN TOTAL DARKNESS? THE STAIR
 TOWERS AND MANY LOCATIONS DO CONTAIN BATTERY BACK UP
 FIXTURES OF SOME SORT DURING AN EMERGENCY FOR OCCUPANTS
 TO FIND THEIR WAY OUT OF THE BUILDING BUT NOT ALL.
 PLEASE BE SURE TO SEE 700.12F FOR CIRCUITING OF
 EMERGENCY AND EXIT LIGHTS. MANY ARE SHOWN CIRCUITED TO
 A LOCAL BRANCH CIRCUIT AS REQUIRED BUT NOT ALL. THERE
 ARE EXCEPTIONS TO THIS SECTION OF THE CODE BUT ONLY FOR
 UNINTERRUPTED AREAS CONTAINING 3 OR MORE BRANCH
 CIRCUITS.
 PLEASE EXPLAIN HOW MANY OF THESE LIGHT FIXTURES ARE
 SHOWN ON DIMMING PANELS? PLANS CONTAIN NOTES FOR SOME
 CIRCUITING BUT NOT ALL.
 PLEASE KNOW THE FOLLOWING LOCATIONS WILL REQUIRE
 BATTERY BACK UP FIXTURES OF SOME SORT: FIRE PUMP ROOM,
 FIRE CONTROL AREA WHICH SHOWS FACP AND GAP, GENERATOR
 ROOM, MAIN ELECTRICAL ROOM, AND ELEVATOR MACHINE ROOM.
 PLEASE KNOW SOME OF THESE ARE SHOWN BUT NOT ALL. PLEASE
 SEE NOTES ABOVE WITH RESPECT TO FBC CHAPTER 13 AS THIS
 WILL AFFECT ALL LIGHTING IN BUILDING. PLEASE SEE
 NFPA-101 7.8., 7.8.1.3, 7.9, 7.9.2.2 ETC. FAC
 61G15-33.004
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION
 NEEDED.
 NEC 700.12F, 700.16
  
 16) NOTE: PLEASE SUBMIT COMPLETED PHOTO-METRICS FOR
 POOL/SPA AREAS STAMPED FROM PALM BEACH COUNTY HEALTH
 DEPARTMENT. AS THIS AREA IS INSIDE BUILDING AND NOT
 OPEN TO SUN LIGHT LEVELS DURING DAY OR NIGHT, ANY DUSK
 TO DAWN NOTES OR RULES WOULD NOT APPLY.
 PLEASE OBTAIN STAMPS.
 FBC ADMIN SECTION 106.1.2 FOR ADDITIONAL INFORMATION.
  
 17) NOTE: PLEASE SEE 2005 NFPA-70 WHICH REQUIRES GFI
 PROTECTION ON ALL 15/20 AMP 120V RECEPTACLES IN KITCHEN
 AREAS AND THE LIKE. PLEASE KNOW THIS ALSO IS REQUIRED
 FOR DEDICATED EQUIPMENT SUCH AS REFRIGERATORS ETC.
 PLEASE SEE FOR EXAMPLE: KITCHEN PLANS, KP1-7. THIS IS
 ONLY ONE EXAMPLE AND THERE ARE SEVERAL OTHERS INCLUDING
 SERVING AREAS/BUFFET ETC.
 THIS WAS CHANGED IN THE 2002 NEC AS WELL AS MINOR
 MODIFICATIONS IN THE 2005.
  
 18) NOTE: PLEASE COMPLETE INFORMATION ON FOOD SERVICE
 PLANS FOR TITLE BLOCKS AND DESIGN PROFESSIONAL(S).
 PLEASE SEE FAC 61G15-23.002.
  
 19) NOTE: PLEASE COMPLETE ALL ROOM AND AREA
 DESIGNATIONS ON PLANS. REVIEW OF CIRCUITING AND
 NUMEROUS OTHER ITEMS FOR LIGHTING CONTROL RISER ETC IS
 NEEDED.
 SOME ROOMS AND AREAS COULD BE FIGURED OUT BUT NOT ALL.
 PLEASE SEE SOME ROOMS FOR EXAMPLE LIKE ROOMS ON EACH
 FLOOR NORTH OF ELECTRIC ROOM 402, 502 ETC
 FBC 106.3.1, 106.3.5.1.2 ETC ADMIN SECTION FOR
 ADDITIONAL INFORMATION.
 NEC 240.4, 310.16 AND 408.4 WHICH REQUIRES ALL CIRCUITS
 TO BE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED.
 AS MANY OF THE ROOMS ARE NOT ALPHA OR NUMERICALLY
 LABELED, MANY CAN NOT BE CONFIRMED.
  
 20) NOTE: PLEASE SEE NEC 620.23 AS THIS REQUIRES
 DEDICATED CIRCUITS FOR LIGHTING AND RECEPTACLES. PLEASE
 SEE THE LIGHTING SHOWN ON PLANS COMES FROM THE SAME
 CIRCUIT WHICH FEEDS OTHER AREAS.
 PLEASE ADJUST CIRCUITING.
  
 21) NOTE: PLEASE SEE SYMBOLS ON PLANS NEED TO MATCH
 WITH THE LEGEND. PLEASE SEE HOST AREA FOR EXAMPLE WHICH
 SHOWS A F1/1 BUT COULD NOT LOCATE THE DEFINITIONS ON
 THE LEGEND FOR THESE SAME DESIGNATIONS.
 PLEASE SEE THE NEXT COMMENT WHICH ALSO RELATES TO THIS
 COMMENT.
  
 22) NOTE: PLEASE SEE SYMBOL IN MAIN ELECTRICAL ROOM
 WHICH IS SHOWN AS WS IN A SQUARE BOX WHICH SEEMS TO BE
 PART OF THE LIGHTING CONTROL. THIS IS UNCLEAR WHAT THIS
 DEVICE IS. PLEASE SEE 110.26D FOR ILLUMINATION CONTROLS
 WHICH DOES NOT ALLOW ONLY ONE SINGLE AUTOMATED
 CONTROL.
  
 23) NOTE: PLEASE CLARIFY THE OCTAGONAL NOTE #4 ON
 E-201. MENTIONS LOAD USED FOR CALCULATIONS AND FIXTURE
 WATTAGES FOR THE SAME NOTE.
 PLEASE REVIEW AND CLARIFY.
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
 220, OR CHAPTER 13.
  
 24) NOTE: PLEASE SEE OCTAGONAL NOTE #6 ON E-102B FOR
 LIGHTS IN EMERGENCY ROOM. PLEASE ADJUST.
  
 25) NOTE: PLEASE SEE EMERGENCY ROOM WHICH IS LABELED AS
 UTILITY ROOM M003.
 DEDICATED ROOMS PER 110.26
  
 26) NOTE: PLEASE PROVIDE NOTES ON PLANS PER 230.2E,
 700.8, 701.9 FOR REQUIRED SIGNAGE AND MAPPING IN EACH
 ROOM LOCATION AND ALSO FIRE COMMAND AREA.
  
 27) NOTE: PLEASE SEE THE CONDUCTORS ON THE SECONDARY
 SIDE OF THE TRANSFORMER ARE REQUIRED TO MEET OR EXCEED
 THE OVER CURRENT PROTECTION IN WHICH THE TAPPED
 CONDUCTORS ARE TERMINATING.
 PLEASE SEE 240.21, 240.4, 310.16, 110.14
 MOST TAPPED CONDUCTORS ARE OK HOWEVER SOME NOTED FOR
 EXAMPLE: T-4W, T-3W, T-1W WHICH ARE BELOW RATING.
 PLEASE ADJUST AND REVIEW ALL.
  
 28) NOTE: PLEASE SEE THE RISER WHICH INDICATES *GFI*
 PROTECTION ON THE 3000AMPS MSB. PLEASE SEE 240.13,
 230.95 AND CONFIRM TYPE OF PROTECTION SHOWN. PLEASE SEE
 THAT GFI IS TYPICALLY CLASS A PROTECTION FOR PERSONNEL
 WHICH IS DIFFERENT FROM THE GFP (GROUND FAULT
 PROTECTION) AS NOTED IN NFPA-70 SECTIONS GIVEN.
  
 29) NOTE: PLEASE CLARIFY EMERGENCY RELAY PANELS? THIS
 FALLS IN LINE WITH THE NOTES ABOVE WITH RESPECT TO
 LIGHTING CONTROLS AND LIFE SAFETY NOTES FOR LIGHTING.
 THIS WILL NEED TO BE GONE OVER.
 THIS IS THE FIRST TIME A REVIEW OF THIS TYPE OF SYSTEM
 IS BEING SUBMITTED/PROPOSED.
 LS 101 7.8, 7.9
  
 30) NOTE: PLEASE SUBMIT A PANEL SCHEDULE FOR THE MSB
 SWITCHBOARD. COULD NOT LOCATE THIS ON PLANS. PLEASE BE
 SURE TO COORDINATE ALL INFORMATION ON PANEL SCHEDULE
 AND RISER.
 408.4, 310.16, 240.4 ETC
 FBC 106.1.2, 106.3.5.1.2
  
 31) NOTE: PLEASE SEE HP2LW WHICH SHOWS A 500AMP RATED
 MAIN CIRCUIT BREAKER ON A 400AMP RATED PANEL. 110.3,
 90.7, 240 ETC
 FBC 106.1.2 FOR COORDINATION.
  
 32) NOTE: PLEASE COORDINATE THE PANEL SCHEDULE ON E501
 FOR PANEL EMDP WITH THAT OF THE INFORMATION SHOWN ON
 RISER. PLEASE SEE THERE ARE SEVERAL ITEMS WHICH ARE NOT
 THE SAME. FOR EXAMPLE: PLEASE SEE OVER CURRENT
 PROTECTION ON RISER FOR ALL SPARES ARE 150,60,60 AND
 30, YET THE SCHEDULE SHOWS 20,30,20,20 AND OTHER LOADS
 SUCH AS EXHAUST FANS WHICH ARE NOT ON THE RISER EMDP.
 FBC 106.1.2 FOR COORDINATION.
 408.4, 240.4, 310.16 ETC NEC.
  
 33) NOTE: PLEASE SEE EDPLS WHICH ON RISER IS NOT THE
 SAME AS THE SCHEDULE FOR DEVICES AND OVER CURRENT
 PROTECTION DEVICES AS LISTED ON RISER.
 PLEASE SEE FOR EXAMPLE: THE RISER SHOWS TWO 70AMP
 CIRCUITS FOR EACH TRANSFORMER T-LSE2 AND T-LSW-2 YET
 THE PANEL SCHEDULE ON E-501 SHOWS THESE WITH 150AMP
 OVER CURRENT PROTECTION WHICH EXCEEDS CONDUCTOR
 RATINGS,(310.16, 240.4)THE MAXIMUM OVER CURRENT
 PROTECTION PER 450.3 ETC.
 PLEASE ALSO SEE THERE ARE OTHER ITEMS SUCH AS THE OVER
 CURRENT PROTECTION DEVICES FOR SPARES.
 PLEASE COORDINATE ALL.
 FBC 106.1.2 FOR COORDINATION AND SECTIONS NOTED FOR
 NEC.
  
 ** PLEASE BE AWARE THE COMMENTS ARE BASED ON PLANS AND
 DOCUMENTS SUBMITTED FOR REVIEW. ANY CHANGES IN DESIGN,
 LOCATIONS AND/OR ADDITIONAL INFORMATION SUBMITTED WHICH
 COULD NOT YET BE REVIEW MAY GENERATE NEW COMMENTS WHICH
 COULD NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2008-02-05 16:04:54 
 REVIEW COMMENCED ON 2/4 AND COMPLETED 2/5. REVIEW WILL
 GO INTO "F" STATUS. NOTES TO FOLLOW.
2008-01-29 08:06:341-ROLL OF MEP IN ELECTRICAL FOR REVIEW ALONG WITH ONE
 SPEC BOOK

Review Stop ENG ENGINEERING CSD
Rev No 4 Status P Date 2008-11-18 Cont ID  
Sent By mgonzale Date 2008-11-18 Time 15:55 Rev Time 1.00
Received By mgonzale Date 2008-11-18 Time 15:54 Sent To ENG
Notes
2008-11-18 15:57:34- PASSED -
  
 TRASH COMPACTOR WILL BE SERVICE THRU PRIVATE PICK-UP.
 COMPLIANCE WAS COORDINATED THRU EMERY FABIAN AT
 ENGINEERING DEPT. (561) 494-1078
 SANITATION DEPT. WAS ALSO CONTACTED IN THE DICUSSION.
 ANY QUESTIONS FEEL TO CONTACT ME.
  
 MANUEL J GONZALEZ, PROJECT COORDINATOR
 LOCATION ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 1000 - 45TH STREET, SUITE 15
 WEST PALM BEACH FL 33407
 MAILING ADDRESS:
 CITY OF WEST PALM BEACH
 ENGINEERING SERVICES DEPARTMENT
 P.O. BOX 3506
 WEST PALM BEACH FL 33401
 TELEPHONE:
 45TH STREET OFFICE : 561-494-1040
 45TH DIRECT: 561-494-1085
 FAX: 561-494-1117
 CITY HALL OFFICE: (561) 805-6723
 CITY HALL DIRECT: (561) 805-6327
 CITY HALL FAX: (561) 805-6731 OR 805-6676
 NEXTEL: 561-644-7301
 NEXTEL DIRECT CONNECT: 159*28165*38
 EMERGENCIES:
 CENTRAL OPERATIONS CENTER (DISPATCH) 561-822-2210
 E-MAIL:
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status F Date 2008-09-24 Cont ID  
Sent By rchokshi Date 2008-09-24 Time 13:42 Rev Time 0.00
Received By rchokshi Date 2008-09-24 Time 13:35 Sent To  
Notes
2008-09-24 13:42:45*** FAILED *****
  
  
 PLEASE EXPLAIN WHAT DID YOU CHANGE FROM PREVIOUS
 DESIGN?? NEED NEW LENGTH, WIDTH OF THE DUMPSTER GATE,
 NEED SLAB LOCATION DIMENSIONS, HOW IS IT GOING TO FIT?
 IS CITY TRUCK ACCESSIBLE TO PICK UP YOUR DUMPSTER?
 PLEASE EXPLAIN ALL OF THESE. YOUR DRAWING SUBMITTED
 DOES NOT EXPLAIN ANY OF THESE ITEMS.
  
 RASIK CHOKSHI 805-6723

Review Stop ENG ENGINEERING CSD
Rev No 2 Status N Date 2008-05-14 Cont ID  
Sent By rchokshi Date 2008-05-14 Time 11:02 Rev Time 0.00
Received By rchokshi Date 2008-05-14 Time 11:02 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 1 Status P Date 2008-01-17 Cont ID  
Sent By rchokshi Date 2008-01-17 Time 10:46 Rev Time 0.00
Received By rchokshi Date 2008-01-17 Time 10:46 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 7 Status P Date 2009-05-21 Cont ID  
Sent By mawillia Date 2009-05-21 Time 15:26 Rev Time 0.00
Received By mawillia Date 2009-05-21 Time 14:24 Sent To  
Notes
2009-05-21 15:33:27*****REVISION #11, APPROVED*****
  
 VARIOUS ELECTRICAL SHEETS WERE REVIEWED IN REFERENCE TO
 THE ADDITIONS, DELETIONS, AND/OR ANY OTHER CHANGES
 REGARDING THE EXIT AND EMERGENCY LIGHTS. THOSE "E"
 SHEETS WERE APPROVED, HOWEVER NO-FIRE-STAMPING
 NECESSARY.

Review Stop FIRE FIRE DEPARTMENT
Rev No 6 Status P Date 2009-01-26 Cont ID  
Sent By mawillia Date 2009-01-26 Time 12:08 Rev Time 0.00
Received By mawillia Date 2009-01-26 Time 10:42 Sent To  
Notes
2009-01-26 12:12:19*****REVISION #7, DATED NOV.2008, APPROVED*****
  
  
 REVISED SHEETS G-007, G-008, A-611, FP-201A, AND E101'S
 A, B, & C WERE STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 5 Status P Date 2008-11-19 Cont ID  
Sent By mcarsill Date 2008-11-19 Time 16:21 Rev Time 0.00
Received By mcarsill Date 2008-11-19 Time 16:14 Sent To  
Notes
2008-11-19 16:21:24REVISION # 5
  
 1. ON PAGE E-101 C EXIT SIGNS STILL APOPEAR TO DIRECT
 PERSONS INTO GARAGE AREA WHICH IS CONSIDERED MORE
 HAZARDOUS THAN THE AREA THEY ARE EXISTING FROM. PLEASE
 REMOVE THESE EXIT SIGNS SO PERSONS DO NOT EXIT INTO A
 MORE HAZARDOUS AREA.
  
 2. THE CARBON MONOXIDE DETECTORS (CO) SHALL BE PROPERLY
 TESTED WITH CALIBRATION GAS AT THE ESTABLISHED SET
 POINTS OF THE MANUFACTURER.
  
 3. THE KNOX BOX SHOULD BE INSTALLED NEAR THE MAIN
 INGRESS/EGRESS DOOR FOR THE HOTEL.
  
 4. CARD READERS OR ANY SECURITY DEVICES SHALL NOT
 INTERFERE WITH REQUIRED EXITING FROM THE BUILDING.
  
 5. NATURAL GAS INSTALLATION SHALL COMPLY WITH
 APPROPRIATE NFPA STANDARDS AND RECOGNIZED SAFE
 PRACTICES.
  
  
 APPROVED PROVISO:
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-07-17 Cont ID  
Sent By mcarsill Date 2008-07-17 Time 16:15 Rev Time 0.00
Received By mcarsill Date 2008-07-17 Time 16:15 Sent To  
Notes
2008-07-17 16:17:22THE FIRE SPRINKLER PLANS WERE REVIEWED AND APPROVED ON
 JULY 17, 2008 AND WAS THE ONLY REMAINING FIRE RESCUE
 OUTSTANDING ISSUE RELATED TO THE PLANS.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-06-12 Cont ID  
Sent By mcarsill Date 2008-06-12 Time 15:09 Rev Time 0.00
Received By mcarsill Date 2008-06-12 Time 14:30 Sent To  
Notes
2008-06-12 15:09:231. THE PREVIOUS PLAN REVIEW COMMENTS APPEAR TO HAVE
 BEEN PROPERLY ADDRESSED WITH THE REVISED PLANS AND
 COMMENT LETTER.
  
 2. THERE STILL APPEARS TO BE CONFUSION RELATED TO THE
 FIRE PROTECTION DRAWINGS. THE FIRE PROTECTION KEYED
 NOTES INDICATES THAT A CLASS III MANUAL WET STANDPIPE
 SYSTEM WITH 2 1/2 TO 1 1/2 REDUCERS WITH CAPS ATTACHED
 TO A CHAIN ARE GOING TO BE PROVIDED. PER NFPA 14, THE
 STANDARD FOR STANDPIPE SYSTEMS A MANUAL WET STANDPIPE
 SYSTEM IS DEFINED AS A WET STANDPIPE SYSTEM CONNECTED
 TO A SMALL WATER SUPPLY FOR THE PURPOSE OF MAINTAINING
 WATER WITHIN THE SYSTEM OR SHARING A WATER SUPPLY WITH
 AN AUTOMATIC SPRINKLER SYSTEM BUT NOT HAVING A WATER
 SUPPLY ATTACHED TO IT. THIS PROPSOSED SYSTEM IS A
 SYSTEM THAT RELIES ON THE FIRE DEPARTMENT TO CONNECT TO
 THE FIRE DEPARTMENT CONNECTION TO SUPPLY SYSTEM DEMAND.
 FURTHER A CLASS III STANDPIPE SYSTEM PROVIDES HOSE
 STATIONS FOR USE BY BUILDING OCCUPANTS. BUILDING
 OCCUPANTS AND STAFF CANNOT BE SUFFICIENTLY TRAINED TO
 USE CLASS III STANDPIPES.
  
 3. NO PRIOR APPROVAL FOR THE MANUAL WET STANDPIPE
 SYSTEM ARRANGEMENT HAS OCCURRED WITH THIS OFFICE. SOME
 TIME AGO THIS INFORMATION WAS DISCUSSED AS THE PREVIOUS
 PLANS DID NOT SEEM TO COORDINATE WITH OTHER DRAWINGS.
 NO APPROVAL FOR A MANUAL WET STANDPIPE SYSTEM WILL BE
 ALLOWED FOR THIS NEW HOTEL.
  
 4. ON PAGE FP-205A A COMBINATION CLASS II STANDPIPE
 SYSTEM HAS BEEN CALLED OUT FOR THE ROOF MANIFOLD.
  
 5. ON PAGE FP-201A A SIX INCH FIRE LINE IS DESCRIBED. A
 100 PSI ELECTRIC PUMP IS ALSO NOTED ALTHOUGH THE EXACT
 GPM FOR THE PUMP COULD NOT BE LOCATED.
  
 6. NO FIRE PUMP DETAILS OR SPECIFIC DRAWINGS COULD BE
 LOCATED.
  
 7. THE FIRE LINE APPEARS TO LEAVE THE EXISTING TWELVE
 INCH FIRE MAIN AND ENTERS PRIVATE PROPERTY AND IS
 REDUCED TO SIX INCHES AND ENTERS THE SPRINKLER BFP
 ROOM. WHERE IS THE POINT OF SERVICE BEING CONSIDERED
 AND WHERE IS THE FIRE SPRINKLER RISER LOCATED.
  
 8. TWELVE FIFTY IS REFERENCED ON THE FIRE PROTECTION
 PLANS HOWEVER ONLY THREE TEST HEADERS ARE AVAILABLE
 WHICH EQUATES TO ONE THOUSAND GPM'S.
  
 9. A CAREFUL REVIEW OF THE CIVIL AND FIRE PROTECTION
 DRAWINGS NEEDS TO OCCUR SO THE DESIGN INTENT IS
 APPARANT. A MANAUL WET STANDPIPE SYSTEM IS NOT APPROVED
 AND SHALL BE REMOVED FROM THE DRAWINGS.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-05-20 Cont ID  
Sent By mcarsill Date 2008-05-20 Time 11:41 Rev Time 0.00
Received By mcarsill Date 2008-05-20 Time 11:26 Sent To  
Notes
2008-05-20 11:41:351. PLEASE EXPLAIN CARD READERS ON STAIR # 1 DOORS. THE
 USE OF EXIT DOORS SHALL NOT REQUIRE THE USE OF A CARD
 SO THAT THEY CAN BE UTILIZED. CARD READERS ALSO NOTED
 ON EXITWAY DOOR AND OTHER LOCATIONS PER THE DOOR
 SCHEDULE DISPLAYED ON PAGE A-611. PLEASE EXPLAIN
 RATIONALE. ALL RATED FIRE DOORS AND APPURTENANT
 EQUIPMENT SHALL COMPLY WITH NFPA 80, THE STANDARD FOR
 FIRE DOORS AND WINDOWS AND BE EQUIPPED WITH
 SELF-CLOSING DEVICES TO CAUSE THE DOORS TO POSITIVELY
 LATCH WHEN CLOSED.
  
 2. PLEASE PROVIDE FLAMESPREAD DATE FOR CANOPY SHOWN ON
 PAGE A-202.
  
 3. THE FIRE DEPARTMENT CONNECTION SHALL BE EQUIPPED
 WITH LOCKING KNOX-BOX CAPS.
  
 4. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF
 THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 5. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
 NOTE # 11 ON ARCHITECTURAL SHEETS REGARDING TACTILE
 SIGNAGE MAY BE CONFUSING TO SOME.
  
 6. KEY NOTES # 2 "KEY CARD ACCESS ON ARCHITECTURAL
 SHEETS NEEDS TO BE FURTHER EXPLAINED. EXIT ACCESS AND
 EXIT DOORS SHALL NOT REQUIRE THE USE OF AKY, TOOL,
 SPECIAL KNOWLDEGE TO EXIT.
  
 7. THE GREASE DUCT ILLUSTRATED ON PAGE A-100D SHALL
 MEET ALL OF THE REQUIREMENTS OF NFPA 96.
  
 8. EMERGENCY INSTRUCTIONS FOR RESIDENTS AND GUESTS ARE
 REQUIRED ON EVERY HOTEL ROOM DOOR. FIRE SAFETY
 INFORMATION SHALL BE PROVIDED TO GUESTS.
  
 9. LISTED QUICK RESPONSE OR LISTED RESIDENTIAL
 SPRINKLERS SHALL BE PROVIDED FOR THE FIRE SPRINKLER
 SYSTEM.
  
 10. HEARING IMPAIRED ROOMS SHALL BE EQUIPPED WITH
 VISIBLE NOTIFICATION APPLIANCES.
  
 11. MECHANICAL DRAWINGS DISPLAY SEVERAL DEFICIENCIES
 THAT HAVE BEEN HIGHLIGHTED IN RED BY THE MECHANICAL
 PLAN REVIEWER. SEVERAL ARE RELATED TO FIRE AND LIFE
 SAFETY.
  
 12. THE NO EXIT SIGNS SHALL COMPLY WITH THE
 REQUIREMENTS OF CHAPTER 7 OF THE LIFE SAFETY CODE.
  
 13. ALL ELECTRICAL PLAN REVIEW COMMENTS ARE TO BE
 CORRECTED.
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4724 PHONE
 804-4774 FAX

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-03-24 Cont ID  
Sent By mcarsill Date 2008-03-24 Time 09:05 Rev Time 0.00
Received By mcarsill Date 2008-03-24 Time 08:34 Sent To  
Notes
2008-03-24 09:05:031. FIRE AND LIFE SAFETY CODE 2004 FLORIDA BUILDING CODE
 SHOULD READ FLORIDA FIRE PREVENTION CODE ON PAGE
 G-000.
  
 2. FIRE WALL RATINGS BETWEEN PORTIONS OF THE HOTEL AND
 PARKING GARAGE APPEARS TO BE ONLY ONE HOUR RATED ON
 PAGE G-007. A TWO HOUR RATING IS REQUIRED BETWEEN
 PARKING GARAGES AND OTHER PORTIONS OF THE BUILDING.
  
 3. EXIT SIGN IN MEETING ROOM # 110 DIRECTS PERSONS INTO
 CLOSET ON PAGE G-007.
  
 4. SOME EXIT SIGNS APPEAR TO BE DIRECTING PERSONS TO
 EXIT INTO GARAGE. THE GARAGE IS A MORE HAZARSOUS AREA
 THAN THE HOTEL. PLEASE SEE PAGE G-007. EXITING IS NOT
 PERMITTED TO PASS INTO A MORE HAZARDOUS AREA.
  
 5. EXIT TRAVEL ROUTE ON PAGE G-007 IN GARAGE ON
 MEZZANINE LEVEL TRAVELS OVER COLUMN TO REACH STAIR #
 2.
  
 6. FIRE RATED WALLS BETWEEN GARAGE AND MEZZANINE ARE
 ONLY ONE HOUR ON PAGE G-007.
  
 7. OTHER EXIT ROUTE FROM GARAGE TOWARDS STAIR # 1
 APPEARS TO TRAVEL OVER A SHAFT, LIFE SAFETY MEZZANINE.
  
 8. TRAVEL DISTANCE ROUTE ON THE LIFE SAFETY, SECOND
 LEVEL APPEARS TO TRAVEL OVER PARKING STALLS ON PAGE
 G-008.
  
 9. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED IN
 CORRIDOR ON SECOND LEVELS AND TYPICAL LEVELS ON PAGE
 G-008.
  
 10. FIRE RATED WALLS APPEAR TO BE ONE HOUR BETWEEN
 GARAGE AND OTHER AREAS ON PAGE G-008.
  
 11. ADDITIONAL EXIT SIGNS APPEAR TO BE NEEDED ON SECOND
 LEVEL ON PAGE G-008.
  
 12. THE PROPOSED LIVE OAK TREE DISPLAYED ON LP1 SHALL
 NOT OBSTRUCT OR INTERFERE WITH THE PROPOSED FIRE
 DEPARTMENT CONNECTION SHOWN ON THE OLIVE AVENUE SIDE
 ELEVATION.
  
 13. WHAT CHEMICALS IF ANY OR ANY PLANNED TO BE STORED
 IN THE SPA EQUIPMENT ROOM 141 ON PAGE AC-103. IF
 CHEMICALS ARE PLANNED WHAT TYPES AND WHAT QUANTITIES.
  
 14. PLEASE PROVIDE PRESCRIPTIVE STRENGTH REQUIREMENTS
 FOR ALL HANDRAILS AND GUARDRAILS PLANNED FOR THE
 PROJECT.
  
 15. ELEVATOR WARNING SIGNS WILL BE REQUIRED AT ELEVATOR
 LOCATIONS.
  
 16. PLEASE PROVIDE DETAILS ON FIRE SHUTTER CALLED OUT
 ON PAGE A100C.
  
 17. DOORS LOCATED ADJACENT TO STAIR # 1 AND STAIR # 2
 THAT MAY BE CONFUSED AS EXITS SHALL BE PROPERLY
 IDENTIFIED WITH SIGNS INDICATING "NO EXIT".
  
 18. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 19. PLEASE PROVIDE FLAMESPREAD INFORMATION FOR FOLDING
 PARTITIONS IN MEETING ROOM 111 ON PAGE A-101A.
  
 20. REFLECTED CEILING PLAN SYMBOLS DOES NOT IDENTIFY
 WHAT A HALF DARKENED CIRCLE IS. PLEASE IDENTIFY AR
 SHEETS.
  
 21. BUILDING ADDRESS SHALL BE SHOWN ON PROPER EXTERIOR
 ELEVATION DRAWING.
  
 22. COULD NOT LOCATE ANY SMOKE DETECTOR IN KING
 ELECTRICAL PLAN ON PAGE A-421.
  
 23. ARCHITECTURAL SOFFIT SHALL NOT INTERFERE WITH ANY
 OPERATION OF ANY FIRE SPRINKLER HEADS.
  
 24. TRASH CHUTE TO COMPLY WITH NFPA 82.
  
 25. DOOR SCHEDULE ON PAGE A-611 WILL HAVE INCORRECT
 DOOR RATINGS DUE TO ONE HOUR WALLS WHEN TWO HOUR WALLS
 SHOULD HAVE BEEN PROVIDED.
  
 26. SEPARATE PLANS AND PERMITS REQUIRED FOR THE HOOD,
 DUCT, AND FIRE SUPPRESSION SYSTEM SHOWN ON PAGE E-202.
  
 27. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE ALARM
 SYSTEM. FIRE ALARM AND FIRE SPRINKLER SYSTEM SHALL BE
 MONITORED BY A UL LISTED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 28. PLEASE FURTHER DEFINE NOTE # 9 ON PAGE E-303.
  
 29. SEPERATE PLANS AND PERMITS REQUIRED FOR THE FIRE
 SPRINKLER SYSTEM. ENTIRE BUILDING SHALL BE COMPLETELY
 FIRE SPRINKLER PROTECTED. THIS INCLUDES ALL VERTICAL
 SHAFTS, ELECTRICAL, MECHANICAL AND ELEVATOR ROOMS.
  
 30. FIRE PROTECTION SYSTEM GENERAL NOTES # 1 SHOULD
 INCLUDE NFPA 20.
  
 31. ALL FIRE DAMPERS ILLUSTRATED ON THE MECHAICAL PLANS
 ARE TO BE DROP TESTED TO ENSURE PROPER OPERATION AFTER
 INSTALLATION.
  
 32. CARBON MONOXIDE DETECTORS ILLUSTRATED IN THE
 PARKING GARAGE SHALL BE TESTED TO ENSURE PROPER
 OPERATION. THESE DETECTORS SHALL BE TESTED WITH
 CALIBRATION GAS AT THE PROPER SET POINT OF THE
 DETECTORS. INFORMATION SHALL BE PROVIDED FOR THE CARBON
 MONOXIDE DETECTORS SELECTED.
  
 33. STAIRWELL IDENTIFICATION SIGNS REQUIRED. STAIR
 IDENTITY, FLOOR LEVEL, TERMINUS TOP AND BOTTOM SHALL BE
 PROVIDED.
  
 34. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS
 SHALL BE PROVIDED.
  
 35. GAS EQUIPMENT AND RISER INSTALLATIONS TO COMPLY
 WITH NFPA STANDARDS THAT ARE SHOWN ON PAGE P-602.
  
 36. FIRE MARSHAL NOTES NOTED ON PLANS SHALL BE
 FOLLOWED.
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
 804-4709 PHONE
 804-4776 FAX

Review Stop G GAS REVIEW
Rev No 10 Status P Date 2009-02-13 Cont ID  
Sent By kstevens Date 2009-02-13 Time 19:34 Rev Time 0.00
Received By kstevens Date 2009-02-13 Time 19:34 Sent To  
Notes
2009-02-13 19:35:46REVISION OK -- SHT P-602

Review Stop G GAS REVIEW
Rev No 9 Status P Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 23:18 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 23:18 Sent To  
Notes
2009-01-24 23:19:20REVISIONS OK -- SHTS P-201A, P-202A (PROVISO: DIRECT
 VENTS FOR THE WATER HEATERS ARE NOT APPROVED AS
 INDICATED THRU THE ZERO LOT LINE WALL - REVISION
 REQUIRED), AND P-203A.

Review Stop G GAS REVIEW
Rev No 8 Status F Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 23:14 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 23:14 Sent To  
Notes
2009-01-24 23:16:45DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FLORIDA STATUTES
  
 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE
 INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE
 EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE
 PLUMBING PLAN REVIEW. FS 589.
  
 2. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM
 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). --
 THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE
 THROUGH A WALL ON THE ZERO LOT LINE.
  
 3. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop G GAS REVIEW
Rev No 7 Status P Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 23:13 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 23:13 Sent To  
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 6 Status F Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-31 Time 16:10 Rev Time 0.00
Received By kstevens Date 2008-10-31 Time 16:10 Sent To  
Notes
2008-10-31 16:11:28GAS REVISION DENIED FOR SHT P-602. SEE COMMENTS ON
 PLUMBING REVIEW STOP #9.

Review Stop G GAS REVIEW
Rev No 5 Status P Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-31 Time 15:47 Rev Time 0.00
Received By kstevens Date 2008-10-29 Time 16:50 Sent To  
Notes
2008-10-31 16:10:05REVISIONS OK -- SHTS P-201A, P-202A & P-302

Review Stop G GAS REVIEW
Rev No 4 Status P Date 2008-07-16 Cont ID  
Sent By kstevens Date 2008-07-16 Time 17:18 Rev Time 0.00
Received By kstevens Date 2008-07-16 Time 17:18 Sent To  
Notes
2008-07-16 17:21:36 
  
 PASSED/PROVISO
  
 MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT REQUIRED AT THE TIME OF APPLICATION FOR
 REQUIRED GAS PERMIT.
  
  
  
  
  
  
 .

Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-07-03 Cont ID  
Sent By kstevens Date 2008-07-03 Time 11:09 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 11:09 Sent To  
Notes
2008-07-03 11:34:10DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT
 SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS
 APPLICATION IS APPLIED FOR).
  
 I. N/A
 J. N/A
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
  
 ***********NEW COMMENT***********
  
 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL
 Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS
 INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-07-03 Cont ID  
Sent By kstevens Date 2008-04-26 Time 11:11 Rev Time 0.00
Received By kstevens Date 2008-04-26 Time 11:11 Sent To  
Notes
2008-07-03 11:32:45DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 ****FROM PREVIOUS REVIEW:
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT
 SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS
 APPLICATION IS APPLIED FOR).
  
 I. N/A
 J. N/A
  
 **********NEW COMMENTS**********
  
  
 1B. THE GAS REGULATOR SUBMITTAL IS NOT APPROVED FOR ALL
 GAS APPLIANCES. THE ONLY SIZE INDICATED IN THE
 SUBMITTAL IS 3/4" BUT THE SHUT OFF VALVE AND REGULATOR
 SHALL BE SIZED PER THE PIPE SIZE REQUIRED TO EACH
 APPLIANCE.
  
 2B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS REQUIRED FOR THE
 GRIDDLE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By kstevens Date 2008-03-10 Time 11:10 Rev Time 0.00
Received By kstevens Date 2008-03-10 Time 11:10 Sent To  
Notes
2008-07-03 11:30:45DENIED
 REFERENCE: FBC-2004 FUEL GAS
  
 1. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC
 DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER
 HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE
 ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH
 SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE
 ENDS.PLEASE CORRELATE. SECTION 106.1.1.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE
 SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE
 INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE
 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6).
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602
 INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS
 PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES
 AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE
 INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT
 DELIVERY PRESSURE.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 37 Status N Date 2009-04-20 Cont ID  
Sent By swurafti Date 2009-04-20 Time 16:36 Rev Time 0.00
Received By swurafti Date 2009-04-20 Time 16:36 Sent To B
Notes
2009-04-20 16:36:45TO "JWITMER" DESK

Review Stop I INCOMING/PROCESSING
Rev No 36 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By jwitmer Date 2009-04-13 Time 09:47 Sent To  
Notes
2009-04-13 09:48:504/13/09 INCOMING TO J WITMER SUBMITTAL FOR ROOF TOP
 CAGES FOR MECHANICAL EGUIPMENT.

Review Stop I INCOMING/PROCESSING
Rev No 35 Status N Date 2009-03-05 Cont ID  
Sent By adarroug Date 2009-03-05 Time 10:03 Rev Time 0.00
Received By adarroug Date 2009-03-05 Time 10:03 Sent To B
Notes
2009-03-05 10:03:50TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 34 Status N Date 2009-02-13 Cont ID  
Sent By adarroug Date 2009-02-13 Time 16:06 Rev Time 0.00
Received By adarroug Date 2009-02-13 Time 16:06 Sent To  
Notes
2009-02-13 16:11:01TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 33 Status N Date 2009-02-12 Cont ID  
Sent By adarroug Date 2009-02-12 Time 16:23 Rev Time 0.00
Received By adarroug Date 2009-02-12 Time 16:23 Sent To  
Notes
2009-02-12 16:25:25TO "COMM" BD#33

Review Stop I INCOMING/PROCESSING
Rev No 32 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 10:33 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 10:33 Sent To  
Notes
2009-02-02 10:36:02TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 31 Status N Date 2009-01-23 Cont ID  
Sent By adarroug Date 2009-01-23 Time 09:56 Rev Time 0.00
Received By adarroug Date 2009-01-23 Time 09:56 Sent To  
Notes
2009-01-23 09:56:24TO "COMM" BD#40

Review Stop I INCOMING/PROCESSING
Rev No 30 Status N Date 2008-12-24 Cont ID  
Sent By adarroug Date 2008-12-24 Time 09:48 Rev Time 0.00
Received By adarroug Date 2008-12-24 Time 09:48 Sent To L
Notes
2008-12-24 09:48:53TO "Z" BOX/REV--LANDSCAPING

Review Stop I INCOMING/PROCESSING
Rev No 29 Status N Date 2008-12-19 Cont ID  
Sent By adarroug Date 2008-12-19 Time 08:47 Rev Time 0.00
Received By adarroug Date 2008-12-19 Time 08:47 Sent To M
Notes
2008-12-19 08:48:56TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 28 Status N Date 2008-12-04 Cont ID  
Sent By adarroug Date 2008-12-04 Time 16:59 Rev Time 0.00
Received By adarroug Date 2008-12-04 Time 16:59 Sent To B
Notes
2008-12-04 17:00:16TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 27 Status N Date 2008-12-04 Cont ID  
Sent By shill Date 2008-12-04 Time 09:42 Rev Time 0.00
Received By shill Date 2008-12-04 Time 09:42 Sent To B
Notes
2008-12-04 09:43:11ROUTED TO JIM WITMER'S DESK MMILLER

Review Stop I INCOMING/PROCESSING
Rev No 26 Status N Date 2008-11-26 Cont ID  
Sent By adarroug Date 2008-11-26 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-11-26 Time 09:00 Sent To B
Notes
2008-11-26 09:00:57TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 25 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 11:24 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 11:24 Sent To B
Notes
2008-11-18 11:24:52TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 24 Status N Date 2008-11-07 Cont ID  
Sent By adarroug Date 2008-11-07 Time 16:53 Rev Time 0.00
Received By adarroug Date 2008-11-07 Time 16:53 Sent To B
Notes
2008-11-07 16:53:38TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 23 Status N Date 2008-11-05 Cont ID  
Sent By adarroug Date 2008-11-05 Time 11:27 Rev Time 0.00
Received By adarroug Date 2008-11-05 Time 11:27 Sent To B
Notes
2008-11-05 11:28:11TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 22 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 13:00 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 13:00 Sent To B
Notes
2008-11-04 13:01:50TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 21 Status N Date 2008-10-27 Cont ID  
Sent By adarroug Date 2008-10-27 Time 16:50 Rev Time 0.00
Received By adarroug Date 2008-10-27 Time 16:50 Sent To B
Notes
2008-10-27 16:51:19TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 20 Status N Date 2008-10-23 Cont ID  
Sent By adarroug Date 2008-10-23 Time 09:50 Rev Time 0.00
Received By adarroug Date 2008-10-23 Time 09:50 Sent To B
Notes
2008-10-23 09:50:45TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 19 Status N Date 2008-10-22 Cont ID  
Sent By adarroug Date 2008-10-22 Time 10:56 Rev Time 0.00
Received By adarroug Date 2008-10-22 Time 10:56 Sent To P
Notes
2008-10-22 10:57:03TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 18 Status N Date 2008-10-16 Cont ID  
Sent By adarroug Date 2008-10-16 Time 15:06 Rev Time 0.00
Received By adarroug Date 2008-10-16 Time 15:06 Sent To  
Notes
2008-10-16 15:09:58TO "COMM" BD#16

Review Stop I INCOMING/PROCESSING
Rev No 17 Status N Date 2008-10-08 Cont ID  
Sent By adarroug Date 2008-10-08 Time 16:40 Rev Time 0.00
Received By adarroug Date 2008-10-08 Time 16:40 Sent To  
Notes
2008-10-08 16:41:45TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 16 Status N Date 2008-10-06 Cont ID  
Sent By adarroug Date 2008-10-06 Time 09:13 Rev Time 0.00
Received By adarroug Date 2008-10-06 Time 09:13 Sent To B
Notes
2008-10-06 09:13:59TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 15 Status N Date 2008-09-24 Cont ID  
Sent By adarroug Date 2008-09-24 Time 09:36 Rev Time 0.00
Received By adarroug Date 2008-09-24 Time 09:36 Sent To B
Notes
2008-09-24 09:37:01TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 14 Status N Date 2008-09-16 Cont ID  
Sent By adarroug Date 2008-09-16 Time 15:47 Rev Time 0.00
Received By adarroug Date 2008-09-16 Time 15:47 Sent To B
Notes
2008-09-16 15:48:09TO "JWITMER" DESK/6 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 13 Status N Date 2008-09-10 Cont ID  
Sent By adarroug Date 2008-09-10 Time 13:00 Rev Time 0.00
Received By adarroug Date 2008-09-10 Time 13:00 Sent To B
Notes
2008-09-10 13:00:37TO "JWITMER" DESK/2 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 12 Status N Date 2008-09-08 Cont ID  
Sent By adarroug Date 2008-09-08 Time 09:47 Rev Time 0.00
Received By adarroug Date 2008-09-08 Time 09:47 Sent To M
Notes
2008-09-08 09:47:34TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 11 Status N Date 2008-09-02 Cont ID  
Sent By adarroug Date 2008-09-02 Time 15:56 Rev Time 0.00
Received By adarroug Date 2008-09-02 Time 15:56 Sent To B
Notes
2008-09-02 15:56:32TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-08-28 Cont ID  
Sent By tgordon Date 2008-08-28 Time 14:03 Rev Time 0.00
Received By tgordon Date 2008-08-28 Time 14:03 Sent To P
Notes
2008-08-28 14:03:38TO "PLUMB"KEN S.

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-08-25 Cont ID  
Sent By tgordon Date 2008-08-25 Time 14:00 Rev Time 0.00
Received By tgordon Date 2008-08-25 Time 14:00 Sent To  
Notes
2008-08-25 14:01:15SUBMITTALSSENT TO"COMM" BD #9 (RACK)

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 08:17 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 08:17 Sent To B
Notes
2008-08-18 08:17:54TO "JWITMER" DESK/11 SUBMITTALS

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 14:02 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 14:02 Sent To M
Notes
2008-08-14 14:03:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-08-14 Cont ID  
Sent By adarroug Date 2008-08-14 Time 13:54 Rev Time 0.00
Received By adarroug Date 2008-08-14 Time 13:54 Sent To P
Notes
2008-08-14 13:55:15TO "P" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-07-10 Cont ID  
Sent By adarroug Date 2008-07-10 Time 14:10 Rev Time 0.00
Received By adarroug Date 2008-07-10 Time 14:10 Sent To  
Notes
2008-07-10 14:13:21TO "COMM" BD#26/PLANS ON RACK/4 ROLLS, 1 LARGE BOX
 W/BINDERS

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-03 Cont ID  
Sent By adarroug Date 2008-06-03 Time 15:03 Rev Time 0.00
Received By adarroug Date 2008-06-03 Time 15:03 Sent To  
Notes
2008-06-03 15:05:39TO "COMM" BD#1/ PLANS ON RACK/ 6 ROLLS/ 1 BOX OF
 BINDERS AND 1 BINDER ON THE SIDE

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 08:43 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 08:43 Sent To  
Notes
2008-05-14 08:44:07ROUTED TO "COMM" BD#21 W/RESUB ALREADY IN REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-18 Cont ID  
Sent By adarroug Date 2008-04-18 Time 10:13 Rev Time 0.00
Received By adarroug Date 2008-04-18 Time 10:13 Sent To  
Notes
2008-04-18 10:17:10TO "COMM" BD#21--PLANS ON RACK/5 ROLLS

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-03-24 Time   Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 10:45 Sent To  
Notes
2008-01-11 10:45:37TO COMM BOARD # 27

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-12-24 Cont ID  
Sent By rkussner Date 2008-12-24 Time 11:06 Rev Time 0.00
Received By rkussner Date 2008-12-24 Time 11:06 Sent To PC
Notes
2008-12-24 11:16:28***LANDSCAPE REVIEW FAILED***
  
 1. ALTHOUGH THE REMOVAL OF THE GREEN BUTTONWOOD TREES
 PLANTED WITHIN THE RIGHT-OF-WAY ADJACENT TO LAKEVIEW
 WAS NOT PERMITTED THROUGH THE CITY, THE APPLICANT SHALL
 PROVIDE DOCUMENTATION TO THE CITY REGARDING THE STATUS
 OF THOSE TREES. IF THEY NEED TO BE REPLACED, THEN THE
 PLANS SHOULD REFLECT THEIR LOCATIONS.
  
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT EITHER ROBERT
 KUSSNER @ (561) 822-1462 OR MATTHEW FLIS @ (561)
 822-1445.

Review Stop M MECHANICAL (A/C)
Rev No 20 Status P Date 2009-02-15 Cont ID  
Sent By rregueir Date 2009-02-15 Time 08:41 Rev Time 0.00
Received By rregueir Date 2009-02-15 Time 08:40 Sent To  
Notes
2009-02-15 08:41:31PAGE M101B REVISION 10

Review Stop M MECHANICAL (A/C)
Rev No 19 Status P Date 2009-02-12 Cont ID  
Sent By rregueir Date 2009-02-12 Time 18:56 Rev Time 0.00
Received By rregueir Date 2009-02-12 Time 18:55 Sent To PC
Notes
2009-02-12 18:56:30PAGE M002, M101A, M102A REVISION 9

Review Stop M MECHANICAL (A/C)
Rev No 18 Status P Date 2009-02-12 Cont ID  
Sent By rregueir Date 2009-02-12 Time 18:55 Rev Time 0.00
Received By rregueir Date 2009-02-12 Time 18:54 Sent To PC
Notes
2009-02-12 18:55:14PAGE M101A REVISION 8

Review Stop M MECHANICAL (A/C)
Rev No 17 Status P Date 2009-01-22 Cont ID  
Sent By rregueir Date 2009-01-22 Time 19:59 Rev Time 0.00
Received By rregueir Date 2009-01-22 Time 19:58 Sent To  
Notes
2009-01-22 19:59:00REVUSED M101A THROUGH M104A AND FOOD SERVICE

Review Stop M MECHANICAL (A/C)
Rev No 16 Status P Date 2008-12-20 Cont ID  
Sent By rregueir Date 2008-12-20 Time 15:23 Rev Time 0.00
Received By rregueir Date 2008-12-20 Time 15:22 Sent To PC
Notes
2008-12-20 15:23:49PAGES M-101A, M-101B, M-102A, M-102B, M-103B REVISION
 #7

Review Stop M MECHANICAL (A/C)
Rev No 15 Status P Date 2008-11-08 Cont ID  
Sent By rregueir Date 2008-11-08 Time 12:08 Rev Time 0.00
Received By rregueir Date 2008-11-08 Time 12:05 Sent To  
Notes
2008-11-08 12:08:06REVISED M-002, M-101A, M-101B, M-102A, M-102B, M-103A,
 M-103B, M-104A, M-104B, M-105A, M-105B, M-402, M-408

Review Stop M MECHANICAL (A/C)
Rev No 14 Status F Date 2008-09-15 Cont ID  
Sent By rregueir Date 2008-09-15 Time 08:17 Rev Time 0.00
Received By rregueir Date 2008-09-12 Time 11:12 Sent To  
Notes
2008-09-15 08:17:47REVIEW #: REVISION 5
 ACTION:DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. PAGE M-101B: THIS PLAN SHOWS SEVERAL CHANGES TO THE
 GENERATOR ROOM EXHAUST SYSTEM. HOWEVER, THESE CHANGES
 ARE NOT IDENTIFIED ON THE PLANS AS A PERT OF THIS
 REVISION. CLEARLY MARK AND INDENTIFY ON PLANS ALL
 CHANGES FROM THE CURRENT PERMIT DOCUMENTS TO FACILITATE
 AN ACCURATE REVIEW OF THE AMENDED CONSTRUCTION
 DOCUMENTS IN ACCORDANCE WITH FBCB 106.4. ALSO, PLEASE
 MAINTAIN THE REVISION HISTORY AT THE TITLE BLOCKS ON
 THE PLANS TO AID IN TRACKING AND RECORDS RETENTION.
 REVISION #4, WHICH HAS BEEN INCORPORATED INTO THE
 PERMIT SET OF PLANS, NO LONGER APPEARS IN THE REVISION
 HISTORY.
  
 NOTE: THIS IS ONE EXAMPLE OF ONE CHANGE WHICH HAS NOT
 BEEN IDENTIFIED. PLEASE CHECK THE ENTIRE REVISION SET
 AND ENSURE ALL REVISIONS ARE CLEARLY INDICATED ON PLANS
 PRIOR TO RESUBMISSION.
  
 2. PAGE M-101B: THERE IS AN UNNECESSARY LAYER SHOWING
 KITCHEN EQUIPMENT IN THE GARAGE AND TRASH COMPACTOR
 AREA. PLEASE REMOVE ERRONEOUS LAYERS AND PROVIDE PLANS
 WHICH ARE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED IN
 ACCORDANCE WITH FBCB 106.1.1.
  
 3. PAGE M-101B: GENERATOR ROOM NOTE INDICATES THAT THE
 DUCT FROM EF-7 IS TO ATTACH TO THE GENERATOR WITH
 FLEXIBLE DUCT CONNECTIONS. IT IS UNCLEAR AS TO WHY THE
 DUCT WOULD CONNECT TO THE GENERATOR ITSELF. PROVIDE
 ADDITIONAL DETAIL WHICH CLARIFIES THE INTENT OF THIS
 DESIGN AND DEMONSTRATES COMPLIANCE WITH FBCM 915.2 AND
 FBCM 304.1.
  
 4. PAGE M-101B: THE CHANGES TO THE GENERATOR ROOM
 VENTILATION AND GENERATOR EXHAUST SYSTEMS WILL HAVE AN
 IMPACT ON THE DESIGN AS SHOWN ON SEVERAL OTHER PAGES OF
 THE PLANS. HOWEVER, THESE OTHER PAGES ARE NOT A PART OF
 THIS REVISION. PLEASE COORDINATE CHANGES ON THIS PAGE
 WITH ALL OTHER PAGES WHICH MAY ME AFFECTED BY THEM.
 SUBMIT ALL PAGES WHICH ARE PART OF THIS CHANGE WITHIN
 THE SAME REVISION TO FACILITATE AN ACCURATE REVIEW AND
 DEMONSTRATE COMPLIANCE WITH THE PROVISIONS OF FBCM
 915.2, FBCM 401.5, 401.6 AND FBCM CHAPTER 5.
  
 5. PAGES M-103B THROUGH M-104B AND M-408: FLOOR PLANS
 HAVE BEEN CHANGED TO SHOW 6 INCH ROUND EXHAUST DUCTS
 GOING TO EXHAUST RISERS. HOWEVER, RISER DIAGRAMS ARE
 STILL SHOWING 4 INCH ROUND DUCTS IN SEVERAL LOCATIONS.
 PLEASE CLARIFY BY COORDINATING DUCT SIZES ON FLOOR
 PLANS WITH DETAILS AND RISER DIAGRAMS IN ACCORDANCE
 WITH FBCM 603.1 AND FBCB 106.1.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 13 Status P Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 09:38 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 09:37 Sent To PC
Notes
2008-09-02 09:38:08SUBMITTAL # 230529-3: CONCRETE DECK ANCHORS FOR EXHAUST
 FANS

Review Stop M MECHANICAL (A/C)
Rev No 12 Status P Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 09:30 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 09:29 Sent To PC
Notes
2008-09-02 09:30:36SUBMITTAL #233300-2: SMOKE DAMPER, ACTUATOR

Review Stop M MECHANICAL (A/C)
Rev No 11 Status P Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 09:12 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 09:12 Sent To PC
Notes
2008-09-02 09:12:38SUBMITTAL #233713-3 REV 1: LINEAR DIFFUSERS

Review Stop M MECHANICAL (A/C)
Rev No 10 Status P Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 09:02 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 08:47 Sent To PC
Notes
2008-09-02 09:02:52SUBMITTAL #233713-2: CO SENSORS,VFD, HVAC CONTROLS,
 DAMPER MOTORS

Review Stop M MECHANICAL (A/C)
Rev No 9 Status P Date 2008-09-02 Cont ID  
Sent By rregueir Date 2008-09-02 Time 08:34 Rev Time 0.00
Received By rregueir Date 2008-09-02 Time 08:33 Sent To PC
Notes
2008-09-02 08:34:14SUBMITTAL #233713-1 DIFFUSERS, REGISTERS, GRILLS, FANS,
 LOUVERS, DAMPERS

Review Stop M MECHANICAL (A/C)
Rev No 8 Status P Date 2008-08-29 Cont ID  
Sent By rregueir Date 2008-08-29 Time 16:53 Rev Time 0.00
Received By rregueir Date 2008-08-29 Time 16:53 Sent To  
Notes
2008-08-29 16:53:56SUBMITTAL #237433-4 ADDISON SPLIT SYSTEM

Review Stop M MECHANICAL (A/C)
Rev No 7 Status P Date 2008-08-29 Cont ID  
Sent By rregueir Date 2008-08-29 Time 16:19 Rev Time 0.00
Received By rregueir Date 2008-08-29 Time 16:17 Sent To  
Notes
2008-08-29 16:18:38SUBMITTAL #237433-3 AAON OARTU'S

Review Stop M MECHANICAL (A/C)
Rev No 6 Status P Date 2008-08-29 Cont ID  
Sent By rregueir Date 2008-08-29 Time 16:02 Rev Time 0.00
Received By rregueir Date 2008-08-29 Time 15:40 Sent To  
Notes
2008-08-29 16:02:31SUBMITTAL #237433-1 TRANE SPLIT A/C SYSTEMS

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-08-29 Cont ID  
Sent By rregueir Date 2008-08-29 Time 15:35 Rev Time 0.00
Received By rregueir Date 2008-08-29 Time 15:16 Sent To  
Notes
2008-08-29 15:35:16SUBMITTAL #236200-02 AMANA DIGISMART PTAC

Review Stop M MECHANICAL (A/C)
Rev No 4 Status P Date 2008-08-28 Cont ID  
Sent By rregueir Date 2008-08-28 Time 14:56 Rev Time 0.00
Received By rregueir Date 2008-08-28 Time 09:45 Sent To PC
Notes
2008-08-28 14:55:59REVISED PAGES M-101B, M-103A, M-103B, M-104A, M-104B,
 M-408 REVISION #4

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-27 Cont ID  
Sent By rregueir Date 2008-06-27 Time 09:43 Rev Time 0.00
Received By rregueir Date 2008-06-25 Time 16:51 Sent To  
Notes
2008-06-27 08:36:42************PROVISOS*************
  
 1. COMPLIANCE WITH THE WIND RESISTANCE REQUIREMENTS
 SHALL BE DEMONSTRATED PRIOR TO INSTALLATION AND
 INSPECTION OF OUTDOOR APPLIANCES AND EQUIPMENT EXPOSED
 TO WIND PRESSURES IN ACCORDANCE WITH FBCM 301.13. ANY
 ALTERNATE MATERIALS AND METHODS PROPOSALS SHALL BE
 SUBMITTED TO THE BUILDING OFFICIAL IN WRITING.
  
 2. A STAIR PRESSURIZATION TEST SHALL BE PERFORMED PRIOR
 TO FINAL INSPECTION TO VERIFY STAIRWAY DOOR OPENING
 FORCES ARE WITHIN ALLOWED RANGE IN COMPLIANCE WITH FBCB
 11-4.13.11.
  
 3. GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL
 PROVIDE AN AIR VELOCITY WITHIN THE DUCT SYSTEM OF 1,500
 TO 2,500 FEET PER MINUTE. KEF-1 ON SCHEDULE (M-002) IS
 TOO SMALL TO PROVIDE REQUIRED EXHAUST VOLUME AND IS
 SMALLER THAN SUPPLY FAN. DEMONSTRATE COMPLIANCE WITH
 FBCM 506.3.4 AND FBCB 13-409.1.ABC.3.6.1. REVISE PLANS
 PRIOR TO ROUGH INSPECTION.
  
 4. ROOF KEF DETAIL (M-404) SHOWS CLEARANCE UNDER FAN AT
 14 INCHES. CLEARANCE UNDER FAN TO ROOF SHALL BE IN
 ACCORDANCE WITH FBCB TABLE 1509.7. REVISE PLANS PRIOR
 TO ROUGH INSPECTION.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-07 Cont ID  
Sent By rregueir Date 2008-05-07 Time 16:11 Rev Time 0.00
Received By rregueir Date 2008-05-06 Time 11:35 Sent To  
Notes
2008-05-07 16:11:08REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
 ONE SET OF PLANS HAS BEEN MARKED-UP DURING REVIEW TO
 ASSIST WITH CLARITY OF COMMENTS.
  
 1 THROUGH 3: OK
  
 4 THROUGH 9: THESE COMMENT RESPONSES ARE NOT ABLE TO BE
 REVIEWED AT THIS TIME. THEY ALL INVOLVE CORRECTIONS TO
 THE ENERGY CALCULATIONS, WHICH WERE NOT INCLUDED WITH
 THIS RESUBMITTAL. PLEASE PROVIDE CORRECTED ENERGY
 CALCULATIONS FOR REVIEW PRIOR TO PERMIT ISSUANCE IN
 ACCORDANCE WITH FBCB 13-103.3.
  
 10. OK
  
 11. PG M-101A:
 A) FIRE-RESISTANCE RATED WALLS HAVE BEEN ADDED TO
 CORRIDOR AND LOBBY AREA AS SHOWN ON PG A-101A, A-401
 AND A-402. BASED ON THESE LOCATIONS, THERE ARE AT LEAST
 FOUR DUCT PENETRATIONS OF RATED WALLS AT OFFICE 124 AND
 OFFICE 126 WHICH ARE NOT PROTECTED. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBCM 607.5. COORDINATE ANY AND ALL CHANGES IN WALL
 TYPES BETWEEN ARCHITECTURAL, LIFE SAFETY AND MECHANICAL
 PLANS.
 NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA
 WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE
 DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE
 DESIGN INTENT.
 B) THE 18X20 GREASE EXHAUST DUCT FROM KITCHEN 115 IS
 NOW SHOWN PENETRATING TWO RATED WALL ASSEMBLIES. A
 GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL IN ACCORDANCE WITH FBCM 506.3.10. SHOW HOW
 THIS DUCT IS TO BE ENCLOSED IN ACCORDANCE WITH THIS
 SECTION OR EXCEPTION #1.
 C) DISHWASHER EXHAUST DUCT IS SHOWN PENETRATING
 CORRIDOR WALL WITH FIRE/SMOKE DAMPER AT WALL
 PENETRATION. THIS DUCT WILL BE CONVEYING HOT,
 MOISTURE-LADEN AIR TO THE OUTDOORS. IS THE FIRE/SMOKE
 DAMPER AND DUCT USED AT THIS LOCATION DESIGNED FOR
 THESE CONDITIONS? DUCTS CONVEYING MOISTURE-LADEN OR
 WASTE-HEAT-LADEN AIR SHALL BE CONSTRUCTED, JOINED AND
 SEALED IN AN APPROVED MANNER IN ACCORDANCE WITH FBCM
 506.4.2. PLEASE PROVIDE ADDITIONAL DETAILS FOR THIS
 APPLICATION.
  
 12 THROUGH 19: OK
  
 20. PG M-102A: NOTES HAVE BEEN CORRECTED AND MADE
 LEGIBLE. HOWEVER, TWO OF THE CO SENSORS IN THIS AREA
 ARE BEING DESIGNATED BY MECHANICAL NOTE #2 RATHER THAN
 NOTE #7. PLEASE CORRECT FBCM 404, FBCB 106.1.1.
  
 21 THROUGH 23: OK
  
 24.M-102A: OK EXCEPT: STAIR PRESSURIZATION TEST WILL
 BE REQUIRED FOR BOTH PRESSURIZED STAIRS TO VERIFY
 COMPLIANCE WITH MAXIMUM DOOR OPENING FORCES ALLOWED PER
 FBCB 11-4.13.11. THIS WILL BE A PROVISO ON IN EFFECT
 UNTIL FINAL MECHANICAL INSPECTION HAS PASSED. ALSO, PG
 M-404 STILL SHOWS STAIR PRESSURIZATION FANS CONNECTED
 TO A BUILDING SMOKE CONTROL SYSTEM WHICH DOES NOT
 EXIST. PLEASE CORRECT. IN ADDITION, BOTH SF-2 AND SF-3
 WILL REQUIRE DUCT SMOKE DETECTORS FOR FAN SHUT-DOWN IN
 ACCORDANCE WITH FBCM 606.2.
  
 25 THROUGH 28: OK
  
 29. PG M-103A: THE DESIGN INTENT IN THIS AREA REMAINS
 UNCLEAR. WHILE ARCHITECTURAL PLANS NOW SHOW THESE DUCTS
 IN A RATED ENCLOSURE, THIS PAGE ALSO SHOWS TWO
 FIRE/SMOKE DAMPERS AT THE FLOOR PENETRATION WHILE PG
 M-102A SHOWS TWO FIRE DAMPERS AT THE FLOOR PENETRATION.
  
 NOTE: WHILE THE DESIGN IS PERMITTED TO EXCEED MINIMUM
 CODE REQUIREMENTS, A SHAFT ENCLOSURE IS NOT REQUIRED AT
 THIS LOCATION IN ACCORDANCE WITH FBCM 607.6.1.
 PROVIDING THE TWO FIRE DAMPERS SHOWN ON M-102A AND TWO
 FIRE DAMPERS AT THE WALL PENETRATIONS BETWEEN ROOMS 231
 AND 235 WOULD ELIMINATE THE NEED FOR A SHAFT ENCLOSURE
 AND THE 6 COMBINATION FIRE/SMOKE DAMPERS SHOWN ON
 M-103A. THIS, OF COURSE, DEPENDS ON THE DESIGN INTENT.
  
 30. PG M-103A: IN EXITWAY 230, PROVIDE A
 THROUGH-PENETRATION FIRESTOP SYSTEM DETAIL FOR THE 6
 INCH ROUND EXHAUST DUCT PENETRATING THE RATED WALL INTO
 EXITWAY 230 WITH NO FIRE DAMPER IN ACCORDANCE WITH FBCM
 607.1.1.
 NOTE: THERE ARE A FEW DUCT PENETRATIONS IN THIS AREA
 WHICH WOULD QUALIFY FOR AN EXCEPTION TO THE SMOKE
 DAMPER REQUIREMENTS FBCM 607.5.4(3), DEPENDING ON THE
 DESIGN INTENT.
  
 31 THROUGH 38: OK
  
 39. M-105A AND M-105B: PLEASE SEE COMMENT #24 ABOVE.
 ALSO, WIND RESISTANCE CRITERIA FOR OUTDOOR APPLIANCES
 WILL BE COVERED BY PROVISO ONCE ALL OTHER OUTSTANDING
 COMMENTS ARE ADDRESSED AND PRIOR TO PERMIT ISSUANCE.
  
 40. OK
  
 41. PG M-404: PLEASE SHOW HEIGHT OF EXHAUST DISCHARGE
 ABOVE ROOF TO BE MINIMUM 40 INCHES IN ACCORDANCE WITH
 FBCM 506.3.12.1. ALSO, PLEASE SEE PG M-105A REGARDING
 THE LOCATION OF KEF-1. EXHAUST OUTLETS SHALL BE LOCATED
 NOT LESS THAN 10 FEET HORIZONTALLY FROM PARTS OF THE
 SAME OR CONTIGUOUS BUILDINGS, ADJACENT PROPERTY LINES
 AND AIR INTAKE OPENINGS INTO ANY BUILDING IN ACCORDANCE
 WITH FBCM 506.3.12.3. THE MINIMUM HORIZONTAL DISTANCE
 BETWEEN VERTICAL DISCHARGE FANS AND PARAPET-TYPE
 BUILDING STRUCTURES SHALL BE 2 FEET PROVIDED THAT SUCH
 STRUCTURES ARE NOT HIGHER THAN THE TOP OF THE FAN
 DISCHARGE OPENING IN ACCORDANCE WITH FBCM 506.5.5.
  
 42. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By rregueir Date 2008-02-11 Time 14:01 Rev Time 0.00
Received By rregueir Date 2008-01-23 Time 18:05 Sent To  
Notes
2008-02-11 14:01:12REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. M-001: HVAC GENERAL NOTE #11, DAMPERS WITH MOVING
 PARTS AND SOME DUCT MATERIALS MAY NOT BE PAINTED AS IT
 CAN VIOLATE THEIR LISTING AND IMPACT THEIR PERFORMANCE.
 EXAMPLES: FIRE DAMPERS, SMOKE DAMPERS AND FIBERGLASS
 DUCT BOARD SHALL NOT BE PAINTED.
  
 2. M-001: GARAGE VENTILATION RATE CALCULATION, THERE IS
 NO VENTILATION RATE SHOWN FOR THE GARAGE DURING THE
 MODE WHERE THE FANS ARE NOT BEING OPERATED BY THE CO
 SENSORS. PROVIDE CALCULATIONS FOR THE REQUIRED
 VENTILATION RATE DURING THIS MODE IN ACCORDANCE WITH
 FBC, M 404.2. SEE COMMENT #3 BELOW.
  
 3. M-002: FAN SCHEDULE, NOTE #7 CALLS FOR FANS TO BE
 CONTROLLED BY CO SENSOR. THIS NOTE IS NOT ATTRIBUTED TO
 ANY FANS ON THE SCHEDULE (IT?S LIKELY THAT EF-1 AND
 EF-2 A/B ARE INTENDED, BUT THIS IS NOT SHOWN ON
 SCHEDULE). NOTE: IF THESE FANS ARE TO BE CONTROLLED BY
 CO SENSORS, THERE WOULD BE NO VENTILATION IN THE GARAGE
 WHEN THE CO LEVELS ARE UNDER 25 PPM. A MINIMUM
 CONTINUOUS VENTILATION RATE OF 0.05 CFM/S.F. IS
 REQUIRED IN ACCORDANCE WITH FBC, M 404.2. PLEASE
 CLARIFY THE DESIGN INTENT AND SHOW COMPLIANCE WITH ALL
 PROVISIONS OF FBC, M SECTION 404.
  
 4. M-002: PACKAGED MAKE-UP AIR UNIT SCHEDULE, OAU-1
 CALLS FOR 29.5 MIN. TONS. HOWEVER, ACCORDING TO THE
 MANUFACTURER (WWW.AONNET.COM/RM.ASPX) THE MAXIMUM
 CAPACITY OF THE MODEL SHOWN ON THE SCHEDULE IS 26 TONS,
 WELL UNDER THE MINIMUM AS STATED ON THE SCHEDULE. ALSO,
 THE VALUES ON THE SCHEDULE DO NOT CORRESPOND WITH THE
 VALUES LISTED ON THE SYSTEM SIZING SUMMARY PROVIDED IN
 THE SPEC BOOK. IN ADDITION, NOTE #9 IN THE SCHEDULE
 CALLS FOR A MINIMUM EER RATING OF 11 WHILE THE
 MANUFACTURER SHOWS THIS UNIT?S EER RATING TO BE 9.5.
 THIS INFORMATION IS ALSO MISREPRESENTED IN THE ENERGY
 CALCULATIONS AS THE INPUT DATA REPORT SHOWS AN
 EFFICIENCY RATING OF 13.0 FOR OAU-1. PLEASE COORDINATE
 THE SCHEDULE, SYSTEM SIZING SUMMARY AND ENERGY
 CALCULATIONS TO PROVIDE ACCURATE INFORMATION AND
 DEMONSTRATE COMPLIANCE WITH FBC, M 304.1; FBC 13-103.2
 AND FBC 13-407.1.ABC.1.
  
 5. M-002: PACKAGED MAKE-UP AIR UNIT SCHEDULE, OAU-2
 VALUES ON THE SCHEDULE DO NOT CORRESPOND WITH THE
 VALUES LISTED ON THE SYSTEM SIZING SUMMARY PROVIDED IN
 THE SPEC BOOK. ALSO, ACCORDING TO THE MANUFACTURER
 (WWW.AONNET.COM/RN.ASPX) THE EER RATING FOR THE MODEL
 LISTED ON THE SCHEDULE IS 11.7. THIS INFORMATION IS
 MISREPRESENTED IN THE ENERGY CALCULATIONS AS THE INPUT
 DATA REPORT SHOWS AN EFFICIENCY RATING OF 13.0 FOR
 OAU-2. PLEASE COORDINATE THE SCHEDULE, SYSTEM SIZING
 SUMMARY AND ENERGY CALCULATIONS TO PROVIDE ACCURATE
 INFORMATION AND DEMONSTRATE COMPLIANCE WITH FBC
 13-103.2 AND FBC 13-407.1.ABC.1.
  
 6. M-002: DX SPLIT SYSTEM SCHEDULE, THE EFFICIENCIES
 LISTED IN THE SCHEDULE COULD NOT BE VERIFIED
 (WWW.ARIDIRECTORY.ORG) BASED ON THE MODEL NUMBERS
 PROVIDED. EQUIPMENT EFFICIENCY VERIFICATION IS REQUIRED
 IN ACCORDANCE WITH FBC 13-407.1.ABC.3.1.1. PROVIDE
 MODEL NUMBERS OR ARI REFERENCE NUMBERS WHICH CAN BE
 USED FOR EFFICIENCY VERIFICATION TO SHOW COMPLIANCE
 WITH THIS SECTION.
  
 7. M-002: DX SPLIT SYSTEM SCHEDULE CALLS FOR ALL
 EQUIPMENT TO HAVE MIN. 13 SEER. HOWEVER, UNITS LARGER
 THAN 65,000 BTU/H ARE NOT RATED BY SEER, SUCH AS CU-1
 AND CU-6. PROVIDE ACTUAL AND CORRECT RATINGS FOR ALL
 EQUIPMENT TO DEMONSTRATE COMPLIANCE WITH MINIMUM
 EFFICIENCIES REQUIRED BY FBC TABLE 13-407.1.ABC.3.2A
  
  
 8. M-002: DX SPLIT SYSTEM SCHEDULE, AHU-4 /CU-4 IS NOT
 LISTED IN THE INPUT DATA REPORT PORTION OF THE ENERGY
 CALCULATIONS. ALL PERTINENT DATA AND FEATURES OF THE
 BUILDING AND THE EQUIPMENT/SYSTEMS SHALL BE INCLUDED IN
 THE ENERGY CALCULATIONS IN ACCORDANCE WITH FBC
 13-103.2.
  
 9. M-002: PTAC UNITS COULD NOT BE LOCATED IN ANY
 EQUIPMENT SCHEDULES ON THIS PAGE. PROVIDE ALL RELEVANT
 INFORMATION AS REQUIRED TO VERIFY SYSTEM SIZING AND
 REQUIRED EFFICIENCIES AS COVERED UNDER PREVIOUS REVIEW
 COMMENTS.
  
 10. M-101A: EF-5 AND EF-11 ARE LOCATED ABOVE A GYPSUM
 BOARD CEILING IN CORRIDOR 148. CLEARANCES AROUND
 APPLIANCES TO ELEMENTS OF PERMANENT CONSTRUCTION SHALL
 BE SUFFICIENT TO ALLOW INSPECTIONS, SERVICE, REPAIR OR
 REPLACEMENT WITHOUT REMOVING SUCH ELEMENTS OF PERMANENT
 CONSTRUCTION OR DISABLING THE FUNCTION OF A REQUIRED
 FIRE RESISTANCE-RATED ASSEMBLY. SHOW HOW THESE FANS
 WILL BE ACCESSIBLE FOR SERVICE AND REPLACEMENT IN
 ACCORDANCE WITH FBC, M 306.1.
  
 11. M-101A: CORRIDOR 148 IS LIKELY TO REQUIRE A FIRE
 RESISTANCE RATING IN ACCORDANCE WITH FBC TABLE 1016.1
 (SEE BUILDING PLAN REVIEW COMMENTS FOR ALL REQUIREMENTS
 RELATED TO FIRE RESISTANCE RATED ASSEMBLIES). IF THIS
 IS THE CASE, THERE ARE SEVERAL DUCT PENETRATIONS WHICH
 WOULD REQUIRE OPENING PROTECTIVES SUCH AS FIRE AND
 POSSIBLY SMOKE DAMPERS IN ACCORDANCE WITH FBC, M
 607.5.3 AND 607.5.4. ANY SMOKE DAMPERS REQUIRED SHALL
 BE ACTUATED IN ACCORDANCE WITH FBC, M 607.5.4.1.
 COORDINATION WITH ARCHITECTURAL PLANS PRIOR TO
 RESUBMITTAL IS CRITICAL TO THESE COMMENTS BEING
 ADEQUATELY ADDRESSED.
  
 12. M-101A: KITCHEN AREA 115
 A) THIS AREA SHOWS A RETURN AIR DROP ADJACENT TO THE
 COMMERCIAL KITCHEN GREASE EXHAUST HOOD. THIS CONDITION
 IS PROHIBITED PER FBC, M 407.1 AS THIS IS A
 NON-DEDICATED KITCHEN HVAC SYSTEM. AHU #6 SERVES AREAS
 OUTSIDE OF THE KITCHEN SUCH AS RESTROOMS AND CORRIDORS.
 CONCENTRATED SOURCES OF CONTAMINANTS OR POLLUTANTS
 SHALL BE CONTROLLED AT THE SOURCE BY CONTAINMENT, LOCAL
 EXHAUST SYSTEMS, OR BOTH. RECIRCULATION OF AIR FROM THE
 KITCHEN TO OTHER SPACES OF THE BUILDING WOULD HAVE A
 NEGATIVE IMPACT ON INDOOR AIR QUALITY IN ACCORDANCE
 WITH FBC, M 407.1 AND FBC 13-409.1.ABC.1.
 B) THIS LOCATION IS LIKELY TO ADVERSELY EFFECT THE
 COOLING LOADS FOR AHU #6. ARE THESE ADDITIONAL LOADS
 ACCOUNTED FOR IN THE COOLING LOAD CALCULATIONS FOR THE
 RETURN TO BE IN THIS LOCATION? FBC 13-407.1.ABC.1. C)
 THE RETURN AT THIS LOCATION HAS THE POTENTIAL TO DRAW
 GREASE LADEN VAPORS FROM THE COOKING AREA SERVED BY THE
 GREASE EXHAUST HOOD SYSTEM. THE FAN FOR AHU #6 IS
 ACTUALLY DESIGNED TO DRAW MORE AIR THAN THE EXHAUST FAN
 SERVING THE HOOD SYSTEM AND WOULD BE COMPETING WITH
 KEF-1 FOR AIR. ACCUMULATION OF GREASE IN A DUCT WHICH
 IS NOT DESIGNED IN ACCORDANCE WITH FBC, M 506.3 WOULD
 CREATE A SERIOUS FIRE HAZARD.
  
 13. M-101A: AIR QUANTITIES SHOWN ON FLOOR PLAN FOR SOME
 SYSTEMS DO NOT MATCH THE VALUES SHOWN ON THE AIR
 BALANCE SCHEDULE ON M-002. THE FOLLOWING IS AN
 EXAMPLE:
 AHU-1 ON THE SCHEDULE CALLS FOR 6010 CFM OF RETURN AIR.
 FLOOR PLAN FOR AHU-1 SHOWS 5230 CFM OF RETURN. CHECK
 ALL VALUES AND COORDINATE WITH FLOOR PLANS TO ASSURE
 AIR BALANCE WILL BE AS INDICATED ON SCHEDULE AS
 REQUIRED BY FBC 13-409.1.ABC.1.2.
  
 14. M-101A: EXHAUST OUTLET FOR TOILET ROOMS 137 AND 138
 IS SHOWN DISCHARGING ONTO A WALKWAY ON THE WEST SIDE OF
 THE BUILDING. EXHAUST AIR SHALL NOT BE DISCHARGED ONTO
 WALKWAYS IN ACCORDANCE WITH FBC, M 401.5.2. A SIMILAR
 CONDITION MAY EXIST WITH THE POOL HEATER VENTS. CONSULT
 MANUFACTURER?S INSTALLATION INSTRUCTIONS.
  
 15. M-101A: THE 24X24 WALL LOUVER AT SPRINKLER RISER
 ROOM 144 IS PENETRATING A 2-HOUR RATED WALL AS
 INDICATED ON PG A-101A AND A-601. SHOW HOW THIS OPENING
 SHALL BE PROTECTED IN ACCORDANCE WITH FBC, M 607.5
  
 16. M-101A: THE 10X6 DUCT PENETRATING THE WALL BETWEEN
 CORR. 148 AND CORR. 149 IS REQUIRED TO BE PROTECTED
 WITH A SMOKE DAMPER IN ADDITION TO THE FIRE DAMPER
 ALREADY SHOWN ON PLANS IN ACCORDANCE WITH FBC, M
 607.5.4.
 NOTE: THIS CONDITION MAY BE AFFECTED BY CHANGES RELATED
 TO COMMENT #11 ABOVE.
  
 17. M-101A: MECHANICAL NOTE #3 IS FOR 10X8 EXHAUST DUCT
 TO DISHWASHER HOOD. WHAT IS THE RELATIONSHIP TO THE
 CARBON MONOXIDE SENSORS IN THE PARKING GARAGE?PLEASE
 CLARIFY AS THIS SAME NOT IS ATTACHED TO THE DETECTORS.
  
 18. M-101B: THE 4X6 OA DUCTS PENETRATING THE FLOOR
 CEILING ASSEMBLY ABOVE THE FIRST FLOOR DOES NOT SHOW
 ANY OPENING PROTECTIVE. WHILE IT DOES SHOW OPENING
 PROTECTIVES AT THE PENETRATIONS OF THE WALL MEMBRANES
 BETWEEN ROOMS 105/106 AND BETWEEN ROOMS 107/108. THE OA
 DUCT PENETRATION FOR ROOM 105 (THE OTHER 105, ROOMS
 APPEAR TO BE MISLABELED ON PG A-101B) IS NOT CLEAR
 WHETHER IT IS INSIDE OR OUTSIDE THE RATED EXHAUST
 CHASE. IF IT IS INSIDE THE EXHAUST CHASE, IT SHALL BE
 PROTECTED WITH FIRE AND SMOKE DAMPER IN ACCORDANCE WITH
 FBC, M 607.5.5.1. THE DESIGN AND INTENT IN THESE AREAS,
 ALONG WITH THE CORRESPONDING AREAS ON PAGES M-120B AND
 M-103B ARE UNCLEAR. PLEASE PROVIDE CLARIFICATION OF THE
 DESIGN IN THESE AREAS RELATED TO OA DUCTS AND
 PENETRATIONS FOR THOROUGH REVIEW.
  
 19. M-101B: PROVIDE MANUFACTURER?S SUBMITTAL WITH
 INSTALLATION INSTRUCTIONS FOR CARBON MONOXIDE SENSORS
 FOR REVIEW. INSTALLATION INSTRUCTIONS ARE REQUIRED TO
 DETERMINE COVERAGE AREA, MAXIMUM SPACING AND
 INSTALLATION HEIGHT OF THE DETECTORS. ALSO, SOME
 MANUFACTURERS REQUIRE CIRCULATION FANS TO ENSURE PROPER
 SAMPLING OF THE AIR IN THE SPACES BEING MONITORED.
  
 20. M-102A: MECHANICAL NOTES APPEAR TO HAVE BEEN
 CUT-OFF AND INCOMPLETE. REVIEW OF THIS PAGE WILL BE
 BASED ON THE INFORMATION PROVIDED. PROVIDE MISSING
 INFORMATION WITH COMPLETE NOTES AND RESUBMIT. FBC
 106.1.1.
  
 21. M-102A: SEVERAL DUCTS ARE SHOWN PENETRATING A RATED
 WALL (TYPE 1B) AT ELECTRICAL ROOM M008. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC, M 607.5. COORDINATE THE LOCATION OF RATED
 ASSEMBLIES AND PENETRATIONS WITH ARCHITECTURAL PLANS.
  
 22. M-102A: 10X8 AND 10X10 EXHAUST DUCTS FROM EF-5 AND
 EF-11 ARE SHOWN PENETRATING A 1-HOUR RATED WALL (TYPE
 1C) BEFORE REACHING 24X12 LOUVER. SHOW HOW THESE
 PENETRATIONS ARE TO BE PROTECTED IN ACCORDANCE WITH
 FBC, M 607.5.
  
 23. M-102A: NOTE #5 REFERS TO AHU-6 BUT ON FLOOR PLAN
 IT DOES NOT RELATE TO AHU-6. IS THIS REFERENCE INTENDED
 FOR AHU-4? PLEASE CLARIFY.
  
 24. M-102A: NW STAIR VENTILATION DUCT RISER, IS THIS
 DUCT FOR THE PURPOSE OF STAIR PRESSURIZATION AS
 INDICATED ON PG M-404? THE STAIR RISER DIAGRAM ON
 M-102A DOES NOT SHOW ANY TYPE OF RELIEF OPENING, SUCH
 AS A BAROMETRIC RELIEF DAMPER, TO ASSURE THAT STAIRS
 ARE PRESSURIZED WITHIN THE STATED RANGE OF 0.05 INCHES
 WC TO 0.25 INCHES WC. EXCESSIVE PRESSURE IN STAIR COULD
 ALSO NEGATIVELY IMPACT THE MAXIMUM DOOR OPENING FORCE
 AS ALLOWED UNDER FBC 11-4.13.11.IN ADDITION, PG M-404
 INDICATES THESE FANS ARE TO BE OPERATED BY A SMOKE
 CONTROL SYSTEM PANEL. THERE IS NO INDICATION ANYWHERE
 ELSE IN PLANS OF THE EXISTENCE OF A SMOKE CONTROL
 PANEL. PLEASE CLARIFY. THIS COMMENT APPLIES TO ALL
 STAIRWAYS.
  
 25. M-102A AND M-102B: GARAGE EXHAUST FOR EF 2A AND EF
 2B, WHAT IS THE SOURCE OF MAKE-UP AIR FOR THESE FANS?
 THERE ARE NO OPENINGS TO THE OUTSIDE SHOWN ON THIS
 PLAN. SHOW MEANS OF MAKE-UP AIR FOR EXHAUST TO PROVIDE
 THE VENTILATION RATES AS REQUIRED BY FBC, M 403.1 AND
 FBC, M 404.2.
  
 26. M-102B: GENERATOR VENTILATION RISER SHOWS GENERATOR
 ROOM EXHAUST DUCT PENETRATING FLOOR/CEILING ASSEMBLY
 BETWEEN FIRST FLOOR AND MEZZANINE/GARAGE LEVEL. LIFE
 SAFETY PLAN G-007 SHOWS THIS ROOM TO BE A 2-HOUR
 FIRE-RATED ENCLOSURE. THERE IS NO INDICATION ON PLANS
 AS TO HOW THE REQUIRED FIRE-RESISTANCE RATED SEPARATION
 WILL BE MAINTAINED IN THIS LOCATION. SHOW HOW THIS
 SEPARATION IS TO BE MAINTAINED IN ACCORDANCE WITH FBC,
 M 607.5.
  
 27. M-103A: OAU-1 RISER DIAGRAM SHOWS THE SHAFT
 TERMINATING AT THE THIRD FLOOR AND OPEN AT THE BOTTOM.
 SHAFTS THAT DO NOT EXTEND TO THE BOTTOM OF THE BUILDING
 OR STRUCTURE SHALL BE ENCLOSED AT THE BOTTOM IN
 ACCORDANCE WITH FBC 707.11. SHOW THE SHAFT CONSTRUCTION
 AT THE BOTTOM TO TERMITE IN ACCORDANCE WITH THIS
 SECTION.
  
 28. M-103A: VENDING EXHAUST RISER, WHILE SHOWING
 FIRE/SMOKE DAMPERS AT EACH BRANCH, IS NOT SHOWN TO BE
 IN A SHAFT ENCLOSURE ON FLOOR PLAN OR IN RISER DIAGRAM.
 THERE IS ALSO NO SHAFT SHOWN AT THE DUCT LOCATION ON
 ARCHITECTURAL FLOOR PLAN. SHOW THIS DUCT TO BE
 PROTECTED IN ACCORDANCE WITH FBC 707.2.
  
 29. M-103A: AHU-10 DUCT IN HOUSEKEEPING ROOM 231 IS
 SHOWN WITH MULTIPLE FIRE DAMPERS PENETRATING WALLS
 WHICH ARE NOT SHOWN TO BE FIRE RATED ACCORDING TO PG
 A-103A. HOWEVER, ON LIFE SAFETY PLAN PG G-008 THE WALL
 BETWEEN HOUSEKEEPING 231 AND LAUNDRY 235 IS SHOWN TO BE
 1-HOUR RATED. ON NO PLAN ARE THE WALLS BETWEEN ROOM 231
 AND 232 OR BETWEEN ROOM 232 AND ROOM 233 SHOWN TO BE
 RATED. PLEASE COORDINATE WITH ARCHITECTURAL AND LIFE
 SAFETY PLANS, SHOWING OPENING PROTECTIVES TO BE
 PROVIDED ONLY IN RATED WALL ASSEMBLIES. FIRE DAMPERS
 LOCATED WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF THIS
 SECTION, AND THE MANUFACTURER?S INSTALLATION
 INSTRUCTIONS AND LISTING PER FBC, M 607.2.
 NOTE: MECHANICAL FLOOR PLAN SHOWS AN ENCLOSURE AROUND
 DUCT RISERS WHILE ARCHITECTURAL PLAN DOES NOT. PLEASE
 COORDINATE PLANS.
  
 30. M-103A: EXITWAY 230 MAY BE ACTING AS AN EXIT ACCESS
 CORRIDOR FROM PARKING GARAGE AREA. AS SUCH, THE DUCT
 PENETRATIONS WOULD REQUIRE SMOKE DAMPERS IN ADDITION TO
 THE FIRE DAMPERS ALREADY SHOWN IN ACCORDANCE WITH FBC,
 M 607.5.4. CHECK WITH BUILDING PLAN REVIEW FOR THESE
 REQUIREMENTS AND SHOW COMPLIANCE WITH THIS SECTION AS
 NEEDED.
  
 31. M-103A: LAUNDRY ROOM 235 SHOWS THREE 16 INCH ROUND
 DUCTS TO TIE INTO LINT FILTER SYSTEM. PROVIDE THE
 FOLLOWING:
 A) A DETAIL SHOWING HOW THE DRYER EXHAUST DUCTS ARE TO
 TIE INTO THE FILTER SYSTEM WITHOUT BEING MANIFOLDED. B)
 A SUBMITTAL FOR THE LINT FILTER SYSTEM SHOWING LISTING
 AND INSTALLATION INSTRUCTIONS.
 THE INSTALLATION OF DRYER EXHAUST DUCTS SERVING TYPE 2
 CLOTHES DRYERS SHALL COMPLY WITH THE APPLIANCE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS IN ACCORDANCE
 WITH FBC, M 504.7.
  
  
 32. M-103A AND M-103B: EF-1, EF-2A AND EF-2B ARE SHOWN
 IN SOME KIND OF WALL ENCLOSURES. CLEARANCES AROUND
 APPLIANCES TO ELEMENTS OF PERMANENT CONSTRUCTION,
 INCLUDING OTHER INSTALLED EQUIPMENT AND APPLIANCES,
 SHALL BE SUFFICIENT TO ALLOW INSPECTIONS, SERVICE,
 REPAIR OR REPLACEMENT WITHOUT REMOVING SUCH ELEMENTS OF
 PERMANENT CONSTRUCTION IN ACCORDANCE WITH FBC, M 306.1.
 SHOW THESE APPLIANCES TO BE ACCESSIBLE FOR SERVICE AND
 REPLACEMENT IN ACCORDANCE WITH THIS SECTION.
  
 33. M-103B: LAUNDRY ROOM 238, WHAT IS THE SOURCE OF
 MAKE-UP AIR FOR ELECTRIC DRYERS? PROVIDE MODEL NUMBERS
 OR MANUFACTURER?S INSTRUCTIONS TO SHOW THE QUANTITIES
 OF MAKEUP AIR REQUIRED IN THIS AREA. SHOW THE SOURCE OF
 THIS REQUIRED MAKEUP AIR. CLOTHES DRYERS SHALL BE
 EXHAUSTED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTRUCTIONS PER FBC, M 504.1. ALSO, INSTALLATIONS
 EXHAUSTING MORE THAN 200 CFM SHALL BE PROVIDED WITH
 MAKEUP AIR IN ACCORDANCE WITH FBC, M 504.5.
  
 34. M-103B: FLOOR PLAN SHOWS OAU-2 RISER DUCT
 PENETRATING STAIR #1 RATED ENCLOSURE. PENETRATIONS INTO
 AND OPENINGS THROUGH AN EXIT ENCLOSURE ARE PROHIBITED
 EXCEPT FOR EQUIPMENT AND DUCTWORK NECESSARY FOR
 INDEPENDENT PRESSURIZATION IN ACCORDANCE WITH FBC
 1019.1.2. SHOW THIS DUCT TO BE SEPARATED FROM THE STAIR
 ENCLOSURE IN ACCORDANCE WITH THIS SECTION AND
 COORDINATE WITH ARCHITECTURAL PLANS.
  
 35. M-103B: GENERATOR EXHAUST RISER TERMINATES ON THIS
 LEVEL WHICH IS OUTDOORS AND THEREFORE SHALL BE
 PROTECTED WITH LOUVERS AND SCREENS IN ACCORDANCE WITH
 FBC, M 401.6.
  
 36. M-104A: GREASE EXHAUST DUCT RISER IN ONE NOTE CALLS
 FOR 18? ROUND DUCT AND IN ANOTHER NOTE CALLS FOR 26X18.
 WHICH ONE IS CORRECT? PLEASE CLARIFY.
  
 37. M-104A: LIFE SAFETY PLAN G-008 SHOWS THE WALL
 BETWEEN VENDING ROOM 450 AND LINEN ROOM 451 AS 1-HOUR
 RATED. THIS WALL WOULD BE A CONTINUATION OF THE RATING
 OF THE CORRIDOR AND WOULD REQUIRE THE 6 INCH ROUND DUCT
 PENETRATION TO BE PROTECTED WITH FIRE AND SMOKE DAMPER
 IN ACCORDANCE WITH FBC, M 607.5.3 AND 607.5.4. SHOW
 PENETRATIONS TO BE PROTECTED IN ACCORDANCE WITH THIS
 SECTION. COORDINATE WITH ARCHITECTURAL AND LIFE SAFETY
 PLANS.
  
 38. M-104B: OAU-2 RISER LOCATED IN STAIR ENCLOSURE, SEE
 COMMENT #34 ABOVE. ALSO, DUCT IS PENETRATING A SHAFT
 ENCLOSURE AND REQUIRES FIRE AND SMOKE DAMPERS IN
 ACCORDANCE WITH FBC, M 607.5.5.1.
  
 39. M-105A AND M-105B: ROOFTOP OR OUTDOOR EQUIPMENT, NO
 INFORMATION COULD BE FOUND ON PLANS OR IN SUBMITTALS
 REGARDING OUTDOOR EQUIPMENT WIND RESISTANCE RATINGS.
 MECHANICAL EQUIPMENT, APPLIANCES AND SUPPORTS THAT ARE
 EXPOSED TO WIND SHALL BE DESIGNED AND INSTALLED TO
 RESIST THE WIND PRESSURES ON THE EQUIPMENT AND THE
 SUPPORTS AS DETERMINED IN ACCORDANCE WITH THE FLORIDA
 BUILDING CODE, BUILDING PER FBC, M 301.13. EQUIPMENT
 SUBJECT TO THIS REQUIREMENT INCLUDES BUT MAY NOT BE
 LIMITED TO THE FOLLOWING: CONDENSING UNITS (CU-#),
 OUTSIDE AIR UNITS (OAU-#), EXHAUST FANS (EF-#),
 ELEVATOR RELIEF VENTILATORS. CONSULT WITH MANUFACTURERS
 TO DETERMINE IF EQUIPMENT HAS BEEN TESTED FOR
 INSTALLATION IN THE 140 MPH WIND ZONE WITH THE
 ANTICIPATED WIND PRESSURES. ALL ROOFTOP EQUIPMENT AND
 DUCT SUPPORT DETAILS SHALL BE CONFIRMED WITH WIND LOAD
 CALCULATIONS AND SUBMITTED FOR BUILDING PLAN REVIEW.
  
 40. M-401: PIPE PENETRATION DETAILS, NOTE THAT THROUGH
 PENETRATION FIRESTOP SYSTEMS DETAILED ON PLANS ARE FOR
 STEEL PIPE ONLY AND THE INSULATED PIPE IS WITH CALCIUM
 SILICATE AND FIBERGLASS INSULATION. NEITHER OF THESE
 SYSTEMS IS APPLICABLE TO COPPER PIPE WITH FOAM RUBBER
 INSULATION. PROVIDE DETAIL FOR A SYSTEM WHICH WILL
 COVER THIS TYPE OF PIPING SYSTEM AS IT WILL BE
 PREVALENT WITH SPLIT AIR CONDITIONING SYSTEMS. SEE FBC
 712.1
  
 41. M-404: ROOF UPBLAST EXHAUST FAN DETAIL, IS THIS
 DETAIL FOR KEF-1? THIS DOES NOT APPEAR TO BE AN
 INSTALLATION FOR A GREASE EXHAUST FAN AS IT SHOWS A
 BACKDRAFT DAMPER AND IS MISSING OTHER COMPONENTS
 NECESSARY FOR GREASE EXHAUST IN ACCORDANCE WITH FBC, M
 SEC. 507. ALSO, KEF-1 IS SHOWN TO PROVIDE 2375 CFM OF
 EXHAUST. THIS AIR IS MOVED THROUGH AN 18 INCH ROUND
 DUCT. AT THAT VOLUME, THE AIR WILL BE MOVING AT A
 VELOCITY OF APPROXIMATELY 1342 FEET PER MINUTE (FPM).
 GREASE DUCT SYSTEMS SERVING A TYPE I HOOD SHALL BE
 DESIGNED AND INSTALLED SO AS TO PROVIDE AN AIR VELOCITY
 WITHIN THE DUCT SYSTEM OF NOT LESS THAN 1,500 FEET PER
 MINUTE AND NOT GREATER THAN 2,500 FEET PER MINUTE IN
 ACCORDANCE WITH FBC, M 506.3.4.
 NOTE: NOT ENOUGH INFORMATION WAS PROVIDED IN PLANS FOR
 A COMPLETE REVIEW OF THE KITCHEN HOOD EXHAUST SYSTEM.
 PROVIDE COMPLETE PLANS AND DETAILS FOR THE TYPE I HOOD
 AND EXHAUST SYSTEM. SEPARATE PERMITS ARE REQUIRED FOR
 HOODS, SUPPRESSION SYSTEMS AND WALK-IN
 COOLERS/FREEZERS.
  
 42. ADDITIONAL INFORMATION REQUIRED: NO INFORMATION WAS
 PROVIDED REGARDING FUEL STORAGE FOR THE STANDBY
 GENERATOR. PROVIDE DETAIL FOR THE FUEL STORAGE SYSTEM
 TO BE USED AND DEMONSTRATE COMPLIANCE WITH NFPA 37-02
 IN ACCORD ANCE WITH FBC, M 915.1. AND 915.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop P PLUMBING
Rev No 14 Status P Date 2009-02-13 Cont ID  
Sent By kstevens Date 2009-02-13 Time 19:36 Rev Time 0.00
Received By kstevens Date 2009-02-13 Time 19:35 Sent To  
Notes
2009-02-13 19:37:52REVISIONS OK -- SHTS P-001, P-101B, P--301 & P-501

Review Stop P PLUMBING
Rev No 13 Status P Date 2009-02-12 Cont ID  
Sent By kstevens Date 2009-02-12 Time 17:26 Rev Time 0.00
Received By kstevens Date 2009-02-12 Time 17:26 Sent To  
Notes
2009-02-12 17:27:23REVISIONS OK -- SHTS P-101A, P-202A & P-600

Review Stop P PLUMBING
Rev No 12 Status F Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 22:27 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 22:27 Sent To  
Notes
2009-01-24 22:44:15DENIED
 REFERENCE:
 FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 BUILDING
 FLORIDA STATUTES
  
 1. SHT P101B THE EXHAUST FROM THE GENERATOR SHALL BE
 INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE
 EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE
 PLUMBING PLAN REVIEW. FS 589.
  
 2. SHT P-301 THE FLOOR SINK SHALL CONNECT TO THE VENTED
 LINE, NOT THE BRANCH LINE TO ANOTHER FIXTURE. SECTION
 912.2.4. ALL INDIRECT PIPING THAT EXCEEEDS 2 FEET
 HORIZONTALLY SHALL BE TRAPPED. SECTION 802.2. EACH
 PLUMBING FIXTURE SHALL BE SEPARATELY TRAPPED SECTION
 1002.1. DOUBLE TRAPS ARE NOT ALLOWED. SECTION 1002.1.
  
 3. SHT P-302 IDENTIFY ITEM 33. THIS IS NOT SHOWN ON THE
 KITCHEN SCHEDULE. SECTIONS 106.1.2 & 601.1.
  
 4. SHT P-501 THE EXHAUST FROM THE GENERATOR SHALL BE
 INDICATED AS A REVISION ON THE MECHANICAL PLANS. THE
 EXHAUST VENT IS NOT WITHIN THE SCOPE OF WORK OF THE
 PLUMBING PLAN REVIEW. FS 589. -- THE FLOOR SINK SHALL
 CONNECT TO THE VENTED LINE, NOT THE BRANCH LINE TO
 ANOTHER FIXTURE. SECTION 912.2.4. ALL INDIRECT PIPING
 THAT EXCEEEDS 2 FEET HORIZONTALLY SHALL BE TRAPPED.
 SECTION 802.2. EACH PLUMBING FIXTURE SHALL BE
 SEPARATELY TRAPPED SECTION 1002.1. DOUBLE TRAPS ARE NOT
 ALLOWED. SECTION 1002.1. -- REVISION 5 NOT CLOUDED IN
 THE GANG BATHS & AT THE DELETED RISER SAN/18. CLOUD &
 NUMBER ALL REVISIONS SUBMITTED FOR REVIEW. SECTION
 106.1.3.
  
 5. SHT P-602 NATURAL GAS SIZING FOR SECTION J MINIMUM
 1-1/4" IS REQUIRED FOR 400 CFH PER TABLE 402.4(2). --
 THE DIRECT VENT IS NOT APPROVED TO START AND TERMINATE
 THROUGH A WALL ON THE ZERO LOT LINE.
  
 6. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  
  

Review Stop P PLUMBING
Rev No 11 Status P Date 2009-01-24 Cont ID  
Sent By kstevens Date 2009-01-24 Time 22:23 Rev Time 0.00
Received By kstevens Date 2009-01-24 Time 22:23 Sent To  
Notes
2009-01-24 22:27:09REVISIONS OK -- SHTS P-OO1, P-101A, P-102A, P-201A,
 P-202A (PROVISO: DIRECT VENTS FOR THE WATER HEATERS ARE
 NOT APPROVED AS INDICATED THRU THE ZERO LOT LINE WALL -
 REVISION REQUIRED), P-203A, P-500, P-503 (PROVISO:
 BACKFLOW SHALL BE INSTALLED MAXIMUM 4 FT ABOVE THE
 FLOOR FOR MAINTENANCE & CERTIFICATION), P-600.

Review Stop P PLUMBING
Rev No 10 Status P Date 2008-11-05 Cont ID  
Sent By kstevens Date 2008-11-05 Time 18:55 Rev Time 0.00
Received By kstevens Date 2008-11-05 Time 18:55 Sent To  
Notes
2008-11-05 18:55:42VARIOUS PLUMBING SUBMITTALS APPROVED.

Review Stop P PLUMBING
Rev No 9 Status F Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-31 Time 13:52 Rev Time 0.00
Received By kstevens Date 2008-10-31 Time 13:52 Sent To  
Notes
2008-10-31 15:46:24REVISION FAILED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
  
 1. SHT P-203A INDICATES 3 GAS DRYERS, BUT ONLY 2 GAS
 DRYERS ARE SHOWN. NO CHANGE IN DRYER AMOUNTS SHOWN ON
 FLOOR PLAN. PLEASE CORRELATE. SECTIONS 106.1.1 & 402.1.
  
 2. SHT P-500 THE FLOOR DRAINS (3) ADDED NEAR THE BASE
 OF STACK SAN-13 AND BY THE TOILET ROOMS FOR THE SPA'S
 ARE NOT VENTED. SECTIONS 901.2.1 & 908.3.
  
 3. SHT P-501 THE SANITARY RISER DIAGRAM DOES NOT
 REFLECT THE FLOOR PLAN AT THE WASH MACHINES FOR THE
 GUEST LAUNDRY ROOM. THE TRAP & LAUNDRY BOX ARE SHOWN ON
 EACH SIDE OF THE STACK ON THE FLOOR PLAN, BUT ARE SHOWN
 ON ONE SIDE OF THE STACK ON THE RISER DIAGRAM. ALSO THE
 SECOND TRAP IS NOT SHOWN CONNECTING TO THE STACK.
 SECTIONS 106.1.1 & 706.3.
  
 4. SHT P-503 REVISION #4 HAS BEEN DELETED FROM THE
 REVISION INDEX. PLEASE KEEP ALL PREVIOUS REVISION
 NUMBERS IN INDEX THROUGH OUT THE PERMIT CYCLE. NO NEW
 CHANGES INDICATED ON THE SHEET AS REVISION #5. IF NO
 CHANGES/REVISIONS NOT REQUIRED FOR PUBLIC RECORD.
 SECTION 106.1.3.
  
 5. SHT P-602 NATURAL GAS SIZING TABLE. NOT ALL CHANGES
 HAVE BEEN INDICATED WITH A CLOUD OR REVISION NUMBER.
 SEE SECTION LOAC (CFH) FOR A, J, K & L AS WELL AS APPL
 LOAD (CFH) FOR J. PIPE SECTION N SECTION LOAD TO BE 700
 AND THE LONGEST RUN TO BE SECTION P, NOT O. PLEASE
 CORRELATE ALL CHANGES TO NATURAL GAS SIZING TABLE AND
 CLOUD ALL REVISIONS AND INDICATE WITH A REVISION
 NUMBER. SECTION 106.1.3.
  
 6. SHT P-602 GAS RISER DIAGRAM INDICATES SECTION P TO
 BE 1/2", BUT IT ALSO SHOWS 3/4" GAS VALVE AND CAP.
 PLEASE CLARIFY. SECTIONS 106.1.1 AND 402.1.
  
 7. SHT P-602 GAS RISER DIAGRAM DOES NOT SHOW SECTION O.
 PLEASE CORRELATE WITH GAS SIZING TABLE. SECTIONS
 106.1.1 & 402.1.
  
 8. SHT P-602 GAS RISER DIAGRAM. UNIONS ARE REQUIRED
 DOWNSTREAM OF THE SHUT OFF VALVES FOR EACH REGULATOR AT
 THE WATER HEATERS AND THE POOL HEATER.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  

Review Stop P PLUMBING
Rev No 8 Status P Date 2008-10-31 Cont ID  
Sent By kstevens Date 2008-10-31 Time 13:50 Rev Time 0.00
Received By kstevens Date 2008-10-29 Time 13:58 Sent To  
Notes
2008-10-31 13:52:40REVISIONS OK -- SHT P-002, P-101A, P-101B, P-102A,
 P-102B, P-103A, P-103B, P-104A, P-104B, P-105A, P-201A
 (GAS), P-202A (GAS), P-302 (GAS), P-402, P-506, P-507,
 P-600 & P-601.

Review Stop P PLUMBING
Rev No 7 Status P Date 2008-09-03 Cont ID  
Sent By kstevens Date 2008-09-03 Time 06:48 Rev Time 0.00
Received By kstevens Date 2008-09-03 Time 06:48 Sent To  
Notes
2008-09-03 06:49:13REVISION OK -- SHT P-600

Review Stop P PLUMBING
Rev No 6 Status F Date 2008-08-18 Cont ID  
Sent By kstevens Date 2008-08-18 Time 09:09 Rev Time 0.00
Received By kstevens Date 2008-08-18 Time 09:09 Sent To  
Notes
2008-08-18 09:11:23REVISION DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT P-600 REVISIONS DO NOT REFLECT THE CHANGES SHOWN
 ON THE FLOOR PLAN. SECTIONS 106.1.1 & 1106.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 5 Status P Date 2008-08-18 Cont ID  
Sent By kstevens Date 2008-08-18 Time 09:08 Rev Time 0.00
Received By kstevens Date 2008-08-18 Time 09:08 Sent To  
Notes
2008-08-18 09:09:10REVISIONS OK --SHTS P-101A, P-201A, P-500 & P-503.

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-17 Cont ID  
Sent By kstevens Date 2008-07-17 Time 08:11 Rev Time 0.00
Received By kstevens Date 2008-07-16 Time 17:17 Sent To  
Notes
2008-07-17 08:13:40 
  
 PASSED/PROVISO
  
 REVISION REQUIRED FOR SHT P-501 SHOWING THE FIXTURES
 FOR THE GUEST LAUNDRY ROOM, (2 W/M'S AND A FLOOR
 DRAIN), AND THE CONNECTION OF THE VENT STACK TO THE
 SANITARY STACK FOR RISER "I".
  
  
  
  
  
 .

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-07-03 Cont ID  
Sent By kstevens Date 2008-07-03 Time 08:52 Rev Time 0.00
Received By kstevens Date 2008-07-02 Time 17:52 Sent To  
Notes
2008-07-03 11:08:29DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 CITY WPB MUNICIPAL CODES
  
 ****FROM PREVIOUS REVIEW:
  
 ******FROM PREVIOUS REVIEWS:
  
 1. OK
 2. OK
 3. OK
 4. OK
 5. OK
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02
 GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING
 TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF.
 INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW
 METHOD. SECTIONS 106.1.2 & 608.
 ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A
 MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE
 RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED
 FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW
 PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM
 BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE
 DRYERS.
 ******RESPONSE NOTED, BUT THE 950XLU BACKFLOW PREVENTOR
 IS STILL SHOWN ON SHEETS P203A & P-504. PLEASE SHOW THE
 N36 VACUUM BREAKER.
  
 16. OK
 17. OK
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
 34. OK
 35. OK
 36. OK
 37. OK
 38. OK
 38A. OK
 39. OK
 40 OK
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
 46. OK
 47. OK
 48. OK
 49. OK
 50. OK
 51. OK
  
 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
 ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT
 STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK
 ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE
 DRAINAGE STACKS.
 ******RESPONSE NOTED, BUT RISER "I" DOES NOT SHOW THE
 BENT FROM THE 2ND FLOOR OR CONNECTION TO THE SANITARY
 STACK. (SHT 502).
  
 53. OK
 54. OK
 55. OK
 56. OK
 57. OK
 58. OK
 59. OK
 60. OK
 61. OK
 62. OK
 63. OK
 64. OK
 65. OK
 66. OK
 67. OK
 68. OK
 69. OK
 70. OK
 71. OK
 72. OK
 73. OK
 74. OK
 75. OK
 76. OK
 77. OK
  
 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12
 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
 ******RESPONSE NOTED, BUT COMMENT STILL NOT ADDRESSED.
 BRANCH LINE SHOWN UPSTREAM OF CONDENSATE CONNECTION AND
 ST13 ON SHT P-101A. PLEASE CORRELATE.
  
 79. OK
 80. OK
 81. OK
 82. OK
 83. OK
 84. OK
 85. OK
 86. OK
 87. OK
 88. OK
 89. OK
  
 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT
 SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS
 APPLICATION IS APPLIED FOR).
  
 I. N/A
 J. N/A
  
 **********NEW COMMENTS**********
  
 1B. OK
 2B. OK
 3B. OK
  
 ***********NEW COMMENT***********
  
 1C. SHT P-602 SHOWS THE REGULATORS TO BE FISHER MODEL
 Y600A BUT THE MANUF SPECIFICATIONS FOR THE REGULATORS
 INDICATE THE REGULATORS TO MODEL S300 SERIES. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-04-26 Cont ID  
Sent By kstevens Date 2008-04-26 Time 16:10 Rev Time 0.00
Received By kstevens Date 2008-04-25 Time 19:00 Sent To  
Notes
2008-04-26 17:04:20DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 CITY WPB MUNICIPAL CODES
  
 ****FROM PREVIOUS REVIEW:
  
 1. OK
 2. OK
 3. OK
 4. OK
  
 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE
 INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201
 THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS
 P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE
 SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES
 ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT
 REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX
 WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3.
 ****RESPONSE NOTED, BUT THE INDEX OF DRAWINGS STILL
 DOES NOT RELFECT THE SHEETS SUBMITTED. MANY SHEETS
 SHOWN ON THE INDEX WERE NOT SUBMITTED. SOME SHEETS
 SUBMITTED ARE NOT SHOWN ON THE INDEX.
  
 6. OK
 7. OK
 8. OK
 9. OK
 10. OK
 11. OK
 12. OK
 13. OK
 14. OK
  
 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02
 GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING
 TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF.
 INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW
 METHOD. SECTIONS 106.1.2 & 608.
 ****RESPONSE NOTED, BUT THE 950XLU IS REQUIRED TO BE A
 MAXIMUM 30" ABOVE THE FLOOR WITH AN INDIRECT WASTE
 RECEPTOR, NOT IN THE CEILING AS SHOWN. THIS IS REQUIRED
 FOR SERVICING AND TESTING. THE REQUIREMENT FOR BACKFLOW
 PREVENTION CAN BE ACHIEVED WITH A "WATTS N36 VACUUM
 BREAKER OR EQUIALENT AT THE TOP OF THE DROP TO THE
 DRYERS.
  
 16. OK
  
 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY
 FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A
 DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER.
 IF CONNECTING TO THE STORM SEWER, A RELIEF VENT,
 (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. SECTION 314.2.1.
 ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3
 SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE
 BRANCH LINE TO ST-13.
  
 18. OK
 19. OK
 20. OK
 21. OK
 22. OK
 23. OK
 24. OK
 25. OK
 26. OK
 27. OK
 28. OK
 29. OK
 30. OK
 31. OK
 32. OK
 33. OK
  
 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE
 IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN
 BE FOUND. SECTION 106.1.2.
 ****RESPONSE NOTED, BUT SHT P-101 WAS NOT SUBMITTED OR
 INDICATED ON SHT G-001A DRAWING INDEX.
  
 35. OK
 36. OK
  
 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE
 REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.--
 THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN
 DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE
 INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL
 EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT
 MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART.
 INDICATE MODEL NUMBERS. SECTION 607.3.2. ****RESPONSE
 NOTED, BUT THE EXPANSION TANK CALCULATION SUBMITTED
 INDICATES THE REQUIRED SIZE IS 28.5 GAL. THE MODEL
 INDICATED IS ONLY 25 GAL. TANK NOT APPROVED.
  
 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
 ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT
 STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK
 ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE
 DRAINAGE STACKS.
  
 38A. OK
 39. OK
 40 OK
 41. OK
 42. OK
 43. OK
 44. OK
 45. OK
 46. OK
 47. OK
 48. OK
 49. OK
 50. OK
 51. OK
  
 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
 ****RESPONSE NOTED, BUT NOT ALL STACKS SHOW THE VENT
 STACKS CONNECTING TO THE DRAINAGE STACKS. PLEASE CHECK
 ALL STACKS TO MAKE SURE THE VENT STACKS CONNECT TO THE
 DRAINAGE STACKS.
  
 53. OK
 54. OK
 55. OK
 56. OK
  
 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT
 REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE CLEANOUT IS MISSING
 UPSTREAM OF THE BRANCH LINE TO RISER 2A AND THE OFFSET
 AT THE BASE OF RISER 1A IS NOT INDICATED.
  
 58. OK
  
 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY
 FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE BRANCH LINE TO THE FLOOR
 DRAIN DOES NOT REFLECT THE FLOOR PLAN, NOR IS IT
 VENTED. SECTION 901.2.1.
  
 60. OK
 61. OK
 62. OK
 63. OK
 64. OK
 65. OK
 66. OK
 67. OK
 68. OK
 69. OK
 70. OK
 71. OK
 72. OK
 73. OK
 74. OK
 75. OK
 76. OK
  
 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR
 ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION
 106.1.1.
 ****RESPONSE NOTED, BUT THE OFFSET BELOW THE ROOF IS
 NOT SHOWN ON THE RISER DIAGRAM.
  
 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12
 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 79. OK
  
 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE
 OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE
 AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM
 DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE
 CORRELATE. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT COMMENT NOT ADDRESSED.
  
 81. OK
 82. OK
 83. OK
  
 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17).
 ****RESPONSE NOTED, BUT THE CONDENSATE LINE FROM AHU-3
 SHALL CONNECT TO THE BUILDING STORM DRAIN LINE, NOT THE
 BRANCH LINE TO ST-13.
  
 85. OK
 86. OK
 87. OK
 88. OK
 89. OK
  
 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. OK
 B. OK
 C. OK
 D. OK
 E. OK
 F. OK
 G. OK
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
 ****RESPONSE NOTED, BUT THE MANUF. SHEET WERE NOT
 SUBMITTED. (THIS CAN BE PROVISO'D UNTIL THE GAS
 APPLICATION IS APPLIED FOR).
  
 I. N/A
 J. N/A
  
 **********NEW COMMENTS**********
  
 1B. SHT P-104A FIXTURES ARE NOT SHOW ON THE FLOOR PLAN
 FOR THE BATHROOM AT RISER SAN/10B. SECTION 106.1.2.
 PLEASE SHOW ALL FIXTURES ON THE FLOOR PLAN.
  
 2B. THE GAS REGULATOR SUBMITTAL IS NOT APPROVED FOR ALL
 GAS APPLIANCES. THE ONLY SIZE INDICATED IN THE
 SUBMITTAL IS 3/4" BUT THE SHUT OFF VALVE AND REGULATOR
 SHALL BE SIZED PER THE PIPE SIZE REQUIRED TO EACH
 APPLIANCE.
  
 3B. EMERGENCY HOOD SHUT DOWN SHUT OFF
 VALVE TO BE BELOW CEILING. MANUAL SHUT
 OFF VALVE TO BE UPSTREAM. UNION TO BE
 DOWN STREAM OF MANUAL VALVE. THIS IS REQUIRED FOR THE
 GRIDDLE.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-03-10 Cont ID  
Sent By kstevens Date 2008-03-10 Time 11:35 Rev Time 0.00
Received By kstevens Date 2008-03-05 Time 19:01 Sent To  
Notes
2008-03-10 15:57:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 BUILDING
 FBC-2004 FUEL GAS
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
 FHA-98 DESIGN MANUAL
 CITY WPB MUNICIPAL CODES
  
 1. SHT G.000 GUESTROOM MATRIX. THE TOTAL FOR FOR THE
 QUEEN STANDARD IS SHOWN AS 81, BUT ADDS UP TO 72.
 PLEASE RECHECK THE CALCULATIONS. SECTIONS 106.1.2 &
 11-9.1.2.
  
 2. SHT G.000 GUESTROOM MATRIX DOES NOT COMPLY WITH
 SECTION 11-9.1.4 AS THERE IS NOT ACCESSIBLE BOARDROOM
 SUITE AVAILABLE.
  
 3. SHT G.000 PER SECTION 11-9.1.2, PURSANT TO CHAPTER
 509, FLORIDA STATUTES, A NUMBER OF ROOMS EQUALLING AT
 LEAST 5% OF THE GUEST ROOMS MINUM THE NUMBER OF
 ACCESSIBLE ROOMS REQUIRED BY TABLE BELOW SHALL PROVIDE
 ADDITIONAL FEATURES OF SECTION 11-9.2.3. ONE ROOM IS
 REQUIRED, PLEASE INDICATE THE ROOM NUMBER & LOCATION OF
 THE REQUIRED ROOM.
  
 4. SHTS G-00- THRU G-009 & SHTS AC-101 THRU A-812. THE
 PRINTED NAME OF THE PERSON SEALING THE DOCUMENTS IS
 REQUIRED ON EACH SHEET. FAC 61G1-16.004(6) & FS
 481.2055.
  
 5. SHT G001 INDEX OF DRAWINGS DOES NOT REFLECT THE
 SHEETS SUBMITTED. SHTS A-813 THRU A-819 SHOWN ON THE
 INDEX WERE NOT SUBMITTED. SHTS P-101 THRU P-105, P-201
 THRU P-204 SHOWN ON THE INDEX WERE NOT SUBMITTED. SHTS
 P-101B THRU P-105B, P-201B THRU 204B, P-602 WERE
 SUBMITTED BUT NOT SHOWN ON THE INDEX. ALSO SHEET TITLES
 ON SHTS P-101A THRU P-204A & P-101B THRU P-204B DO NOT
 REFLECT THE INDEX TITLES. PLEASE CORRELATE THE INDEX
 WITH SHEETS & INFORMATION SUBMITTED. SECTION 106.1.3.
  
 6. SHT AC-102 SHOWS A COMPACTOR PAD FLOOR DRAIN. PLEASE
 INDICATE IF THE COMPACTOR WILL BE COMPACTING GREASY
 WASTE. ALSO THE STORM WATER CAN NOT DRAIN INTO THE
 SANITARY SYSTEM. INDICATE THE METHOD OF KEEPING THE
 STORM WATER OUT OF THE SANT. SYSTEM. ARTICLE III,
 SECTION 90-125(B)(5). IN THE PAST WHEN THIS ISSUE CAME
 UP, WE INDICATED THAT THE DRAIN IS NOT REQUIRED. PLEASE
 CLARIFY.
  
 7. ALL PLUMBING SHEETS THAT INDICATE "TYPICAL LEVEL
 PLAN". PLEASE INDICATE WHAT FLOORS THE PLANS ARE
 TYPICAL OF. SECTIONS 106.1.1 & 106.1.2.
  
 8. SHT A-100D IS INDICATED AS TYPICAL LEVEL PLAN 4TH
 FLOOR. ARE THE 3RD & 5TH FLOORS DIFFERENT. THESE FLOORS
 HAVE NOT BEEN SUBMITTED. SECTIONS 106.1.1 & 106.1.2.
  
 9. PLANS SHALL BE ROUTED TO THE STATE OF FLORIDA, DEPT.
 OF BUSINESS REGULATION. (DBPR), DIVISION OF HOTEL AND
 RESTAURANT FOOD SERVICE LICENSE FOR REVIEW PRIOR TO
 RESUBMITTING TO THE CITY FOR REVIEW. A MINIMUM OF 3
 SETS OF PLANS WITH THE DBPR REVIEW SHALL BE SUBMITTED.
 THE "SPECIFICATION WORKSHEETS" SHALL BE ATTACHED TO THE
 SHEET WITH THE DBPR PLAN REVIEW STAMP. SECTION
 102.2.1.
  
 10. SHT A-423 DETAILS 1, 3, 7 & 8 THE TURNING AREA
 SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE
 TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 8
 SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV
 PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 11. SHT A-425 DETAILS 1, 3, 4 & 5 THE TURNING AREA
 SHALL BE UNOBSTRUCTED. THE W/C CAN NOT BE IN THE
 TURNING AREA. SECTION 11-4.22.3.--DETAILS 1 & 5
 SHALL SHOW THE CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV
 PER SECTIONS 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 12 SHT A-4.26 DETAIL 1 THE TURNING AREA SHALL BE
 UNOBSTRUCTED. THE W/C CAN NOT BE IN THE TURNING AREA.
 SECTION 11-4.22.3.--DETAILS 1 & 6 SHALL SHOW THE
 CLEAR FLOOR SPACE FOR THE W/C, TUB & LAV PER SECTIONS
 11-4.16.2, 11-4.19.3 & 11-4.20.2.
  
 13. SHT A-612 THE WALL FINISH FOR THE TOILET ROOMS 112,
 113, 137 & 138 IS STATED AS "VARIES"PLEASE SHOW
 COMPLIANCE WITH SECTION 1210.2 REQUIREMENT FOR THE
 WALLS WITHIN 2 FT OF THE TOILETS OR URINALS SHALL HAVE
 A "SMOOTH, HARD, NONABSORBENT" SURFACE.
  
 14. ALL MECH, PLMG & ELECT SHEETS. THE ADDRESS OF THE
 ENGINEER FIRM ON THE TITLE BLOCKS DOES NOT REFLECT THE
 ADDRESS OF RECORD ON THE STATE OF FLORIDA DBPR WEBSITE.
 PLEASE UPDATE THE TITLE BLOCKS OR THE DBPR WEBSITE SO
 THEY REFLECT PRIOR TO RESUBMITTING TO THE CITY FOR
 REVIEW. IF MULTIPLE ADDRESS, PLEASE ADD THE ADDRESS OF
 RECORD TO TITLE BLOCKS. FAC 61G15-23.002(2) & FS
 471.025.
  
 15. SHT P-001 LAUNDRY EQUIPMENT LOAD SCHEDULE ITEM 02
 GAS DRYER INDICATES A 3/4" HOT WATER SUPPLY CONNECTING
 TO THE DRYER. PLEASE CLARIFY. SUBMIT MANUF.
 INSTALLATION INSTRUCTIONS. IF REQUIRED, SHOW BACKFLOW
 METHOD. SECTIONS 106.1.2 & 608.
  
 16. SHT P-101A A 2-WAY CLEANOUT IS REQUIRED AT THE
 INLET AND EXIT OF EACH GREASE INTERCEPTOR. PLEASE
 INDICATE ON THE CLEANOUT BETWEEN THE GREASE
 INTERCEPTORS. UTILITY STANDARD FOR GREASE INTERCEPTORS
 & SECTION 708.3.2.
  
 17. SHT P-101A THE CONDENSATE SHALL DRAIN SEPARATELY
 FROM THE BUILDING AND TERMINATE IN A CATCH BASIN, A
 DRYWELL, A PLANTED AREA, OR CONNECT TO THE STORM SEWER.
 IF CONNECTING TO THE STORM SEWER, A RELIEF VENT,
 (GOOSENECK), IS REQUIRED AS THE CONDENSATE EXITS THE
 BUILDING. SECTION 314.2.1.
  
 18. SHT P101AINDICATES "6 INCH PDD DN 4546SF. PLEASE
 SHOW WHERE THE LINE IS AND INDICATE WHAT PDD STANDS FOR
 AS IT IS NOT INDICATED ON THE ABBREVIATION SCHEDULE ON
 SHT P-001. SECTION 106.1.2.
  
 19. SHT P-101B THE COMPACTOR INDICATES4" GREASE
 (4DFU'S), BUT SHOWS THE FLOOR DRAIN CONNECTING TO THE
 SANITARY SYSTEM. PLEASE SEE COMMENT #6. SECTION
 106.1.1
  
 20. SHT P-101B CLEANOUTS ARE REQUIRED ON THE SANITARY &
 STORM SYSTEMS PER SECTIONS 708.3.5 & 1101.8.
  
 21. SHTS P-102A P-102B, P-103A & P-103B THE CONDENSATE
 SHALL DRAIN FROM THE BUILDING SEPARATELY. (SEE COMMENT
 #17).--THE BACKWATER VALVES ARE NOT REQUIRED IF THE
 RELIEF VENTS ARE INSTALLED.
  
 22. SHT P-103A THE W/C & LAV ARE NOT SHOWN ON THE FLOOR
 PLAN IN ROOM 219. PLEASE SHOW ALL FIXTURES ON FLOOR
 PLAN. SECTION 106.1.1.
  
 23. SHT P-103A SAN-8A RISER "B" SHOWS TUBS ON THE
 RISER, BUT SHOWERS ON THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 24. SHT P-103A SHOWERS ARE NOT SHOWN ON THE FLOOR PLAN
 IN ROOMS 213 THRU 216, 224 & 225.--PLEASE SHOW
 RISER DESIGNATIONS FOR RISERS ST/14 & STO/14. SECTION
 106.1.2.
  
 25. SHT P-103B SANITARY RISER SAN-4A SHOWS SHOWERS ON
 THE FLOOR PLAN, BUT TUBS ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 26. SHT P-104A KING ROOMS 449, *48, 447, 445, 432, 430,
 429 & 431 SHOW SHOWERS ON THE FLOOR PLAN, BUT TUBS ON
 THE RISER DIAGRAMS. PLEASE CORRELATE. SECTION 106.1.1.
  
 27. SHT P-104A INDICATES RISER "C" ON THE FLOOR PLAN,
 BUT RISER "C" NOT SUBMITTED. PLEASE CLARIFY. SECTION
 106.1.1.
  
 28. SHT P-104A RISER SAN-10A THE SINK, (S-1) SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT FOR THE BATHROOM
 FIXTURES. SECTION 909.1.
  
 29. SHT P-104B KING ROOMS 413, 414, 415 &416 SHOWS
 SHOWERS ON THE FLOOR PLAN, BUT SHOWS TUBS ON THE RISER
 DIAGRAM. PLEASE CORRELATE. SECTION 106.1.1.
  
 30. SHTS P-105A & P-105B INDICATE THE RISER DESIGNATION
 NUMBERS AT THE ROOF DRAINS/OD'S TO TRACK RISER THRU
 BUILDING. SECTION 106.1.2.
  
 31. SHT P-203A THE SHOWERS ARE NOT SHOWN ON THE FLOOR
 PLAN IN MANY ROOMS/UNITS. PLEASE SHOW ALL FIXTURES ON
 THE FLOOR PLAN. SECTION 106.1.1.
  
 32. SHT P-203A SUBMIT THE RISER DIAGRAM FOR THE LAUNDRY
 ROOM. SHOW ALL PIPE SIZES, VALVES & REQUIRED WATER
 HAMMER ARRESTORS. SECTIONS 103.5.1.3, 604.1, 604.9,
 606.2(1).
  
 33. SHT. P-203A IDENTIFY FIXTURE (TMV-3) SHOWN AT COL.
 LINE D BETWEEN COLS 10 & 11. SECTION 106.1.2.
  
 34. SHT P-301 NOTE FOR CONTINUATION OF 2-1/2" VENT LINE
 IS NOT COMPLETE. PLEASE CLARIFY WHERE CONTINUATION CAN
 BE FOUND. SECTION 106.1.2.
  
 35. SHT P-302 IDENTIFY COLD WATER RISER NEAR COL. LINE
 E/8.5. (NOT SHOWN ON THE RISER DIAGRAM). SECTION
 106.1.2.
  
 36. SHT P-302 HOT WATER SUPPLY ONLY SHOWN TO RISER #45
 ON THE FLOOR PLAN, BUT THE NOTE INDICATES HW & CW TO
 RISER. PLEASE CORRELATE. SECTION 106.1.1.
  
 37. SHT P-402 HOT WATER DETAILS. TRAP PRIMERS ARE
 REQUIRED AT THE FLOOR DRAINS. SECTION 1002.4.--
 THERMAL EXPANSION CONTROL REQUIRED FOR WATER HEATERS IN
 DETAIL NUMBER 13. IF AN EXPANSION TANK WILL BE
 INSTALLED, SUBMIT CALCULATIONS FOR EXPANSION CONTROL
 EXPANSION TANKS, (FOR DETAIL # 14 ALSO), & SUBMIT
 MANUF. SPECIFICATION SHEETS WITH INSTALLION/SIZE CHART.
 INDICATE MODEL NUMBERS. SECTION 607.3.2.
  
 38. SHT P-500 WEST END SANT. RISERS. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
  
 38. SHT P-500 RISER SAN-10B SHOWS A DRY HORIZONTAL VENT
 PAST FIXTURE BT-1. THIS IS PROHIBITED PER SECTIONS
 905.3 & 905.4.
  
 39. SHT P-500 RISER SAN-10A THE S-1 SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM
 FIXTURES. SECTION 909.1.
  
 40 SHT P-500 RISER SAN-9A DOES NOT REFLECT THE FLOOR
 PLAN AT THE 2ND FLOOR AND NOT ALL FIXTURES ARE VENTED.
 PLEASE CORRELATE. SECTIONS 106.1.1 & 901.2.1.
  
 41. SHT P-500 RISER SAN-8A DOES NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 42. SHT P-500 FIXTURE UPSTREAM OF RISER SAN-10 DOES NOT
 REFLECT THE FLOOR PLAN. SHOWER INDICATED ON THE FLOOR
 PLAN, FLOOR DRAIN ON RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 43. SHT P-500 CONNECTIONS TO THE BUILDING DRAIN AT
 RISER SAN-10 & BRANCH LINE DO NOT REFLECT THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 44. SHT P-500 RISER SAN-8/9 OFFSET IN THE 1ST FLOOR
 CEILING DOES NOT REFLECT THE FLOOR PLAN OFFSET. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 45. SHT P-500 RISERS SAN-6A, 7A, 8A, 12A & 13 DO NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 46. SHT P-500 RISER SAN-6 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSET BELOW THE 3RD FLOOR. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 47. SHT P-500 RISER SAN-11 DOES NOT REFLECT THE FLOOR
 PLAN AT THE BASE OF THE STACK. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 48. SHT P-500 VENTING ABOVE TOILET ROOMS 137 & 138 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 49. SHT P-500 RISER SAN-12A DOES NOT REFLECT THE FLOOR
 PLAN AT TOILET ROOM 2ND FLOOR. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 50. SHT P-500 RISER SAN-13 DOES NOT REFLECT THE FLOOR
 PLAN 2ND FLOOR. FLOOR PLAN SHOWS SHOWER,RISER SHOWS
 TUB. PLEASE CORRELATE. SECTION 106.1.1.
  
 51. SHT P-500 2 WAY CLEANOUT REQUIRED BETWEEN THE
 GREASE INTERCEPTORS. UTILITY STANDARD & SECTION
 708.3.2.
  
 52. SHT P-501 EAST END SANITARY RISER. EVERY VENT STACK
 SHALL CONNECT TO THE BASE OF THE DRAINAGE STACK PER
 SECTION 903.4.
  
 53. SHT P-501 SHOW ALL PIPE SIZES FOR THE GREASE
 SYSTEM. SECTIONS 701.1 AND TABLES 710.1(1) & 710.1(2).
  
 54. SHT P-501 THE VENT PIPING FROM TOILET ROOMS 112 &
 113 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 55. SHT P-501 RISERS SAN-5A, 4A, 3A & 2A DO NOT REFLECT
 THE FLOOR PLAN, NOR DO THEY MEET CODE REQUIREMENTS FOR
 VENTING FOR THE SECOND FLOOR FIXTURES. PLEASE
 CORRELATE. SECTIONS 106.1.1 & 901.2.1.
  
 56. SHT P-501 RISERS FOR ROOMS 104, 105, 106 & 107 DO
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 57. SHT P-501 CONNECTIONS TO RISERS SAN-2A & 1A DO NOT
 REFLECT THE FLOOR PLANS. PLEASE CORRELATE. SECTION
 106.1.1.
  
 58. SHT P-501 2 FLOOR DRAINS ARE SHOWN ON THE FLOOR
 PLAN AT THE COMPACTOR, BUT ONLY ONE IS SHOWN ON THE
 RISER DIAGRAM. PLEASE CLARIFY & PLEASE CORRELATE.
 SECTION 106.1.1. (PLEASE SEE COMMENT #6).
  
 59. SHT P-501 RISER SAN-1/2 3" BRANCH LINE TO LAUNDRY
 FLOOR DRAIN IS NOT SHOWN ON THE RISER. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 60. SHT P-501 PIPING IN THE MEZZANINE CEILING FOR
 RISERS SAN-3 & SAN-4 DO NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 61. SHTS P-500 & P-501 CLEANOUTS ARE REQUIRED AT THE
 BASE OF EACH STACK PER SECTION 708.3.4. PLEASE SHOW ON
 RISERS.
  
 62. SHT P-502 SHOW 2 RISERS DESIGNATED RISER "E" PLEASE
 CLARIFY. SECTION 106.1.1.
  
 63. SHT P-502 SECOND RISER "E"THE S-1 SINK SHALL
 DISCHARGE DOWNSTREAM OF THE WET-VENTED BATHROOM
 FIXTURES. SECTION 909.1.
  
 64. SHT P-503 FIVE HOSE BIBB LINES SHOWN ON THE FLOOR
 PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 65. SHT P-504 THREE HOSE BIBB LINES SHOWN ON THE FLOOR
 PLAN ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 66. SHT P-504 THE BRANCH LINE TO CW/18 DOES NOT REFLECT
 THE FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 67. SHT P-504 THE BASE OF RISER CW/14A CONNECTION TO
 THE WATER MAINS DOES NOT REFLECT THE FLOOR PLAN. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 68. SHT P-504 THE 1-1/4" HOT WATER BRANCH LINE DOES NOT
 REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 69. SHT P-505 2 HOSE BIBB LINES SHOWN ON THE FLOOR PLAN
 ARE NOT SHOWN ON THE RISER DIAGRAM. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 70. SHT P-507 RISER "H" DOES NOT REFLECT THE FLOOR PLAN
 PIPING FROM THE RISER AND TUBS ARE SHOWN ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 71. SHT P-600 CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17).
  
 72. SHT P-600 CONDENSATE INFORMATION NOTE STATES "SEE
 DWG P-103 FOR CONT". SHT P-103 WAS NOT SUBMITTED. SHT
 103A 2ND FLOOR WEST DOES NOT SHOW RISER. PLEASE
 INDICATE WHERE INFORMATION CONTINUES. SECTION 106.1.1.
  
 73. SHT P-600 RISERS STO/8 & STO/9 DO NOT REFLECT THE
 FLOOR PLAN AT THE TERMINATION. (SEE SHT P-101A). PLEASE
 CORRELATE. SECTION 106.1.1.
  
 74. SHT P-600 CLEANOUTS REQUIRED PER SECTION 1101.8.
 PLEASE SHOW ALL REQUIRED C/O'S ON PLANS.
  
 75. SHT P-600 PDD CONNECTION TO RISER ST/8-ST/9 DOES
 NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE. SECTION
 106.1.1.
  
 76. SHT P-600 RISERS ST/10 & STO/10 DO NOT REFLECT THE
 FLOOR PLAN AT THE OFFSET & LOCATION OF RISER STO/10.
 (SEE SHT P-102A). PLEASE CORRELATE. SECTION 106.1.1.
  
 77. SHT P-600 RISER ST/11 DOES NOT REFLECT THE FLOOR
 PLAN AT THE OFFSET IN THE MEZZ. LEVEL & OFFSETS FOR
 ST/11 - STO/11. (SEE P-404A). PLEASE CORRELATE. SECTION
 106.1.1.
  
 78. SHT P-600 THE BRANCH CONNECTION FOR RISER ST/12
 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 79. SHT P-600 THE LOCATION OF STO/12 DOES NOT REFLECT
 THE FLOOR PLAN.. PLEASE CORRELATE. SECTION 106.1.1.
  
 80. SHT P-600 RISER STO/13 STARTS OUT ON THE RIGHT SIDE
 OF ST/13 AT THE ROOF LEVEL BUT CROSSES TO THE LEFT SIDE
 AT THE MEZZ. LEVEL TO THE 1ST FLOOR. THE RISER DIAGRAM
 DOES NOT REFLECT THIS. PLEASE CLARIFY. PLEASE
 CORRELATE. SECTION 106.1.1.
  
 81. SHT P-600 RISER STO/13 ALSO DOES NOT REFLECT THE
 FLOOR PLAN. (SHT P-101A). PLEASE CORRELATE. SECTION
 106.1.1.
  
 82. SHT P-600 RISER STO/14 IS SHOWN TO THE SOUTH SIDE
 OF ST/14 ON THE FLOOR PLAN. RISER DOES NOT REFLECT THE
 FLOOR PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 83. SHT P-600 RISERS ST/14 & STO/14 DO NOT REFLECT THE
 FLOOR PLAN AS IT SHOWS THE RISERS THRU THE 5TH FLOOR
 AND TO THE UPPER ROOF. THE FLOOR PLAN SHOWS THE ROOF
 DRAINS AT THE 2ND LEVEL LOWER ROOF. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 84. SHT P-601 CONDENSATE SHALL DRAIN SEPARATELY FROM
 THE BUILDING. SECTION 314.2.1. (SEE COMMENT # 17).
  
 85. SHT P-601 CLEANOUTS REQUIRED PER SECTION 1101.8.
 PLEASE SHOW ALL REQUIRED C/O'S ON PLANS.
  
 86. SHT P-601 THE PIPING AT THE BASE OF RISERS ST/6 -
 ST/7 DOES NOT REFLECT THE FLOOR PLAN. PLEASE CORRELATE.
 SECTION 106.1.1.
  
 87. SHT P-601 CONDENSATE NOTE REFERS TO DWG P--103A,
 BUT NO RISER CONT. WAS FOUND. PLEASE INDICATE THE
 LOCATION OF THE RISER DIAGRAMS. SECTION 106.1.2.
  
 88. SHT P-601 THE PIPING OUT OF THE CATCH BASIN TO
 RISERS ST/1 & ST/2 DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE CORRELATE. SECTION 106.1.1.
  
 89. A SEPARATE IRRIGATION PERMIT AND PLANS ARE
 REQUIRED. THIS CAN BE SUBMITTED AFTER BUILDING PERMITS
 ARE ISSUED BUT PRIOR TO COMMENCMENT OF IRR. WORK.
 (INFORMATIONAL).
  
 90. A SEPARATE GAS PERMIT IS REQUIRED. THE FOLLOWING
 INFORMATION IS REQUIRED:
  
 A. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE.--RISER NOTED, BUT THE ISOMETRIC
 DRAWING DOES NOT REFLECT THE FLOOR PLAN AT THE WATER
 HEATERS AND AT THE DRYERS. ALSOTHE LENGTHS OF PIPE
 ARE NOT CLEAR AS INDICATED. PLEASE SHOW WHERE EACH
 SECTION OF PIPE BEGINS AND WHERE EACH SECTION OF PIPE
 ENDS.PLEASE CORRELATE. SECTION 106.1.1.
  
 B. SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED.--THE PIPE
 SIZES FOR THE RUNS INDICATED AS "A", "C" & "E" ARE
 INCORRECT SIZES. RUN "A" SHALL BE 4", RUN "C" SHALL BE
 2-1/2" AND RUN "E" SHALL BE 2-1/2" PER TABLE 402.4(6).
  
 C. TYPE OF GAS, (LP OR NATURAL).
  
 D. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 E. SUBMIT CALCULATIONS FOR COMBUSTION
 AIR (IF APPLICABLE) PER FBC-2004 FUEL
 GAS CODE SECTION 304.
  
 F. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.--SHT P-602
 INDICATES THE UTILITY COMPANY AS TECO GAS. THE GAS
 PROVIDER IN WEST PALM BEACH IS FLORIDA PUBLIC UTILITIES
 AND THEY PROVIDE THE GAS AT 1/2 PSI OR 2 PSI. PLEASE
 INDICATE THE PROPER PROVIDER AND INDICATE THE CORRECT
 DELIVERY PRESSURE.
  
 G. SUBMIT A DETAIL SHOWING THE TYPE,
 LOCATION, SIZE AND TERMINATION OF THE
 GAS VENTS PER FBC-2004 FUEL GAS CODE
 SECS. 502 THRU 505.
  
 H. SUBMIT MANUFACTURE SHEETS FOR ALL GAS
 EQUIPMENT TO VERIFY COMPLIANCE WITH
 STANDARDS NFPA 54, NFPA 58, AND THE
 FBC-2004 FUEL GAS CODE SEC 402.2.
  
 I. CLEARLY SHOW THE LOCATION AND CAP-
 ACITY OF LP TANK(S), TYPE OF TANK (DOT
 OR ASME), THE DISTANCE OF THE TANK FROM
 THE BUILDING AND ADJACENT PROPERTY LINES
 THE DISTANCE OF THE TANK FROM ALL SOUR-
 CES OF IGNITION, OTHER CONTAINERS, BUILD
 INGS, AND THE LOCATION OF ANY BUILDING
 OPENINGS BELOW THE RELIEF VALVE OF THE
 TANK PER NFPA 58, TABLE 3-2.2.2.
  
 J. CLEARLY INDICATE ON THE PLAN IF THE
 LP TANK IS ABOVE OR BELOW GROUND, AND
 SHOW REQUIRED PROTECTION OF THE TANK AND APPURTENANCES
 PER NFPA 58. IF THE TANK
 IS BELOW GROUND THE CONTAINER SHALL BE
 SECURILY ANCHORED PER NFPA 58 SECTION
 3-2.2.7(H).
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED. PLEASE RESUBMIT THE RED
 LINED PLUMBING SHEETS FROM THE FIRST REVIEW. THIS WILL
 HELP EXPEDITE THE PLUMBING/GAS PLAN REVIEW.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 6 Status N Date 2009-02-11 Cont ID  
Sent By mflis Date 2009-02-11 Time 14:53 Rev Time 0.00
Received By mflis Date 2009-02-11 Time 14:53 Sent To  
Notes
2009-02-11 14:54:29ZONING REVIEW: NOT REQUIRED
  
 ** REVISED M & P ONLY; PROJECT ELEVATIONS SHALL BE
 MODIFIED TO INDICATE NEW LOUVER LOCATIONS.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 5 Status P Date 2009-01-30 Cont ID  
Sent By mflis Date 2009-01-30 Time 17:14 Rev Time 0.00
Received By mflis Date 2009-01-30 Time 17:14 Sent To  
Notes
2009-01-30 17:15:42ZONING REVIEW: PASSED
  
 ** PLAN REVISIONS
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 4 Status P Date 2008-10-27 Cont ID  
Sent By mflis Date 2008-10-27 Time 09:13 Rev Time 0.00
Received By mflis Date 2008-10-27 Time 09:13 Sent To  
Notes
2008-10-27 09:18:00ZONING REVIEW: PASSED WITH PROVISO:
  
 1) ENGINEERING DEPT SHALL REVIEW AND CONFIRM NEW TRASH
 PICK-UP CONFIGURATION PROPOSAL.
  
 2) BIKE RACKS SHALL BE "U" MODEL, PER DISCUSSION WITH
 CONTRACTOR'S REP AND APPROVED BY ARCHITECT. (ONE RACK
 PER 40 VEHICULAR PARKING SPACES).
  
 3) CREEPING FIG ALONG NORTH ELEVATION AGAINST ADJACENT
 PARKING GARAGE MAY BE ELIMINATED, AS THERE WILL NOT BE
 ENOUGH ROOM BETWEEN TWO BUILDINGS.
  
 4) GATE AND WALL AT EAST END OF PROPERTY DOES NOT
 APPEAR TO TURN BACK AND ENCLOSE PROPERTY. CONFIRM IT
 WILL BE EXTEND NORTH TO SECURE AREA.
  
 5) PLEASE COORDINATE TREE RELOCATION/REPLACEMENT WITH
 ROBERT KUSSNER, LANDSCAPE PLANNER, AT 822-1435; WILL BE
 REQUIRED PRIOR TO C/O.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 3 Status F Date 2008-09-23 Cont ID  
Sent By mflis Date 2008-09-23 Time 10:32 Rev Time 0.00
Received By mflis Date 2008-09-23 Time 10:32 Sent To  
Notes
2008-09-23 10:33:39ZONING REVIEW: FAILED
  
 ** BIKE RACK MODEL AND PLACEMENT ONLY
  
 1) PLEASE INDICATE HOW PROPOSED RACK MEETS REQUIREMENT
 (1 BIKE PARKING SPACE PER 20 CAR PARKING SPACES).
  
 2) CITY-RECOMMENDED BIKE RACK MODELS ARE "INVERTED 'U'"
 OR "HITCHING POST" TYPES. COPIES ATTACHED.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 2 Status P Date 2008-04-29 Cont ID  
Sent By mflis Date 2008-04-29 Time 10:20 Rev Time 0.00
Received By mflis Date 2008-04-29 Time 10:20 Sent To  
Notes
2008-04-29 10:22:15ZONING REVIEW: PASSED WITH PROVISO
  
 1) UPON RESUBMITTAL OR REVISION, PLEASE AMEND AC 101
 AND A 100A SUCH THAT THE CURB CUT AT LAKEVIEW DRIVE
 MATCHES THE DIRECTIONAL DRIVEWAY INDICATED BY THE CIVIL
 DRAWINGS. THEY DO NOT MATCH.
  
 2) PLEASE PROVIDE FURTHER DETAIL ON THE
 CANOPIES/AWNINGS PROPOSED FOR THE BUILDING ELEVATIONS.
 THEY ARE NOT INCLUDED IN THIS PACKAGE.
  
 3) NO GENERAL PLANTING DETAILS ARE INCLUDED. PLEASE ADD
 TO REVISED DRAWINGS.
  
 MATT FLIS - 822-1445

Review Stop Z ZONING
Rev No 1 Status P Date 2008-01-16 Cont ID  
Sent By mflis Date 2008-01-16 Time 15:09 Rev Time 0.00
Received By mflis Date 2008-01-16 Time 15:09 Sent To  
Notes
2008-01-16 15:24:54ZONING REVIEW: PASSED WITH PROVISO:
  
 UPON RESUBMITTAL OR REVISION, PLEASE ADDRESS THE
 FOLLOWING:
  
 1) ON ENGINEERING SHEET #4, PLEASE CHANGE ZONING
 DESIGNATION TO READ "BUILDING TYPE III" INSTEAD OF
 CC3.
 2) ON ENGINEERING SHEET #4, STANDARD AND VALET PARKING
 SPACES SHOULD BE INDICATED AS 8'-6" WIDE INSTEAD OF
 9'-0" WIDE.
 3) PLEASE PROVIDE INFORMATION ON SCREENING OF ROOF-TOP
 UNITS, PER SITE PLAN APPROVAL. EQUIPMENT SHOULD NOT BE
 VISIBLE FROM THE STREET.
 4) PLEASE PROVIDE INFORMATION ON FLOOD LIGHTS (RE
 FIXTURE ON E-505) FOR TOP LEVEL OF PARKING TO CONFIRM
 FIXTURE TYPE WILL NOT BE CASTING SIGNIFICANT LIGHT OR
 GLARE TO ADJACENT PROPERTIES.
 5) PLEASE INDICATE FOOTCANDLES LEVELS WITHIN PARKING
 GARAGE AND TOP PARKING LEVEL.
 6) PLEASE CONFIRM DETAIL FOR "SCORE LINES" AND THAT
 SCALE OF REVEAL IS SUFFICIENT TO BE VISIBLE AS A
 ARCHITECTURAL ELEMENT IN THE BUILDING FACADE.
 7) BUILDING SECTIONS DO NOT PROVIDE ANY DETAIL AS TO
 CONSTRUCTION OF CANOPY ELEMENTS. PLEASE ADD DETAILS,
 INCLUDING MATERIALS FOR THESE ELEMENTS.
  
  
 OTHER COMMENTS:
  
 * PROJECT IS SUBJECT TO APPROVALS AND CONDITIONS AS
 PROVIDED IN THE SITE PLAN APPROVAL AND DAC APPROVAL.
  
 MATT FLIS - 822-1445