Plan Review Details - Permit 08010243
| Plan Review Stops For Permit 08010243 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-02-11 |
Time |
10:01 |
Rev Time |
1.00 |
| Received By |
jleahy |
Date |
2008-02-11 |
Time |
10:00 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-17 |
Time |
15:19 |
Rev Time |
1.30 |
| Received By |
adarroug |
Date |
2008-01-17 |
Time |
16:32 |
Sent To |
|
|
| Notes |
| 2008-01-17 16:51:58 | 1. NO OUTLETS SHOWN OUTSIDEFRONT AND BACK.210.52,E | | | 2. NO COMPRESSORS SHOWN | | | 3. NEED PANEL SCHEDULES FOR ALL PANELS.408.4 | | | 4. GARAGE PANEL NEEDS MAIN AS SHOWN AND GROUND RODS. | | | 225.31, 250.32 | | | 5. CHECK ALL OUTLET SPACING FOR THE 6 AND 12 RULE. | | | 210.52 A1 | | | 6. OTHER BEDROOMS REQUIRE ARCFAULT BREAKERS INCLUDING | | | THE SAS. 210.12 | | | 7. WIRES FROM METER TO THE TWO MAINS NOT SHOWN215.5 | | | 8. DOES GARAGE HAVE GFCI PROTECTION FOR OUTLETS?210.8 | | | A2. |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-02-01 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-01 |
Time |
15:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-01 |
Time |
15:20 |
Sent To |
E |
|
| Notes |
| 2008-02-01 15:20:29 | TO "JLEAHY" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
F |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
jleahy |
Date |
2008-01-17 |
Time |
16:53 |
Rev Time |
1.30 |
| Received By |
jleahy |
Date |
2008-01-10 |
Time |
16:34 |
Sent To |
|
|
| Notes |
| 2008-01-10 16:34:28 | SENT TO ELECTRICAL INBOX MMILLER |
|
|
|