Plan Review Details - Permit 08010243
Plan Review Stops For Permit 08010243
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By jleahy Date 2008-02-11 Time 10:01 Rev Time 1.00
Received By jleahy Date 2008-02-11 Time 10:00 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status N Date 2008-01-17 Cont ID  
Sent By adarroug Date 2008-01-17 Time 15:19 Rev Time 1.30
Received By adarroug Date 2008-01-17 Time 16:32 Sent To  
Notes
2008-01-17 16:51:581. NO OUTLETS SHOWN OUTSIDEFRONT AND BACK.210.52,E
 2. NO COMPRESSORS SHOWN
 3. NEED PANEL SCHEDULES FOR ALL PANELS.408.4
 4. GARAGE PANEL NEEDS MAIN AS SHOWN AND GROUND RODS.
 225.31, 250.32
 5. CHECK ALL OUTLET SPACING FOR THE 6 AND 12 RULE.
 210.52 A1
 6. OTHER BEDROOMS REQUIRE ARCFAULT BREAKERS INCLUDING
 THE SAS. 210.12
 7. WIRES FROM METER TO THE TWO MAINS NOT SHOWN215.5
 8. DOES GARAGE HAVE GFCI PROTECTION FOR OUTLETS?210.8
 A2.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 15:20 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 15:20 Sent To E
Notes
2008-02-01 15:20:29TO "JLEAHY" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status F Date 2008-01-17 Cont ID  
Sent By jleahy Date 2008-01-17 Time 16:53 Rev Time 1.30
Received By jleahy Date 2008-01-10 Time 16:34 Sent To  
Notes
2008-01-10 16:34:28SENT TO ELECTRICAL INBOX MMILLER