Plan Review Details - Permit 08010237
Plan Review Stops For Permit 08010237
Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2010-10-13 Cont ID  
Sent By lmartine Date 2010-10-13 Time 12:35 Rev Time 0.00
Received By lmartine Date 2010-10-13 Time 12:35 Sent To  
Notes
2010-10-13 12:35:59APPROVED ROOF SUBMITTAL

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2009-10-29 Cont ID  
Sent By lmartine Date 2009-10-29 Time 14:37 Rev Time 0.00
Received By lmartine Date 2009-10-29 Time 14:37 Sent To  
Notes
2009-10-29 14:38:44REVISION FOR STRUCTURAL CORRECTIONS NOTED BY FIELD
 INSPECTOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status P Date 2009-03-05 Cont ID  
Sent By lmartine Date 2009-03-05 Time 08:11 Rev Time 0.00
Received By lmartine Date 2009-03-05 Time 08:11 Sent To  
Notes
2009-03-05 08:14:18REVISION, OK, CHANGE FLOOR SYSTEM FROM WOOD TO CONCRETE
 AND MOVE BUILDING FOOTPRINT EAST A FEW FEET.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2009-02-09 Cont ID  
Sent By lmartine Date 2009-02-09 Time 15:06 Rev Time 0.00
Received By lmartine Date 2009-02-09 Time 15:06 Sent To  
Notes
2009-02-09 15:07:13REVISION FOR NEW STEEL GLAZED DOOR

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-18 Cont ID  
Sent By amorse Date 2008-08-18 Time 16:28 Rev Time 0.00
Received By amorse Date 2008-08-18 Time 16:28 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-07-19 Cont ID  
Sent By amorse Date 2008-07-19 Time 10:42 Rev Time 0.00
Received By amorse Date 2008-07-19 Time 10:42 Sent To PC
Notes
2008-07-19 10:45:26 
  
 DENIED
  
 OUTSTANDING COMMENTS FROM 1ST AND 2ND REVIEWS
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SETS OF PLANS MUST BE STAMPED BY THAT OFFICE,
 AND A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION.
  
 3)PER LIMITATION #7 OF THE MODIFIED BITUMEN ROOFING
 PRODUCT APPROVAL CALCULATIONS FOR ENHANCED FASTENING IS
 REQUIRED FOR THE PERIMETER AND CORNER ZONES TO BE
 PREPARED, SIGNED AND SEALED BY A REGISTERED ENGINEER,
 ARCHITECT OR ROOFING CONSULTANT.
  
 ****** THE FASTENER DENSITIES AND MAX DESIGN PRESSURE
 FROM THE PRODUCT NOA WERE NOT INSERTED IN THE FORMULA'S
 FROM RAS 117 THEREFORE THE CALCULATED O/C FASTENER
 PATTERN IS INCORRECT.PLEASE SEE ATTACHED CALC'S AND
 CHOSEN SYSTEM FROM NOA*******
  
 6)NO PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS
 BETWEEN FRENCH DOORS/ SIDE LITESAND FRENCH DOORS /
 TRANSOMS
  
 *******THIS PRODUCT IS LIMITED TO ONLY THE WINDOWS
 LISTED ON SHEET 4 OF THE PRODUCT APPROVAL . PLEASE NOTE
 THAT THE CONFIGURATION OF THESE FRENCH DOOR,SIDELITES
 AND TRANSOM ARE GOING TO MAKE IT VERY HARD TO PROVIDE
 AN OF THE SHELF MULLION THAT WILL WORK. PGT HAS A 2X6
 MULLION AND EVEN THAT WOULD ONLY WORK WITH
 EXTRAPOLATION, UNITS MAY REQUIRE A STRUCTURAL MEMBER
 BETWEEN THE 2 FRENCH DOORS IN ORDER TO GET WORKABLE
 MULLION LENGTHS FOR TRANSOM AND SIDELITES******
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-06-03 Cont ID  
Sent By amorse Date 2008-06-03 Time 15:54 Rev Time 0.00
Received By amorse Date 2008-06-03 Time 15:54 Sent To  
Notes
2008-06-03 16:12:35 
  
 DENIED
  
 THE FOLLOWING COMMENTS WERE NOT ADDRESSED FROM 1ST
 REVIEW:
  
 10)NO PRODUCT APPROVALS WERE SUBMITTED FOR CONNECTORS
 AND STRAPS. IN LUE OF PRODUCT APPROVALS
 STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE ON THE
 DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT APPROVAL
 NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE FLORIDA INDEX
 WITH CONNECTORS TO BE USED HIGHLIGHTED.
  
 16)ADDITIONS ARE TREATED AS NEW CONSTRUCTION, PROVIDE
 AT MINIMUM 1 ACCESSIBLE BATHROOM PER R322.1.1 FBC 29"
 CLEAR WITH DOOR OPEN 90 DEGREES.
 **********DOOR NOT SHOWN AS 32" PER ARCHITECTS RESPONSE
 LETTER*********
  
 18)PROVIDE DETAIL OF FOUNDATION AND COLUMN TIE INS
 INTO EXISTING FOUNDATIONS AND WALLS *********SUPPORT IS
 OK, COMMENT REFERS TO CONNECTION OF NEW ADDITION TO
 EXISTING BUILDING, IS 8" X 12" COLUMN OR NEW FOUNDATION
 AT SITTING AREA FREE STANDING OR ARE THEY DOWELED INTO
 EXISTING WALL? IS THERE AN EXPANSION JOINT AT THESE
 LOCATIONS? DOES ROOF TIE IN WITH CRICKET TO EXISTING
 SHED ROOF ?
  
 NEW COMMENTS
  
 1)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SETS OF PLANS MUST BE STAMPED BY THAT
 OFFICE AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561) 233-5025 FOR MORE
 INFORMATION
  
 2)ENERGY CALC'S FOR GUEST HOUSE WERE NOT SIGNED BUY
 OWNER/AGENT
  
 3)PER LIMITATION #7 OF THE MODIFIED BITUMEN ROOFING
 PRODUCT APPROVAL CALCULATIONS FOR ENHANCED FASTENING IS
 REQUIRED FOR THE PERIMETER AND CORNER ZONES TO BE
 PREPARED, SIGNED AND SEALED BY A REGISTERED ENGINEER,
 ARCHITECT OR ROOFING CONSULTANT.
  
 4)CLARIFY WERE THE SINGLE PLY ROOFING SYSTEM WILL BE
 USED
  
 5)PROVIDE PRODUCT THAT WILL BE USED FOR RIDGE VENTING
 OF ACFOAM CROSSVENT PRODUCT AND STAND 'N' SEAM ALUMINUM
 ROOFING
  
 6)NO PRODUCT APPROVALS WERE SUBMITTED FOR MULLIONS
 BETWEEN FRENCH DOORS/ SIDE LITESAND FRENCH DOORS /
 TRANSOMS
  
 NOTE FEES HAVE BEEN ADJUSTED FOR BOTTOM OF ACCESSORY
 STRUCTURE PER APPROVAL OF ROBERT BROWN 100 SQ FT AS
 UTILITY (ELEVATOR AND ELEVATOR MACHINE ROOM) THE
 REMAINDER DISCOUNTED $10.33 PER SQ FT FROM UTILITY
 RATE. THE NEW FEE TOTAL FOR STRUCTURES AND RADON FEES
 IS $595.98
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-18 Cont ID  
Sent By amorse Date 2008-01-18 Time 16:18 Rev Time 0.00
Received By amorse Date 2008-01-18 Time 16:18 Sent To PC
Notes
2008-01-18 16:28:28 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $719.09FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 4)PROVIDE 2 COPIES OF ORIGINAL SIGNED AND SEALED SOIL
 REPORT PHOTO COPIED, STAMPED OR REPRODUCED SIGNATURES
 ARE NOT ACCEPTABLE PER 471.025 F.S.
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDINGS/ADDITION WITH ALL SIDE AND REAR
 SETBACKS. AREA IS IN AN "A" FLOOD ZONE, PLEASE BE SURE
 TO HAVE ELEVATIONS OF GRADE/FINISHED FLOOR FOR PROPOSED
 BUILDINGS SHOWN ON SURVEY
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG
  
 8)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 9)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED.
 *****PLEASE NOTE THAT FLORIDA PRODUCT APPROVAL NUMBERS
 HAVE BEEN WRITTEN AT TOP OF NOA'S********
  
 10)NO PRODUCT APPROVALS WERE SUBMITTED FOR BUILT UP
 ROOFING, LINTELS, AND CONNECTORS AND STRAPS. IN LUE OF
 PRODUCT APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A
 SCHEDULE ON THE DRAWINGS COMPLETE WITH THE STATEWIDE
 PRODUCT APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S
 COMPLETE FLORIDA INDEX WITH CONNECTORS TO BE USED
 HIGHLIGHTED
  
 11)IN THE PRODUCT APPROVALS FOR CLAD WOOD FRENCH
 DOORS THE FIRST PAGE OF THE DRAWINGS IS CUT OFF AND
 INFORMATION REQUIRED FOR INSPECTION IS MISSING, PLEASE
 REPRINT THIS PAGE AND INSERT INTO APPROVAL
  
 12)CLARIFY ROOF SYSTEM THAT IS TO BE USED TRUSSES
 WITH PLYWOOD SHEATHING AS SHOWN ON DETAIL H/6 ON SHEET
 A6 OR 6X8 CYPRESS RAFTERS WITH T&G CYPRESS DECKING AS
 SHOWN ON DETAIL C/2 OF SHEET A2 AND THE ROOF FRAMING
 PLAN ON A4
  
 13)PLEASE NOTE THAT IF SYSTEM IN DETAIL C/2 IS USED
 THE PRODUCT APPROVAL FOR THE STAND N SEAM METAL ROOF IS
 NOT APPROVED TO INSTALL OVER AN INSULATED DECK (SEE
 PAGE 3 OF NOA)
  
 14)CLARIFY DECK OVER MASTER BATHROOM AND CLOSET AREA,
 A/2 ON SHEET A2 AGAIN SHOWS 6X8 CYPRESS WITH CYPRESS
 T&G DECKING WHILE H/6 ON A6 HAS 2X8 JOISTS AND T&G
 PLYWOOD FOR DECKING AND KNEE WALL
  
 15)SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS FOR
 ROOF AND FLOOR TRUSSES THAT COMPLY WITH R802.10.1 FBC
 WITH PERMIT APPLICATION OR BEFORE INSTALLATION THAT
 HAVE BEEN REVIEWED AND APPROVED BY THE DESIGNER OF
 RECORD
  
 16)ADDITIONS ARE TREATED AS NEW CONSTRUCTION, PROVIDE
 AT MINIMUM 1 ACCESSIBLE BATHROOM PER R322.1.1 FBC 29"
 CLEAR WITH DOOR OPEN 90 DEGREES
  
 17)PROVIDE INFORMATION ON DOOR AND WINDOW LINTEL AND
 SILLS, ARE MAIN BEAMS POURED DOWN OR ARE PRECAST
 LINTELS BEING USED. IF PRECASTPROVIDE SCHEDULE FOR
 PRECAST LINTEL THAT WILL BE USED AND OPENING SIZES TO
 COMPLY WITH 2104.1.5 FBC FOR MIN BEARING ON DRAWING. IF
 POUR DOWN IS USED PROVIDE DETAIL
  
 18)PROVIDE DETAIL OF FOUNDATION AND COLUMN TIE INS
 INTO EXISTING FOUNDATIONS AND WALLS
  
 19)PROVIDE UNDER FLOOR VENTILATION AND ACCESS PER
 R402.2 AND R403.2 FBC RES.
  
 20)SHEETS FOR THE ADDITION AND THE APARTMENT HAVE THE
 SAME PAGE DESIGNATIONS PLEASE CORRECT
  
 21)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-18 Cont ID  
Sent By dpalmer Date 2008-07-18 Time 08:57 Rev Time 0.00
Received By dpalmer Date 2008-07-18 Time 08:57 Sent To M
Notes
2008-07-18 08:58:53REDLINED PLANS
  
 NO EQUIPMENT GROUNDING BEFORE FIRST MEANS OF DISCONNECT
 250.6, 250.24.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-22 Cont ID  
Sent By dpalmer Date 2008-05-22 Time 16:37 Rev Time 0.00
Received By dpalmer Date 2008-05-22 Time 16:37 Sent To  
Notes
2008-05-22 16:37:46** DENIED2ND REVIEW**
  
  
 *** PLEASE SEE NEW COMMENTS AS SEVERAL ITEMS WERE
 CHANGED FROM PREVIOUS REVIEWED PLANS
  
  
 1) NOTE: PLEASE SEE THE PLANS HAVE BEEN REVISED WITH
 ALL CIRCUITING TO PANEL *C* YET PANEL *C* SCHEDULE DOES
 NOT CONTAIN ANY OF THESE CIRCUITS ON THE MAIN HOUSE. IT
 WAS THOUGHT THAT PERHAPS THE PANEL DESIGNATION WAS THE
 ONLY ITEM AND PERHAPS A MISPRINT HOWEVER THE CIRCUIT
 NUMBERS DO NOT CORRELATE WITH EITHER PANEL.
 PLEASE REVISE AND COORDINATE.
 PLEASE SEE THIS IS THE SAME FOR THE NEW DETACHED
 APT/UNIT BUILDING. ALL CIRCUITS IN THIS BUILDING ALSO
 SHOW GOING TO PANEL *C* YET THIS BUILDING IS FED FROM A
 PANEL *E*.
 PLEASE COORDINATE ALLAND REVISE.
 408.4, 240.4, 310.16
 FBC 106.1.2, 106.3.5.4
  
 2) NOTE: PLEASE INDICATE ON RISER THE NEW METER BANK AS
 400AMP. ONLY NOTES EACH METER AS 200 AMP AND RISER AS
 400AMP.
 230.70
  
 3) NOTE: PLEASE SEE THE RISER AS THE MAINS ARE NOT
 GROUPED. IN FACT PLEASE SEE THE NEW 200AMP DISCONNECT
 PANEL IS LABELED AS BEING LOCATED AT THE ACCESSORY
 BUILDING. HOW IS THIS POSSIBLE WHEN THE NEW ACCESSORY
 BUILDING CONTAINS NEW PANEL AND MAIN *E*.
 PLEASE PROVIDE A LAYOUT SHOWING THE LOCATIONS OF THESE
 PANELS. PLEASE BE SURE ALL MAINS ARE GROUPED AS
 REQUIRED PER 230.72.
 110.26
 FBC 106.3.5.4
  
 4) NOTE: PLEASE SEE SHEET B-4 WHICH NOW SHOWS A NEW
 OUTLET FOR A PORTABLE GENERATOR. WILL THIS GENERATOR BE
 CONNECTED TO THIS OR ANY OTHER BUILDING IN ANYWAY?
 IS THIS GOING TO ONLY BE FOR EXTENSION CORDS AND *NOT*
 FOR USE BEING CONNECTED INTO ANY ELECTRICAL PANELS?
 IF THIS IS GOING TO BE CONNECTED TO ANY ELECTRICAL
 EQUIPMENT PLEASE INCLUDE ON RISER, PLEASE INDICATE THE
 FAIL-SAFE INADVERTENT CONNECTION OF NORMAL AND
 EMERGENCY POWER.
 IF UNIT WILL BE CONNECTED TO ANY ELECTRICAL EQUIPMENT
 IT MUST BE INSTALLED SO THAT POWER MAY NOT BE FED TO
 ANY APPLIANCE OR ELECTRICAL EQUIPMENT WITH THE
 POSSIBILITY OF BEING FED FROM TWO SOURCES.
 PLEASE SEE NEC 702.6 AND PLEASE SEE FPL MINIMUM
 SERVICES GUIDELINES WHICH CAN BE FOUND ON THE FPL
 WEBSITE.
  
 5) NOTE: PLEASE COORDINATE PLANS. PLEASE SEE B4 AND A5.
 PANEL *E* IS SHOWN AS 150AMP PANEL HOWEVER PLEASE SEE
 ACTUAL ELECTRICAL PLANS ON B4 WHICH STILL SHOWS THIS
 SAME PANEL *E* AS 200AMP.
 IF THIS IS GOING TO BE 200AMP, PLEASE REVISE
 CONDUCTORS, BREAKERS ETC. IF THIS IS GOING TO REMAIN
 150AMP, PLEASE REVISE ELECTRICAL PLANS.
 FBC 106.1.2, 106.3.5.4.
 240.4, 310.16, 225.39 ETC
  
 6) NOTE: PLEASE SEE CITY OF WEST PALM BEACH FINANCE
 DEPARTMENT HOLD WHICH IS ON ADDRESS. THIS REQUIRES AS
 SIGN OFF FROM FINANCE DEPT BEFORE PLANS MAY BE
 RE-SUBMITTED. WE HAVE ATTACHED A COPY OF THIS HOLD ONTO
 THE NOTES.
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-15 Cont ID  
Sent By dpalmer Date 2008-01-15 Time 19:37 Rev Time 0.00
Received By dpalmer Date 2008-01-15 Time 19:37 Sent To M
Notes
2008-01-15 19:38:08** DENIED REVIEW **
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE PRESENT ON PLANS AS REQUIRED.
 2002 NFPA-72
 2005 NFPA-70
  
 2) NOTE: PLEASE KNOW AT THIS TIME ONE PERMIT IS BEING
 APPLIED FOR THE SCOPE OF WORK OF THE ADDITION ON THE
 EXISTING HOUSE AND THE NEW APARTMENT ALSO TO BE
 CONSTRUCTED. PLEASE KNOW THIS IS OK, HOWEVER PLEASE
 ALSO KNOW AS ONE PERMIT THIS MAY CREATE ANY ISSUES WITH
 THE CERTIFICATE OF OCCUPANCY AND FINAL ON EACH OF THE
 STRUCTURES AND SCOPE OF WORK. THIS IS ONLY NOTED.
  
 3) NOTE: PLEASE SEE THERE ARE MULTIPLE PAGE
 DESIGNATIONS WITH REPEAT PAGE NUMBERS. PLEASE SEE THIS
 IS CONFUSING FOR RECORDS RETENTION, PUBLIC RECORDS AND
 RECORDED DOCUMENTS. EXAMPLE: TWO PAGE A-04 AND THE
 SCOPE OF WORK ON EACH OF THESE PAGES ARE COMPLETELY
 DIFFERENT.
 PLEASE ADJUST DESIGNATIONS FOR CLARITY.
 FBC 106.1.2, 106.5.
  
 4) NOTE: PLEASE KNOW AT THIS TIME THE SERVICES AND
 LOCATIONS AS SHOWN ARE NOT PERMITTED. PLEASE KNOW AS
 THE EXISTING GARAGE IS FED FROM A SEPARATE SERVICE, MAY
 NOT CONTAIN THE NEW ELECTRICAL SERVICE FOR APARTMENT
 BUILDING ON THIS STRUCTURE.
 PLEASE KNOW BASED ON ZONING AND USES PERMITTED. THIS IS
 AN ACCESSORY STRUCTURE WHICH MAY OR MAY NOT REQUIRE
 ONLY ONE METER FOR THE ENTIRE PROPERTY DUE TO THE
 ZONING OF SF (SINGLE FAMILY).
 PLEASE KNOW THE SERVICES AS SHOWN NEED TO BE COMPLETED
 AND SHOWN ON PLANS.
 FOR EXAMPLE THE SERVICE ON THE EXISTING HOUSE IS NOT
 SHOWN. ONLY SHOWS AN EXISTING PANEL YET THE RISER SHOWS
 ALL NEW SERVICE EQUIPMENT?
 THESE WILL BE REVISED SUBSTANTIALLY ALONG WITH THE
 COMMENTS BELOW WHICH ALSO NEED TO BE ADDRESSED.
 225.31-225.39, 230.70, 230.71, 230.72 TEC
 FBC 106.3.5.4, 106.1.2
  
 5) NOTE: PLEASE SUBMIT MISSING AIC RATINGS FOR ALL NEW
 SERVICE EQUIPMENT.
 NEC 110.9
 FBC 106.1.2, 106.3.5.4
  
 6) NOTE: PLEASE SEE MISSING GROUNDING ELECTRODE SYSTEMS
 AT DETACHED STRUCTURES PER 250.32, 250.50
  
 7) NOTE: PLEASE SEE 250.110, 250.24, 250.6, 250.122 FOR
 MISSING EQUIPMENT GROUNDING CONDUCTORS AFTER FIRST
 MEANS OF DISCONNECT.
  
 8) NOTE: PLEASE SEE 220.83B FOR LOADS BEING ADDED TO
 EXISTING SERVICES.
 PLEASE KNOW AS THE SERVICE AS SHOWN WILL MOST LIKELY
 CHANGE SUBSTANTIALLY THE LOAD CALCULATIONS AS QUOTED
 FOR CODE COMPLIANCE CAN NOT BE DETERMINED AT THIS
 TIME.
  
 9) NOTE: PLEASE SEE NFPA-72 DEFINITIONS FOR SMOKE
 DETECTION DEVICES. THESE ARE SHOWN AS SD AND NOTED FOR
 SMOKE DETECTORS ON PLANS. IF USING SD DESIGNATIONS THIS
 WOULD MEAN THIS DWELLING WOULD CONTAIN A FIRE ALARM
 PANEL AND SYSTEM.
 IS THE DESIGNATION NOT SA FOR SMOKE ALARMS?
 PLEASE ALSO SHOW THE LOCATIONS FOR ALL NEW SMOKE ALARMS
 PER R313 WHERE APPLICABLE.
 PLEASE SEE R313, NFPA-72 11.5.1.1.1
  
 10) NOTE: PLEASE SEE MISSING REQUIRED DEDICATED BATH
 CIRCUIT(S) AT NEW APARTMENT.
 210.11C3. SHALL BE #12 AND 20AMP(SHOWN AT MAIN
 HOUSE).
  
 11) NOTE: PLEASE SEE 210.52 FOR RECEPTACLE SPACING
 ALONG WALLS.
 MISSING SOME, 2FT OF WALL IN BEDROOM.)
  
 12) NOTE: PLEASE SEE MISSING GFI RECEPTACLE FOR OUTSIDE
 CU AT MAIN HOUSE REQUIRED PER210.63, 210.8A3.
  
 13) NOTE: PLEASE SEE MISSING CONTROLS FOR STAIRS
 REQUIRED PER 210.70, LS 101 7.8
 PLEASE SEE THE CONTROLS FOR POSSIBLE 3-WAY CONTROLS.
  
 14) NOTE: PLEASE SEE MISSING DINING ROOM CIRCUITS OR
 AREAS OF THE LIKE PER 210.52B1, 210.11C1, 220.53.
 (1500VA MIN PER EACH)
  
 15) NOTE: PLEASE LIST THE ARC FAULT PROTECTED CIRCUITS
 ON PANEL SCHEDULES TO BE PROVIDED.
 PLEASE SEE 210.12
  
 16) NOTE: PLEASE SUBMIT ACCURATE PANEL SCHEDULES PER
 408.4, 240.4, 310.16.
 SHOWING BRANCH CIRCUITS, SIZES OF BREAKER, CONDUCTORS
 ETC.
 EXAMPLE: CIRCUIT 3, BTH RM, CIRCUITS 2/4 COND UNIT
 ETC.
 FBC 106.3.5.4, 106.1.2.
  
  
 ** PLEASE KNOW AS MANY CHANGES MAY OCCUR ALL COMMENTS
 CAN NOT POSSIBLY BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop G GAS REVIEW
Rev No 3 Status N Date 2008-07-18 Cont ID  
Sent By mperson Date 2008-07-18 Time 16:32 Rev Time 0.00
Received By mperson Date 2008-07-18 Time 16:32 Sent To B
Notes
2008-07-18 16:35:40NOTE: SHEET B5, PER ARCHITECT, ALL GAS PIPING DELETED
 FROM THIS PERMIT SET AND WILL BE RESUBMITTED AT A LATER
 DATE. **MRPERSON.

Review Stop G GAS REVIEW
Rev No 2 Status F Date 2008-05-23 Cont ID  
Sent By mperson Date 2008-05-23 Time 14:18 Rev Time 0.00
Received By mperson Date 2008-05-23 Time 14:18 Sent To B
Notes
2008-05-23 14:23:53GAS PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS GAS REVIEW COMMENTS AS WELL AS THE
 DESIGNER'S RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW
 COMMENTS WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
  
 1. "OK" COMMENT ADDRESSED.
  
 2. "OK" COMMENT ADDRESSED.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 **RESPONSE NOTED, HOWEVER PER OUR MEETING ON 4/10/08
 IT WAS STATED THAT THERE WERE EXISTING GAS APPLIANCES
 AND GAS PIPING IN THE EXISTING MAIN RESIDENCE AND THAT
 THE EXISTING LONGEST LENGTH AND BTU LOAD WOULD BE
 INDICATED ON THE RESUBMITTED GAS RISER FOR THE EXISTING
 MAIN RESIDENCE. THAT INFORMATION IS NOT ON THE
 RESUBMITTED GAS RISER AND IS REQUIRED DUE TO THE FACT
 THAT GAS SYSTEMS ARE SIZED BY THE LONGEST LENGTH AND
 BTU LOADS. PER FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 4. "OK" COMMENT ADDRESSED.
  
 5. "OK" COMMENT ADDRESSED.
  
 6. "OK" COMMENT ADDRESSED.
  
 **THE FOLLOWING ARE NEW COMMENTS**
  
 7. SHEET B5 GAS RISER: PER THE RESUBMITTED INFORMATION
 THAT THE DELIVERY PRESSURE IS 0.5 PSI AND THE LONGEST
 LENGTH IS 129' THE GAS PIPING IS UNDER SIZED PER
 FBC-2004 FUEL GAS TABLE 402.4(2). REFERENCE THE RED
 LINE CORRECTIONS TO THE RISER DIAGRAM AS WELL AS THE
 ATTACHED TABLE TO THESE COMMENTS INDICATING THIS.
 NOTE: UNTIL COMMENT #3 IS FULLY ADDRESSED THIS IS ONLY
 A REVIEW OF WHAT INFORMATION IS ON THE RESUBMITTED GAS
 RISER AND COULD CHANGE IF THE EXISTING GAS SYSTEM HAS A
 LONGER LENGTH OF 129'.
  
 8. SHEET B5 GAS RISER: IF THE DELIVERY PRESSURE IS
 ONLY 0.5 PSI WHY IS A MAIN REGULATOR BEING INDICATED
 FOR THE ACCESSORY BUILDING? THIS REGULATOR IS NOT
 REQUIRED FOR 0.5 PSI SYSTEMS. PLEASE CLARIFY THIS PER
 FBC-2004 FUEL GAS SECTION 401.1 SCOPE.
  
 9. SHEET B5 GAS RISER: PLEASE KNOW THAT THE FITTING
 FOR THE WTR/HTR AND GENERATOR DOES NOT EXIST AND SHOULD
 BE CLEARLY INDICATED AS TWO SEPERATE TEES ON THE
 RESUBMITTAL. PER FBC-2004 FUEL GAS SECTION 401.1
 SCOPE.
  
 10. SEE MECHANICAL COMMENTS #3 AND #4 AND COMPLY.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE PROVIDE A COPY OF THE
 OLD PLANS, CLEARLY INDICATE THE REVISION ON THE NEW
 PLANS, REMOVE AND REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2008-01-16 Cont ID  
Sent By mperson Date 2008-01-16 Time 15:40 Rev Time 0.00
Received By mperson Date 2008-01-16 Time 15:39 Sent To M
Notes
2008-01-16 16:01:39PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 SHEET A5 NEW ACCESSORY BUILDING: THE FOLLOWING
 CORRECTIONS/INFORMATION ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE.
  
 1. SUBMIT AN ISOMETRIC DRAWING THAT
 CLEARLY SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. **NOT ALL CUT SECTIONS OF PIPE ARE
 INDICATING CORRESPONDING LENGTHS. PER FBC FUEL GAS
 SECTION 401.1, SCOPE.
  
 2. TYPE OF GAS, (LP OR NATURAL) **RISER IS NOT CLEARLY
 INDICATING THE GAS TYPE. PER FBC FUEL GAS SECTION
 *401.1, SCOPE.
  
 3. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 4. INDICATE THE DELIVERY PRESSURE (PSI)
 PER FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI.
  
 5. ADD THE WATER HEATER TO THE APPLIANCES REQUIRED TO
 HAVE A SEDIMENT TRAP. PER FBC FUEL GAS SECTION *408.4
  
 6. SHEET A5 NOTES: CAST IRON FITTINGS ARE NOT ALLOWED.
 PER FBC FUEL GAS SECTION *403.12.4 METALLIC FITTINGS.
 (5) CAST IRON FITTINGS: (5.3) FITTINGS SHALL NOT BE
 USED IN SYSTEMS CONTAINING FLAMMABLE GAS-AIR MIXTURES.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop HIST HISTORICAL
Rev No 2 Status P Date 2011-12-14 Cont ID  
Sent By fmittner Date 2011-12-14 Time 10:08 Rev Time 0.00
Received By fmittner Date 2011-12-14 Time 10:08 Sent To  
Notes
***NONE***

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2008-01-10 Cont ID  
Sent By swurafti Date 2008-01-10 Time 14:57 Rev Time 0.00
Received By swurafti Date 2008-01-10 Time 14:56 Sent To  
Notes
2008-01-10 14:57:25HISTORIC APPROVED BY FMITTNER

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2013-02-19 Cont ID  
Sent By lwagner Date 2013-02-19 Time 13:48 Rev Time 0.00
Received By lwagner Date 2013-02-14 Time 15:07 Sent To  
Notes
2013-02-14 15:17:05IN PLUMBING BOX

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2013-02-14 Cont ID  
Sent By lmartine Date 2011-12-14 Time 15:05 Rev Time 0.00
Received By lmartine Date 2011-12-10 Time 11:45 Sent To  
Notes
2011-12-10 11:46:10SENT TO ZONING FOR HISTORICAL REVIEW.

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2011-10-18 Cont ID  
Sent By lmartine Date 2011-10-18 Time 14:13 Rev Time 0.00
Received By lmartine Date 2011-10-18 Time 14:13 Sent To  
Notes
2011-10-18 14:13:48SUBMITTAL GIVEN TO CONRAD

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-10-01 Cont ID  
Sent By lmartine Date 2009-10-01 Time 17:36 Rev Time 0.00
Received By lmartine Date 2009-10-01 Time 17:36 Sent To  
Notes
2009-10-01 17:36:50STRUCTURAL REVISIONS, GAVE TO LUIS

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-02-02 Cont ID  
Sent By adarroug Date 2009-02-02 Time 15:33 Rev Time 0.00
Received By adarroug Date 2009-02-02 Time 15:33 Sent To B
Notes
2009-02-02 15:33:36TO "LMARTINEZ" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-08-18 Cont ID  
Sent By adarroug Date 2008-08-18 Time 10:30 Rev Time 0.00
Received By adarroug Date 2008-08-18 Time 10:30 Sent To B
Notes
2008-08-18 10:31:00TO "AMORSE" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-07-15 Cont ID  
Sent By adarroug Date 2008-07-15 Time 11:20 Rev Time 0.00
Received By adarroug Date 2008-07-15 Time 11:20 Sent To E
Notes
2008-07-15 11:20:29TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-19 Cont ID  
Sent By adarroug Date 2008-05-19 Time 09:16 Rev Time 0.00
Received By adarroug Date 2008-05-19 Time 09:16 Sent To Z
Notes
2008-05-19 09:16:17TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-01-18 Time   Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 16:30 Sent To  
Notes
2008-01-10 16:30:42SENT TO SFD (Z) RACK MMILLER

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-07-18 Cont ID  
Sent By tgordon Date 2008-07-18 Time 10:32 Rev Time 0.45
Received By tgordon Date 2008-07-18 Time 10:32 Sent To P
Notes
2008-07-18 10:38:44*** PROVISO ***
 1) PER 2004 FBC/R G2407.6.2 COMBUSTION AIR,
 ONE-PERMANENT-OPENING METHOD.
 ONE PERMANENT OPENING, COMMENCING WITHIN 12 INCHES OF
 THE TOP OF THE ENCLOSURE, SHALL BE PROVIDED.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-23 Cont ID  
Sent By tgordon Date 2008-05-23 Time 09:29 Rev Time 1.15
Received By tgordon Date 2008-05-23 Time 09:29 Sent To P
Notes
2008-05-23 10:02:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) ENERGY CALCULATIONS FOR GUEST HOUSE LINE 12A SHOWS
 SEER 15.30, SEE ATTACHED ARI CERTIFICATE SHOWING THE
 SYSTEM IS A 15.00 SEER. PLEASE CORRECT ENERGY CAL'S.
 PER 2004 FBC 13-600.3.ABC.2.
  
 2) WHEN RESUBMITTING ENERGY CALCULATIONS HAVE THEM
 (ALL) SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-103.3.
  
 3) PLAN B4 GROUND FLOOR LEVEL, SHOWS A 16X16 VENT AT
 FLOOR FOR GAS WATER HEATER IN STORAGE ROOM. PER 2004
 FBC/R G2407.6.2 ONE-PERMANENT-OPENING METHOD.
 ONE PERMANENT OPENING, COMMENCING WITHIN 12 INCHES OF
 THE TOP OF THE ENCLOSURE, SHALL BE PROVIDED. PLEASE
 CORRECT.
  
 4) AS NOTED IN LAST REVIEW 1-16-08 NOTE #6. THE GAS
 CLOTHES DRYER IN THE GUEST HOUSE IS IN A CONFINED
 SPACE, PROVIDE FOR COMBUSTION AIR AND MAKE-UP AIR, PER
 2004 FBC/R G2407.1, G2407.4, AND G2407.5.1.
  
 5) AS NOTED IN LAST REVIEW 1-16-08 NOTE #4. MAIN HOUSE
 ENERGY CALCULATIONS LINE 11A SHOWS THE SUPPLY AND
 RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, THE PLANS
 SHOW ALL DUCTS ARE IN THE ATTIC. PLEASE CORRECT THE
 ENERGY CALCULATIONS PER 2004 FBC 13-600.3.ABC.2. SEE
 NOTE #2 ABOVE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-16 Cont ID  
Sent By tgordon Date 2008-01-16 Time 09:35 Rev Time 1.45
Received By tgordon Date 2008-01-16 Time 09:35 Sent To B
Notes
2008-01-16 09:54:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
  
 1) SEE A/C EQUIPMENT LIST ON MECHANICAL PLAN PAGE A-4
 FOR APARTMENT. AIR HANDLER UNIT TWE040 COULD NOT BE
 FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI
 REFERENCE NUMBER OR THE CERTIFICATE. (SEE ATTACHED ARI
 CERT. FOR MODEL 2TEE3F40A1). SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 2) SEE A/C EQUIPMENT LIST ON MECHANICAL PLAN PAGE A-5
 FOR ADDITION. AIR HANDLER UNIT TWE037 COULD NOT BE
 FOUND ON THE ARI DIRECTORY WEB-SITE, PLEASE SUBMIT ARI
 REFERENCE NUMBER OR THE CERTIFICATE. (SEE ATTACHED ARI
 CERT. FOR MODEL 2TEE3D37A1). SEE 2004 FBC
 13-607.1.ABC.3.1.1.
  
 3) APARTMENT COOLING LOAD CALCULATIONS ARE CALLING FOR
 30,350 TOTAL COOLING BTU'S, PLANS FOR APARTMENT PAGE
 A-4 ARE STATING 38,000. THE PLANS CAN ONLY CALL FOR 15%
 MORE THAN THE COOLING LOAD CAL,S, SEE 2004 FBC
 13-607.1.ABC.1.1. PLEASE CORRECT (SEE ATTACHED ARI
 CERT. FOR A 2.5 TON SYSTEM THAT AMONG OTHERS WILL MEET
 THIS REQUIREMENT).
  
 4) ENERGY CALCULATIONS LINE 11A STATES THE SUPPLY AND
 RETURN AIR DUCTS ARE IN A CONDITIONED SPACE, THE PLANS
 SHOW THE DUCTS TO BE IN THE ATTIC, SEE 2004 FBC
 13-600.3.ABC.2. PLEASE CORRECT.
  
 5) SHOW THE LOCATION OF THE GAS FIRE PLACE ON THE
 PLANS, SEE 2004 FBC/R G2407.1.
  
 6) THE APARTMENT PLAN SHOWS THE GAS WATER HEATER,
 CLOTHES DRYER, AND GAS OUTLET IN SLAT ROOM (IF BBQ
 GRILL) ARE IN CONFINED SPACES, SEE 2004 FBC/R G2407.5.
 PLEASE CORRECT.
  
 7) PLEASE PROVIDE COMBUSTION AIR CALCULATIONS, AND
 COMBUSTION AIR (IF NEEDED) FOR ALL GAS APPLIANCES, SEE
 2004 FBC/R G2407.1.
  
 8) PLEASE SHOW WHAT GAS APPLIANCE IS TO BE INSTALLED IN
 THE SLAT ROOM ON PLAN. IF A BBQ GRILL IT WILL REQUIRE
 AN APPROVED EXHAUST HOOD, SEE 2004 FBC/R M1504.1.
  
 9)PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR ALL
 GAS APPLIANCES, SEE 2004 FBC/R G2408.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2013-02-19 Cont ID  
Sent By lwagner Date 2013-02-19 Time 13:47 Rev Time 0.00
Received By lwagner Date 2013-02-19 Time 11:06 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-05-23 Cont ID  
Sent By mperson Date 2008-05-23 Time 13:49 Rev Time 0.00
Received By mperson Date 2008-05-23 Time 13:49 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-16 Cont ID  
Sent By mperson Date 2008-01-16 Time 14:23 Rev Time 0.00
Received By mperson Date 2008-01-16 Time 14:23 Sent To G
Notes
2008-01-16 15:39:38PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A5 NEW ACCESSORY BLDG SANITARY RISER DIAGRAM
 DOES NOT REFLECT THE FLOOR PLAN OF SHEET A2 IN THE
 FOLLOWING AREAS.
 A} VEG. SINK IS MISSING. PER FBC PLUMBING SECTION
 *701.1, SCOPE.
 B} SHEET A2 FLOOR PLAN IS INDICATING A SINGLE BOWL
 SINK W/ DISHWASHER AND DISP. HOWEVER SHEET A5 PLUMBING
 RISER IS INDICATING A DOUBLE BOWL SINK AND THE
 DISHWASHER DRAIN IS NOT BEING INDICATED. PLEASE CORRECT
 AND CORRELATE. PER FBC PLUMBING SECTION *701.1, SCOPE.
  
 2. SHEET A5 NEW ACCESSORY BUILDING SANITARY RISER
 DIAGRAM: PER FBC PLUMBING SECTION *708.3.5 BUILDING
 DRAIN AND BUILDING SEWER JUNCTION. THERE SHALL BE A
 TWO-WAY CLEANOUT NEAR THE JUNCTION OF THE BUILDING
 DRAIN AND THE BUILDING SEWER.
  
 3. SHEET A3 ADDITION AND RENOVATION SANITARY RISER
 DIAGRAM: THE WASHING MACHINE CAN NOT DRAIN INTO THE NEW
 POWDER ROOM BATHROOM WET VENT PER FBC PLUMBING, SECTION
 *909.1 WET VENT PERMITTED: ONLY THE FIXTURES WITHIN THE
 BATHROOM GROUPS SHALL CONNECTTO THE WET-VENTED
 HORIZONTAL BRANCH DRAIN. ANY ADDITIONAL FIXTURES SHALL
 DISCHARGE DOWNSTREAM OF THE WET VENT.
  
 **PLEASE PROVIDE THE FOLLOWING FOR THE WASHING
 MACHINE:
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM) **CLEACOUT FOR THE
 WASHING MACHINE TO BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS. **CLEANOUT FOR THE WASHING
 MACHINE TO BE LOCATED AT 4' A.F.F.
  
 4. SHEET A3 ADDITION AND RENOVATION SANITARY RISER
 DIAGRAM: THE HORIZONTAL DRY VENT IN THE MASTER BATH FOR
 THE TUB AND SHOWER IS NOT ALLOWED. PER FBC PLUMBING
 SECTION *905.3, VENT CONNECTION TO DRAINAGE SYSTEM.
  
 5. SHEET A3 ADDITION AND RENOVATION: PER FBC PLUMBING
 SECTION *708.3.5 BUILDING DRAIN AND BUILDING SEWER
 JUNCTION. THERE SHALL BE A TWO-WAY
 CLEANOUT NEAR THE JUNCTION OF THE BUILDING DRAIN AND
 THE BUILDING SEWER.
  
 6. SHEET A2 ADDITION AND RENOVATION IS INDICATING A
 STEAM UNIT UNDER THE TUB DECK. PLEASE PROVIDE THE
 FOLLOWING INFORMATION ON THIS UNIT AND PLEASE SUBMIT
 TWO COPIES OF MANUFACTURER SPECIFICATION SHEETS AND
 INSTALLATION INSTRUCTIONS ON THIS UNIT. **PER SECTION
 *101.1.1, INFORMATION ON CONSTRUCTION DOCUMENTS, FBC
 PLUMBING SECTIONS *401.1 AND 501.1, SCOPE.
  
 A} WHAT IS THE STEAM UNIT FEEDING? IS IT FOR THE TUB,
 SHOWER OR THE ENTIRE MASTER BATHROOM?
  
 B} HOW WILL ACCESS BE PROVIDE TO THE UNIT?
  
 C} WHERE WILL THE UNIT DISCHARGE PIPING BE LOCATED?
  
 D} DOES THE UNIT HAVE A TEMPERATURE AND PRESSURE
 DISCHARGE AND IF IT DOES WHERE WILL THE DISCHARGE
 PIPING BE LOCATED.
  
 E} WHERE ARE THE CONTROLS TO THE UNIT LOCATED?
  
 7. SHEET A5 NEW ACCESSORY BUILDING: PLEASE DELETE THE
 BOLD LINE THAT GOES THROUGH BOTH THE SANITARY AND GAS
 RISER DIAGRAMS. PER *106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2011-12-14 Cont ID  
Sent By fmittner Date 2011-12-14 Time 10:09 Rev Time 0.00
Received By fmittner Date 2011-12-14 Time 10:09 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By choops Date 2008-05-20 Time 12:11 Rev Time 0.00
Received By choops Date 2008-05-20 Time 12:11 Sent To E
Notes
2008-05-20 11:19:01***APPROVED - RESUB #1***
  
 NOTE:ADDITIONAL SQUARE FOOTAGE/ACCESSORY APARTMENT
 PERMITTED PURSUANT TO ZBA CLASS B SPECIAL USE PERMIT
 #3191-06
  
 PROVISO:PROHIBITED TREES. THE FOLLOWING TREE SPECIES
 ARE CONSIDERED INVASIVE AND WILL OVERTAKE OTHER PLANT
 HABITATS. THE FOLLOWING TREE SPECIES ARE THEREFORE
 CONSIDERED UNACCEPTABLE FOR USE AS LANDSCAPE TREES AND
 SHALL NOT BE PLANTED WITHIN THE CITY.ANY/ALL OF THE
 FOLLOWING EXISTING PLANT SPECIES SHALL BE REMOVED AND
 ERADICATED FROM THE PROPERTY:
  
 1.CASUARINA SPECIES (AUSTRALIAN PINE TREE)
  
 2.SCHINUS TEREBINTHIFOLIUS (BRAZILIAN PEPPER TREE)
  
 3.MELALEUCA QUINQUENERVIA (MELALEUCA TREE)
  
 4.BISCHOFIA JAVANICA (BISHOPWOOD)
  
 5.RHODOMYRTUS TOMENTOSA (DOWNY ROSE MYRTLE)
  
 6.ACACIA AURICULAEFORMIS (EARLEAF ACACIA)
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-11 Cont ID  
Sent By choops Date 2008-01-11 Time 16:12 Rev Time 0.00
Received By choops Date 2008-01-11 Time 16:12 Sent To E
Notes
2008-01-11 17:02:36***FAILED***
  
  
 NOTE:ADDITIONAL SQUARE FOOTAGE/ACCESSORY APARTMENT
 PERMITTED PURSUANT TO ZBA CLASS B SPECIAL USE PERMIT
 #3191-06
  
 1)PLEASE PROVIDE TWO (2) COPIES OF A CURRENT
 SURVEY.
  
 2)PURSUANT TO SECTION 94-441(C)(2) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS): AS THE VALUE OF
 THE PROPOSED WORK EXCEEDS 50% OF THE STRUCTURE'S VALUE
 (NOT INCLUDING LAND VALUE), LANDSCAPING SHALL BE IN
 COMPLIANCE WITH ALL APPLICABLE REGULATIONS FOUND IN
 ARTICLE XIV OF THE ZLDRS.PLEASE SUBMIT A LANDSCAPE
 PLAN SHOWING COMPLIANCE WITH SECTION 94-442 AND 94-445
 OF THE ZLDRS.
  
 3)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 4)SHEET A1 LABELS THE PROPOSED ACCESSORY APARTMENT
 AS "APARTMENTS", AS ONLY ONE IS PERMITTED, THE PLAN
 SHALL BE LABELED AS "APARTMENT".
  
 5)INDICATE HEIGHT DIMENSIONS FROM GRADE RATHER THAN
 FINISHED FLOOR.MAXIMUM ALLOWABLE HEIGHT OF ACCESSORY
 STRUCTURE SHALL NOT EXCEED 25 FEET FROM GRADE.
  
 NOTE:TOTAL UNDER AIR GROSS SQUARE FOOTAGE OF
 ACCESSORY APARTMENT SHALL NOT EXCEED 1,000 SQUARE FEET
 PER ZBA CASE NO. 3191.
  
 NOTE:ANY NEWLY SUBMITTED PLANS/SHEETS WILL NEED
 HISTORIC PRESERVATION APPROVAL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720