Plan Review Details - Permit 08010235
Plan Review Stops For Permit 08010235
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-26 Cont ID  
Sent By jwitmer Date 2008-01-26 Time 15:32 Rev Time 1.33
Received By jwitmer Date 2008-01-26 Time 15:31 Sent To  
Notes
2008-01-26 16:31:36BUILDING PLAN REVIEW
 PERMIT: 08010235
 ADD: 1221 ANDREWS RD
 CONT: WOOLEMS INC
 TEL: (561)603-4904
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. SHEET S-1
 INDICATES THE DESIGN INCORPORATES THE 2006 FBC
 SUPPLEMENTS BUT NOT THE 2007, PLEASE REVISE TO INCLUDE
 THE 2007 SUPLEMENTS.
  
 2) THERE IS NO SITE PLAN AND THE SURVEY DOESN'T
 INDICATE WHERETHE NEW STRUCTURE IS TO BE LOCATED.
 PLEASE PROVIDE HE LOCATION OF THE NEW STRUCTURE ON
 EITHER A SURVEY OR SITE PLAN, SHEET S-1 IT APPEARS THIS
 STRUCTURE BUTS AGAINST AN EXISTING BUILDING, PLEASE
 FILL OUT THE INFORMATION BELOW TO DETERMINE IF THIS IS
 AN ADDITION TO THE EXISTING STRUCTURE OR (2) SEPERATE
 STRUCTURES (SEE 503.1.3) TO BE CONSIDERED ONE OR IF TWO
 INDEPENDANT STRUCTURES WITH A FIREWALL BETWEEN.
 110.2* W. P. B. ADMINISTRATIVE CODE, INFORMATION THAT
 IS REQUIRED FOR RECORD KEEPING & FOR CERTIFICATE OF
 OCCUPANCY:
 A) THE EDITION OFTHE CODE UNDER WHICH THE PROJECT IS
 DESIGNED.
 B) PLEASE SEE EXISTING BLDG CODE 2004 W/ 2007
 SUPPLEMENTS, TO DETERMINE IF AN ADDITION OR 2 BUILDINGS
 SAME LOT SEE FBC BUILDING 503.1(3), OR A FIREWALL
 BETWEEN 2 BUILDINGS.
 C) THE USE AND OCCUPANCY, IN ACCORDANCE WITH THE
 PROVISIONS OF CHAPTER 3.
 C) THE TYPE OF CONSTRUCTION AS DEFINED IN CHAPTER 6,
 TABLE 601. FOR BOYH STRUCTURES.
 D) THE OCCUPANT LOAD, SEE 1004. BOTH STRUCTURES
 E) IF AN AUTOMATIC SPRINKLER SYSTEM ISPROVIDED
 F) WHETHER THE SPRINKLER SYSTEM IS REQUIRED.
 G) ANY SPECIAL STIPULATIONS & CONDITIONS OF THE
 BUILDING PERMIT
 H)) SQ. FT. FOOTPRINT FORBOTH STRUCTURES
  
 3) SHEET S-1 ALSO INDICATES THERE IS A SOILS REPORT
 COMPLETED BY DUNKELBERGER, PROVIDE 2 ORIGINAL
 SIGNATURE( NOT COPIES) RAISED SEAL. 1802.2.1
 QUESTIONABLE SOIL. WHERE THE SAFE-SUSTAINING POWER OF
 THE SOIL IS IN DOUBT, OR WHERE A LOAD-BEARING VALUE
 SUPERIOR TO THAT SPECIFIED IN THIS CODE IS CLAIMED, THE
 BUILDING OFFICIAL SHALL REQUIRE THAT THE NECESSARY
 INVESTIGATION BE MADE. SUCH INVESTIGATION SHALL COMPLY
 WITH THE PROVISIONS OF SECTIONS 1802.4 THROUGH 1802.6
 .
  
 4)FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) METAL ROOFING
  
 5)PRODUCT APPROVALS SUBMITTED WITH PERMIT APPLICATION
 AFTER OCTOBER 1, 2003 ARE REQUIRED TO COMPLY WITH THE
 FLORIDA PRODUCT APPROVAL SYSTEM. FOR INFORMATION PLEASE
 SEE THE STATE WEBSITE AT WWW.FLORIDABUILDING.ORG.
 PRODUCTS WITH STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS THE PRODUCT
 IDENTITY NUMBER FROM THE STATE. IF THE PRODUCT DOES NOT
 HAVE STATEWIDE APPROVAL, SUBMIT AN APPLICATION FOR
 LOCAL PRODUCT APPROVAL OR SITE SPECIFIC FORM PER RULE
 9B-72. SEE ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 6) WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7))BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 ATHROUGH REVIEW CAN NOT BE COMPLETED AT THIS TIME AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC REQUIREMENT SHALL BE
 APPLICABLE.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop ENG ENGINEERING CSD
Rev No 1 Status N Date 2008-01-15 Cont ID  
Sent By rchokshi Date 2008-01-15 Time 15:51 Rev Time 0.00
Received By rchokshi Date 2008-01-15 Time 14:48 Sent To  
Notes
2008-01-15 15:51:21NO CIVIL DRAWING PROVIDED. THEREFORE, CAN NOT SAY IF
 THEY HAVE ANY DRIVEWAY, SIDEWALK, STORM WATER DRAINAGE
 SYSTEM PER LUIS M.
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-02-11 Cont ID  
Sent By mawillia Date 2008-02-11 Time 15:24 Rev Time 0.00
Received By mawillia Date 2008-02-11 Time 13:50 Sent To  
Notes
2008-02-11 15:11:17*****DENIED*****
  
  
 1.THE ACTUAL ADDRESS OF THE PROJECT SITE LOCATION
 SHALL BE IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.NO ADDRESS SHOWN ON THE BLUE SHEETS, AND THE
 ADDRESS LISTED ON SHEET S-1 & S-2 DO NOT CORRELATE WITH
 THAT ON THE APPLICATION OR LISTED IN OUR SYSTEM.
  
 2.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 3.PLEASE LIST THE OCCUPANCY TYPE, OCCUPANT LOAD,
 SQUARE FOOTAGE OF THE OCCUPANCY, AND ANY OTHER
 PERTINENT INFORMATION TO DETAIL THE BUILDING.
  
 4.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 5.IS THE PROJECT AN ADDITION TO AN EXISTING BUILDING
 OR AN INDEPENDANT STRUCTURE?
  
 6.A FLOOR PLAN / LIFE SAFETY PLAN NEEDED FOR THE
 STRUCTURE.EXIT LIGHTS, EMERGENCY LIGHTS, AND THE
 LOCATION OF THE FIRE EXTINGUISHER(S) SHALL BE SHOWN. IF
 THE BUILDING IS REQUIRED TO BE EQUIPPED WITH A FIRE
 ALARM AND/OR FIRE SPRINKLER SYSTEM, A LAYOUT OF THOSE
 SYSTEMS SHALL BE PROVIDED.
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
 **ATTENTION:ADDITIONAL COMMENTS MAY APPEAR BASED UPON
 THE ABOVE REQUESTED INFORMATION**
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-02-11 Cont ID  
Sent By mawillia Date 2008-02-11 Time 13:52 Rev Time 0.00
Received By mawillia Date 2008-01-10 Time 16:12 Sent To  
Notes
2008-01-10 16:13:05SENT TO COMM BOARD # 18

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-22 Cont ID  
Sent By bpowell Date 2008-01-22 Time 09:42 Rev Time 0.00
Received By bpowell Date 2008-01-22 Time 09:42 Sent To  
Notes
2008-01-22 09:43:31 
 1. A SITE PLAN REVIEW WILL BE REQUIRED, PER SECTION
 94-35 OF THE ZONING AND LAND DEVELOPMENT REGULATIONS,
 SITE PLAN REVIEWS ARE REQUIRED FOR BUILDINGS LARGER
 THAN 1,000 SF.
  
 2. PLEASE PROVIDE INFORMATION AS TO WHETHER THIS
 BUILDING WILL BE REPLACING THE OLD BUILDING OR IS IT A
 COMPLETELY NEW BUILDING.
  
 3. PLEASE SHOW THE BUILDING IN CONTEXT WITH THE ENTIRE
 PROPERTY ON THE SITE PLAN.
  
 4. ALL NEW CONSTRUCTION IN THE INDUSTRIAL DISTRICT
 SHALL ADHERE TO THE STANDARDS SET FORTH IN SECTION
 94-173 OF THE ZLDRS.
  
 5. PLEASE PROVIDE ELEVATIONS OF THE NEW BUILDING.
  
 FOR QUESTIONS AND COMMENTS PLEASE CONTACT; BOBBY POWELL
 JR., PLANNING, (561) 822-1435, [email protected]