Plan Review Details - Permit 08010199
Plan Review Stops For Permit 08010199
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-01-16 Cont ID  
Sent By lursu Date 2008-01-16 Time 14:02 Rev Time 0.00
Received By lursu Date 2008-01-15 Time 16:31 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By mjacobs Date 2008-02-21 Time 12:08 Rev Time 0.00
Received By mjacobs Date 2008-02-21 Time 08:46 Sent To  
Notes
2008-02-21 12:08:10 
 BUILDING PLAN REVIEW
 PERMIT: 08010199
 ADD: 104 CLEMATIS ST.
 CONT: PCF CONSTRUCTION.
 TEL: (561)655-6330
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 2-21-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) OK.
  
 **NOTED HOWEVER, A LEVEL OF ALTERATION MUST BE
 SELECTED**
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 **NO RESPONSE NOT ADDRESSED**
 3)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE
 SUBMITTED INDICATING THE USE OF EACH ROOM. THE EXISTING
 PLANS SHALL SHOW ALL WALL TO BE DEMOED ALONG WITH ALL
 OTHER SYSTEM CHANGES. THE PROPOSED PLANS SHALL SHOW ALL
 THE NEW WALLS AND SYSTEMS. A WALL LEGEND INDICATING THE
 DIFFERENT TYPES AND SIZE OF EACH WALL SHALL BE ON THE
 DRAWINGS FOR CLARITY. THE TYPE OF MATERIALS TO
 CONSTRUCT THE NEW WALLS SHALL BE SHOWN WITH A DETAIL
 DRAWING. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS. FBC 106.1.1.
  
 4)OK
  
 **NO RESPONSE NOT ADDRESSED**
 5) FBC 11-4.17.3(NEW CONSTRUCTION) THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17 [SEE FIGURE 30
 (A) AND FIGURE 30 (E)] AND TO COMPLY WITH SECTION
 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING.
 THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
 **NOTED, HOWEVER, INDICATE WHAT MATERIALS WILL BE USED
 ON THE WALLS.**
 6)FBC 1210.1 THE FLOORS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE WALLS
 AT LEAST 6 INCHES.
  
 **NOTED, INDICATE THE MATERIALS TO BE USED**
 7)ALL WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL A SMOOTH, HARD, NONABSORBENT SURFACE, TO
 A HEIGHT OF 4 FEET AND SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE. FBC 1210.2
  
 **NEW**
 11-4.13.6 MINIMUM MANEUVERING CLEARANCES AT DOORS THAT
 ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN
 IN FIGURE 25. THE FLOOR OR GROUND AREA WITHIN THE
 REQUIRED CLEARANCES SHALL BE LEVEL AND CLEAR. SEE
 SECTION 1008.1.3.2 THE DESIGN SHALL BE SUCH THAT IN THE
 EVENT OF POWER FAILURE, THE DOOR IS CAPABLE OF BEING
 OPENED MANUALLY TO PERMIT MEANS OF EGRESS TRAVEL OR
 CLOSED WHERE NECESSARY TO SAFEGUARD MEANS OF EGRESS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-14 Cont ID  
Sent By mjacobs Date 2008-01-14 Time 16:16 Rev Time 0.00
Received By mjacobs Date 2008-01-14 Time 16:16 Sent To  
Notes
2008-01-14 16:16:10 
 BUILDING PLAN REVIEW
 PERMIT: 08010199
 ADD: 104 CLEMATIS ST.
 CONT: PCF CONSTRUCTION.
 TEL: (561)655-6330
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 3)AN EXISTING AND A PROPOSED FLOOR PLAN SHALL BE
 SUBMITTED INDICATING THE USE OF EACH ROOM. THE EXISTING
 PLANS SHALL SHOW ALL WALL TO BE DEMOED ALONG WITH ALL
 OTHER SYSTEM CHANGES. THE PROPOSED PLANS SHALL SHOW ALL
 THE NEW WALLS AND SYSTEMS. A WALL LEGEND INDICATING THE
 DIFFERENT TYPES AND SIZE OF EACH WALL SHALL BE ON THE
 DRAWINGS FOR CLARITY. THE TYPE OF MATERIALS TO
 CONSTRUCT THE NEW WALLS SHALL BE SHOWN WITH A DETAIL
 DRAWING. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS. FBC 106.1.1.
  
 4)FBC 106.3.5.1.1 THE USE AND OCCUPANCY OF THE
 BUILDING SHALL BE INDICATED ON THE DRAWINGS ALONG WITH
 THE OCCUPANT LOAD.
  
 5) FBC 11-4.17.3(NEW CONSTRUCTION) THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17 [SEE FIGURE 30
 (A) AND FIGURE 30 (E)] AND TO COMPLY WITH SECTION
 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE BUILDING.
  
 THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
 6)FBC 1210.1 THE FLOORS SHALL HAVE A SMOOTH, HARD,
 NONABSORBENT SURFACE THAT EXTENDS UPWARD ONTO THE WALLS
 AT LEAST 6 INCHES.
  
 7)ALL WALLS WITHIN 2 FEET OF URINALS AND WATER
 CLOSETS SHALL A SMOOTH, HARD, NONABSORBENT SURFACE, TO
 A HEIGHT OF 4 FEET AND SHALL BE OF A TYPE THAT IS NOT
 ADVERSELY AFFECTED BY MOISTURE. FBC 1210.2
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-15 Cont ID  
Sent By dpalmer Date 2008-02-15 Time 09:33 Rev Time 0.00
Received By dpalmer Date 2008-02-15 Time 09:33 Sent To  
Notes
2008-02-15 09:33:38LTS NOW SHOWN AS EXISTING

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-14 Cont ID  
Sent By dpalmer Date 2008-01-14 Time 09:47 Rev Time 0.00
Received By dpalmer Date 2008-01-14 Time 09:47 Sent To  
Notes
2008-01-14 09:47:52** DENIED**
  
 1) NOTE: PLANS INDICATE A MOTION SWITCH BEING INSTALLED
 HOWEVER THIS WILL BE REQUIRED TO BE A DEVICE CAPABLE OF
 MULTI-TURN ON TECHNOLOGY SUCH AS INFRARED, ULTRASONIC
 ETC
 AS THESE BATHROOMS CONTAIN MULTIPLE STALLS/POINTS OF
 USE THE MOTION SENSOR ALONE WOULD NOT PROVIDE
 COVERAGE.
 13-415.1.ABC.1.1, .1.2
  
 2) NOTE: PLEASE PROVIDE LOCATIONS OF NEW OR EXISTING
 EMERGENCY LIGHT FIXTURES REQUIRED FOR EGRESS FROM THESE
 LOCATIONS.
 PLEASE SEE 7.8 AND 7.9 OF NFPA-101 2003.
  
 3) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE STATED ON PLANS AS REQUIRED.
 FBC 2004 W/2007 REVISIONS.
 2003 NFPA-101
 2005 NFPA-70
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-21 Cont ID  
Sent By mawillia Date 2008-02-21 Time 13:01 Rev Time 0.00
Received By mawillia Date 2008-02-21 Time 12:41 Sent To  
Notes
2008-02-21 13:01:38*****APPROVED*****
  
  
 PLAN SHEET WHICH WAS PREVIOUSLY STAMPED ON STAMPED ON
 01/16/08 BY CAPT. WENNERGREN;WAS RE-STAMPED,
 INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-01-16 Cont ID  
Sent By mwennerg Date 2008-01-16 Time 10:58 Rev Time 0.00
Received By mwennerg Date 2008-01-16 Time 10:58 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-13 Cont ID  
Sent By adarroug Date 2008-02-13 Time 14:54 Rev Time 0.00
Received By adarroug Date 2008-02-13 Time 14:54 Sent To  
Notes
2008-02-13 15:00:17TO "BOB"#1

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-17 Cont ID  
Sent By adarroug Date 2008-01-17 Time 09:57 Rev Time 0.00
Received By adarroug Date 2008-01-10 Time 08:58 Sent To  
Notes
2008-01-10 08:58:13TO "BOB" # 15

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-14 Cont ID  
Sent By tgordon Date 2008-02-14 Time 10:42 Rev Time 0.25
Received By tgordon Date 2008-02-14 Time 10:42 Sent To  
Notes
2008-02-14 10:43:39ONE BATHROOM EXHAUST FAN.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-01-10 Cont ID  
Sent By tgordon Date 2008-01-10 Time 14:09 Rev Time 0.25
Received By tgordon Date 2008-01-10 Time 14:09 Sent To  
Notes
2008-01-10 14:10:131 BATHROOM EXHAUST FAN.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By mperson Date 2008-02-21 Time 13:15 Rev Time 0.00
Received By mperson Date 2008-02-21 Time 14:12 Sent To PC
Notes
2008-02-21 14:46:14PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS PLUMBING REVIEW COMMENTS FOR THE PURPOSE
 OF CONTINUITY.
 NOTE: THERE WAS NO TRANSMITTAL RESPONSE LETTER TO THE
 PLUMBING COMMENTS FROM THE DESIGNER. NEW COMMENTS WILL
 BE SO NOTED FOLLOWING THE PREVIOUS REVIEW COMMENTS.
  
 1. **OK**COMMENT ADDRESSED.
  
 2. FBC- 11-4.17.3 (NEW CONSTRUCTION) THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17 [SEE FIGURE 30
 (A) AND FIGURE 30 (E)] AND TO COMPLY WITH SECTION
 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE
 BUILDING.
  
 THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 REQUIRED ACCESSIBLE WATER CLOSET, LAVATORY AND
 BATHROOM.
  
 A}**11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED
 WITH THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 B}**11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 C}**11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 3. **OK** COMMENT ADDRESSED.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 4. A TWO-WAY CLEANOUT IS REQUIRED AT THE JUNCTION OF
 THE BUILDING DRAIN AND BULDING SEWER. PER FBC PLUMBING
 SECTION *708.3.5.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]`
2008-02-15 13:18:19 

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-15 Cont ID  
Sent By mperson Date 2008-01-15 Time 09:37 Rev Time 0.00
Received By mperson Date 2008-01-15 Time 09:37 Sent To  
Notes
2008-01-15 10:20:29PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. FBC- 106.3.5.1.1 THE USE AND OCCUPANCY OF THE
 BUILDING SHALL BE INDICATED ON THE DRAWINGS ALONG WITH
 THE OCCUPANCY LOAD. THE MINIMUM REQUIRED PLUMBING
 FIXTURES SHALL BE DETERMINED BY THE FOLLOWING.403.1
 MINIMUM NUMBER OF FIXTURES.
 PLUMBING FIXTURES SHALL BE PROVIDED FOR THE TYPE OF
 OCCUPANCY AND IN THE MINIMUM NUMBER SHOWN IN TABLE
 403.1 . THE NUMBER OF OCCUPANTS SHALL BE DETERMINED BY
 THE FLORIDA BUILDING CODE, BUILDING. OCCUPANCY
 CLASSIFICATION SHALL BE DETERMINED IN ACCORDANCE WITH
 THE FLORIDA BUILDING CODE, BUILDING.
  
 2. FBC- 11-4.17.3 (NEW CONSTRUCTION) THE STANDARD
 ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN ACCESSIBLE
 LAVATORY WITHIN IT, THE SIZE OF SUCH LAVATORY TO BE NOT
 LESS THAN 19 INCHES WIDE BY 17 INCHES (483 MM BY 432
 MM) DEEP, NOMINAL SIZE, AND WALL MOUNTED. THE LAVATORY
 SHALL BE MOUNTED SO AS NOT TO OVERLAP THE CLEAR FLOOR
 SPACE AREAS REQUIRED BY SECTION 11-4.17 [SEE FIGURE 30
 (A) AND FIGURE 30 (E)] AND TO COMPLY WITH SECTION
 11-4.19 OF THE CODE. SUCH LAVATORIES SHALL BE COUNTED
 AS PART OF THE REQUIRED FIXTURE COUNT FOR THE
 BUILDING.
  
 THE ACCESSIBLE WATER CLOSET SHALL BE LOCATED IN THE
 CORNER, DIAGONAL TO THE DOOR.
  
 PLEASE PROVIDE THE FOLLOWING INFORMATION FOR THE
 REQUIRED ACCESSIBLE WATER CLOSET, LAVATORY AND
 BATHROOM.
  
 A}**11-4.16 WATER CLOSETS (ELEVATION DETAIL REQUIRED
 WITH THE FOLLOWING INFORMATION)
 11-4.16.2 CLEAR FLOOR SPACE. SEE FIGURE 28. 11-4.16.3
 HEIGHT. 17" TO 19".
 11-4.16.4 GRAB BARS. SEE FIGURE 29. GRAB BAR BEHIND W/C
 36" LONG.
 11-4.16.5 FLUSH CONTROLS. MOUNTED ON WIDE SIDE MAX. 44"
 HIGH.
 11-4.16.6 DISPENSERS. SEE FIGURE 29(B).
  
 B}**11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.2 HEIGHT AND CLEARANCES. MAXIMUM 34" TO RIM OR
 COUNTER. 29" A.F.F. TO THE BOTTOM OF THE APRON. (SEE
 FIGURE 31)
 11-4.19.3 CLEAR FLOOR SPACE.30" X 48" AND SHALL EXTEND
 A MAXIMUM OF 19" UNDERNEATH THE LAVATORY. (SEE FIGURE
 32)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
 11-4.19.6 MIRRORS. 40" MAXIMUM A.F.F.
  
 C}**11-4.23 BATHROOMS, BATHING FACILITIES AND SHOWER
 ROOMS.
 11-4.22.2 DOOR. DOOR SWING NOT ALLOWED IN CLEAR FLOOR
 SPACE
 11-4.22.3 CLEAR FLOOR SPACE. WHEELCHAIR TURNING SPACE
 SHALL BE 180-DEGREE WITH A MINIMUM 60" CLEAR FLOOR
 SPACE (PER 11-4.2.3)
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 WATER HEATER LOCATION, LOCATION OF THE WATER SUPPLY
 LINE WITH BACKFLOW PREVENTER **608, THERMAL EXPANSION
 CONTROL FOR THE WATER HEATER **607.3, AND LOCATION OF
 THE WATER-HAMMER ARRESTORS WHERE QUICK CLOSING VALVES
 ARE UTILIZED (EXAMPLES=WASHING MACHINES, DISHWASHERS,
 ICE MAKERS) **604.9.
 NOTE: CLEARLY INDICATE ON THE PLANS WHAT IS NEW AND
 EXISTING.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2008-01-16 Cont ID  
Sent By mflis Date 2008-01-16 Time 16:01 Rev Time 0.00
Received By mflis Date 2008-01-16 Time 16:01 Sent To  
Notes
2008-01-16 16:02:44ZONING REVIEW: NOT REQUIRED WITH COMMENT:
  
 * ANY LANDSCAPING WHICH IS REMOVED DUE TO UTILITY
 WORK/CONNECTIONS SHALL BE REPLACED WITHIN THE PLANTERS
  
 MATT FLIS - 822-1445