| 2008-01-17 17:30:31 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | |
| | FBCFLORIDA BUILDING CODE 2004 |
| | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING |
| | CODE |
| | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL |
| | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| | FAC FLORIDA ADMINISTRATIVE CODE |
| | FSFLORIDA STATUTE |
| | |
| | |
| | 1.THE SHUTTER CONNECTION MOUNTING TYPE SHOULD |
| | CORRELATE WITH THE ANCHOR CHARTS; IN THIS CASE, WALL |
| | MOUNT 1 THROUGH 4, CEILING MOUNT 5, FLOOR MOUNT 6 |
| | THROUGH 8, ETC. |
| | |
| | 2.THIS BUILDING APPEARS TO BE IN EXPOSURE C; PLEASE |
| | REVISE DESIGN PRESSURES.FOR INSTANCE, OPENING 4 |
| | SHOULD HAVE A DP OF -46.22 FOR ZONE 4, FBC R301.2(2) |
| | AND (3).PLEASE CONTACT ME IF YOU NEED ASSISTANCE IN |
| | DETERMINING DESIGN PRESSURES.WORST CASE, ZONE 5 LESS |
| | THAN 10FT, WOULD BE 57.11. |
| | |
| | 3.NOTE THAT YOU HAVE SPECIFIED CONCRETE BLOCK AS A |
| | SUBSTRATE AND THIS IS NOT ALLOWED FOR ALL CONNECTION |
| | TYPES.THE SUBSTRATE SHOULD BE THE SUBSTRATE OF THE |
| | OPENING; FILLED CELLS (INCLUDING BOND BEAMS) ARE |
| | CONSIDERED BLOCK, FORMED AND POURED TIE BEAMS AND SILLS |
| | ARE CONSIDERED POURED CONCRETE.THIS NOTE IS ADVISORY |
| | ONLY TO ASSIST YOU IN PROVIDING COMPLETE, CORRECT |
| | INFORMATION TO AVOID FUTURE CHECKLISTS. |
| | |
| | 4.SEE SHEET 11.A 3" EDGE DISTANCE REQUIRES A FACTOR |
| | TO BE APPLIED; .83 FOR TAPCONS. |
| | |