Plan Review Details - Permit 08010158
Plan Review Stops For Permit 08010158
Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 13:49 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 13:49 Sent To M
Notes
2008-01-22 13:50:09TO "M" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-11 Cont ID  
Sent By tgordon Date 2008-01-11 Time 14:49 Rev Time 0.00
Received By tgordon Date 2008-01-09 Time 09:18 Sent To  
Notes
2008-01-09 09:18:12TO "M" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By tgordon Date 2008-01-23 Time 11:17 Rev Time 0.40
Received By tgordon Date 2008-01-23 Time 11:17 Sent To  
Notes
2008-01-23 11:19:52*** PROVISO ***
 1) 2004 FBC/M 506.3.10 DUCT ENCLOSURE.
 A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A
 FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE
 ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET
 TERMINAL. A DUCT SHALL ONLY PENETRATE EXTERIOR WALLS AT
 LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY
 THE BUILDING CODE. DUCTS SHALL BE ENCLOSED IN
 ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR
 SHAFT CONSTRUCTION. THE DUCT ENCLOSURE SHALL BE SEALED
 AROUND THE DUCT AT THE POINT OF PENETRATION AND VENTED
 TO THE OUTSIDE OF THE BUILDING THROUGH THE USE OF
 WEATHER-PROTECTED OPENINGS. THE ENCLOSURE SHALL BE
 SEPARATED FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A
 MAXIMUM OF 12 INCHES AND SHALL SERVE A SINGLE GREASE
 EXHAUST DUCT SYSTEM.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-11 Cont ID  
Sent By tgordon Date 2008-01-11 Time 14:40 Rev Time 0.30
Received By tgordon Date 2008-01-11 Time 14:40 Sent To  
Notes
2008-01-11 14:46:50PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) KITCHEN HOOD PLANS NEED TO BE REVIEWED BY THE
 ENGINEER OF RECORD 'EDUARDO SAMOUR P.E. AND HAVE HIM
 PUT A SHOP REVIEW STAMP ON THEM ALSO DATE AND SIGN IT.
  
 ** BE ADVISED THE MECHANICAL PLANS OF THE MASTER PLAN
 WILL NEED TO BE REVISED BEFOR YOUR ROUGH INSPECTION TO
 SHOW THE CORRECTED HOOD AND FAN INFORMATION ON THEM.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]