Plan Review Details - Permit 08010158
| Plan Review Stops For Permit 08010158 |
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-22 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-22 |
Time |
13:49 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-22 |
Time |
13:49 |
Sent To |
M |
|
| Notes |
| 2008-01-22 13:50:09 | TO "M" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-11 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
tgordon |
Date |
2008-01-09 |
Time |
09:18 |
Sent To |
|
|
| Notes |
| 2008-01-09 09:18:12 | TO "M" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-23 |
Time |
11:17 |
Rev Time |
0.40 |
| Received By |
tgordon |
Date |
2008-01-23 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2008-01-23 11:19:52 | *** PROVISO *** | | | 1) 2004 FBC/M 506.3.10 DUCT ENCLOSURE. | | | A GREASE DUCT SERVING A TYPE I HOOD THAT PENETRATES A | | | FIRE RATED CEILING, FIRE RATED WALL OR FLOOR SHALL BE | | | ENCLOSED FROM THE POINT OF PENETRATION TO THE OUTLET | | | TERMINAL. A DUCT SHALL ONLY PENETRATE EXTERIOR WALLS AT | | | LOCATIONS WHERE UNPROTECTED OPENINGS ARE PERMITTED BY | | | THE BUILDING CODE. DUCTS SHALL BE ENCLOSED IN | | | ACCORDANCE WITH THE BUILDING CODE REQUIREMENTS FOR | | | SHAFT CONSTRUCTION. THE DUCT ENCLOSURE SHALL BE SEALED | | | AROUND THE DUCT AT THE POINT OF PENETRATION AND VENTED | | | TO THE OUTSIDE OF THE BUILDING THROUGH THE USE OF | | | WEATHER-PROTECTED OPENINGS. THE ENCLOSURE SHALL BE | | | SEPARATED FROM THE DUCT BY A MINIMUM OF 6 INCHES AND A | | | MAXIMUM OF 12 INCHES AND SHALL SERVE A SINGLE GREASE | | | EXHAUST DUCT SYSTEM. | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-11 |
Time |
14:40 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-01-11 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2008-01-11 14:46:50 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) KITCHEN HOOD PLANS NEED TO BE REVIEWED BY THE | | | ENGINEER OF RECORD 'EDUARDO SAMOUR P.E. AND HAVE HIM | | | PUT A SHOP REVIEW STAMP ON THEM ALSO DATE AND SIGN IT. | | | | | | ** BE ADVISED THE MECHANICAL PLANS OF THE MASTER PLAN | | | WILL NEED TO BE REVISED BEFOR YOUR ROUGH INSPECTION TO | | | SHOW THE CORRECTED HOOD AND FAN INFORMATION ON THEM. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
|