| Plan Review Stops For Permit 07120633 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-25 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-06-25 |
Time |
11:33 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-06-25 |
Time |
11:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-04-01 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-04-01 |
Time |
11:34 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-04-01 |
Time |
11:34 |
Sent To |
|
|
| Notes |
| 2008-04-01 11:34:29 | 2004 FBC W/2007 REVISIONS | | | CONVERT GARAGE TO LIVING SPACE | | | | | | DENIED BY BUILDING | | | | | | 1) THE ENERGY CALCULATION FORMS DO NOT CONCUR WITH THE | | | PLANS. THE PLANS SPECIFY A RAISED WOOD FLOOR WITH R-11 | | | INSULATION IN A PORTION OF THE GARAGE CONVERSION. THE | | | PLANS SPECIFY R-30 ATTIC INSULATION AND THE FORM | | | SPECIFIES R-19. THE PLANS SPECIFY R-5 INSULATION ON THE | | | BLOCK WALLS AND THE FORM LISTS R-4. PLEASE CORRECT. | | | | | | 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | THE ENGINEER IS REQUIRED TO REVIEW AND APPROVE THE | | | PRODUCT APPROVALS IN WRITING. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-11 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-01-11 |
Time |
07:00 |
Sent To |
|
|
| Notes |
| 2008-01-11 13:58:50 | 2004 FBC W/2007 REVISIONS | | | CONVERT GARAGE TO LIVING SPACE | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) SPECIFY THE FLOOR LIVE LOAD ON THE PLANS. 2004 FBC | | | R501.2 REQUIREMENTS. | | | FLOOR CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING | | | ALL LOADS ACCORDING TO SECTION R301 AND OF TRANSMITTING | | | THE RESULTING LOADS TO THE SUPPORTING STRUCTURAL | | | ELEMENTS. SEE TABLE R301.5. | | | | | | 4) SPECIFY THE HANGERS THAT WILL BE USED TO SUPPORT THE | | | FLOOR JOIST. FBC 106.1.1* CITY AMENDMENTS. | | | | | | 5) A 2X6 LEDGER IS SPECIFIED TO PROVIDE ATTACHMENT FOR | | | THE 2 X12 FLOOR JOISTS. PLEASE EVALUATE THAT THESE WILL | | | PROVIDE ADEQUATE SURFACE AREA FOR FASTENING OF THE | | | JOIST HANGERS. | | | | | | 6) SPECIFY THE REQUIRED EMBED DEPTH OF THE 3/8" TAP | | | CONS THAT WILL BE USED TO ATTACH THE 2 X 6 LEDGER TO | | | THE CBS WALLS. PROVIDE A SIGNED AND SEALED EVALUATION | | | WITH CALCULATIONS OF THE ATTACHMENT OF THE 2 X 6 LEDGER | | | TO CONCRETE BLOCK WITH 3/8" TAPCONS AT 24" O.C. AND | | | THEIR CAPACITY TO SUPPORT ALL IMPOSED LOADS.FBC | | | 106.1.1* CITY AMENDMENTS. | | | | | | 7) SPECIFY THE CEILING HEIGHT ON THE PLANS. SHOW | | | COMPLIANCE WITHR305.1 MINIMUM HEIGHT . | | | HABITABLE ROOMS, HALLWAYS, CORRIDORS, BATHROOMS, TOILET | | | ROOMS, LAUNDRY ROOMS AND BASEMENTS SHALL HAVE A CEILING | | | HEIGHT OF NOT LESS THAN 7 FEET (2134 MM). THE REQUIRED | | | HEIGHT SHALL BE MEASURED FROM THE FINISH FLOOR TO THE | | | LOWEST PROJECTION FROM THE CEILING . | | | | | | 8)SUBMIT TWO COPIES OF ENERGY CALCUALTIONS SIGNED AND | | | DATED BY THE PREPARER AND THE OWNER/AGENT AS REQUIRED | | | BY FBC CHAPTER 13. | | | | | | 10)SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE NEW | | | IN-SWING EXTERIOR DOOR. FAC RULE 9B-72. | | | | | | 11)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. | | | THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 | | | SHALL BE REVIEWED AND APPROVED IN WRITING BY THE | | | DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. | | | | | | - ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-18 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-18 |
Time |
10:16 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-26 |
Time |
14:34 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-26 |
Time |
13:56 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-03 |
Time |
15:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-03 |
Time |
14:18 |
Sent To |
M |
|
| Notes |
| 2008-01-03 15:13:01 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | ALL COMMENTS RELATE TO SHEET #2 , UNLESS OTHERWISE | | | NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS | | | OTHERWISE NOTED. | | | | | | 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED | | | PER 230.70(A) & (A)(1). | | | | | | 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT | | | CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE | | | EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS | | | EQUAL TO OR GREATER THAN THE AVAILABLE FAULT. | | | | | | 3} THE APPLICATION DESCRIBES THE WORK AS "CONVERTING TO | | | HOME OFFICE", THE PLAN INDICATES A NEW BEDROOM. PLEASE | | | CORRELATE TO INDICATE THE INTENT OF WORK. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-17 |
Time |
10:19 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-17 |
Time |
10:19 |
Sent To |
Z |
|
| Notes |
| 2008-06-17 10:19:36 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-21 |
Time |
16:09 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-21 |
Time |
16:09 |
Sent To |
Z |
|
| Notes |
| 2008-03-21 16:10:14 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-11 |
Time |
10:38 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-12-31 |
Time |
12:02 |
Sent To |
|
|
| Notes |
| 2007-12-31 12:02:42 | TO SFR ZONING |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-18 |
Time |
11:09 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-06-18 |
Time |
11:08 |
Sent To |
P |
|
| Notes |
| 2008-06-18 11:09:43 | FOR CLOTHES DRYER VENT ONLY. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-26 |
Time |
15:21 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-03-26 |
Time |
15:21 |
Sent To |
P |
|
| Notes |
| 2008-03-26 15:26:58 | *** PROVISO *** | | | 1) THE CLOTHES DRYER VENT MAY NOT BE MADE OF 3" PVC BUT | | | MUST BE RIGID METAL AND COMPLY WITH 2004 FBC/R M1501. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-01-03 |
Time |
16:18 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-01-03 |
Time |
16:18 |
Sent To |
P |
|
| Notes |
| 2008-01-03 16:28:43 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC | | | 13-101.2.3. | | | | | | 2) SHOW ON THE PLAN THE R. VALUE FOR THE INSULATION IN | | | THE FLOOR JOISTS, SEE 2004 FBC 13-605.1.C.1. | | | | | | 3) SHOW ON PLAN ATTIC INSULATION AND R. VALUE, SEE 2004 | | | FBC 13-604.1.C.1. | | | | | | 4) SHOW ON PLAN THE CLOTHES DRYER VENT, SEE 2004 FBC/R | | | M1501.1. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-20 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-06-20 |
Time |
11:30 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-06-20 |
Time |
11:30 |
Sent To |
B |
|
| Notes |
| 2008-06-20 11:31:40 | ******PROVISO****** | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING | | | PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF | | | PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH | | | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-27 |
Time |
08:06 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-27 |
Time |
08:06 |
Sent To |
B |
|
| Notes |
| 2008-03-27 08:18:41 | PLUMBING PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE | | | COMPLIANCE. | | | | | | 1. SHEET 2, ISOMETRIC SANITARY PLUMBING RISER DIAGRAM: | | | THE WASHING MACHINE HORIZONTAL WASTE BRANCH NEEDS TO BE | | | DOWNSTREAM OF THE WET VENTED BATHROOM GROUP. PER FBC | | | PLUMBING SECTION 909.1 WET VENT PERMITTED. | | | 909.1 WET VENT PERMITTED. | | | ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS | | | LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE | | | VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED | | | THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE | | | CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE | | | FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE | | | DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY | | | THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT | | | TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY | | | ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE | | | WET VENT. | | | | | | 2. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: A | | | TWO-WAY CLEANOUT IS REQUIRED AT THE JUNCTION OF THE | | | BUILDING DRAIN AND BUILDING SEWER. PER FBC PLUMBING | | | SECTION 708.3.5. ALSO LOCATE THE CLEANOUT FOR THE | | | BATHROOM LAV AT THE BASE OF THE WASTE STACK. PER FBC | | | PLUMBING SECTION 708.3.4. | | | | | | 3. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: CLEARLY | | | INDICATE THE SIZE OF THE WASHING MACHINE TRAP AND | | | STANDPIPE AS BEING 2". PER FBC PLUMBING SECTION 406.3. | | | | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-01-07 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-01-07 |
Time |
08:16 |
Sent To |
B |
|
| Notes |
| 2008-01-07 08:38:44 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. MORE INFORMATION IS REQUIRED, PLEASE PROVIDE AN | | | EXISTING FLOOR PLAN LAYOUT WITH THE LOCATION OF THE | | | EXISTING LAUNDRY ROOM APPLIANCES. IF THE PROPOSED | | | LOCATION OF THE WASHING MACHINE IS DIFFERENT FROM THE | | | EXISTING THE FOLLOWING WILL BE REQUIRED AND NEEDS TO BE | | | ADDED TO THE SANITARY RISER DIAGRAM. PER *106.1.2, | | | ADDITIONAL DATA AND *701.1, SCOPE. | | | | | | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND | | | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | | (51MM) IN DIAMETER. THE AUTOMATIC | | | CLOTHES WASHER FIXTURE DRAIN SHALL | | | CONNECT TO A BRANCH DRAIN OR DRAINAGE | | | STACK A MINIMUM OF 3 INCHES (76MM) IN | | | DIAMETER. | | | | | | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY | | | TRAPPED. STANDPIPES SHALL | | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | | AND A MAXIMUM OF 42 INCHES (1066MM) | | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | | PROVIDED TO ALL STANDPIPES AND DRAINS | | | FOR RODDING. | | | **INDICATE STANDPIPE FOR WASHING MACHINE. | | | | | | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | | BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102MM). | | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". | | | | | | (D) 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4' | | | A.F.F. | | | | | | 2. SHEET 2: WITH THE REMOVAL OF THE LAUNDRY TUB (TRAY) | | | THE FOLLOWING WILL BE REQUIRED. | | | PER FBC-2004 PLUMBING, SECTION 704.5 | | | DEAD ENDS: IN THE INSTALLATION OR | | | REMOVAL OF ANY PART OF A DRAINAGE | | | SYSTEM, DEAD ENDS SHALL BE PROHIBITED. | | | A PLUMBING PERMIT REQUIRED AND | | | INSPECTION REQUIRED OF DEMO WORK PRIOR | | | TO COVERING DEMO WORK WITH FINNISH | | | WALLS, CIELINGS, OR POURED CONCRETE | | | SLABS.(ADD TO NOTES) | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-06-17 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-06-17 |
Time |
14:25 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-06-17 |
Time |
14:25 |
Sent To |
E |
|
| Notes |
| 2008-06-17 14:25:45 | ***APPROVED - RESUB #2 (RESTAMPED PLANS)*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-26 |
Time |
11:38 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-26 |
Time |
11:38 |
Sent To |
E |
|
| Notes |
| 2008-03-26 11:39:29 | ***APPROVED - RESUB #1 (RESTAMPED PLANS)*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
P |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-03 |
Time |
08:32 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-03 |
Time |
08:32 |
Sent To |
E |
|
| Notes |
| 2008-01-03 08:33:10 | ***APPROVED*** | | | | | | | | | | | | SENT TO "E" - METAL SF RACK |
|
|