Plan Review Details - Permit 07120633
Plan Review Stops For Permit 07120633
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-06-25 Cont ID  
Sent By rmcdouga Date 2008-06-25 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2008-06-25 Time 11:33 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-04-01 Cont ID  
Sent By rmcdouga Date 2008-04-01 Time 11:34 Rev Time 0.00
Received By rmcdouga Date 2008-04-01 Time 11:34 Sent To  
Notes
2008-04-01 11:34:292004 FBC W/2007 REVISIONS
 CONVERT GARAGE TO LIVING SPACE
  
 DENIED BY BUILDING
  
 1) THE ENERGY CALCULATION FORMS DO NOT CONCUR WITH THE
 PLANS. THE PLANS SPECIFY A RAISED WOOD FLOOR WITH R-11
 INSULATION IN A PORTION OF THE GARAGE CONVERSION. THE
 PLANS SPECIFY R-30 ATTIC INSULATION AND THE FORM
 SPECIFIES R-19. THE PLANS SPECIFY R-5 INSULATION ON THE
 BLOCK WALLS AND THE FORM LISTS R-4. PLEASE CORRECT.
  
 2) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 THE ENGINEER IS REQUIRED TO REVIEW AND APPROVE THE
 PRODUCT APPROVALS IN WRITING.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-11 Cont ID  
Sent By rmcdouga Date 2008-01-11 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2008-01-11 Time 07:00 Sent To  
Notes
2008-01-11 13:58:502004 FBC W/2007 REVISIONS
 CONVERT GARAGE TO LIVING SPACE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY THE FLOOR LIVE LOAD ON THE PLANS. 2004 FBC
 R501.2 REQUIREMENTS.
 FLOOR CONSTRUCTION SHALL BE CAPABLE OF ACCOMMODATING
 ALL LOADS ACCORDING TO SECTION R301 AND OF TRANSMITTING
 THE RESULTING LOADS TO THE SUPPORTING STRUCTURAL
 ELEMENTS. SEE TABLE R301.5.
  
 4) SPECIFY THE HANGERS THAT WILL BE USED TO SUPPORT THE
 FLOOR JOIST. FBC 106.1.1* CITY AMENDMENTS.
  
 5) A 2X6 LEDGER IS SPECIFIED TO PROVIDE ATTACHMENT FOR
 THE 2 X12 FLOOR JOISTS. PLEASE EVALUATE THAT THESE WILL
 PROVIDE ADEQUATE SURFACE AREA FOR FASTENING OF THE
 JOIST HANGERS.
  
 6) SPECIFY THE REQUIRED EMBED DEPTH OF THE 3/8" TAP
 CONS THAT WILL BE USED TO ATTACH THE 2 X 6 LEDGER TO
 THE CBS WALLS. PROVIDE A SIGNED AND SEALED EVALUATION
 WITH CALCULATIONS OF THE ATTACHMENT OF THE 2 X 6 LEDGER
 TO CONCRETE BLOCK WITH 3/8" TAPCONS AT 24" O.C. AND
 THEIR CAPACITY TO SUPPORT ALL IMPOSED LOADS.FBC
 106.1.1* CITY AMENDMENTS.
  
 7) SPECIFY THE CEILING HEIGHT ON THE PLANS. SHOW
 COMPLIANCE WITHR305.1 MINIMUM HEIGHT .
 HABITABLE ROOMS, HALLWAYS, CORRIDORS, BATHROOMS, TOILET
 ROOMS, LAUNDRY ROOMS AND BASEMENTS SHALL HAVE A CEILING
 HEIGHT OF NOT LESS THAN 7 FEET (2134 MM). THE REQUIRED
 HEIGHT SHALL BE MEASURED FROM THE FINISH FLOOR TO THE
 LOWEST PROJECTION FROM THE CEILING .
  
 8)SUBMIT TWO COPIES OF ENERGY CALCUALTIONS SIGNED AND
 DATED BY THE PREPARER AND THE OWNER/AGENT AS REQUIRED
 BY FBC CHAPTER 13.
  
 10)SUBMIT 2 COPIES OF PRODUCT APPROVALS FOR THE NEW
 IN-SWING EXTERIOR DOOR. FAC RULE 9B-72.
  
 11)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS.
 THOSE PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72
 SHALL BE REVIEWED AND APPROVED IN WRITING BY THE
 DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-18 Cont ID  
Sent By btrobaug Date 2008-06-18 Time 10:29 Rev Time 0.00
Received By btrobaug Date 2008-06-18 Time 10:16 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By btrobaug Date 2008-03-26 Time 14:34 Rev Time 0.00
Received By btrobaug Date 2008-03-26 Time 13:56 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By btrobaug Date 2008-01-03 Time 15:13 Rev Time 0.00
Received By btrobaug Date 2008-01-03 Time 14:18 Sent To M
Notes
2008-01-03 15:13:01 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 ALL COMMENTS RELATE TO SHEET #2 , UNLESS OTHERWISE
 NOTED. ALL CODE ARTICLES REFERENCED ARE 2005 NEC UNLESS
 OTHERWISE NOTED.
  
 1} DUE TO THE METER LOCATION, A DISCONNECT IS REQUIRED
 PER 230.70(A) & (A)(1).
  
 2} PER 110.9 AND 110.10: OBTAIN THE AVAILABLE FAULT
 CURRENT AT THE UTILITY AND CALCULATE THE SAME AT THE
 EQUIPMENT. INDICATE THE AIC RATING FOR THE EQUIPMENT IS
 EQUAL TO OR GREATER THAN THE AVAILABLE FAULT.
  
 3} THE APPLICATION DESCRIBES THE WORK AS "CONVERTING TO
 HOME OFFICE", THE PLAN INDICATES A NEW BEDROOM. PLEASE
 CORRELATE TO INDICATE THE INTENT OF WORK.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-17 Cont ID  
Sent By adarroug Date 2008-06-17 Time 10:19 Rev Time 0.00
Received By adarroug Date 2008-06-17 Time 10:19 Sent To Z
Notes
2008-06-17 10:19:36TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 16:09 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 16:09 Sent To Z
Notes
2008-03-21 16:10:14TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-11 Cont ID  
Sent By rmcdouga Date 2008-01-11 Time 10:38 Rev Time 0.00
Received By rmcdouga Date 2007-12-31 Time 12:02 Sent To  
Notes
2007-12-31 12:02:42TO SFR ZONING

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-18 Cont ID  
Sent By tgordon Date 2008-06-18 Time 11:09 Rev Time 0.25
Received By tgordon Date 2008-06-18 Time 11:08 Sent To P
Notes
2008-06-18 11:09:43FOR CLOTHES DRYER VENT ONLY.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 15:21 Rev Time 0.30
Received By tgordon Date 2008-03-26 Time 15:21 Sent To P
Notes
2008-03-26 15:26:58*** PROVISO ***
 1) THE CLOTHES DRYER VENT MAY NOT BE MADE OF 3" PVC BUT
 MUST BE RIGID METAL AND COMPLY WITH 2004 FBC/R M1501.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By tgordon Date 2008-01-03 Time 16:18 Rev Time 0.30
Received By tgordon Date 2008-01-03 Time 16:18 Sent To P
Notes
2008-01-03 16:28:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONS, SEE 2004 FBC
 13-101.2.3.
  
 2) SHOW ON THE PLAN THE R. VALUE FOR THE INSULATION IN
 THE FLOOR JOISTS, SEE 2004 FBC 13-605.1.C.1.
  
 3) SHOW ON PLAN ATTIC INSULATION AND R. VALUE, SEE 2004
 FBC 13-604.1.C.1.
  
 4) SHOW ON PLAN THE CLOTHES DRYER VENT, SEE 2004 FBC/R
 M1501.1.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-06-20 Cont ID  
Sent By mperson Date 2008-06-20 Time 11:30 Rev Time 0.00
Received By mperson Date 2008-06-20 Time 11:30 Sent To B
Notes
2008-06-20 11:31:40******PROVISO******
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 INSTALLATION OR REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED. A PLUMBING
 PERMIT IS REQUIRED AND AN INSPECTION IS REQUIRED OF
 PLUMBING DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-27 Cont ID  
Sent By mperson Date 2008-03-27 Time 08:06 Rev Time 0.00
Received By mperson Date 2008-03-27 Time 08:06 Sent To B
Notes
2008-03-27 08:18:41PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW ON THE RESUBMITTAL TO MEET CODE
 COMPLIANCE.
  
 1. SHEET 2, ISOMETRIC SANITARY PLUMBING RISER DIAGRAM:
 THE WASHING MACHINE HORIZONTAL WASTE BRANCH NEEDS TO BE
 DOWNSTREAM OF THE WET VENTED BATHROOM GROUP. PER FBC
 PLUMBING SECTION 909.1 WET VENT PERMITTED.
 909.1 WET VENT PERMITTED.
 ANY COMBINATION OF FIXTURES WITHIN TWO BATHROOM GROUPS
 LOCATED ON THE SAME FLOOR LEVEL ARE PERMITTED TO BE
 VENTED BY A WET VENT. THE WET VENT SHALL BE CONSIDERED
 THE VENT FOR THE FIXTURES AND SHALL EXTEND FROM THE
 CONNECTION OF THE DRY VENT ALONG THE DIRECTION OF THE
 FLOW IN THE DRAIN PIPE TO THE MOST DOWNSTREAM FIXTURE
 DRAIN CONNECTION TO THE HORIZONTAL BRANCH DRAIN. ONLY
 THE FIXTURES WITHIN THE BATHROOM GROUPS SHALL CONNECT
 TO THE WET-VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE DOWNSTREAM OF THE
 WET VENT.
  
 2. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: A
 TWO-WAY CLEANOUT IS REQUIRED AT THE JUNCTION OF THE
 BUILDING DRAIN AND BUILDING SEWER. PER FBC PLUMBING
 SECTION 708.3.5. ALSO LOCATE THE CLEANOUT FOR THE
 BATHROOM LAV AT THE BASE OF THE WASTE STACK. PER FBC
 PLUMBING SECTION 708.3.4.
  
 3. SHEET 2, ISOMETRIC SANITARY RISER DIAGRAM: CLEARLY
 INDICATE THE SIZE OF THE WASHING MACHINE TRAP AND
 STANDPIPE AS BEING 2". PER FBC PLUMBING SECTION 406.3.
  
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-07 Cont ID  
Sent By mperson Date 2008-01-07 Time 08:16 Rev Time 0.00
Received By mperson Date 2008-01-07 Time 08:16 Sent To B
Notes
2008-01-07 08:38:44PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. MORE INFORMATION IS REQUIRED, PLEASE PROVIDE AN
 EXISTING FLOOR PLAN LAYOUT WITH THE LOCATION OF THE
 EXISTING LAUNDRY ROOM APPLIANCES. IF THE PROPOSED
 LOCATION OF THE WASHING MACHINE IS DIFFERENT FROM THE
 EXISTING THE FOLLOWING WILL BE REQUIRED AND NEEDS TO BE
 ADDED TO THE SANITARY RISER DIAGRAM. PER *106.1.2,
 ADDITIONAL DATA AND *701.1, SCOPE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 **INDICATE STANDPIPE FOR WASHING MACHINE.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED 4'
 A.F.F.
  
 2. SHEET 2: WITH THE REMOVAL OF THE LAUNDRY TUB (TRAY)
 THE FOLLOWING WILL BE REQUIRED.
 PER FBC-2004 PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT REQUIRED AND
 INSPECTION REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.(ADD TO NOTES)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-17 Cont ID  
Sent By choops Date 2008-06-17 Time 14:25 Rev Time 0.00
Received By choops Date 2008-06-17 Time 14:25 Sent To E
Notes
2008-06-17 14:25:45***APPROVED - RESUB #2 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 11:38 Rev Time 0.00
Received By choops Date 2008-03-26 Time 11:38 Sent To E
Notes
2008-03-26 11:39:29***APPROVED - RESUB #1 (RESTAMPED PLANS)***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status P Date 2008-01-03 Cont ID  
Sent By choops Date 2008-01-03 Time 08:32 Rev Time 0.00
Received By choops Date 2008-01-03 Time 08:32 Sent To E
Notes
2008-01-03 08:33:10***APPROVED***
  
  
  
 SENT TO "E" - METAL SF RACK