Plan Review Details - Permit 07120598
Plan Review Stops For Permit 07120598
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By shill Date 2008-01-23 Time 19:25 Rev Time 0.00
Received By shill Date 2008-01-23 Time 19:25 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2008-01-10 Cont ID  
Sent By shill Date 2008-01-10 Time 17:33 Rev Time 0.00
Received By shill Date 2008-01-10 Time 17:33 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By btrobaug Date 2008-01-17 Time 08:43 Rev Time 0.00
Received By btrobaug Date 2008-01-17 Time 08:34 Sent To P
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-28 Cont ID  
Sent By btrobaug Date 2007-12-28 Time 15:38 Rev Time 0.00
Received By btrobaug Date 2007-12-28 Time 15:38 Sent To P
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 2 Status N Date 2008-01-17 Cont ID  
Sent By mperson Date 2008-01-17 Time 13:26 Rev Time 0.00
Received By mperson Date 2008-01-17 Time 13:26 Sent To B
Notes
2008-01-17 13:27:25CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL INSPECTION.
  
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop G GAS REVIEW
Rev No 1 Status N Date 2008-01-02 Cont ID  
Sent By mperson Date 2008-01-02 Time 08:21 Rev Time 0.00
Received By mperson Date 2008-01-02 Time 08:21 Sent To B
Notes
2008-01-02 08:23:04CONTRACTOR INFORMATION
 NOTE: GAS PERMIT REQUIRED. LICENSED GAS OR PLUMBING
 CONTRACTOR TO SUBMIT PLANS WITH PERMIT APPLICATION. ALL
 GAS INSPECTIONS TO BE COMPLETE BEFORE FINAL POOL
 INSPECTION.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 10:50 Rev Time 0.00
Received By shill Date 2008-01-25 Time 10:50 Sent To Z
Notes
2008-01-25 10:50:47TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-11 Cont ID  
Sent By spalmer Date 2008-01-11 Time 17:04 Rev Time 0.00
Received By spalmer Date 2008-01-11 Time 17:04 Sent To Z
Notes
2008-01-11 17:04:27TO ZONING BOX

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-10 Cont ID  
Sent By   Date 2008-01-10 Time   Rev Time 0.00
Received By spalmer Date 2007-12-26 Time 14:20 Sent To Z
Notes
2007-12-26 14:20:07TO ZONING BOX

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-01-17 Cont ID  
Sent By mperson Date 2008-01-17 Time 13:25 Rev Time 0.00
Received By mperson Date 2008-01-17 Time 13:25 Sent To G
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By mperson Date 2008-01-02 Time 08:08 Rev Time 0.00
Received By mperson Date 2008-01-02 Time 08:08 Sent To G
Notes
2008-01-02 08:21:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE (4) ROSETTE FOUNTAINS W/ 1" SUPPLY LINES AND
 VALVES ON SHEET 1, ARE NOT INDICATED ON THE EQUIPMENT
 LAYOUT, LEGEND, OR POOL SPECIFICATIONS ON SHEET 2.
 PLEASE CORRELATE SHEET 2, WITH SHEET 1. PER SECTION
 *106.1.1 INFORMATION ON CONSTRUCTION DOCUMENTS AND PER
 SECTION *106.1.2 ADDITIONAL DATA.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 3 Status P Date 2008-01-28 Cont ID  
Sent By choops Date 2008-01-28 Time 14:03 Rev Time 0.00
Received By choops Date 2008-01-28 Time 14:03 Sent To B
Notes
2008-01-28 14:04:04***APPROVED - RESUB #2***
  
 FENCE ENCLOSURE ON PERMIT #08010166
  
  
  
 SENT TO "B" - SH

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-14 Cont ID  
Sent By choops Date 2008-01-14 Time 14:20 Rev Time 0.00
Received By choops Date 2008-01-14 Time 14:20 Sent To E
Notes
2008-01-14 14:21:49***FAILED***
  
  
 REPEAT COMMENTS:
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW. (THE "BABY
 BARRIER" DOES NOT MEET THE ZONING REQUIREMENT FOR A
 PERMANENT FENCE ENCLOSURE).
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), SECTION,
 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 NOTE:IBIS HOA MAY REQUIRE ADDITIONAL SCREENING OF
 MECHANICAL EQUIPMENT.
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By choops Date 2007-12-27 Time 09:39 Rev Time 0.00
Received By choops Date 2007-12-27 Time 09:39 Sent To E
Notes
2007-12-27 09:44:56***FAILED***
  
  
 1)AS THE SURVEY DOES NOT SHOW AN EXISTING PERMANENT
 FENCE COMPLETELY SURROUNDING THE POOL, A FENCE PERMIT
 SHALL BE SUBMITTED CONCURRENTLY AND SHALL CONFORM TO
 THE MINIMUM STANDARDS PROVIDED BELOW.
  
 PURSUANT TO THE CITY OF WEST PALM BEACH ZONING AND LAND
 DEVELOPMENT REGULATIONS (ZLDRS), SECTION,
 94-304(D)(2)(B)+(C):
 B.EVERY SWIMMING POOL SHALL BE ENCLOSED BY A FENCE
 OR SIMILAR STRUCTURE WHICH IS INSTALLED TO OBSTRUCT
 ACCESS BY PERSONS OTHER THAN THE OWNERS OR OCCUPANTS OF
 THE RESIDENCE WITHIN WHICH A SWIMMING POOL IS LOCATED.
 BARRIERS OR FENCES SHALL BE AT LEAST FOUR FEET IN
 HEIGHT ABOVE GRADE.
 C.ACCESS TO AN ACCESSORY SWIMMING POOL MUST BE
 THROUGH A BUILDING OR THROUGH A SELF-CLOSING AND
 SELF-LATCHING GATE OR THROUGH A SCREEN ENCLOSURE DOOR
 WITH LATCHES PLACED AT LEAST 54 INCHES ABOVE BOTTOM OF
 GATE. AT LEAST 90 PERCENT OF THE SURFACE AREA OF ALL
 SCREEN ENCLOSURES SHALL BE SCREENING MATERIAL THROUGH
 WHICH AIR SHALL FLOW. ALL POOLS LOCATED ON A CORNER LOT
 SHALL BE SCREENED AT THE CORNER LOT LINE BY AT LEAST A
 42-INCH HIGH LANDSCAPE BUFFER, AS MEASURED FROM GRADE,
 AT THE PROPERTY LINE, TO ENSURE PRIVACY.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED POOL
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 NOTE:IBIS HOA MAY REQUIRE ADDITIONAL SCREENING OF
 MECHANICAL EQUIPMENT.
  
 NOTE:IF A PATIO OR PAVED AREA IS PROVIDED ADJACENT
 TO OR SURROUNDING A POOL, IT SHALL BE DESIGNED TO DRAIN
 AWAY FROM THE POOL, BUT NOT ONTO ADJACENT PROPERTIES.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved