Plan Review Details - Permit 07120572
Plan Review Stops For Permit 07120572
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-12 Cont ID  
Sent By rmcdouga Date 2008-03-12 Time 16:52 Rev Time 0.00
Received By rmcdouga Date 2008-03-12 Time 16:52 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-07 Cont ID  
Sent By rmcdouga Date 2008-02-07 Time 11:33 Rev Time 0.00
Received By rmcdouga Date 2008-02-07 Time 07:02 Sent To  
Notes
2008-02-07 11:30:362004 FBC W/2007 REVISIONS
  
 RESIDENTIAL ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. SEE FBC 13-6.
  
 3)THE PRODUCT APPROVALS FOR THE STRUCTURAL MULLIONS
 THAT WERE SUBMITTED DO NOT HAVE ADEQUATE DESIGN
 PRESSURES TO BE USED BETWEEN THE SLIDING GLASS DOORS
 AND THE TRANSOM ABOVE. PLEASE CORRECT. SEE FAC RULE
 9B-72 AND FBC TABLE R301.2(2).
  
 4) THE PRODUCT APPROVAL NOA THAT WAS SUBMITTED FOR THE
 SINGLE OUTSWING DOOR IS FOR A FIXED SIDELITE AND NOT A
 DOOR. PLEASE CORRECT. FBC 106.1.1* CITY AMENDMENTS.
  
 5) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE CLAY ROOF TILES. CIRCLE THE APPROPRIATE
 ITEM ON THE NOA.FBC 106.1.1* CITY AMENDMENTS. THIS
 NEEDS TO BE SPECIFIED IN ORDER TO DETERMINE IF IT WILL
 BE ADEQUATE TO RESIST THE WINDLOADS. SEE FBC 1609.7.2.
  
 6) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION
 THAT WILL BE USED TO INSTALL THE GAF MODIFIED ROOFING.
 CIRCLE THE APPROPRIATE ITEM ON THE NOA. PROVIDE RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FOR PERIMETER AND
 CORNER AREAS. BASED ON THE RAS 117 CALCULATIONS THAT
 WERE SUBMITTED, THE WRONG FASTENING OPTION IS CIRCLED
 ON PAGE 26 OF THE NOA. THE ONE THAT IS CIRCLED IS FOR
 SCREWS AND PLATES NOT NAILS. PLEASE CORRECT. THE
 ENHANCED FASTENING SPECIFIED IN THE LETTER THAT WAS
 SUBMITTED IS NOT ADEQUATE FOR ROOF ZONE 3. BASED ON THE
 FASTENING OPTION USING RING SHANK NAILS WITH A -45 PSF
 DESIGN PRESSURE, THE SPACING WILL NEED TO BE 5" O.C.
 CENTER AT THE LAP AND 5" O.C. IN TWO ROWS IN THE FIELD
 FOR ROOF ZONE 3. PLEASE CORRECT.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-09 Cont ID  
Sent By rmcdouga Date 2008-01-09 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2008-01-09 Time 16:12 Sent To  
Notes
2008-01-09 16:54:322004 FBC W/2007 REVISIONS
  
 RESIDENTIAL ADDITION
  
 DENIED BY BUILDING
  
 1) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 2) THE WALL OF THE ADDITION IS LESS THAN 6 FEET FROM
 THE PROPERTY LINE.
 SHOW COMPLIANCE WITH R302.1 EXTERIOR WALLS AND R302.2
 OPENINGS.
 R302.1 EXTERIOR WALLS. EXTERIOR WALLS SEPARATED BY LESS
 THAN 6 FEET (1828 MM) SHALL HAVE NOT LESS THAN A
 ONE-HOUR FIRE-RESISTIVE RATING WITH EXPOSURE FROM BOTH
 SIDES. PROJECTIONS SHALL NOT EXTEND TO A POINT CLOSER
 THAN 4 FEET (1220 MM) FROM AN ADJACENT PROJECTION OR
 WALL. PROJECTIONS EXTENDING INTO THE 6-FOOT (1829 MM)
 SEPARATION DISTANCE SHALL HAVE NOT LESS THAN 1-HOUR
 FIRE-RESISTIVE CONSTRUCTION ON THE UNDERSIDE. THE ABOVE
 PROVISIONS SHALL NOT APPLY TO WALLS WHICH ARE
 PERPENDICULAR TO A LINE EXTENDING FROM THE POINT FROM
 WHICH THE SEPARATION DISTANCE HAS BEEN MEASURED RUNNING
 AND PARALLEL TO THE PROPERTY LINE.
 R302.2 OPENINGS. OPENINGS SHALL NOT BE PERMITTED IN THE
 EXTERIOR WALL OF A DWELLING OR ACCESSORY BUILDING THAT
 IS SEPARATED FROM AN ADJACENT BUILDING BY A DISTANCE OF
 LESS THAN 6 FEET (1828 MM). THIS DISTANCE SHALL BE
 MEASURED PERPENDICULAR TO THE LINE USED TO DETERMINE
 THE SEPARATION DISTANCE. NOTE: IF THE WALLS OF THE
 STRUCTURES ON THE ADJACENT PROPERTY ARE MORE THAN SIX
 FEET FROM THE WALLS OF THE ADDITION, THIS CAN BE SHOWN
 ON THE SURVEY/ SITE PLAN.
  
 3) THE PROPERTY IS LOCATED ADJACENT TO A GOLF COURSE
 AND HAS TYPE C TERRAIN FOR A DISTANCE OF 600 FEET.
 THEREFORE, THIS STRUCTURE IS EXPOSURE CATEGORY C.
 PLEASE REVISE DESIGN PARAMETERS AND COMPONENT AND
 CLADDING PRESSURES ACCORDINGLY. SEE FBCR301.2.1.4
 EXPOSURE CATEGORY. 3. EXPOSURE C. OPEN TERRAIN WITH
 SCATTERED OBSTRUCTIONS, INCLUDING SURFACE UNDULATIONS
 OR OTHER IRREGULARITIES, HAVING HEIGHTS GENERALLY LESS
 THAN 30 FEET (9144 MM) EXTENDING MORE THAN 1,500 FEET
 (457.2 M) FROM THE BUILDING SITE IN ANY QUADRANT. THIS
 EXPOSURE SHALL ALSO APPLY TO ANY BUILDING LOCATED
 WITHIN EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS
 DIRECTLY ADJACENT TO OPEN AREAS OF EXPOSURE C-TYPE
 TERRAIN IN ANY QUADRANT FOR A DISTANCE OF MORE THAN 600
 FEET (182.9 M).
  
 4) THE OWNER/AGENT IS REQUIRED TO SIGN THE ENERGY
 CALCULATION FORM. THE FORM DOES NOT LIST THE INSULATION
 IN THE WOOD FRAME WALL ADJACENT TO THE GARAGE. PLEASE
 CORRECT. SEE FBC 13-600.
  
 5) THE MINIMUM R-VALUE ALLOWED BY THE ENERGY EFFICIENCY
 CODE PRESCRIPTIVE METHOD C FOR CONCRETE BLOCK WALLS IS
 R-5. PLEASE REVISE THE WALL SECTION ON SHEET A-1. SEE
 TABLE 6C-1 ON FORM 600C-04R.
  
 6) PROVIDE A BUCK DETAIL ON THE PLANS FOR THE OVERHEAD
 GARAGE DOOR. FBC 106.1.1* CITY AMENDMENTS.
  
 7) SHOW COMPLIANCE WITH R807.1 ATTIC ACCESS.
 IN BUILDINGS WITH COMBUSTIBLE CEILING OR ROOF
 CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE PROVIDED
 TO ATTIC AREAS THAT EXCEED 30 SQUARE FEET (2.8 M 2 )
 AND HAVE A VERTICAL HEIGHT OF 30 INCHES (762 MM) OR
 GREATER.
 THE ROUGH-FRAMED OPENING SHALL NOT BE LESS THAN 22
 INCHES BY 30 INCHES (559 MM BY 762 MM) AND SHALL BE
 LOCATED IN A HALLWAY OR OTHER READILY ACCESSIBLE
 LOCATION. A 30-INCH (762 MM) MINIMUM UNOBSTRUCTED
 HEADROOM IN THE ATTIC SPACE SHALL BE PROVIDED AT SOME
 POINT ABOVE THE ACCESS OPENING.
  
 8) ROOF SHEATHING IS REQUIRED TO BE IN ACCORDANCE WITH
 SECTION R803.2.3.1 OF 2006 REVISIONS TO 2004 FBC
 RESIDENTIAL CODE. WOOD STRUCTURAL PANEL SHEATHING SHALL
 BE FASTENED TO ROOF FRAMING WITH 8D RING-SHANK NAILS AT
 6 INCHES ON CENTER AT EDGES AND 6 INCHES ON CENTER AT
 INTERMEDIATE FRAMING. SPACING OF RING-SHANK FASTENERS
 SHALL BE 4 INCHES ON CENTER IN NAILING ZONE 3 FOR 130
 MPH OR GREATER DESIGN WIND SPEEDS IN ACCORDANCE WITH
 FIGURE R803.2.3.1. PLEASE REVISE NOTES ON PLANS TO
 SPECIFY RING SHANK NAILS.
  
 9)FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 HAVE THE PRODUCT APPROVALS REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD.
  
 10) SUBMIT TWO PRODUCT APPROVALS FOR THE STRUCTURAL
 MULLIONS THAT WILL BE USED TO CONNECT TRANSOM WINDOWS
 TO DOORS. FAC RULE 9B-72.
  
 11) SUBMIT TWO CURRENT NOAS FOR THE GLASS BLOCK. THE
 ONES THAT WERE SUBMITTED ARE EXPIRED. FAC RULE 9B-72.
  
 12) SUBMIT A KEY PLAN AND INSTALLATION SCHEDULE FOR THE
 STORM PANELS. SEE ATTACHED. SPECIFY THE TYPE OF MOUNT,
 THE FASTENERS, FASTENER SPACING, EDGE DISTANCE, SPANS,
 ETC.
  
 13) SPECIFY THE ATTACHMENT METHOD THAT WILL BE USED TO
 INSTALL THE CLAY ROOF TILES. CIRCLE THE APPROPRIATE
 ITEM ON THE NOA.FBC 106.1.1* CITY AMENDMENTS.
  
 14) SPECIFY THE APPROVED ASSEMBLY AND FASTENING OPTION
 THAT WILL BE USED TO INSTALL THE GAF MODIFIED ROOFING.
 CIRCLE THE APPROPRIATE ITEM ON THE NOA. PROVIDE RAS 117
 CALCULATIONS FOR ENHANCED FASTENING FOR PERIMETER AND
 CORNER AREAS.
  
 15) THE VALUE OF THE WORK HAS BEEN ADJUSTED BASED ON
 THE LATEST ICC BUILDING VALUATION DATA. ADDITIONAL FEES
 ARE DUE.
  
 - ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By dpalmer Date 2008-03-11 Time 07:57 Rev Time 0.00
Received By dpalmer Date 2008-03-11 Time 07:57 Sent To M
Notes
2008-03-11 07:58:42 
 NEW ELECTRICALSHEETS IN SETS WHICH WERE PREVIOUSLY
 PASSED.STAMPED AND ROUTED TO OTHER TRADES

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-04 Cont ID  
Sent By dpalmer Date 2008-02-04 Time 14:04 Rev Time 0.00
Received By dpalmer Date 2008-02-04 Time 14:04 Sent To M
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By dpalmer Date 2007-12-24 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2007-12-24 Time 14:03 Sent To M
Notes
2007-12-24 14:19:15** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL PLANS CONTAIN
 THE FOLLOWING ADOPTED CODE(S) BY THE STATE.
 THE 2005 NFPA-70 IS ALREADY SHOWN.
 2002 NFPA-72
  
 2) NOTE: PLEASE THE NEW GYM WHICH IS CONSIDERED AN
 ADAPTABLE SLEEPING ROOM WILL REQUIRE SMOKE ALARMS
 INSIDE AND OUTSIDE THIS ROOM.
 PLEASE ALSO SHOW LAYOUT OF THE EXISTING DWELLING WHICH
 SHOWS ALL EXISTING SLEEPING ROOMS WITH SMOKE ALARMS
 INSIDE AND OUTSIDE ROOMS. PLEASE SHOW IF EXISTING MEETS
 NFPA-72 11.5.1.1, 11.8.3 OR NEW WILL BE INSTALLED.
 PLEASE SEE FBC R313, NFPA-72 SECTIONS GIVEN.
  
 3) NOTE: PLEASE CLARIFY PANEL SCHEDULE WHICH INDICATE A
 NEW SMALL APPLIANCE CIRCUIT> WHERE IS THIS?
 FBC 106.1.2 FOR ADDITIONAL INFORMATION.
 NEC 210.52B1
  
 4) NOTE: PLEASE SEE MISSING DISCONNECTS FOR THE AHU AND
 CU PER 440.11. THE SYMBOL AS SHOWN IS A UNIVERSAL
 SYMBOL FOR A 240V OUTLET.
 PLEASE SHOW DISCONNECTS.
  
 5) NOTE: PLEASE LIST THE NEW CIRCUIT(S) FOR
 GYM/ADAPTABLE SLEEPING ROOM WITH ARC FAULT PROTECTION
 PER 210.12.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-07 Cont ID  
Sent By adarroug Date 2008-03-07 Time 12:25 Rev Time 0.00
Received By adarroug Date 2008-03-07 Time 12:25 Sent To Z
Notes
2008-03-07 12:25:44TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 16:07 Sent To Z
Notes
2008-01-31 16:07:50TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-09 Cont ID  
Sent By rmcdouga Date 2008-01-09 Time 16:12 Rev Time 0.00
Received By rmcdouga Date 2007-12-21 Time 16:28 Sent To Z
Notes
2007-12-21 16:28:16TO SFR RACK

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By tgordon Date 2008-03-11 Time 08:43 Rev Time 0.25
Received By tgordon Date 2008-03-11 Time 08:43 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-04 Cont ID  
Sent By tgordon Date 2008-02-04 Time 14:43 Rev Time 0.25
Received By tgordon Date 2008-02-04 Time 14:43 Sent To P
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 09:35 Rev Time 0.30
Received By tgordon Date 2007-12-26 Time 09:34 Sent To P
Notes
***NONE***

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-11 Cont ID  
Sent By mperson Date 2008-03-11 Time 10:02 Rev Time 0.00
Received By mperson Date 2008-03-11 Time 10:02 Sent To B
Notes
2008-03-11 10:06:50****************PROVISO****************
 (A) 708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
 THERE SHALL BE AN APPROVED TWO-WAY CLEANOUT NEAR THE
 JUNCTION OF THE BUILDING DRAIN AND THE BUILDING SEWER.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-04 Cont ID  
Sent By mperson Date 2008-02-04 Time 16:27 Rev Time 0.00
Received By mperson Date 2008-02-04 Time 16:27 Sent To B
Notes
2008-02-04 16:34:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 NOTE: THERE IS A PLAN REVIEW COMMENT FROM THE PREVIOUS
 REVIEW THAT STILL NEEDS TO BE ADDRESSED.
  
 1. **RESPONSE NOTED, HOWEVER THE RESUBMITTED SANITARY
 RISER DIAGRAM IS NOT COMPLIANT PER *905.3, REFERENCE
 NOTE**SHEET A-3 PLUMBING PLAN AND SANITARY RISER
 DIAGRAM: VENT REQUIRED FOR THE SHOWER PER THE
 FOLLOWING.
  
 901.2.1 VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 **NOTE: THE RESUBMITTED SANITARY RISER DIAGRAM IS
 INDICATING A HORIZONTAL DRY VENT AND IS NOT COMPLIANT.
 PER FBC, PLUMBING SECTION *905.3 VENT CONNECTION TO
 DRAINAGE SYSTEM.
 EVERY DRY VENT CONNECTING TO A HORIZONTAL DRAIN SHALL
 CONNECT ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN
 PIPE.
  
 **THE INDICATED VENT ON THE DRAWINGS DOES NOT CONNECT
 ABOVE THE CENTERLINE OF THE HORIZONTAL DRAIN PIPE.
 PLEASE REFERENCE FIGURE 905.3 VENT CONNECTIONS
 INDICATING ACCEPTABLE AND UNACCEPTABLE VENT CONNECTIONS
 ATTACHED TO THESE PLUMBING COMMENTS.
  
 2. **OK, COMMENT ADDRESSED**
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mperson Date 2007-12-28 Time 16:35 Rev Time 0.00
Received By mperson Date 2007-12-28 Time 16:35 Sent To B
Notes
2007-12-28 16:46:21PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A-3 PLUMBING PLAN AND SANITARY RISER DIAGRAM:
 VENT REQUIRED FOR THE SHOWER PER THE FOLLOWING.
  
 901.2.1 VENTING REQUIRED.
 EVERY TRAP AND TRAPPED FIXTURE SHALL BE VENTED IN
 ACCORDANCE WITH ONE OF THE VENTING METHODS SPECIFIED IN
 THIS CHAPTER.
  
 2. SHEET A-3 SANITARY RISER DIAGRAM: ON THE
 UNDERGROUND SANITARY PLEASE DELETE "VENT" FOR THE
 RESUBMITTAL. PER *701.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 3 Status F Date 2008-03-10 Cont ID  
Sent By choops Date 2008-03-10 Time 14:58 Rev Time 0.00
Received By choops Date 2008-03-10 Time 14:58 Sent To E
Notes
2008-03-10 15:00:11***FAILED - RESUB #2***
  
  
 REPEAT COMMENT:
  
 1) PURSUANT TO SECTION 94-72(A)(2) OF THE ZLDRS:
  
 MINIMUM REQUIRED SETBACKS:
 FRONT = 25'
 SIDE = 5' MINIMUM WITH A TOTAL OF 15' BETWEEN THE TWO
 SIDES.
 REAR = 15' OR 10% OF LOT DEPTH, WHICHEVER IS LESS.IN
 YOUR CASE THE REAR SETBACK REQUIREMENT = 14' (10% OF
 LOT DEPTH).
  
 THE PROPOSED ADDITION DOES NOT MEET THE REAR SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-04 Cont ID  
Sent By choops Date 2008-02-04 Time 09:34 Rev Time 0.00
Received By choops Date 2008-02-04 Time 09:35 Sent To E
Notes
2008-02-04 09:38:39***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 2) PURSUANT TO SECTION 94-72(A)(2) OF THE ZLDRS:
  
 MINIMUM REQUIRED SETBACKS:
 FRONT = 25'
 SIDE = 5' MINIMUM WITH A TOTAL OF 15' BETWEEN THE TWO
 SIDES.
 REAR = 15' OR 10% OF LOT DEPTH, WHICHEVER IS LESS.IN
 YOUR CASE THE REAR SETBACK REQUIREMENT = 14' (10% OF
 LOT DEPTH).
  
 THE PROPOSED ADDITION DOES NOT MEET THE REAR SETBACK.
  
 ***THE HOA HAS NO JURISDICTION TO WAIVE THE
 REQUIREMENTS OF THE CITY'S ZONING AND LAND DEVELOPMENT
 REGULATIONS.THE REQUIRED REAR SETBACK IS 14'.THIS
 REQUIREMENT MUST BE MET OR A REQUEST FOR VARIANCE MAY
 BE APPLIED FOR THROUGH THE CITY'S PLANNING AND ZONING
 DEPARTMENT, 561-822-1435.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By rmcdouga Date 2008-01-09 Time 16:12 Rev Time 0.00
Received By choops Date 2007-12-24 Time 09:16 Sent To E
Notes
2007-12-24 09:22:09***FAILED***
  
  
 1)AN APPROVED EASEMENT CONSENT FORM FROM THE CITY OF
 WEST PALM BEACH DEPARTMENT OF PUBLIC UTILITIES (1ST
 FLOOR, CITY HALL) IS REQUIRED FOR ALL PROPOSED
 FENCES/WALLS.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZONING AND LAND DEVELOPMENT
 REGULATIONS (ZLDRS): MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
 3) PURSUANT TO SECTION 94-72(A)(2) OF THE ZLDRS:
  
 MINIMUM REQUIRED SETBACKS:
 FRONT = 25'
 SIDE = 5' MINIMUM WITH A TOTAL OF 15' BETWEEN THE TWO
 SIDES.
 REAR = 15' OR 10% OF LOT DEPTH, WHICHEVER IS LESS.IN
 YOUR CASE THE REAR SETBACK REQUIREMENT = 14' (10% OF
 LOT DEPTH).
  
 THE PROPOSED ADDITION DOES NOT APPEAR TO MEET THE REAR
 SETBACK.PLEASE INDICATE SETBACK DIMENSIONS FROM
 PROPOSED ADDITIONS TO ALL PROPERTY LINES.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - METAL RACK