| Plan Review Stops For Permit 07120563 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
N |
Date |
2008-03-27 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-27 |
Time |
10:59 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-27 |
Time |
10:59 |
Sent To |
PC |
|
| Notes |
| 2008-03-27 10:46:59 | PROCESS PLANS: |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-26 |
Time |
07:25 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-25 |
Time |
12:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-03-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-06 |
Time |
09:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-06 |
Time |
07:02 |
Sent To |
|
|
| Notes |
| 2008-03-06 09:04:00 | BUILDING PLAN REVIEW | | | PERMIT: 07120563 | | | ADD: 1400 CENTRE PARK BLVD | | | CONT: REGENCY COMMUNICATION INC. | | | TEL: (865)300-3003 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | | | | 1) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 2)OK | | | 3)OK | | | 4)OK | | | 5)OK | | | 6)OK | | | **NEW** | | | THERE ONLY SIX SHEETS SUBMITTED IN THE NEW SETS OF | | | PLANS, HOWEVER, SHEET T1 INDICATES THERE SHOULD BE | | | THIRTEEN SHEETS. THE INDESX PAGE NEEDS TO CORRESPOND | | | WITHE THE NUMBER OF PAGES SUBMITTED. CLARIFY. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-11 |
Time |
16:04 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-11 |
Time |
15:45 |
Sent To |
|
|
| Notes |
| 2008-01-11 16:04:51 | BUILDING PLAN REVIEW | | | PERMIT: 07120563 | | | ADD: 1400 CENTRE PARK BLVD | | | CONT: REGENCY COMMUNICATION INC. | | | TEL: (865)300-3003 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | | | | 1) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 2) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER | | | JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 SUPPLEMENTS. | | | | | | 3)1603.1.4 WIND DESIGN DATA. | | | THE FOLLOWING INFORMATION RELATED TO WIND LOADS SHALL | | | BE SHOWN, REGARDLESS OF WHETHER WIND LOADS GOVERN THE | | | DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM OF THE | | | BUILDING: | | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | 2. WIND IMPORTANCE FACTOR, IW , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. 3. | | | WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | 4. THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. THIS INFORMATION SHALL BE CLEARLY | | | INDICATED ON THE PLANS. PLEASE INDICATE THE EXPOSURE | | | CATEGORY #3 ABOVE. | | | | | | 4)ALL PLANS, SPECIFICATIONS, REPORTS, OR OTHER | | | DOCUMENTS PREPARED OR ISSUED BY A DESIGN PROFESSIONAL | | | AND BEING FILED FOR PUBLIC RECORD, SHALL CONTAIN THE | | | DATE, SIGNATURE AND SEAL OF THE DESIGN PROFESSIONAL. | | | ENGINEERS SHALL LEGIBLY INDICATE THEIR NAME, ADDRESS | | | AND LICENSE NUMBER ON EACH SHEET. SHEET T1 IS MISSING | | | THE DATE SEAL AND SIGNATURE OF THE ENGINEER. THE SEAL | | | OF P.E MARTIN H. SAHN IS NOT LEGIBLE ON THE SHEETS. | | | F.A.C 61G15-23.002 | | | | | | 5)THE ADDRESS ON THE PLAN FOR MACTEC ENGINEERING AND | | | CONSULTING, INC. NEEDS TO CORRESPOND WITH THE DBPR | | | WEBSITE. SEE INFORMATION SHEET ATTACH. | | | | | | 6)6)NOTE: THIS PROJECT APPEARS HAVE MORE WORK THAN | | | THE PROJECT AT 1400 CENTRE PARK BLVD, HOWEVER, THE | | | VALUE IS THE SAME. THE CLAIMED VALUATION ON THE PERMIT | | | APPLICATION IS LOW. FOR PERMITTING PURPOSES, VALUATION | | | OF BUILDINGS AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT | | | COST EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS | | | ICC (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS | | | SERVICES PER 108.3 FBC* | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-03-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-17 |
Time |
18:33 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-17 |
Time |
18:33 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-03-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-04 |
Time |
20:19 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-04 |
Time |
20:13 |
Sent To |
|
|
| Notes |
| 2008-03-04 20:20:09 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED FOR | | | ALL OLD/VOIDED SHEETS TO BE REMOVED FROM SETS AND | | | INSERT NEW SHEETS INTO COMPLETED SETS FOR REVIEW AND | | | STAMPING. | | | PLEASE CALL TO SET UP A TIME TO MAKE PLANS INTO | | | COMPLETE SETS FOR REVIEW AND STAMPING. | | | | | | | | | ** INCORRECT ADDRESS WAS PLACED ON RE-SUB SHEET. | | | ADDRESS FOR PROJECT IS NOT ON | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-23 |
Time |
12:12 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-23 |
Time |
12:12 |
Sent To |
|
|
| Notes |
| 2007-12-23 12:12:36 | ** DENIEDREVIEW ** | | | | | | 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE | | | NEEDED AS FOLLOWS | | | 2004 FBC W/2007 REVISIONS | | | 2005 NFPA-70 | | | | | | 2) NOTE: PLEASE SEE SHEET T-I IN BOTH SETS ARE NOT | | | SIGNED, DATED AND SEALED AS REQUIRED PER FS 481.221, | | | 471.025, FAC 61G15-23.002 | | | | | | 3) NOTE: PLEASE SEE THERE ARE TWO PROJECTS SUBMITTED BY | | | THE SAME CONTRACTOR FOR SOME OF THE SAME SCOPE OF WORK | | | HOWEVER THE ACTUAL WORK INVOLVED IN MORE ON ONE PROJECT | | | INCLUDING LARGER EQUIPMENT. HOW IS IT THAT THE VALUE | | | FOR THE SCOPE OF WORK AND EQUIPMENT IS BEING SHOWN THE | | | SAME ON BOTH PROJECTS? | | | PLEASE SEE FBC 108.3 AS VALUE SHALL INCLUDE ALL LABOR, | | | MATERIALS, EQUIPMENT, AND DESIGN COST ETC EVEN IF ANY | | | IS OWNER SUPPLIED. | | | PLEASE SUBMIT SIGNED CONTRACT SHOWING AND INCLUDING | | | ALL. | | | THIS NOTE WILL ALSO BE PLACED ON OTHER APPLIED PERMIT | | | SCOPE #07120563 | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-26 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-26 |
Time |
11:50 |
Sent To |
B1 |
|
| Notes |
| 2008-03-26 11:55:02 | *****APPROVED***** | | | | | | | | | PLAN SHEETS C-2 AND E-2 WERE STAMPED, INITIALED, AND | | | DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-03-12 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-12 |
Time |
15:44 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-12 |
Time |
15:26 |
Sent To |
|
|
| Notes |
| 2008-03-12 15:38:39 | *****FIRE STAMPING NEEDED***** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;HOWEVER THE APPROPIATE PLAN SHEET(S) | | | TO BE FIRE-STAMPED WHEN THE OTHER REVIEWERS HAVE BEEN | | | SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-25 |
Time |
10:23 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-25 |
Time |
10:10 |
Sent To |
|
|
| Notes |
| 2008-01-25 10:19:25 | *****DENIED***** | | | | | | | | | 1.NO ELECTRICAL CONDUITS SHALL ENTER ANY OF THE | | | REQUIRED EXIT STAIRTOWERS.PLEASE PROVIDE A NOTE ON | | | THE PLANS THAT NO CONDUITS SHALL BE CHASED THROUGH ANY | | | EXIT STAIRTOWER EITHER VERTICALLY OR HORIZONTALLY. | | | | | | 2.ANY PROPOSED INSTALLATION OF EQUIPMENT SHALL NOT | | | INTERFERE WITH ANY EXISTING FIRE PROTECTION SYSTEMS OR | | | DEVICES. | | | | | | 3.ANY EQUIPMENT INSTALLED ON THE ROOF SHALL NOT | | | INTERFERE ANY STANDPIPE ROOF MANIFOLDS. | | | | | | 4.ALL CONSTRUCTION, DEMOLITION, AND RENOVATION WORK | | | TO COMPLY WITH NFPA 241. | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-14 |
Time |
13:24 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-14 |
Time |
13:24 |
Sent To |
|
|
| Notes |
| 2008-03-20 08:59:53 | TO "COMM" BD#11 | | 2008-03-14 13:36:08 | WAITING FOR "COMM" BD |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-02-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-27 |
Time |
11:46 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-27 |
Time |
11:46 |
Sent To |
|
|
| Notes |
| 2008-02-27 11:49:02 | TO "COMM" BD#15 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-25 |
Time |
10:10 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-21 |
Time |
16:47 |
Sent To |
|
|
| Notes |
| 2007-12-21 16:47:34 | SENT TO COMMERICAL BOARD # 52 MMILLER |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2008-03-03 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2008-03-03 |
Time |
14:31 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
eschneid |
Date |
2007-12-27 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
eschneid |
Date |
2007-12-27 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2007-12-27 10:41:51 | FAILED | | | | | | 1) THE INSTALLATION OF A NEW CABINET IN THE NEW | | | LOCATION REQUIRES THE APPROVAL OF AN INFORMAL SITE PLAN | | | REVIEW BY THE PLANNING AND ZONING DEPARTMENT. | | | | | | 2) THE HEIGHT OF THE CABINET AS WELL AS GROUND LEVEL | | | SCREENING OF THE CABINET WILL BE REQUIRED. | | | | | | CONTACT ERIC SCHNEIDER @ (561) 822-1435. |
|
|