Plan Review Details - Permit 07120540
Plan Review Stops For Permit 07120540
Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-30 Cont ID  
Sent By btrobaug Date 2008-01-30 Time 17:18 Rev Time 0.00
Received By btrobaug Date 2008-01-30 Time 17:01 Sent To FIRE
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By adarroug Date 2008-01-24 Time 11:10 Rev Time 0.00
Received By btrobaug Date 2007-12-27 Time 11:05 Sent To FIRE
Notes
2007-12-27 11:08:37 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
 IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471
 FS, RESPECTIVELY.
 THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL
 IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES,
 IF EXEMPTIONS APPLY.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 WILLIAM R. TROBAUGH
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 561/805-6718
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-31 Cont ID  
Sent By mawillia Date 2008-01-31 Time 16:15 Rev Time 0.00
Received By mawillia Date 2008-01-31 Time 16:09 Sent To E
Notes
2008-01-31 16:14:34*****APPROVED******
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEET FA-1 STAMPED, INITIALED,
 AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mwennerg Date 2007-12-28 Time 15:07 Rev Time 0.00
Received By mwennerg Date 2007-12-28 Time 15:07 Sent To  
Notes
2007-12-28 15:16:38***DENIED***
  
 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY
 DESIGN PROFESSIONAL.
  
 2) WORK SHALL COMPLY WITH NFPA 101, SEC. 7.2.1.6.2
 REGARDING ACCESS CONTROLLED EGRESS DOORS.
  
 3) HOW WILL EXIT DOORS OPERATE REGARDING EGRESS DURING
 A FIRE ALARM?
  
 4) WHAT FAILSAFE MECHANISM IS PROVIDED SHOULD THERE BE
 A LOSS OF POWER?
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2008-01-24 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-01-24 Time 11:11 Sent To E
Notes
2008-01-24 11:11:30TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-24 Cont ID  
Sent By adarroug Date 2007-12-28 Time 11:10 Rev Time 0.00
Received By adarroug Date 2007-12-21 Time 10:05 Sent To E
Notes
***NONE***