Plan Review Details - Permit 07120540
| Plan Review Stops For Permit 07120540 |
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-01-30 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-01-30 |
Time |
17:18 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-01-30 |
Time |
17:01 |
Sent To |
FIRE |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-24 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-27 |
Time |
11:05 |
Sent To |
FIRE |
|
| Notes |
| 2007-12-27 11:08:37 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST | | | PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. | | | IF AN ARCHITECT OR ENGINEER, COMPLY WITH 481 AND 471 | | | FS, RESPECTIVELY. | | | THE CONTRACTOR OF RECORD MAY BE THE DESIGN PROFESSIONAL | | | IF EXEMPTIONS UNDER CHAPTER 471.003, FLORIDA STATUTES, | | | IF EXEMPTIONS APPLY. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | WILLIAM R. TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-31 |
Time |
16:15 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-31 |
Time |
16:09 |
Sent To |
E |
|
| Notes |
| 2008-01-31 16:14:34 | *****APPROVED****** | | | | | | ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;PLAN SHEET FA-1 STAMPED, INITIALED, | | | AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-12-28 |
Time |
15:07 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-12-28 |
Time |
15:07 |
Sent To |
|
|
| Notes |
| 2007-12-28 15:16:38 | ***DENIED*** | | | | | | 1) PLANS ARE REQUIRED TO BE SIGNED, SEALED AND DATED BY | | | DESIGN PROFESSIONAL. | | | | | | 2) WORK SHALL COMPLY WITH NFPA 101, SEC. 7.2.1.6.2 | | | REGARDING ACCESS CONTROLLED EGRESS DOORS. | | | | | | 3) HOW WILL EXIT DOORS OPERATE REGARDING EGRESS DURING | | | A FIRE ALARM? | | | | | | 4) WHAT FAILSAFE MECHANISM IS PROVIDED SHOULD THERE BE | | | A LOSS OF POWER? | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-24 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-24 |
Time |
11:11 |
Sent To |
E |
|
| Notes |
| 2008-01-24 11:11:30 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-28 |
Time |
11:10 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-21 |
Time |
10:05 |
Sent To |
E |
|
| Notes |
|
|
|
Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved |
 |
 |