| 2007-12-26 10:10:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | PLUMBING PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE PROPOSED NEW GREASE INTERCEPTOR SHALL BE |
| | APPROVED PER THE FOLLOWING. |
| | PER MUNICIPAL CODE ARTICLE III SECTION 90-124, THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR SHALL BE SIZED AND |
| | LOCATED BY ENVIRONMENTAL COMPLIANCE DIVISION OF THE |
| | UTILITY DEPARTMENT. PLEASE CONTACT RODNEY COMPO, PHONE: |
| | (561) 822-2272, E-MAIL: [email protected] OR CLAVIN |
| | WILLIAMS, PHONE: (561) 822-2284, E-MAIL: |
| | [email protected]. THEIR FAX NUMBER IS (561) 822-2287. |
| | NOTE: WRITTEN APPROVAL IS REQUIRED OF THE |
| | EXISTING/PROPOSED GREASE INTERCEPTOR FROM ENVIRONMENTAL |
| | COMPLIANCE BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2. SHEET 1.0A, GREASE TRAP DETAIL: THE INLET PIPING |
| | SHALL EXTEND 24" BELOW THE SURFACE. PER *1003.5.3, |
| | INLET AND OUTLET PIPING. |
| | |
| | 3. SHEET 1.0A, GREASE TRAP DETAIL: MINIMUM SIZE OF |
| | MANHOLE WITH LID SHALL BE 24". PER APPROVED "THE CITY |
| | OF WEST PALM BEACH, STANDARD GREASE TRAP DETAIL". |
| | **PLEASE REFERENCE THE APPROVED "THE CITY OF WEST PALM |
| | BEACH, STANDARD GREASE TRAP DETAIL" ATTACHED TO THESE |
| | PLUMBING COMMENTS FOR REFERENCE FOR THE RESUBMITTAL. |
| | |
| | 4. SHEET 1.0A, SANITARY ISOMETRIC RISER DIAGRAM: THE |
| | INLET AND OUTLET PIPING SHALL HAVE A TWO-WAY CLEANOT |
| | TEE INSTALLED. PER *1003.5.3, INLET AND OUTLET PIPING. |
| | **THE INLET PIPING IS MISSING THE REQUIRED TWO-WAY |
| | CLEANOUT AND THE LOCATION OF THE OUTLET TWO-WAY |
| | CLEANOUT SHOULD BE CLOSER TO THE GREASE TRAP. |
| | |
| | 5. PER FS 713.13 (1) THRU (6): A NOTICE OF |
| | COMMENCEMENT IS REQUIRED FROM THE - PALM BEACH COUNTY |
| | COURTHOUSE - 4TH FLOOR RECORDING DEPT. 205 N. DIXIE |
| | HWY., BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |