Plan Review Details - Permit 07120526
Plan Review Stops For Permit 07120526
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By shill Date 2008-01-03 Time 10:32 Rev Time 0.00
Received By shill Date 2008-01-03 Time 09:53 Sent To  
Notes
2008-01-03 09:57:03****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A DETAIL FOR THE SLAB AND ANCHORING,
 FBC1609.1.3.PREFAB SLABS REQUIRE ENGINEERING.
  
 2.THIS PARCEL IS IN A FLOOD ZONE.WPB ADMIN CODE
 94-546(B) REQUIRES THAT THE TOP OF SLAB BE 6" ABOVE
 BFE.A FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED. (INFORMATIONAL)

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By btrobaug Date 2007-12-28 Time 10:53 Rev Time 0.00
Received By btrobaug Date 2007-12-28 Time 10:40 Sent To G
Notes
2007-12-28 10:51:11 
  
 THIS WORK WAS DONE AD CLOSED ELECTRICALLY UNDER PERMIT
 NUMBER 07010978 AND WILL PASS WHEN ZONING ISSUE IS
 RESOLVED./WRT.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-31 Cont ID  
Sent By mperson Date 2007-12-31 Time 09:14 Rev Time 0.00
Received By mperson Date 2007-12-31 Time 09:14 Sent To B
Notes
2007-12-31 09:24:41PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE GEN/RES
 PERMIT APPLICATION HAS BEEN APPROVED BY ZONING FOR THE
 GENERATOR LOCATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-03 Cont ID  
Sent By shill Date 2008-01-03 Time 09:57 Rev Time 0.00
Received By shill Date 2007-12-20 Time 17:36 Sent To Z
Notes
2007-12-20 17:37:04SENT TO ZONING INBOX

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 13:06 Rev Time 0.20
Received By tgordon Date 2007-12-26 Time 13:06 Sent To E
Notes
2007-12-26 13:10:15PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SEE ZONING REVIEW NOTES, PLEASE CORRECT.
  
 2) PLEASE SUBMIT DETAILED MANUFACTURER'S
 SPECIFICATION'S AND INSTALLATION INSTRUCTIONS FOR
 GENERATOR.
  
 3) PLEASE BE ADVISED.PER 2004 FBC, FUEL GAS - POWERED
 EQUIPMENT PERMANENTLY INSTALLED EQUIPMENT POWERED BY
 INTERNALCOMBUSTION ENGINES SHALL BE INSTALLED IN
 ACCORDANCE WITH MANUFACTURER'S INSTALLATION
 INSTRUCTIONS AND NFPA 37.NFPA 37 INSTALLATION &
 USE OF STATIONARY COMBUSTION ENGINES & GAS TURBINES:
 4.1.4ENGINES (GENERATORS) LOCATED OUTDOORS SHALL BE
 MINIMUM OF 5 FT FROM OPENINGS IN WALLS & AT LEAST 5 FT
 FROM STRUCTURES HAVING COMBUSTIBLE WALLS.A MINIMUM
 CLEARANCE IS NOT REQUIRED WHEN (1) THE ADJACENT WALL
 HAS A MINIMUM FIRE RESISTANCE RATING OF 1 HOUR OR (2)
 THE WEATHERPROOF ENCLOSURE IS CONSTRUCTED OF
 NON-COMBUSTIBLE MATERIALS, AND IT HAS BEEN DEMONSTRATED
 THAT A FIRE WITHIN THE ENCLOSURE WILL NOT IGNITE
 COMBUSTIBLE
 MATERIALS OUTSIDE THE ENCLOSURE. INFORMATIVE: A.8.2.3.1
 EXHAUST SYSTEMS SHOULD NOT TERMINATE UNDER STRUCTURES
 OR
 WHERE THE EXHAUST MIGHT BE DRAWN INTO THE VENTILATION
 INTAKES.
 2004 FMC 804.3.5 #3, WHERE THE TERMINATION IS
 LOCATED BELOW AN ADJACENT ROOF STRUCTURE, THE
 TERMINATION POINT
 SHALL BE LOCATED AT LEAST 3 FT FROM THE ROOF
 STRUCTURE.
 PLEASE NOTE, WHILE ZONING ALLOWS MECHANICAL
 EQUIPMENT TO ENCROACH 4 FT INTO THE REQUIRED SETBACK,
 GENERATORS SHALL MAINTAIN THE REQUIRED ABOVE MENTIONED
 CLEARANCES TO THE ADJACENT PROPERTY STRUCTURES, I.E.
 FENCE, BUILDING, WINDOWS, DOORS, OR OPENINGS.
 FOLLOW MANUFACTURER'S RECOMMENDED CLEARANCES
 AROUND EQUIPMENT FOR SERVICING,AND PROVIDE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS AT THE JOBSITE
 FOR THE FIELD INSPECTOR. .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By shill Date 2008-01-03 Time 09:57 Rev Time 0.00
Received By choops Date 2007-12-26 Time 09:30 Sent To E
Notes
2007-12-26 09:39:39***FAILED***
  
  
 1)PROPOSED GENERATOR LOCATION DOES NOT MEET MINIMUM
 REQUIRED SETBACKS.PURSUANT TO SECTION 94-305(B)(4) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS: MECHANICAL
 EQUIPMENT MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED
 SETBACK.AS THE REQUIRED REAR SETBACK FOR THE HOME IS
 15', THIS YIELDS A MINIMUM REAR SETBACK OF 11' TO THE
 GENERATOR.
  
 THERE ARE A FEW DIFFERENT ROUTES YOU CAN TAKE WITH
 THIS:
  
 1)MOVE THE GENERATOR TO MEET THE MINIMUM REQUIRED
 SETBACKS.
  
 2)APPLY FOR A VARIANCE FROM THE DIMENSIONAL
 REQUIREMENT. (THIS IS A FEW MONTH PROCESS AND I THINK
 COSTS AROUND $1000)
  
 3)THE CITY IS CONSIDERING REVISING THIS REGULATION.
 IT WOULD BE 3-4 MONTHS BEFORE THIS WOULD TAKE EFFECT.
  
 IF YOU WOULD LIKE TO DISCUSS THIS FURTHER, PLEASE DON'T
 HESITATE TO CALL.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720