Plan Review Details - Permit 07120512
Plan Review Stops For Permit 07120512
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 13:30 Rev Time 0.00
Received By shill Date 2008-01-08 Time 13:30 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-02 Cont ID  
Sent By shill Date 2008-01-02 Time 14:37 Rev Time 0.00
Received By shill Date 2008-01-02 Time 14:37 Sent To  
Notes
2008-01-02 14:38:42****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 FROM PREVIOUS LIST:
  
 1.)CHANGES TO THE ISSUED PERMIT ARE TO BE SUBMITTED
 AS REVISIONS TO THE PRIMARY PERMIT.THE METAL ROOF
 ISSUED WITH THE PERMIT WAS FOR BEMO 305 ALUMINUM
 STANDING SEAM.YOUR APPLICATION STATES "SERIES 2000"
 BUT NO PAPERWORK WAS SUBMITTED.
  
 2.)PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 FOR EACH ROOF SYSTEM, FAC9B72.THIS IS IN ADDITION TO
 THE EVALUATION REPORT (NOA).WWW.FLORIDABUILDING.ORG
  
 3.)ADDRESSED.
  
 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD PRIOR TO SUBMITTAL, FBC*106.3.3.
  
 THIS WAS DONE FOR THE METAL ROOF BUT NOT FOR THE BUILT
 UP ROOF.
  
 5.)ADDRESSED.
  
 6.)SEE GENERAL LIMITATION #7 OF THE JOHNS MANVILLE
 BUR.ENHANCED FASTENING CALCS ARE TO BE PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT.
 PRESSURES SPECIFIED BY THE ENGINEER FOR THIS PROJECT
 ARE -47, -79, -119 FOR ZONES 1, 2, AND 3 RESPECTIVELY.
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-20 Cont ID  
Sent By shill Date 2007-12-20 Time 15:06 Rev Time 0.00
Received By shill Date 2007-12-20 Time 15:06 Sent To  
Notes
2007-12-20 15:25:27****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
  
  
 1.)CHANGES TO THE ISSUED PERMIT ARE TO BE SUBMITTED
 AS REVISIONS TO THE PRIMARY PERMIT.THE METAL ROOF
 ISSUED WITH THE PERMIT WAS FOR BEMO 305 ALUMINUM
 STANDING SEAM.YOUR APPLICATION STATES "SERIES 2000"
 BUT NO PAPERWORK WAS SUBMITTED.
  
 2.)PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL
 FOR EACH ROOF SYSTEM, FAC9B72.THIS IS IN ADDITION TO
 THE EVALUATION REPORT (NOA).WWW.FLORIDABUILDING.ORG
  
 3.)PROVIDE PRODUCT APPROVAL FOR THE METAL ROOF.
  
 4.)PRODUCT APPROVALS ARE TO BE REVIEWED BY DESIGNER
 OF RECORD PRIOR TO SUBMITTAL, FBC*106.3.3.
  
 5.)FOR THE LOW SLOPE ROOF, INDICATE WHICH APPROVED
 ASSEMBY YOU WILL BE USING.
  
 6.)SEE GENERAL LIMITATION #7 OF THE JOHNS MANVILLE
 BUR.ENHANCED FASTENING CALCS ARE TO BE PREPARED BY AN
 ARCHITECT, ENGINEER, OR REGISTERED ROOF CONSULTANT.
 PRESSURES SPECIFIED BY THE ENGINEER FOR THIS PROJECT
 ARE -47, -79, -119 FOR ZONES 1, 2, AND 3 RESPECTIVELY.
  
  
 7.)IF THE METAL ROOF HAS DIFFERENT FASTENING OPTIONS,
 PLEASE INDICATE WHICH SYSTEM YOU WILL BE USING.IF
 ENGINEERING IS REQUIRED, PLEASE SUBMIT.