Plan Review Details - Permit 07120497
Plan Review Stops For Permit 07120497
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-07-18 Cont ID  
Sent By mjacobs Date 2008-07-18 Time 11:10 Rev Time 0.00
Received By mjacobs Date 2008-07-18 Time 09:02 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-20 Cont ID  
Sent By mjacobs Date 2008-02-20 Time 07:42 Rev Time 0.00
Received By mjacobs Date 2008-02-19 Time 15:35 Sent To  
Notes
2008-02-20 07:41:56 
 BUILDING PLAN REVIEW
 PERMIT: 07120497
 ADD: 1661 WORTHINGTON RD. #100
 CONT: A CUSTOM ELECTRIC.
 TEL: (561)868-6809
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 2-20-08
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)OK
 1C)OK
  
 1D) INFORMATIONAL:FL S S 713.13 NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLY COMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS.
  
 2)OK
  
 3) ENGINEERING CALCULATIONS SUBMITTED FROM PROTEK
 ENGINEERING ALSO INCLUDE CALCULATIONS FOR THE MOMENT OF
 OVERTURNING BUT NOT AGAINST SLIDING AS FOUND IN
 1609.1.3 ANCHORAGE AGAINST OVERTURNING, UPLIFT AND
 SLIDING. PLEASE PROVIDE THE CALCULATIONS FOR SLIDING,
 CO-EFFICIENT OF FRICTION OR PROVIDE CALCULATIONS FOR
 ANCHORS. THE ENGINEER OF RECORD IS RESPONSIBLE FOR THE
 ANCHORAGE OF THE GENERATORS.
 4) THE ELEVATION CERTIFICATE IS SET FOR 13?-0? WHICH IS
 6? TO LOW, THE CITY IS MORE RESTRICTIVE WITH AN
 ADDITIONAL 6? SEE.HOW CAN THE ELEVATION CERTIFICATE
 BE COMPLETED BEFORE THE GENERATOR IS INSTALLED?
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By jwitmer Date 2008-01-04 Time 16:23 Rev Time 1.33
Received By jwitmer Date 2008-01-04 Time 16:23 Sent To  
Notes
2008-01-04 16:49:51BUILDING PLAN REVIEW
 PERMIT: 07120497
 ADD: 1661 WORTHINGTON RD
 CONT: FL CUSTOM ELECTRIC SOLUTION
 TEL: (954)868-6809
 FL BLD CODE= 2004 FLORIDA BUILDING CODE W/ 2007 FBC
 REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B) INFORMATIONAL: PLEASE SUBMIT 2 OF ALL SURVEYS,
 PLANS, REPORTS, REVISIONS , PRODUCT APPROVALS AND OR
 SUBMITTALS FOR REVIEW FOR PERMIT. IF YOUR PROJECT WILL
 REQUIRE A RESIDENT INSPECTOR OR IF YOUR PROJECT IS A
 THRESHOLD BUILDING REQUIRING A THRESHOLD INSPECTOR THEN
 (3) THREE SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED
 FOR PERMIT ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTS
 WEST PALM BEACH ADMINISTRATIVE CODE.
  
 1C)INFORMATIONAL: 106.1.1* W.P.B. ADMINISTRATIVE
 CODE/2004 DRAWINGS & SPECIFICATIONS SHALL CONTAIN
 INFORMATION, IN THE FORM OF NOTES OR OTHERWISE, AS TO
 THE QUALITY OF MATERIALS, WHERE QUALITY IS ESSENTIAL TO
 CONFORMITY WITH THE TECHNICAL CODES. SUCH INFORMATION
 SHALL BE SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE
 CITED AS A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR
 ITS EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D INFORMATIONAL:) FL S S 713.13NOTICE OF
 COMMENCEMENT, TO BE FILED WITH THE CLERK OF THE COURT.
 NOTE: 713.13(2) IF THE WORK DESCRIBED IN THE NOTICE OF
 COMMENCEMENT IS NOT ACTUALLYCOMMENCED WITHIN 90 DAYS
 AFTER THE RECORDING THEREOF, SUCH NOTICE IS NULL &
 VOID. NOTE: 713.13(6) THE POSTING OF THE NOTICE OF
 COMMENCEMENT AT THE CONSTRUCTION SITE BEFORE THE FIRST
 INSPECTION.
  
 1E)PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) ENGINEERING CALCULATIONS FOR THE GENERATOR ARE FOR A
 400 KW GENERATOR AND FOUNDATION , THE PERMIT
 APPLICATION INDICATES THAT A 500 KW GENERTOR IS BEING
 INSTALLED, PLEASE VERIFY AND MAKE CORRECTIONS WHERE
 NEEDED. 106.1.2
 ADDITIONAL INFORMATION IS REQUIED.
  
 3) ENGINEERING CALCULATIONS SUBMITTED FROM PROTEK
 ENGINEERING ALSO INCLUDE CALCULATIONS FOR THE MOMENT OF
 OVERTURNING BUT NOT AGAINST SLIDDING AS FOUND IN
 1609.1.3 ANCHORAGE AGAINSTOVERTURNING, UPLIFT AND
 SLIDDING. PLEASE PROVIDE THE CALCULATIONS
 FOR SLIDDING , CO-EFFICIENT OF FRICTION OR PROVIDE
 CALCULATIONS FOR ANCHORS.
  
 4) THE ELEVATION CERTIFICATE IS SET FOR 13'-0" WHICH IS
 6 INCHES TO LOW, THE CITY IS MORE RETRICTIVE WITH AN
 ADDITIONAL 6" SEE ATTACHMENT.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  

Review Stop E ELECTRICAL
Rev No 5 Status N Date 2009-03-26 Cont ID  
Sent By dpalmer Date 2009-03-26 Time 08:26 Rev Time 0.00
Received By dpalmer Date 2009-03-26 Time 08:26 Sent To  
Notes
2009-03-26 08:27:39THE REVISED E-1 WAS REVISED FOR LANDSCAPE CHANGES ONLY.
 NO REVIEW DONE FOR ELECTRICAL.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2009-03-12 Cont ID  
Sent By dpalmer Date 2009-03-12 Time 15:31 Rev Time 0.00
Received By dpalmer Date 2009-03-12 Time 15:31 Sent To PC
Notes
2009-03-12 15:32:43LETTER FROM ENGINEER REVISING ENCLOSURE FROM ALUM TO
 STEEL

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 14:29 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 14:29 Sent To  
Notes
2008-07-03 14:29:50NEW REVISED ELECTRICAL PLANS WERE PLACED INTO SETS.
 OLD/VOIDED SHEETS WERE NOT REMOVED.

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By dpalmer Date 2008-02-09 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2008-02-09 Time 08:50 Sent To  
Notes
2008-02-11 08:50:38** REDLINED PLANS ***
 SIGNAGE PER 230.2E, 702.8
 SCOPE OF WORK FOR DISCONNECT NOTES TO BE INSTALLED BY
 GENERAL CONTRACTOR HOWEVER PER STATE AND LOCAL
 LICENSING, A GC MAY NOT INSTALL ELECTRICAL EQUIPMENT
 THIS IS REQUIRED TO BE DONE BY THE ELECTRICAL
 CONTRACTOR. THIS IS NOTED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 12:41 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 12:41 Sent To  
Notes
2007-12-23 12:41:46** DENIEDREVIEW **
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70
 2002 NFPA-110
  
 2) NOTE: PLEASE SEE FBC 108.3 AS VALUE SHALL INCLUDE
 ALL LABOR, MATERIALS, EQUIPMENT, AND DESIGN COST ETC
 EVEN IF ANY EQUIPMENT OR OTHER ITEMS ARE OWNER
 SUPPLIED.
 PLEASE ADJUST VALUE.
  
 3) NOTE: PLEASE VERIFY SCOPE AND SIZE OF GENERATOR UNIT
 BEING INSTALLED AS THE PERMIT APPLICATION STATES 500KW
 AND ELECTRICAL PLANS AS WELL AS THE STRUCTURAL
 CALCULATIONS INDICATE 400KW.?
 AS THESE ARE BOTH DIFFERENT MINIMUM CODE COMPLIANCE AS
 SHOWN ON PLANS NOT BE VERIFIED. IF UNIT IS 500KW MANY
 ITEMS ON ELECTRICAL PLANS WILL CHANGE.
 240.4, 310.16, ETC
 FBC 106.1.2, 106.3.5.1.2 FOR COORDINATION AND
 ADDITIONAL INFORMATION.
  
 4) NOTE: PLEASE SEE COMMENTS FROM OTHER TRADES FOR SIZE
 OF FUEL TANK TO BE SPECIFIC.
 PLEASE BE SURE THE MANUFACTURE SPECS/CUTS SHEETS
 APPLIED TO PLANS CONTAINS ALL MINIMUM CLEARANCES.
 PLEASE SEE 110.3, 90.7 AS THESE WILL BE REQUIRED TO BE
 ON PLANS OR SUPPORTING DOCUMENTATION TO BE SUBMITTED.
  
 5) NOTE: PLEASE SEE MISSING DISCONNECT PER
 225.31-225.39, 702.11.
 PLEASE KNOW AS ZONING REVIEW WILL REQUIRED AN CLOSURE
 AROUND UNIT AND BASED ON PLANS THE MEANS OF DISCONNECT
 WILL NOT BE READILY AVAILABLE.
 PLEASE KNOW THE DISCONNECTING MEANS WILL NOT REQUIRE
 OVER CURRENT PROTECTION ONLY A RATED DISCONNECT FOR
 FEEDERS COMING INTO BUILDING.
 PLEASE SEE 225.34, 702.8 AND PLACE NOTES ON PLANS
 ACCORDINGLY.
  
 ** PLEASE SEE COMMENTS FROM OTHER TRADES WHICH WILL
 HAVE AN AFFECT ON ALL PLANS AND PROJECT AS SUBMITTED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-07-08 Cont ID  
Sent By mwennerg Date 2008-07-08 Time 14:29 Rev Time 0.00
Received By mwennerg Date 2008-07-08 Time 14:29 Sent To  
Notes
2008-07-08 14:29:55NEW SHEET E-1 STAMPED

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-25 Cont ID  
Sent By mawillia Date 2008-02-25 Time 11:15 Rev Time 0.00
Received By mawillia Date 2008-02-25 Time 10:59 Sent To  
Notes
2008-02-25 11:09:17*****APPROVED*****
  
 PLAN SHEET E-1 STAMPED, INTIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-24 Cont ID  
Sent By mawillia Date 2008-01-24 Time 13:49 Rev Time 0.00
Received By mawillia Date 2008-01-24 Time 13:04 Sent To  
Notes
2008-01-24 13:47:54*****UNSAT*****
  
 1.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH ACCESS TO AND/OR EGRESS FROM OTHER AREAS OF THE
 BUILDING OR PROPERTY.
  
 2.PLEASE INDICATE FOR THE NEW GENERATOR AS TO WHETHER
 IT IS FOR EMERGENCY USE AND/OR STANDBY POWER FOR THE
 FIRE PROTECTION SYSTEM AND FEATURES.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FUEL DIESEL GENERATOR
Rev No 3 Status P Date 2008-06-30 Cont ID  
Sent By rregueir Date 2008-06-30 Time 14:55 Rev Time 0.00
Received By rregueir Date 2008-06-30 Time 14:51 Sent To  
Notes
***NONE***

Review Stop FUEL DIESEL GENERATOR
Rev No 2 Status F Date 2008-03-04 Cont ID  
Sent By rregueir Date 2008-03-04 Time 15:55 Rev Time 0.00
Received By rregueir Date 2008-03-04 Time 15:47 Sent To PC
Notes
2008-03-04 15:55:46REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 PREVIOUS PLAN REVIEW COMMENTS WERE NOT ADDDRESSED.
 PLEASE SEE ATTACHED FROM PREVIOUS REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop FUEL DIESEL GENERATOR
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By rregueir Date 2008-01-08 Time 13:42 Rev Time 0.00
Received By rregueir Date 2008-01-08 Time 13:37 Sent To  
Notes
2008-01-08 13:42:37REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 ABOVE GROUND FUEL TANKS IN EXCESS OF 550 GALLONS ARE
 REQUIRED TO BE APPROVED BY PALM BEACH COUNTY DERM PRIOR
 TO PERMIT ISSUANCE. FOR MORE INFORMATION PLEASE CONTACT
 CHIP GREEN AT 561-233-2400 OR VISIT
 WWW.CO.PALM-BEACH.FL.US/ERM/CONTACT.ASP
  
 WHEN RESUBMITTING, PROVIDE 2 SETS OF PLANS WITH DERM
 APPROVAL.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2009-03-10 Cont ID  
Sent By adarroug Date 2009-03-10 Time 14:19 Rev Time 0.00
Received By adarroug Date 2009-03-10 Time 14:19 Sent To E
Notes
2009-03-10 14:19:54TO "E" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 11:19 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 11:19 Sent To  
Notes
2009-03-04 11:28:58TO "COMM" BD#50

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2009-03-04 Cont ID  
Sent By adarroug Date 2009-03-04 Time 11:18 Rev Time 0.00
Received By adarroug Date 2009-03-04 Time 11:18 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 09:25 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 09:25 Sent To  
Notes
2008-06-06 09:25:50TO "COMM" BD#46

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-06 Cont ID  
Sent By adarroug Date 2008-02-06 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-02-06 Time 10:08 Sent To  
Notes
2008-02-06 10:11:31TO "COMM" BD#45

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-24 Cont ID  
Sent By mawillia Date 2008-01-24 Time 13:04 Rev Time 0.00
Received By mawillia Date 2007-12-20 Time 17:52 Sent To  
Notes
2007-12-20 17:52:28SENT TO COM BOARD # 02 MMILLER

Review Stop L LANDSCAPING
Rev No 1 Status P Date 2009-03-09 Cont ID  
Sent By rkussner Date 2009-03-09 Time 11:16 Rev Time 0.00
Received By rkussner Date 2009-03-09 Time 11:15 Sent To Z
Notes
2009-03-09 11:25:07***LANDSCAPE REVIEW PASSED WITH PROVISO:
  
 1. MUST REPLACE LIVE OAK TREE IN ISLAND TO THE SOUTH OF
 NEW GENERATOR.
  
 2. REMOVE ALL INVASIVE SPECIES AND REPLACE ALL DEAD OR
 MISSING PLANT MATERIAL IN GENERAL VACINITY OF NEW
 GENERATOR.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT ROBERT
 KUSSNER @ (561) 822-1462.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-01-08 Cont ID  
Sent By rregueir Date 2008-01-08 Time 13:37 Rev Time 0.00
Received By rregueir Date 2008-01-08 Time 13:37 Sent To FUEL
Notes
2008-01-08 13:37:49SEE FUEL PLAN REVIEW.

Review Stop Z ZONING
Rev No 4 Status P Date 2009-03-10 Cont ID  
Sent By jroach Date 2009-03-10 Time 08:23 Rev Time 0.00
Received By jroach Date 2009-03-10 Time 08:23 Sent To  
Notes
2009-03-10 08:23:59***PASSED WITH PROVISO***
  
 1) SCREEN WALL AND ALL LANDSCAPING SHALL BE INSTALLED
 AND INSPECTED PRIOR TO ISSUANCE OF A CERTIFICATE OF
 COMPLETION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-17 Cont ID  
Sent By jroach Date 2008-06-17 Time 13:35 Rev Time 0.00
Received By jroach Date 2008-06-17 Time 13:35 Sent To  
Notes
2008-06-17 13:36:32***PASSED WITH PROVISO***
  
 1) SCREEN WALL AND ALL LANDSCAPING SHALL BE INSTALLED
 AND INSPECTED PRIOR TO ISSUANCE OF A CERTIFICATE OF
 COMPLETION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-18 Cont ID  
Sent By jroach Date 2008-02-18 Time 16:43 Rev Time 0.00
Received By jroach Date 2008-02-18 Time 16:43 Sent To  
Notes
2008-02-18 16:58:37***FAILED***
  
 ALL OF THE FOLLOWING ARE REPEAT COMMENTS...
  
 1) APPLICATION FOR A MINOR AMENDMENT TO THE CENTREPARK
 WEST COMMERCIAL PLANNED DEVELOPMENT (CPD) SHALL BE
 SUBMITTED TO AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 2) PLEASE CLARIFY WHETHER OR NOT ANY EXISTING
 LANDSCAPING WILL BE REMOVED/RELOCATED...A TREE
 ALTERATION PERMIT MAY BE REQUIRED.PLEASE CONTACT
 ROBERT KUSSNER, LANDSCAPE PLANNER, AT (561) 822-1435
 FOR MORE INFORMATION.
  
 3) PER SECTION 94-443(C)(3)(A) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), A FIVE (5) FOOT
 WIDE LANDSCAPE ISLAND SHALL BE MAINTAINED AT THE END OF
 EVERY ROW OF PARKING...IT APPEARS THAT THE PROPOSED
 LOCATION OF THE GENERATOR WILL REMOVE THIS EXISTING
 PROVISION.EACH LANDSCAPE ISLAND SHALL CONTAIN AT
 LEAST ONE (1) SHADE TREE.
  
 5) PER SECTION 94-444(B) OF THE CITY'S ZLDRS,
 GENERATORS SHALL PROVIDE ADEQUATE SCREENING.PLEASE
 NOTE THE CODE PROVISION BELOW:
  
 "SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS."
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2008-01-07 Cont ID  
Sent By jroach Date 2008-01-07 Time 16:17 Rev Time 0.00
Received By jroach Date 2008-01-07 Time 16:17 Sent To  
Notes
2008-01-07 16:30:16***FAILED***
  
 1) APPLICATION FOR A MINOR AMENDMENT TO THE CENTREPARK
 WEST COMMERCIAL PLANNED DEVELOPMENT (CPD) SHALL BE
 SUBMITTED TO AND APPROVED BY THE PLANNING AND ZONING
 DEPARTMENT PRIOR TO THE ISSUANCE OF A BUILDING PERMIT.
  
 2) PLEASE CLARIFY WHETHER OR NOT ANY EXISTING
 LANDSCAPING WILL BE REMOVED/RELOCATED...A TREE
 ALTERATION PERMIT MAY BE REQUIRED.PLEASE CONTACT
 ROBERT KUSSNER, LANDSCAPE PLANNER, AT (561) 822-1435
 FOR MORE INFORMATION.
  
 3) PER SECTION 94-443(C)(3)(A) OF THE CITY'S ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS), A FIVE (5) FOOT
 WIDE LANDSCAPE ISLAND SHALL BE MAINTAINED AT THE END OF
 EVERY ROW OF PARKING...IT APPEARS THAT THE PROPOSED
 LOCATION OF THE GENERATOR WILL REMOVE THIS EXISTING
 PROVISION.EACH ISLAND SHALL CONTAIN AT LEAST ONE (1)
 SHADE TREE.
  
 4) PLEASE BE SURE TO NOT THE SETBACKS FROM THE
 GENERATOR TO THE PROPERTY LINE.
  
 5) PER SECTION 94-444(B) OF THE CITY'S ZLDRS,
 GENERATORS SHALL PROVIDE ADEQUATE SCREENING.PLEASE
 NOTE THE CODE PROVISION BELOW:
  
 "SCREENING SHALL BE CONSTRUCTED OF BRICK, DECORATIVE
 CONCRETE, OTHER DECORATIVE MASONRY, OR COMPARABLY
 DURABLE WOOD AND STEEL. WALLS SHALL BE LANDSCAPED WITH
 SHRUBS AND HEDGES PLANTED AT TWO-FOOT INTERVALS."
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved