Plan Review Details - Permit 07120491
Plan Review Stops For Permit 07120491
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-28 Cont ID  
Sent By mjacobs Date 2008-03-28 Time 06:56 Rev Time 0.00
Received By mjacobs Date 2008-03-28 Time 06:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-22 Cont ID  
Sent By mjacobs Date 2007-12-22 Time 13:05 Rev Time 0.00
Received By mjacobs Date 2007-12-22 Time 10:16 Sent To  
Notes
2007-12-22 13:05:24BUILDING PLAN REVIEW
 PERMIT:07120491
 ADD:700 S. ROSEMARY AVE #158
 CONT:CHAMPION RETAIL SERVICES INC.
 TEL: (561)441-9124
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
  
 PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) AFTER
 JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 REVISIONS.
  
 NOTE: FBC(EXSISTING) 301.5. IN THE FUTURE, A REGISTERED
 DESIGN PROFESSIONAL OR THE OWNER MUST ELECT ONE OR A
 COMBINATION OF LEVELS OF ALTERATION IN ACCORDANCE WITH
 FBC(EXISTING) SECTIONS 303/ 304 AND 305.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 10:13 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 07:49 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2007-12-27 Cont ID  
Sent By dpalmer Date 2007-12-27 Time 15:03 Rev Time 0.00
Received By dpalmer Date 2007-12-27 Time 15:03 Sent To PC
Notes
2007-12-27 15:03:25 
 *** DENIED REVIEW***
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE REFLECTED ON ELECTRICAL PLANS AND PROJECT.
 2004 FBC W/2007 SUPPLEMENTS
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72
  
 2) NOTE: PLEASE BE SURE ALL CODE REFERENCES ARE FROM
 THE MOST CURRENT ADOPTED CODES UNDER FLORIDA STATUTES
 553.73 AND CHAPTER 27 OF THE FLORIDA BUILDING CODE.
 FOR EXAMPLE: PLEASE SEE CODE REFERENCES WHICH ARE FROM
 THE 1999 NEC. NOTE #20 ON E.1
  
 3) NOTE: PLEASE BE SURE THE SUITE/UNITNUMBER IS
 STATED ON TITLE BLOCKS. THIS MAY BE HAND PRINTED FOR
 ALL SHEETS WHICH DO NOT NEED TO BE RE-PRINTED. (SUITE #
 IS 158)
 FAC61G1-16.004, 61G15-23.002, FBC ADMIN 106.1.2, 106.5
 ETC
  
 4) NOTE: PLEASE SEE THE COLOR CODING STATED ON ES-1 FOR
 277/480V SYSTEMS IS NOT CORRECT.
 PLEASE KNOW THE COLOR CODING SHALL BE AS FOLLOWS (A)
 BROWN, (B) PURPLE AND (C) YELLOW. THESE SEEM TO HAVE
 BEEN REVERSED OR MISPRINTED.
 AS PLANS ARE COMING BACK FOR OTHER COMMENTS AND ARE OF
 PRIVATE PROVIDER THESE CAN NOT BE RED-LINED.
 210.5, 215.12, 90.4
  
 5) NOTE: PLEASE SEE 422.11 AND 422.13 AS THE MINIMUM
 BRANCH CIRCUIT SIZING AND OVERCURRENT PROTECTION FOR
 THE WATERS HEATERS SHALL BE 125%.
 PLEASE SEE THE WATER HEATERS AND LOAD AS SHOWN DOES NOT
 CONTAIN THE 1255 SIZING FOR BRANCH CIRCUIT CONDUCTORS
 AND OCP.
 PLEASE ADJUST.
  
 6) NOTE: PLEASE SEE 220.43B AND SHOW ON LOAD
 CALCULATIONS HOW THE TRACK LIGHTING REQUIRED LOADS WERE
 FIGURED INTO SERVICE.
  
 7) NOTE: PLEASE CLARIFY NOTE ON THE LIGHTING
 CALCULATIONS ON SHEET E-2 WHICH STATES *BUILDING
 DEPARTMENT NOTES*. THIS IS THE FIRST REVIEW UNDER
 PERMIT APPLICATION FOR THIS PROJECT. PLEASE EXPLAIN.
 PLEASE SEE METHOD *B* CALCULATIONS UNDER THE 2004 FBC
 BEFORE CODE CHANGES OF DECEMBER 8TH, 2006 WERE
 SUBMITTED. (VERSION 2.11 SUBMITTED MAY NOT BE USED
 AFTER DATE ABOVE.
 PLEASE SEE 13-400.3.B
 PLEASE EXPLAIN HOW THESE MAY BE SUBMITTED AND USED.
 PLEASE ALSO SEE COMMENTS FROM MECHANICAL REVIEWER FOR
 INFORMATION WHICH IS PLACED IN THE INPUT DATA REPORT
 WHICH DOES NOT CORRELATE WITH ACTUAL KNOWN COMPONENTS
 OF THE EXISTING BUILDING.
 PLEASE SEE 13-415.2.ABC.1.2 (1) AND CLARIFY IF ALL
 WATTAGES FIGURED ARE BASED ON FIXTURES AND NOT BULBS
 AND PART (2) THE VA RATING OF THE BALLAST.
 PLEASE SEE 13-415.2.ABC.1.3 AS THE PLANS DO INDICATE
 EXTERIOR LIGHTS YET THESE ARE NOT SHOWN ON THE LIGHTING
 PERFORMANCE CALCULATIONS ON PLANS AND THEY ARE SHOWN ON
 THE IDR.
 PLEASE COMPLETE FIXTURE INFORMATION AND FIXTURE LEGEND.
  
 PLEASE VERIFY ALLOWANCES GIVEN FOR STATED FUTURE LIGHT
 FIXTURE AS NOTED IN CODED NOTE #4.
 *** PLEASE VERIFY THAT COMMON AREA FIXTURES AS SHOWN
 ARE INDEED FED FROM THE TENANT ELECTRICAL SERVICE AND
 SPACE.
  
 8) NOTE: PLEASE SEE FBC 11-4.28.1, .2 AND .3(4). PLEASE
 SHOW THE MINIMUM LEVELS OF DEVICES ON PLANS FOR ADA
 COMPLIANCE.
  
 9) NOTE: PLEASE SHEET ED-1 NOTE FOR DOOR SYSTEM STATES
 RECEPTACLE TO BE INSTALLED ABOVE CEILING. PLEASE SEE
 400.8 (1-7) AS THIS IS NOT PERMITTED FOR USE AS SHOWN.
  
 10) NOTE: PLEASE SEE LIGHTING PLANS WHICH ONLY SHOWN
 ONE OVER RIDE SWITCH AT THE REAR DOOR AS NOTED ON
 LIGHTING CODED NOTES# 3.
 PLEASE CORRELATE AND SHOW LOCATIONS.
 13-415.1.ABC.1.1 AND .1.2
  
 11) NOTE: PLEASE SEE THE ELECTRICAL PLANS CONTAIN NOT
 CONTAIN SCALE ON SHEETS.
 PLEASE CLARIFY WHERE THIS IS SHOWN.
 110.26,
 FBC 106.3.1 MIN SCALE REQUIREMENTS.
  
 12) NOTE: PLEASE SEE 210.62 AS THE SHOW WINDOW
 RECEPTACLES SHALL BE ABOVE WINDOW(S). PLEASE SEE NOTE
 ON PLANS STATES BELOW WINDOW WHICH IS NOT PERMITTED.
 THIS IS DIFFERENT FROM THE OTHER NOTE ON PLANS WHICH
 MENTIONS *ABOVE WINDOW*
 PLEASE CLARIFY WHICH DEVICES ARE ABOVE WINDOW; PLEASE
 SEE AS NOTED ABOVE IN NOTE #9, ABOVE WINDOW MAY NOT BE
 ABOVE CEILING.
  
 13) NOTE: PLEASE KNOW FOR INFORMATIONAL PURPOSE ONLY
 THE LOW VOLTAGE WHICH IS SHOWN ON PLANS IS REQUIRED TO
 BE UNDER SEPARATE PERMIT(S).
 THESE PLANS MAY BE REFERENCED FOR WORK.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status N Date   Cont ID  
Sent By   Date   Time   Rev Time 0.00
Received By btrobaug Date 2007-12-21 Time 13:44 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-24 Cont ID  
Sent By mwennerg Date 2007-12-24 Time 10:01 Rev Time 0.00
Received By mwennerg Date 2007-12-24 Time 10:01 Sent To  
Notes
2007-12-24 10:04:45***APPROVED***
  
 1) ADDRESS SUITE NUMBER TO COMPLY WITH CITY OF WEST
 PALM BEACH REQUIREMENTS REGARDING SIZE AND
 CONTRASTING.
  
 2) COMBUSTIBLES NOT PERMITTED ABOVE CEILINGS USED AS
 RETURN AIR PLENUM.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-24 Cont ID  
Sent By adarroug Date 2008-03-24 Time 09:43 Rev Time 0.00
Received By adarroug Date 2008-03-24 Time 09:43 Sent To B
Notes
2008-03-24 09:43:47TO "MJACOBS" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 10:11 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 10:11 Sent To E
Notes
2008-01-18 10:11:49TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-12-27 Time   Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 17:08 Sent To  
Notes
2007-12-19 17:08:34TO "BOB"#7--EXPEDITED--

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-21 Cont ID  
Sent By rregueir Date 2007-12-21 Time 13:18 Rev Time 0.00
Received By rregueir Date 2007-12-20 Time 16:04 Sent To  
Notes
2007-12-21 13:18:39REVIEW #: 1ST
 ACTION: PASSED
  
 FBC 2004 CODE FAMILY W/ 2007 AMENDMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 NOTE: METHOD B ENERGY CALCULATIONS HAVE BEEN PROVIDED
 WITH THIS PERMIT APPLICATION. THESE CALCULATIONS HAVE
 NOT BEEN REVIEWED FOR THE PURPOSE OF BEING INCLUDED IN
 THE PERMIT SET OF PLANS FOR THE FOLLOWING REASONS:
 A) FORM 400B-2004 V2.11 HAS BEEN SUBMITTED. AS OF
 DECEMBER 8, 2006, THE CORRECT FORM IS 400B-04R (V2.5 OR
 HIGHER) IN ACCORDANCE WITH FBC 13-400.3.B.
 B) IF THIS FORM WERE TO BE USED TO DEMONSTRATE
 COMPLIANCE, IT HAS NOT BEEN ACCURATELY COMPLETED AS
 REQUIRED BY THE SAME SECTION. EXAMPLE: THIS IS A FIRST
 FLOOR TENANT SPACE IN A TWO STORY BUILDING. IT IS NOT
 POSSIBLE FOR THIS SPACE TO HAVE A METAL BUILDING ROOF
 WITH R-19 BATTS AS INDICATED IN THE INPUT DATA REPORT.
 C) THIS WORK IS WITHIN THE CONFINES OF AN EXISTING
 BUILDING AND THE WORK PERFORMED DOES NOT MEET THE
 THRESHOLD FOR A RENOVATION AS DEFINED IN FBC 13-202.
 THEREFORE COMPLIANCE WITH FBC CHAPTER 13 IS SUBJECT TO
 FBC 13-400.0.C.4 AND FBC 13-101.6. METHOD B IS NOT AN
 APPLICABLE COMPLIANCE METHOD FOR THIS SPACE.
  
 THIS DOES NOT HAVE AN IMPACT ON MECHANICAL CODE
 COMPLIANCE FOR THIS PROJECT AS ALL COMPONENTS SHOWN ON
 PLANS RELATED TO MECHANICAL, SUCH AS DUCTWORK,
 INSULATION AND THE AHU, ARE WITHIN THE MINIMUM
 PRESCRIPTIVE REQUIREMENTS OF CHAPTER 13. THIS NOTE IS
 ONLY TO SERVE AS NOTICE THAT THE METHOD B FORM
 SUBMITTED WAS NOT CONSIDERED AS PART OF THIS
 APPLICATION AND WILL NOT BE INCLUDED AS PART OF THE
 PERMIT RECORD.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-24 Cont ID  
Sent By mperson Date 2007-12-24 Time 08:34 Rev Time 0.00
Received By mperson Date 2007-12-24 Time 08:34 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-20 Cont ID  
Sent By eschneid Date 2007-12-20 Time 17:06 Rev Time 0.00
Received By eschneid Date 2007-12-20 Time 17:05 Sent To  
Notes
2007-12-20 17:06:14AWNING AND SIGN UNDER SEPARTE PERMITS.