Plan Review Details - Permit 07120471
Plan Review Stops For Permit 07120471
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-17 Cont ID  
Sent By jwitmer Date 2008-01-17 Time 16:19 Rev Time 2.22
Received By jwitmer Date 2008-01-17 Time 16:19 Sent To PC
Notes
2008-01-17 16:21:44CANNES RESIDENCES
 510 4TH ST
 JAN. 17,2008
  
 BUILDING PLAN REVIEW/ FOUNDATION ONLY
 PERMIT: 07120471
 ADD: 505 4TH ST
 CONT: TRENTO CONSTRUCTION CO.
 TEL: (786)271-9448
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
  
 2)WPB AMENDMENT 105.13.6. W.P.B. CONSTRUCTION
 SERVICES DEPARTMENT REQUEST FOR THRESHOLD BUILDINGS A
 SPECIAL INSPECTOR AS REQUIRED BY S. 553.79(5) FLORIDA
 STATUTES TO THE MINIMUM INSPECTIONS REQUIRED BY THIS
 CODE. CONTACT HAROLD PISKURA MANAGER OF THE SPECIAL
 INSPECTOR PROGRAM AT (561) 805-6711 FOR FURTHER
 INFORMATION BEFORE THE PERMIT MAY BE ISSUED.
  
 3)BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND A COPY
 OF THE PAID RECEIPT ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE INFORMATION.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By dpalmer Date 2007-12-21 Time 15:46 Rev Time 0.00
Received By dpalmer Date 2007-12-21 Time 15:46 Sent To  
Notes
2007-12-21 15:46:35** DENIED 2ND REVIEW **
  
 1) NOTE:PLEASE KNOW AT THIS TIME THE ELECTRICAL
 REVIEW IS PLACED INTO A FAILED STATUS. PLEASE SEE THE
 LOCATION OF THE MAIN ELECTRICAL ROOM WILL NOT BE
 PERMITTED ON THE 2ND FLOOR WHICH IS ACTUALLY THE THIRD
 LEVEL. (GROUND, MEZZ, THEN 2ND FLR).
 PLEASE KNOW AS THIS MAY AFFECT THE STRUCTURAL
 FOUNDATION PERMIT REVIEW CAN NOT BE PASSED AT THIS
 TIME.
 THE MAIN ELECTRICAL ROOM SHALL BE A MAXIMUM OF THE
 MEZZANINE LEVEL AND SHALL CONTAIN DIRECT ACCESS FOR
 EMERGENCY PERSONNEL.
 AS THE PLANS ARE COMING BACK FOR COMMENTS FROM OTHER
 TRADES AT THIS TIME, PLEASE ADJUST.
 PLEASE KNOW THE PLANS COULD BE STRUCK THROUGH TO
 INCLUDE ONLY THE GROUNDING ELECTRODE SYSTEM ONLY *IF*
 THE DETAIL AS SHOWN DOES NOT AFFECT THE ELECTRICAL ROOM
 LOCATION.
  
 2) NOTE: PLEASE SEE AS NOTED ON PREVIOUS REVIEW, THE
 SIGNATURE ON THE SURVEY SHEETS IS *NOT* ORIGINAL AS
 REQUIRED PER FS 472.025. THIS IS NOTED AS INFORMATION
 AND NEEDS TO BE CORRECTED BEFORE PERMIT ISSUANCE.
 THIS DOES NOT AFFECT THE ELECTRICAL PLANS/REVIEW.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop ENG ENGINEERING CSD
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2008-01-17 Cont ID  
Sent By mawillia Date 2008-01-17 Time 14:16 Rev Time 0.00
Received By mawillia Date 2008-01-17 Time 14:02 Sent To  
Notes
2008-01-17 14:10:10*****APPROVED*****
  
 PLAN SHEET FP-2.0A STAMPED, INITIALED, AND DATED
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-09-03 Cont ID  
Sent By rbrown Date 2008-09-03 Time 09:50 Rev Time 0.00
Received By rbrown Date 2008-09-03 Time 09:50 Sent To  
Notes
2008-09-24 09:51:17RECEIVED LETTER REQUESTING EXTENSION OF PERMIT
 APPLICATION.

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-17 Cont ID  
Sent By jwitmer Date 2008-01-17 Time 16:25 Rev Time 0.00
Received By jwitmer Date 2007-12-19 Time 09:15 Sent To  
Notes
2007-12-19 09:15:22TO "COMM" BD#53

Review Stop M MECHANICAL (A/C)
Rev No 1 Status   Date   Cont ID  
Sent By   Date   Time   Rev Time  
Received By   Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 18:14 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 18:14 Sent To  
Notes
***NONE***

Review Stop X PERMIT EXTENSION
Rev No 1 Status N Date 2008-09-25 Cont ID  
Sent By amckenzi Date 2008-09-25 Time 08:36 Rev Time 0.00
Received By amckenzi Date 2008-09-25 Time 08:36 Sent To  
Notes
2008-09-25 08:39:33EXTENSION REQUEST GRANTED UNTIL 12/11/08 PER RAB/AMM

Review Stop Z ZONING
Rev No 1 Status P Date 2008-01-08 Cont ID  
Sent By aaponte Date 2008-01-08 Time 08:28 Rev Time 0.00
Received By aaponte Date 2008-01-08 Time 08:28 Sent To  
Notes
2008-01-08 08:32:01COMMENTS FOR MAIN PERMIT:
 1. COLUMNS LOCATED NEXT TO THE CURB AND IN THE MIDDLE
 OF THE INTERNAL ROAD ARE NOT ALLOWED. PLEASE REMOVE.
 FROM EARLY DISCUSSIONS, THE APPLICANT DECISION TO
 LOCATE THE OPEN SPACE ALONG THE PRIVATE ROAD REQUIRED
 THE TREATMENT OF THE PRIVATE ROAD AS A PUBLIC ROAD
 ,THEREFORE COLUMNS CAN NOT LAND ON THE ROAD.
 2. SIDEWALK UNDER THE ARCADE SHALL BE 10 FEET CLEAR.
 DOOR SHALL BE RECESS TO PROVIDE FOR THE CLEAR PATH
 BETWEEN THE FACE OF THE BUILDING AND THE FACE OF THE
 COLUMN.