Plan Review Details - Permit 07120462
Plan Review Stops For Permit 07120462
Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By btrobaug Date 2007-12-26 Time 15:31 Rev Time 0.00
Received By btrobaug Date 2007-12-26 Time 15:25 Sent To Z
Notes
2007-12-26 15:31:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} PROVIDE A PANEL SCHEDULE FOR THE PANEL FEEDING THE
 NEW EQUIPMENT AS IT IS CURRENTLY, PER 408.4. INCLUDE
 OCP AND CONDUCTOR SIZES.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW.
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-28 Cont ID  
Sent By mperson Date 2007-12-28 Time 10:14 Rev Time 0.00
Received By mperson Date 2007-12-19 Time 14:29 Sent To  
Notes
2007-12-19 14:31:28TO "E" BOX

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mperson Date 2007-12-28 Time 10:09 Rev Time 0.00
Received By mperson Date 2007-12-28 Time 10:09 Sent To PC
Notes
2007-12-28 10:13:53PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1) FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
 **NOTE: THE SUBMITTED MANUFACTURER SHEETS DO NOT HAVE
 A LISTING FROM A TESTING AGENCY.
  
 2) FBC-2004 SEC. 424.2.7.2, OR
 FBCR-2004 SEC. R4101.7.2 PUMPS AND
 EQUIPMENT SHALL BE MOUNTED ON A
 SUBSTANTIAL BASE IN A MANNER THAT WILL
 ELIMINATE STRAIN ON PIPING.SLAB SHALL
 BE A NOMINAL 4" THICK. (DETAIL)
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By choops Date 2007-12-27 Time 09:57 Rev Time 0.00
Received By choops Date 2007-12-27 Time 09:56 Sent To P
Notes
2007-12-27 09:59:10***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY SHOWING
 THE LOCATION OF THE EQUIPMENT.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 POOL/HEAT PUMP EQUIPMENT TO ALL PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720