| Plan Review Stops For Permit 07120459 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-03-28 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-03-28 |
Time |
10:21 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-03-28 |
Time |
07:15 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-06 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-06 |
Time |
15:36 |
Sent To |
|
|
| Notes |
| 2008-02-06 16:47:08 | BUILDING PLAN REVIEW | | | PERMIT: 07120459 | | | ADD: 8989 OKEECHOBEE BLVD #212 | | | CONT: CHOEN INC. | | | TEL: (561)362-4217 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD | | | ACTION: DENIED | | | 2/06/08 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1C) OK | | | 2)OK | | | 3)OK | | | 4)OK | | | 5)OK | | | 6)OK | | | | | | **NEW** | | | **NO RESPONSE NOT ADDRESSED** | | | A) THE NEW DRINKING FOUNTAIN LOCATION WILL HAVE TO | | | COMPLY WITH FBC 1016.2 (EXCEPTIONS) #2. THE CORRIDOR | | | WIDTH SHALL BE 36 INCHES WHEN THE OCCUPANT LOAD IS 50 | | | OR LESS. THE INSTALLATION OF THE DRINKING FOUNTAIN AT | | | THIS LOCATION WILL PROHIBIT A PERSON IN A WHEELCHAIR | | | ACCESS TO THE BATHROOM. THE SPACE INDICATED ON THE | | | DRAWINGS IS 30 INCHES. SHEET A2 SHOWS FOUR DIFFERENT | | | TYPES OF DRINKING FOUNTAINS; CIRCLE THE ONE WHICH WILL | | | BE INSTALLED. | | | | | | FBC1008.1.1.1. THERE SHALL NOT BE PROJECTIONS INTO THE | | | REQUIRED CLEAR WIDTH LOWER THAN 34 INCHES (864 MM) | | | ABOVE THE FLOOR OR GROUND. PROJECTIONS INTO THE CLEAR | | | OPENING WIDTH BETWEEN 34 INCHES (864 MM) AND 80 INCHES | | | (2032 MM) ABOVE THE FLOOR OR GROUND SHALL NOT EXCEED 4 | | | INCHES (102 MM) | | | | | | FBC11-4.4.1 | | | OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES) | | | WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80 | | | INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR | | | SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO | | | WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE | | | FIGURE 8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING EDGES | | | AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED FLOOR | | | MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8 (A) AND FIGURE 8 | | | (B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS | | | MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO | | | 80 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR | | | FINISHED FLOOR [SEE FIGURE 8 (C) AND FIGURE 8 (D)]. | | | PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF | | | AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE 8 | | | (E)]. | | | | | | B)61G1-16.004. THE TITLE BLOCK ON THE DRAWINGS SHALL | | | INCLUDE. | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. OK | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT.OK | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-01-15 |
Time |
16:34 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-01-15 |
Time |
12:06 |
Sent To |
|
|
| Notes |
| 2008-01-15 16:34:30 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07120459 | | | ADD: 8989 OKEECHOBEE BLVD #212 | | | CONT: CHOEN INC. | | | TEL: (561)362-4217 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND | | | ACTION: DENIED | | | 1/15/08 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 REVISIONS. | | | | | | 2)THE SQUARE FOOTAGE PER OCCUPANT LOAD FOR A | | | MERCANTILE OCCUPANCY IS NOT 15. SEE FBC TABLE 1004.1.2 | | | FOR THE CORRECT SQUARE FOOTAGE PER OCCUPANT LOAD. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 3)THE ACCESSIBLE COUNTER ON SHEET A1 SHALL INDICATE | | | THE HEIGHT AND LENGTH OF THE COUNTER. FBC 11-7(2) (I) | | | STATES, A PORTION OF THE MAIN COUNTER SHALL BE A | | | MINIMUM OF 36 INCHES IN LENGTH AND 36 INCH HIGH. SEE | | | SECTION 11-7 FOR MORE INFORMATION PERTAINING CHECK-OUT | | | AISLES. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 4)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PERTAINING TO | | | THE PROJECT. SEE SECTIONS 303, 304 AND 305 OF THIS | | | CODE. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 5) ON THE APPLICATION CLEARLY DESCRIBE THE PROJECT TO | | | AVOID DELAYS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. FBC | | | 106.1.1.INDICATE THE WIDTH OF EACH AISLE ON THE | | | PLANS. | | | | | | **NO RESPONSE NOT ADDRESSED** | | | 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY. | | | | | | **NEW** | | | A)THE NEW DRINKING FOUNTAIN LOCATION WILL HAVE TO | | | COMPLY WITH FBC 1016.2 (EXCEPTIONS) #2. THE CORRIDOR | | | WIDTH SHALL BE 36 INCHES WHEN THE OCCUPANT LOAD IS 50 | | | OR LESS. THE INSTALLATION OF THE DRINKING FOUNTAIN AT | | | THIS LOCATION WILL PROHIBIT A PERSON IN A WHEELCHAIR | | | ACCESS TO THE BATHROOM. THE SPACE INDICATED ON THE | | | DRAWINGS IS 30 INCHES. SHEET A2 SHOWS FOUR DIFFERENT | | | TYPES OF DRINKING FOUNTAINS; CIRCLE THE ONE WHICH WILL | | | BE INSTALLED. | | | . | | | B)61G1-16.004 THE TITLE BLOCK ON THE DRAWINGS SHALL | | | INCLUDE. | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | 2008-01-15 16:32:54 | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-29 |
Time |
11:51 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-28 |
Time |
16:38 |
Sent To |
PC |
|
| Notes |
| 2007-12-28 16:56:14 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07120459 | | | ADD: 8989 OKEECHOBEE BLVD | | | CONT: CHOEN INC. | | | TEL: (561)362-4217 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST | | | ACTION: DENIED | | | 12/28/07 | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 REVISIONS. | | | | | | 2)THE SQUARE FOOTAGE PER OCCUPANT LOAD FOR A | | | MERCANTILE OCCUPANCY IS NOT 15. SEE FBC TABLE 1004.1.2 | | | FOR THE CORRECT SQUARE FOOTAGE PER OCCUPANT LOAD. | | | | | | 3)THE ACCESSIBLE COUNTER ON SHEET A1 SHALL INDICATE | | | THE HEIGHT AND LENGTH OF THE COUNTER. FBC 11-7(2) (I) | | | STATES, A PORTION OF THE MAIN COUNTER SHALL BE A | | | MINIMUM OF 36 INCHES IN LENGTH AND 36 INCH HIGH. SEE | | | SECTION 11-7 FOR MORE INFORMATION PERTAINING CHECK-OUT | | | AISLES. | | | | | | 4)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PERTAINING TO | | | THE PROJECT. SEE SECTIONS 303, 304 AND 305 OF THIS | | | CODE. | | | | | | 5) ON THE APPLICATION CLEARLY DESCRIBE THE PROJECT TO | | | AVOID DELAYS. CONSTRUCTION DOCUMENTS SHALL BE OF | | | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND | | | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT | | | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND | | | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. FBC | | | 106.1.1.INDICATE THE WIDTH OF EACH AISLE ON THE | | | PLANS. | | | | | | 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-04-09 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-04-09 |
Time |
12:42 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-04-09 |
Time |
12:12 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-03-20 |
Time |
17:21 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-03-20 |
Time |
15:37 |
Sent To |
|
|
| Notes |
| 2008-03-20 17:08:00 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005 | | | NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED, | | | CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING | | | OR A SEPARATELY METERED OR PERMITTED PORTION OF A | | | BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING | | | AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE | | | SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1. | | | TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG | | | PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD | | | OF CALCULATION HAS BEEN USED ARE NOT PERMITTED. THE | | | INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN | | | ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED | | | THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN | | | ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS | | | CAN BE DEMONSTRATED ON THE PLANS INDICATED THE WATTAGES | | | OF THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE | | | DENSITY REQUIREMENTS. THIS WAS NOT DONE.THE STATEMENT | | | THAT THE MAXIMUM IS 1.4 W/SF DOES NOT INDICATE WHAT THE | | | CALCULATED WATTAGE IS. THE DESIGNER MUST INDICATE HOW | | | THE DENSITY COMPLIANCE WAS ACHIEVED. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-04 |
Time |
16:55 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-04 |
Time |
16:55 |
Sent To |
|
|
| Notes |
| 2008-02-04 16:55:23 | ** DENIED 3RD REVIEW ** | | | | | | ** PLEASE SEE THERE ARE STILL COMMENTS WHICH ARE | | | REPEATED FROM THE TWO PREVIOUS REVIEWS WHICH ARE STILL | | | IN NEED OF ADDRESSING. | | | | | | 1) NOTE: PLEASE SEE PREVIOUS COMMENTS WHICHSTATED THE | | | TITLE BLOCKS WERE MISSING REQUIRED LICENSE INFORMATION | | | PER FAC 61G1-16.004 AND FS 481.219. AN ATTACHED SHEET | | | INDICATING THE FIRM HAS A LICENSE WAS VERIFIED WITH THE | | | DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION | | | HOWEVER PLEASE SEE AS STATED ON PREVIOUS REVIEWS THIS | | | FIRM LICENSE NUMBER IS REQUIRED TO BE ON TITLE BLOCKS. | | | IF THIS HAD BEEN THE ONLY COMMENT THIS WOULD BE BEEN | | | WRITTEN ON PLANS, HOWEVER AS THERE ARE OTHER COMMENTS, | | | THIS NEEDS TO BE CORRECTED AND ADDED TO TITLE BLOCKS | | | ACCORDINGLY. | | | | | | 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH | | | RESPECT TO CHAPTER 13 COMPLIANCE. | | | A NOTE IS NOW PLACED ON PLANS WHICH STATES IT WILL BE | | | TIED INTO THE BUILDINGS LIGHTING CONTROL SYSTEM WITH | | | OVER RIDES IN SPACE. | | | PLEASE KNOW THE BUILDING AS A WHOLE BY DEFINITION DOES | | | NOT CONTAIN A WHOLE BUILDING SYSTEM. THESE LIGHTING | | | CONTROLS AS NOTED ARE REQUIRED IN THE TENANT SPACE | | | ALONG WITH SEPARATE SPACES WITHIN THE TENANT SPACE. | | | THE PLANS NOTE THAT LIGHTING CONTROLS ARE TO MEET CODE | | | HOWEVER SHOW ABSOLUTELY NO DESIGN CRITERIA. THE CODE OR | | | PARTS OF THE CODE MAY NOT BE *QUOTED* IN LIEU OF | | | SHOWING *MINIMUM CODE COMPLIANCE DESIGN*. | | | AS STATED ON PREVIOUS REVIEWS, PLEASE SEE | | | 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING | | | CONTROLS WHICH ARE MISSING. | | | PLEASE COMPLETE INFORMATION ON TYPES OF DEVICES, TYPES | | | OF SYSTEM, TIMES ON OVER RIDES, SCHEDULING, ETC. | | | | | | PLEASE SEE 13-415.2 AS NOTED ON BOTH PREVIOUS REVIEWS. | | | PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS AS | | | MENTIONED. | | | THE SUBMITTED SHEETS FROM AN *ELITE SOFTWARE | | | DEVELOPMENT IN* IS NOT ADOPTED BY THE FBC CHAPTER 13. | | | PLEASE SEE 13-400.3.B, 13-400.3.B. PLEASE KNOW THE | | | ADOPTED PROGRAM UNDER THE STATE OF FLORIDA AND THE | | | FLORIDA BUILDING COMMISSION IS THAT OF FLA-COM WHICH IS | | | STATED IN THE CODE SECTIONS AS GIVEN ON BOTH PREVIOUS | | | REVIEWS INCLUSIVE OF THIS REVIEW. | | | PLEASE SEE AS REQUIRED, PLEASE COMPLETE FIXTURE LEGEND | | | ON PLANS AND BE SURE TO COORDINATE WITH THE INPUT | | | DATA. | | | ** PLEASE KNOW THE LIGHTING LEVELS AS SHOWN ON | | | DOCUMENTS SUBMITTED ON PAGE #3 FAR EXCEED THE MAXIMUM | | | ALLOWANCES PERMITTED IN 13-415.2, 13-415.2.ABC.1.1 ETC | | | | | | 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD | | | CALCULATIONS PER THE NEC PER | | | 220.12,220.14,220.42,220.44,215.3,230.42 ETC. | | | SAME COMMENT AS NOTED PREVIOUSLY. | | | | | | 4) NOTE: PLEASE FBC AS ANY REQUIRED FIRE ALARM SYSTEM | | | AS REQUIRED UNDER THE FBC SHALL SHOW THE BASE REQUIRED | | | DESIGN ON BUILDING PLANS. IT IS KNOWN THAT SEPARATE | | | PERMITS AND SHOP DRAWINGS ARE SUBMITTED AT A LATER DATE | | | FOR PERMITTING HOWEVER THE PLANS ARE REQUIRED TO SHOW | | | MINIMUM COMPLIANCE FOR ANY REQUIRED SYSTEM AND/OR | | | DEVICES. | | | PLEASE SEE CHAPTER 11 AS STATED ON PREVIOUS REVIEW WITH | | | RESPECT TO ADA COMPLIANCE WHICH IS REQUIRED ON BASE | | | PLANS AS WELL AS ANY SEPARATE PERMITS. | | | PLEASE SEE 11-4.28.1,.2,.3(4) FOR DEVICES, LOCATIONS AS | | | WELL AS MINIMUM ADA COMPLIANCE LEVELS. | | | THIS IS REQUIRED FOR ANY REQUIRED SYSTEM BY OTHER CODES | | | BY BUILDING REVIEW OR FIRE MARSHAL. | | | | | | 5) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS | | | 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE | | | COMMENTS. THE RESPONSE FROM DESIGNER SPEAKS OF | | | OCCUPANCY OF THE MERCANTILE LOCATION? | | | PLEASE KNOW AS THERE ARE REPEATED COMMENTS AND AS | | | REQUIRED BY FLORIDA STATUES A FEE OF $2040.00 HAS BEEN | | | ASSESSED TO THE DESIGNER OF RECORD.\ | | | THIS FEE IS NOT FOR THE OWNER OR CONTRACTOR AND IS | | | REQUIRED BY STATE STATUTES TO BE PAID BEFORE PLANS MAY | | | BE RESUBMITTED FOR THE 4TH REVIEW. | | | ONE COPY OF ELECTRICAL PLANS IS BEING RETAINED BY THIS | | | OFFICE. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-01-15 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-15 |
Time |
10:58 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-15 |
Time |
10:58 |
Sent To |
|
|
| Notes |
| 2008-01-15 10:59:57 | | | | | | | ** DENIED2ND REVIEW ** | | | | | | ** PLEASE SEE ALMOST EVERY COMMENT FROM THE PREVIOUS | | | REVIEW IS THE EXACT SAME COMMENT WITHOUT ANY CHANGES OR | | | CORRECTIONS MADE. | | | ** THERE ARE RESPONSE LETTERS FOR PLUMBING REVIEW | | | HOWEVER NOT FOR ELECTRICAL OR OTHER TRADES. | | | | | | | | | 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO | | | REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE BE SURE | | | ADDRESS COMMENTS. THIS IS ONLY AN NOTICE AT THIS TIME. | | | ONE SET OF PLANS WILL BE RETAINED | | | | | | 2) NOTE:SAME COMMENT: | | | PLEASE SEE CODES TO BE STATED ON PLANS ARE NEEDED AS | | | FOLLOWS | | | 2004 FBC W/2007 REVISIONS | | | 2005 NFPA-70 (SHOWS 2002) | | | 2003 NFPA-101 | | | | | | 3) NOTE:SAME COMMENT: | | | PLEASE SEE WHAT APPEARS TO BE MISSING CERTIFICATE OF | | | AUTHORIZATION NUMBER PER FAC 61G1-16.004 AND FS | | | 481.219. PLEASE SEE FS 481.219 AS STATED AS A *DESIGN | | | FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY NOT | | | DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM AS | | | SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE PROVIDE | | | THE CA NUMBER AS REQUIRED. | | | PLEASE CONFIRM. | | | | | | 4) NOTE: SAME COMMENT: | | | PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW AND | | | INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR | | | CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL | | | BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN | | | THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL | | | SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS | | | INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON | | | PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF | | | MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE | | | SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED. | | | NEC 408.4, 310.16, 240.4 ETC | | | FBC106.1.2, 106.3.5.1.2 | | | | | | 5) NOTE:SAME COMMENT: CALCULATIONS WERE ADJUSTED WITH | | | SOME MINOR CHANGES HOWEVER THEYA RE NOT CODE COMPLIANT | | | FOR COMMERCIAL. | | | | | | PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON PANEL ARE | | | THAT FOR A RESIDENCE. PLEASE SEE 220.12, 220.14, | | | 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42 FOR | | | CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%. PLEASE | | | SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR SIGN | | | CIRCUIT IS 1200VA. | | | PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE | | | SHOWN PER 220.43 | | | PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET | | | COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT | | | CALCULATIONS CAN NOT BE DONE AT THIS TIME. | | | | | | 6) NOTE:SAME COMMENT: | | | PLEASE SEE THE PLANS INDICATE TWO PANELS YET THE PLANS | | | ONLY SHOW ONE? | | | PLEASE COMPLETE AND CORRELATE. | | | 408.4, 240.24, ETC | | | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. | | | | | | 7) NOTE: SAME COMMENT: | | | PLEASE SEE THE DRYER AS SHOWN ON PANEL SCHEDULE IS | | | SHOWN AS 5KW YET THE BRANCH CIRCUIT IS SHOWN AS A | | | 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD EXCEEDS | | | THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT A | | | 2-POLE CIRCUIT? | | | PLEASE SEE 240.4, 310.16, ETC | | | FBC 106.1.2 | | | | | | 8) NOTE: COMMENT OK FOR COOLER UNDER SEPARATE PERMIT. | | | | | | 9) NOTE:SAME COMMENT: | | | PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED | | | SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS | | | A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K | | | SQ FT. | | | PLEASE CLEARLY SHOW NEW WORK AND EXISTING. | | | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER | | | 13-415.2. | | | PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME | | | AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE | | | COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON | | | FIXTURES AS SHOWN. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 10) NOTE: SAME COMMENT: | | | PLEASE CLARIFY WHAT APPEARS TO BE A FIRE ALARM DEVICE | | | ON PLANS. PLANS INDICATE A FA IN A BOX HOWEVER AS THE | | | SYMBOL LEGEND DOES NOT SHOW THIS IT IS UNCLEAR WHAT | | | THIS IS? | | | PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE | | | SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR | | | ADA. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-23 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-23 |
Time |
08:29 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-22 |
Time |
16:59 |
Sent To |
|
|
| Notes |
| 2007-12-23 08:29:58 | ** DENIED** | | | | | | | | | 1) NOTE: PLEASE CLARIFY PROPOSED SCOPE OF WORK AND | | | OCCUPANCY. THE PERMIT APPLICATION ORIGINALLY INDICATED | | | A *MASSAGE THERAPY* FIT-OUT, THEN THAT WAS CROSSED OUT | | | FOR * FOOD RETAIL*. THE PACKAGE CONTAINS A LETTER FROM | | | GESULT DESIGN STUDIO WHICH IS ADDRESSED TO PALM BEACH | | | COUNTY BLDG DEPT, AND SEEMS TO RESPOND TO COMMENTS. | | | THIS LETTER SPECIFIES THE OCCUPANCY AS FRESH FRUIT | | | BOUQUET CO. | | | PLEASE INDICATE AND CORRELATEALL . | | | | | | 2) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE | | | NEEDED AS FOLLOWS | | | 2004 FBC W/2007 REVISIONS | | | 2005 NFPA-70 (SHOWS 2002) | | | 2003 NFPA-101 | | | | | | 3) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING | | | CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004 | | | AND FS 481.219. PLEASE SEE FS 481.219 AS STATED AS A | | | *DESIGN FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY | | | NOT DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM | | | AS SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE | | | PROVIDE THE CA NUMBER AS REQUIRED. | | | PLEASE CONFIRM. | | | | | | 4) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW | | | AND INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR | | | CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL | | | BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN | | | THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL | | | SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS | | | INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON | | | PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF | | | MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE | | | SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED. | | | NEC 408.4, 310.16, 240.4 ETC | | | FBC106.1.2, 106.3.5.1.2 | | | | | | 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON | | | PANEL ARE THAT FOR A RESIDENCE. PLEASE SEE 220.12, | | | 220.14, 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42 | | | FOR CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%. | | | PLEASE SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR | | | SIGN CIRCUIT IS 1200VA. | | | PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE | | | SHOWN PER 220.43 | | | PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET | | | COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT | | | CALCULATIONS CAN NOT BE DONE AT THIS TIME. | | | | | | 6) NOTE: PLEASE SEE THE PLANS INDICATE TWO PANELS YET | | | THE PLANS ONLY SHOW ONE? | | | PLEASE COMPLETE AND CORRELATE. | | | 408.4, 240.24, ETC | | | FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION. | | | | | | 7) NOTE: PLEASE SEE THE DRYER AS SHOWN ON PANEL | | | SCHEDULE IS SHOWN AS 5KW YET THE BRANCH CIRCUIT IS | | | SHOWN AS A 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD | | | EXCEEDS THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT | | | A 2-POLE CIRCUIT? | | | PLEASE SEE 240.4, 310.16, ETC | | | FBC 106.1.2 | | | | | | 8) NOTE: PLEASE SEE PLANS MENTIONS COOLER IS TO BE | | | INSTALLED BY OTHERS HOWEVER ELECTRICAL IS NEEDED AT | | | THIS TIME UNLESS ALL WILL BE UNDER SEPARATE PERMITS OR | | | REVISED AT A LATER DATE? | | | 240,220, 310, ETC | | | FBC 106.1.2 | | | | | | 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND | | | .1.3. | | | PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED | | | SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS | | | A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K | | | SQ FT. | | | PLEASE CLEARLY SHOW NEW WORK AND EXISTING. | | | PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER | | | 13-415.2. | | | PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME | | | AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE | | | COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON | | | FIXTURES AS SHOWN. | | | FBC 106.3.5.1.2, 106.1.2 | | | | | | 10) NOTE: PLEASE CLARIFY WHAT APPEARS TO BE A FIRE | | | ALARM DEVICE ON PLANS. PLANS INDICATE A FA IN A BOX | | | HOWEVER AS THE SYMBOL LEGEND DOES NOT SHOW THIS IT IS | | | UNCLEAR WHAT THIS IS? | | | PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE | | | SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR | | | ADA. | | | | | | | | | * ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
4 |
Status |
P |
Date |
2008-03-31 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-31 |
Time |
11:56 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-31 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2008-03-31 11:52:30 | *****APPROVED***** | | | | | | | | | PLAN SHEETS A-1.2, A-1.3, E-1.1, AND FP-1.1 WERE | | | STAMPED, INITIALED, AND DATED. |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
F |
Date |
2008-02-13 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-02-13 |
Time |
15:33 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-02-13 |
Time |
15:33 |
Sent To |
|
|
| Notes |
| 2008-02-13 15:45:02 | ***DENIED*** | | | | | | 1) OK | | | | | | 2) RESPONSE INDICATES THAT FIRE EXTINGUISHERS ARE SHOWN | | | ON PLAN. PLEASE NOTE UNABLE TO LOCATE. | | | | | | 3) OK | | | | | | 4) IF FIRE ALARM EQUIPMENT IS PART OF THE SCOPE OF THIS | | | WORK, ALL APPLICABLE EQUIPMENT IS TO BE ILLUSTRATED ON | | | PLANS.THE TERM FIRE ALARM CAN BE CONSIDERED GENERIC AND | | | DOES NOT IDENTIFY THE SPECIFIC DEVICE SHOWN ON PLANS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-01-16 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2008-01-16 |
Time |
14:56 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2008-01-16 |
Time |
14:56 |
Sent To |
|
|
| Notes |
| 2008-01-16 14:57:39 | ***DENIED*** | | | | | | THESE COMMENTS WERE TAKEN DIRECTLY FROM THE FIRST FIRE | | | REVIEW. | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE. | | | | | | 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75' | | | TRAVEL DISTANCE. | | | | | | 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE | | | WITH FIRE SPRINKLER COVERAGE. | | | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON | | | PLANS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mwennerg |
Date |
2007-12-28 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mwennerg |
Date |
2007-12-28 |
Time |
10:37 |
Sent To |
|
|
| Notes |
| 2007-12-28 10:44:38 | ***DENIED*** | | | | | | 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE. | | | | | | 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE | | | REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75' | | | TRAVEL DISTANCE. | | | | | | 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE | | | WITH FIRE SPRINKLER COVERAGE. | | | | | | 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION. | | | | | | 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON | | | PLANS. | | | | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | | FIRE PLAN REVIEW | | | FIRE PREVENTION (561) 804-4756 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-16 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-16 |
Time |
09:08 |
Sent To |
M |
|
| Notes |
| 2008-06-16 09:09:02 | TO "M" BOX/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-04-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-04-03 |
Time |
16:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-04-03 |
Time |
16:47 |
Sent To |
E |
|
| Notes |
| 2008-04-03 16:47:33 | TO "BTROBAUG" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-03-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-19 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-19 |
Time |
14:08 |
Sent To |
|
|
| Notes |
| 2008-03-19 14:11:30 | TO "BOB"#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-31 |
Time |
09:00 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-31 |
Time |
09:00 |
Sent To |
|
|
| Notes |
| 2008-01-31 09:02:37 | TO "BOB"#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-10 |
|
|
Cont ID |
|
| Sent By |
mmiller |
Date |
2008-01-10 |
Time |
16:08 |
Rev Time |
0.00 |
| Received By |
mmiller |
Date |
2008-01-10 |
Time |
16:08 |
Sent To |
|
|
| Notes |
| 2008-01-10 16:09:32 | SENT TO BOB # 05 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
|
|
|
Cont ID |
|
| Sent By |
|
Date |
2007-12-29 |
Time |
|
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-19 |
Time |
11:17 |
Sent To |
|
|
| Notes |
| 2007-12-21 17:11:20 | TO "BOB" # 412/21/07SPALMER | | 2007-12-19 11:22:18 | WAITING FOR "BOB" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-06-16 |
Time |
14:30 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-06-16 |
Time |
14:30 |
Sent To |
|
|
| Notes |
| 2008-06-16 14:32:30 | RECIVED NOA FOR ROOF TOP CONDENSER UNIT STANDS FOR | | | WALK-IN COOLER. | | | | | | *** FILED WITH PERMIT # 08040403 *** |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-24 |
Time |
14:20 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2008-03-24 |
Time |
14:19 |
Sent To |
|
|
| Notes |
| 2008-03-24 14:25:43 | *** PROVISO *** | | | 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-12-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-26 |
Time |
10:35 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-26 |
Time |
10:35 |
Sent To |
|
|
| Notes |
| 2007-12-26 10:38:43 | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. | | | | | | *** PROVISO *** | | | 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR | | | (A) WALK-IN-COOLER. | | | (B) CLOTHES DRYER VENT. | | | ** SUBMIT PLANS WITH PERMIT APPLICATION. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
4 |
Status |
P |
Date |
2008-03-24 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-24 |
Time |
09:09 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-24 |
Time |
09:09 |
Sent To |
|
|
| Notes |
| 2008-03-24 09:16:19 | ****************PROVISO**************** | | | AIR CHAMBERS ARE NOT COMPLIANT WITH FBC PLUMBING | | | CHAPTER 6, SECTION 604.9, WATER HAMMER AND SHALL NOT BE | | | INSTALLED. REFERENCE PLUMBING GENERAL NOTES AND | | | SPECIFICATIONS (NOTE # 4) ON SHEET P-2.1 AND COMPLY. | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
F |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-05 |
Time |
10:32 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-05 |
Time |
10:32 |
Sent To |
|
|
| Notes |
| 2008-02-05 10:44:48 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 3RD TIME: | | | | | | 1. NOTE: PREVIOUS PLUMBING PLAN REVIEW COMMENTS HAVE | | | BEEN ADDRESSED, HOWEVER UNTIL ELECTRICAL COMMENT #1 | | | ABOUT THE TITLE BLOCKARE ADDRESSED PLANS WILL REMAIN | | | IN FAILED STATUS. PER FAC 61G1-16.004 AND FS 481.219. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-01-18 |
Time |
16:37 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-01-18 |
Time |
07:51 |
Sent To |
|
|
| Notes |
| 2008-01-17 16:58:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | **PREVIOUS PLAN REVIEW COMMENTS** | | | | | | 1. **OK** COMMENT ADDRESSED. | | | | | | 2. **OK** COMMENT ADDRESSED. | | | | | | 3. NOTE: COMMENT RESPONSE NOTED, HOWEVER SEE NEW | | | COMMENTS BELOW ORIGINAL COMMENT. | | | **PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, | | | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS | | | REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND | | | COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, | | | LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW | | | PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE | | | WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER | | | ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED | | | (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) | | | **604.9. | | | | | | **NEW COMMENTS FOR COMMENT #3** | | | | | | A} ADD COLD WATER SUPPLY AND WATER-HAMMER ARRESTOR FOR | | | ICE MAKER "G". PER FBC PLUMBING SECTION *601.1 SCOPE | | | AND SECTION *604.9 WATER HAMMER. | | | | | | B} INDICATE WATER-HAMMER ARRESTORS FOR WASHING MACHINE | | | CLOSER TO THE WATER OUTLET PER MANUFACTURER'S | | | RECOMMENDATIONS, NOT ON TOP OF RISER. PER FBC PLUMBING | | | SECTION *601.1 SCOPE AND SECTION *604.9 WATER HAMMER. | | | | | | C} PLEASE CORRECT THE FOLLOWING: THE HOT AND COLD | | | WATER ARE CROSSED (COLD SHOULD BE ON THE RIGHT AND HOT | | | SHOULD BE ON THE ON LEFT) FOR THE WASHING MACHINE AND | | | THE HAND SINK BY THE 3 COMP. SINK. PER FBC PLUMBING | | | SECTION *601.1 SCOPE. | | | | | | D} PLEASE DELETE THE FOLLOWING: THE EXTRA COLD WATER | | | FOR THE 3 COMP. SINK OR IDENTIFY WHAT IT IS FOR AND THE | | | TEE FITTINGS FOR BOTH THE COLD AND HOT WATER AFTER THE | | | VALVES TO THE 3 COMP. SINKS. PER FBC PLUMBING SECTION | | | *601.1 SCOPE. | | | | | | E} PLEASE CLEARLY INDICATE THAT THERE IS AN EXISTING | | | BACKFLOW PREVENTER OR A NEW ONE WILL BE INSTALLED AND | | | THAT THE EXISTING WATER HEATER IS PROTECTED FROM | | | EXPANSION CONTROL. PER FBC PLUMBING SECTIONS 608 AND | | | 607.3. | | | | | | 4. **OK** COMMENT ADDRESSED. | | | | | | 5. **OK** COMMENT ADDRESSED. | | | | | | 6. **OK** COMMENT ADDRESSED. | | | | | | 7. **OK** COMMENT ADDRESSED. | | | | | | 8. **OK** COMMENT ADDRESSED. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-27 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-27 |
Time |
10:00 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-27 |
Time |
10:00 |
Sent To |
|
|
| Notes |
| 2007-12-27 11:46:57 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. SHEET A1 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM: | | | THE TWO 3 COMPARTMENT SINKS SHALL DISCHARGE THROUGH AN | | | INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. PER | | | *802.1.1, FOOD HANDLING. SIZING OF THE COMBINATION | | | WASTE AND VENT SYSTEM SHALL BE PER SECTION *912, TABLE | | | *912.3. | | | | | | 2. A DRINKING FOUNTAIN IS REQUIRED PER TABLE *403.1(6) | | | MERCANTILE AND SHALL BE ACCESSIBLE PER THE FOLLOWING | | | REQUIREMENTS. | | | | | | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS | | | (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING | | | INFORMATION) | | | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET | | | MAXIMUM. | | | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN | | | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT | | | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN | | | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" | | | OF THE FRONT OF FOUNTAIN. | | | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE | | | MOUNTED NEAR FRONT EDGE. | | | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR | | | SPACE. | | | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS | | | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN | | | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS | | | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE | | | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS | | | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR | | | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED | | | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). | | | | | | 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3, | | | PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS | | | REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND | | | COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS, | | | LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW | | | PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE | | | WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER | | | ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED | | | (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS) | | | **604.9. | | | | | | 4. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY | | | INDICATE ON THE RESUBMITTAL THE FOLLOWING FOR THE | | | WASHING MACHINE. | | | | | | (A) 406.3 WASTE CONNECTIONS.THE TRAP AND | | | FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES | | | WASHER SHALL BE A MINIMUM OF 2 INCHES | | | (51MM) IN DIAMETER. | | | | | | (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY | | | TRAPPED. STANDPIPES SHALL | | | EXTEND A MINIMUM OF 18 INCHES (457MM) | | | AND A MAXIMUM OF 42 INCHES (1066MM) | | | ABOVE THE TRAP WEIR. ACCESS SHALL BE | | | PROVIDED TO ALL STANDPIPES AND DRAINS | | | FOR RODDING. | | | **INDICATE THE REQUIRED STANDPIPE. | | | | | | (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL | | | BE THE SAME NOMINAL SIZE AS THE PIPE | | | THEY SERVE UP TO 4 INCHES (102MM). | | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3". | | | | | | (D) 708.9 ACCESS. ACCESS SHALL BE | | | PROVIDED TO ALL CLEANOUTS. | | | **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT | | | 4' A.F.F. | | | | | | 5. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: PER | | | *708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION. | | | THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE JUNCTION OF | | | THE BUILDING DRAIN AND THE BUILDING SEWER. **CLEARLY | | | INDICATE THAT THERE IS AN EXISTING ONE OR THAT A NEW | | | ONE WILL BE PROVIDED ON THE RESUBMITTAL. | | | | | | 6. SHEET A1 NEW FLOOR PLAN WALK-IN COOLER: CLEARLY | | | INDICATE IF THIS COOLER WILL HAVE A CONENSATE DRAIN AND | | | WHERE IT WILL DISCHARGE. | | | 314.2.1 CONDENSATE DISPOSAL. | | | CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL | | | BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED | | | PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO | | | A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A | | | NUISANCE. | | | | | | 7. SHEET A1 EXISTING FLOOR PLAN DEMOLITION. | | | PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE | | | REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS | | | SHALL BE PROHIBITED. A PLUMBING PERMIT AND INSPECTION | | | REQUIRED OF DEMO WORK PRIOR TO COVERING DEMO WORK WITH | | | FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS. | | | **CLEARLYINDICATE THESE REQUIREMENTS ON THE | | | RESUBMITTED PLANS. | | | | | | 8. SHEET A1 PLUMBING NOTES #3 PLEASE DELETE AND ADD | | | THE FOLLOWING: MINIMUM SLOPE OF HORIZONTAL DRAINAGE | | | PIPE PER TABLE *704.1. PIPE SIZE 2-1/2" OR LESS MINIMUM | | | SLOPE IS 1/4" PER FOOT, PIPE 3" TO 6" MINIMUM SLOPE IS | | | 1/8" PER FOOT, PIPE 8" OR LARGER MINIMUM SLOPE IS 1/16" | | | PER FOOT. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | NOTE: THERE IS ONLY ONE CORRECTED DRAWING | | | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS | | | EXAMINER FOR REFERENCE FOR THE | | | RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-24 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-24 |
Time |
10:15 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-24 |
Time |
10:15 |
Sent To |
|
|
| Notes |
| 2007-12-24 10:15:47 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|