Plan Review Details - Permit 07120459
Plan Review Stops For Permit 07120459
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-03-28 Cont ID  
Sent By mjacobs Date 2008-03-28 Time 10:21 Rev Time 0.00
Received By mjacobs Date 2008-03-28 Time 07:15 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-02-06 Cont ID  
Sent By mjacobs Date 2008-02-06 Time 16:47 Rev Time 0.00
Received By mjacobs Date 2008-02-06 Time 15:36 Sent To  
Notes
2008-02-06 16:47:08BUILDING PLAN REVIEW
 PERMIT: 07120459
 ADD: 8989 OKEECHOBEE BLVD #212
 CONT: CHOEN INC.
 TEL: (561)362-4217
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
 2/06/08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NO RESPONSE NOT ADDRESSED**
 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) OK
 2)OK
 3)OK
 4)OK
 5)OK
 6)OK
  
 **NEW**
 **NO RESPONSE NOT ADDRESSED**
 A) THE NEW DRINKING FOUNTAIN LOCATION WILL HAVE TO
 COMPLY WITH FBC 1016.2 (EXCEPTIONS) #2. THE CORRIDOR
 WIDTH SHALL BE 36 INCHES WHEN THE OCCUPANT LOAD IS 50
 OR LESS. THE INSTALLATION OF THE DRINKING FOUNTAIN AT
 THIS LOCATION WILL PROHIBIT A PERSON IN A WHEELCHAIR
 ACCESS TO THE BATHROOM. THE SPACE INDICATED ON THE
 DRAWINGS IS 30 INCHES. SHEET A2 SHOWS FOUR DIFFERENT
 TYPES OF DRINKING FOUNTAINS; CIRCLE THE ONE WHICH WILL
 BE INSTALLED.
  
 FBC1008.1.1.1. THERE SHALL NOT BE PROJECTIONS INTO THE
 REQUIRED CLEAR WIDTH LOWER THAN 34 INCHES (864 MM)
 ABOVE THE FLOOR OR GROUND. PROJECTIONS INTO THE CLEAR
 OPENING WIDTH BETWEEN 34 INCHES (864 MM) AND 80 INCHES
 (2032 MM) ABOVE THE FLOOR OR GROUND SHALL NOT EXCEED 4
 INCHES (102 MM)
  
 FBC11-4.4.1
 OBJECTS PROJECTING FROM WALLS (FOR EXAMPLE, TELEPHONES)
 WITH THEIR LEADING EDGES BETWEEN 27 INCHES AND 80
 INCHES (685 MM AND 2030 MM) ABOVE THE FINISHED FLOOR
 SHALL PROTRUDE NO MORE THAN 4 INCHES (102 MM) INTO
 WALKS, HALLS, CORRIDORS, PASSAGEWAYS, OR AISLES [SEE
 FIGURE 8 (A)]. OBJECTS MOUNTED WITH THEIR LEADING EDGES
 AT OR BELOW 27 INCHES (685 MM) ABOVE THE FINISHED FLOOR
 MAY PROTRUDE ANY AMOUNT [SEE FIGURE 8 (A) AND FIGURE 8
 (B)]. FREE-STANDING OBJECTS MOUNTED ON POSTS OR PYLONS
 MAY OVERHANG 12 IN (305 MM) MAXIMUM FROM 27 INCHES TO
 80 INCHES (685 MM TO 2030 MM) ABOVE THE GROUND OR
 FINISHED FLOOR [SEE FIGURE 8 (C) AND FIGURE 8 (D)].
 PROTRUDING OBJECTS SHALL NOT REDUCE THE CLEAR WIDTH OF
 AN ACCESSIBLE ROUTE OR MANEUVERING SPACE [SEE FIGURE 8
 (E)].
  
 B)61G1-16.004. THE TITLE BLOCK ON THE DRAWINGS SHALL
 INCLUDE.
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT. OK
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.OK
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-15 Cont ID  
Sent By mjacobs Date 2008-01-15 Time 16:34 Rev Time 0.00
Received By mjacobs Date 2008-01-15 Time 12:06 Sent To  
Notes
2008-01-15 16:34:30 
 BUILDING PLAN REVIEW
 PERMIT: 07120459
 ADD: 8989 OKEECHOBEE BLVD #212
 CONT: CHOEN INC.
 TEL: (561)362-4217
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND
 ACTION: DENIED
 1/15/08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 **NO RESPONSE NOT ADDRESSED**
 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)THE SQUARE FOOTAGE PER OCCUPANT LOAD FOR A
 MERCANTILE OCCUPANCY IS NOT 15. SEE FBC TABLE 1004.1.2
 FOR THE CORRECT SQUARE FOOTAGE PER OCCUPANT LOAD.
  
 **NO RESPONSE NOT ADDRESSED**
 3)THE ACCESSIBLE COUNTER ON SHEET A1 SHALL INDICATE
 THE HEIGHT AND LENGTH OF THE COUNTER. FBC 11-7(2) (I)
 STATES, A PORTION OF THE MAIN COUNTER SHALL BE A
 MINIMUM OF 36 INCHES IN LENGTH AND 36 INCH HIGH. SEE
 SECTION 11-7 FOR MORE INFORMATION PERTAINING CHECK-OUT
 AISLES.
  
 **NO RESPONSE NOT ADDRESSED**
 4)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PERTAINING TO
 THE PROJECT. SEE SECTIONS 303, 304 AND 305 OF THIS
 CODE.
  
 **NO RESPONSE NOT ADDRESSED**
 5) ON THE APPLICATION CLEARLY DESCRIBE THE PROJECT TO
 AVOID DELAYS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. FBC
 106.1.1.INDICATE THE WIDTH OF EACH AISLE ON THE
 PLANS.
  
 **NO RESPONSE NOT ADDRESSED**
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 **NEW**
 A)THE NEW DRINKING FOUNTAIN LOCATION WILL HAVE TO
 COMPLY WITH FBC 1016.2 (EXCEPTIONS) #2. THE CORRIDOR
 WIDTH SHALL BE 36 INCHES WHEN THE OCCUPANT LOAD IS 50
 OR LESS. THE INSTALLATION OF THE DRINKING FOUNTAIN AT
 THIS LOCATION WILL PROHIBIT A PERSON IN A WHEELCHAIR
 ACCESS TO THE BATHROOM. THE SPACE INDICATED ON THE
 DRAWINGS IS 30 INCHES. SHEET A2 SHOWS FOUR DIFFERENT
 TYPES OF DRINKING FOUNTAINS; CIRCLE THE ONE WHICH WILL
 BE INSTALLED.
 .
 B)61G1-16.004 THE TITLE BLOCK ON THE DRAWINGS SHALL
 INCLUDE.
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
2008-01-15 16:32:54 

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-29 Cont ID  
Sent By mjacobs Date 2007-12-29 Time 11:51 Rev Time 0.00
Received By mjacobs Date 2007-12-28 Time 16:38 Sent To PC
Notes
2007-12-28 16:56:14 
 BUILDING PLAN REVIEW
 PERMIT: 07120459
 ADD: 8989 OKEECHOBEE BLVD
 CONT: CHOEN INC.
 TEL: (561)362-4217
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 12/28/07
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)THE SQUARE FOOTAGE PER OCCUPANT LOAD FOR A
 MERCANTILE OCCUPANCY IS NOT 15. SEE FBC TABLE 1004.1.2
 FOR THE CORRECT SQUARE FOOTAGE PER OCCUPANT LOAD.
  
 3)THE ACCESSIBLE COUNTER ON SHEET A1 SHALL INDICATE
 THE HEIGHT AND LENGTH OF THE COUNTER. FBC 11-7(2) (I)
 STATES, A PORTION OF THE MAIN COUNTER SHALL BE A
 MINIMUM OF 36 INCHES IN LENGTH AND 36 INCH HIGH. SEE
 SECTION 11-7 FOR MORE INFORMATION PERTAINING CHECK-OUT
 AISLES.
  
 4)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PERTAINING TO
 THE PROJECT. SEE SECTIONS 303, 304 AND 305 OF THIS
 CODE.
  
 5) ON THE APPLICATION CLEARLY DESCRIBE THE PROJECT TO
 AVOID DELAYS. CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS. FBC
 106.1.1.INDICATE THE WIDTH OF EACH AISLE ON THE
 PLANS.
  
 6)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-04-09 Cont ID  
Sent By btrobaug Date 2008-04-09 Time 12:42 Rev Time 0.00
Received By btrobaug Date 2008-04-09 Time 12:12 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-03-20 Cont ID  
Sent By btrobaug Date 2008-03-20 Time 17:21 Rev Time 0.00
Received By btrobaug Date 2008-03-20 Time 15:37 Sent To  
Notes
2008-03-20 17:08:00 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2007 REVISIONS, 2005
 NEC, NFPA-72 2002, NFPA-101 2003, 2004 FBC AS AMENDED,
 CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE FOLLOWING:
  
 1} THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING
 OR A SEPARATELY METERED OR PERMITTED PORTION OF A
 BUILDING SHALL BE DETERMINED BY EITHER THE BUILDING
 AREA METHOD DESCRIBED IN SECTION 415.2.C.1 OR THE
 SPACE-BY-SPACE METHOD DESCRIBED IN SECTION 415.2.B.1.
 TRADE-OFFS OF INTERIOR LIGHTING POWER ALLOWANCE AMONG
 PORTIONS OF THE BUILDING FOR WHICH A DIFFERENT METHOD
 OF CALCULATION HAS BEEN USED ARE NOT PERMITTED. THE
 INSTALLED INTERIOR LIGHTING POWER IDENTIFIED IN
 ACCORDANCE WITH SECTION 415.2.ABC.1.1 SHALL NOT EXCEED
 THE INTERIOR LIGHTING POWER ALLOWANCE DEVELOPED IN
 ACCORDANCE WITH SECTION 415.2.C.1 OR 415.2.B.1. THIS
 CAN BE DEMONSTRATED ON THE PLANS INDICATED THE WATTAGES
 OF THE LUMINAIRES CHOSEN FOR THE PROJECT CONFORM TO THE
 DENSITY REQUIREMENTS. THIS WAS NOT DONE.THE STATEMENT
 THAT THE MAXIMUM IS 1.4 W/SF DOES NOT INDICATE WHAT THE
 CALCULATED WATTAGE IS. THE DESIGNER MUST INDICATE HOW
 THE DENSITY COMPLIANCE WAS ACHIEVED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-02-04 Cont ID  
Sent By dpalmer Date 2008-02-04 Time 16:55 Rev Time 0.00
Received By dpalmer Date 2008-02-04 Time 16:55 Sent To  
Notes
2008-02-04 16:55:23** DENIED 3RD REVIEW **
  
 ** PLEASE SEE THERE ARE STILL COMMENTS WHICH ARE
 REPEATED FROM THE TWO PREVIOUS REVIEWS WHICH ARE STILL
 IN NEED OF ADDRESSING.
  
 1) NOTE: PLEASE SEE PREVIOUS COMMENTS WHICHSTATED THE
 TITLE BLOCKS WERE MISSING REQUIRED LICENSE INFORMATION
 PER FAC 61G1-16.004 AND FS 481.219. AN ATTACHED SHEET
 INDICATING THE FIRM HAS A LICENSE WAS VERIFIED WITH THE
 DEPARTMENT OF BUSINESS AND PROFESSIONAL REGULATION
 HOWEVER PLEASE SEE AS STATED ON PREVIOUS REVIEWS THIS
 FIRM LICENSE NUMBER IS REQUIRED TO BE ON TITLE BLOCKS.
 IF THIS HAD BEEN THE ONLY COMMENT THIS WOULD BE BEEN
 WRITTEN ON PLANS, HOWEVER AS THERE ARE OTHER COMMENTS,
 THIS NEEDS TO BE CORRECTED AND ADDED TO TITLE BLOCKS
 ACCORDINGLY.
  
 2) NOTE: PLEASE SEE PREVIOUS REVIEW COMMENTS WITH
 RESPECT TO CHAPTER 13 COMPLIANCE.
 A NOTE IS NOW PLACED ON PLANS WHICH STATES IT WILL BE
 TIED INTO THE BUILDINGS LIGHTING CONTROL SYSTEM WITH
 OVER RIDES IN SPACE.
 PLEASE KNOW THE BUILDING AS A WHOLE BY DEFINITION DOES
 NOT CONTAIN A WHOLE BUILDING SYSTEM. THESE LIGHTING
 CONTROLS AS NOTED ARE REQUIRED IN THE TENANT SPACE
 ALONG WITH SEPARATE SPACES WITHIN THE TENANT SPACE.
 THE PLANS NOTE THAT LIGHTING CONTROLS ARE TO MEET CODE
 HOWEVER SHOW ABSOLUTELY NO DESIGN CRITERIA. THE CODE OR
 PARTS OF THE CODE MAY NOT BE *QUOTED* IN LIEU OF
 SHOWING *MINIMUM CODE COMPLIANCE DESIGN*.
 AS STATED ON PREVIOUS REVIEWS, PLEASE SEE
 13-415.1.ABC.1.1, .1.2 AND .1.3 FOR REQUIRED LIGHTING
 CONTROLS WHICH ARE MISSING.
 PLEASE COMPLETE INFORMATION ON TYPES OF DEVICES, TYPES
 OF SYSTEM, TIMES ON OVER RIDES, SCHEDULING, ETC.
  
 PLEASE SEE 13-415.2 AS NOTED ON BOTH PREVIOUS REVIEWS.
 PLEASE SUBMIT LIGHTING PERFORMANCE CALCULATIONS AS
 MENTIONED.
 THE SUBMITTED SHEETS FROM AN *ELITE SOFTWARE
 DEVELOPMENT IN* IS NOT ADOPTED BY THE FBC CHAPTER 13.
 PLEASE SEE 13-400.3.B, 13-400.3.B. PLEASE KNOW THE
 ADOPTED PROGRAM UNDER THE STATE OF FLORIDA AND THE
 FLORIDA BUILDING COMMISSION IS THAT OF FLA-COM WHICH IS
 STATED IN THE CODE SECTIONS AS GIVEN ON BOTH PREVIOUS
 REVIEWS INCLUSIVE OF THIS REVIEW.
 PLEASE SEE AS REQUIRED, PLEASE COMPLETE FIXTURE LEGEND
 ON PLANS AND BE SURE TO COORDINATE WITH THE INPUT
 DATA.
 ** PLEASE KNOW THE LIGHTING LEVELS AS SHOWN ON
 DOCUMENTS SUBMITTED ON PAGE #3 FAR EXCEED THE MAXIMUM
 ALLOWANCES PERMITTED IN 13-415.2, 13-415.2.ABC.1.1 ETC
  
 3) NOTE: PLEASE SEE PREVIOUS NOTES WITH RESPECT TO LOAD
 CALCULATIONS PER THE NEC PER
 220.12,220.14,220.42,220.44,215.3,230.42 ETC.
 SAME COMMENT AS NOTED PREVIOUSLY.
  
 4) NOTE: PLEASE FBC AS ANY REQUIRED FIRE ALARM SYSTEM
 AS REQUIRED UNDER THE FBC SHALL SHOW THE BASE REQUIRED
 DESIGN ON BUILDING PLANS. IT IS KNOWN THAT SEPARATE
 PERMITS AND SHOP DRAWINGS ARE SUBMITTED AT A LATER DATE
 FOR PERMITTING HOWEVER THE PLANS ARE REQUIRED TO SHOW
 MINIMUM COMPLIANCE FOR ANY REQUIRED SYSTEM AND/OR
 DEVICES.
 PLEASE SEE CHAPTER 11 AS STATED ON PREVIOUS REVIEW WITH
 RESPECT TO ADA COMPLIANCE WHICH IS REQUIRED ON BASE
 PLANS AS WELL AS ANY SEPARATE PERMITS.
 PLEASE SEE 11-4.28.1,.2,.3(4) FOR DEVICES, LOCATIONS AS
 WELL AS MINIMUM ADA COMPLIANCE LEVELS.
 THIS IS REQUIRED FOR ANY REQUIRED SYSTEM BY OTHER CODES
 BY BUILDING REVIEW OR FIRE MARSHAL.
  
 5) NOTE: PLEASE SEE PREVIOUS REVIEW GAVE NOTICE TO FS
 553.80(2)(B) WITH RESPECT TO REPEAT CODE COMPLIANCE
 COMMENTS. THE RESPONSE FROM DESIGNER SPEAKS OF
 OCCUPANCY OF THE MERCANTILE LOCATION?
 PLEASE KNOW AS THERE ARE REPEATED COMMENTS AND AS
 REQUIRED BY FLORIDA STATUES A FEE OF $2040.00 HAS BEEN
 ASSESSED TO THE DESIGNER OF RECORD.\
 THIS FEE IS NOT FOR THE OWNER OR CONTRACTOR AND IS
 REQUIRED BY STATE STATUTES TO BE PAID BEFORE PLANS MAY
 BE RESUBMITTED FOR THE 4TH REVIEW.
 ONE COPY OF ELECTRICAL PLANS IS BEING RETAINED BY THIS
 OFFICE.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-15 Cont ID  
Sent By dpalmer Date 2008-01-15 Time 10:58 Rev Time 0.00
Received By dpalmer Date 2008-01-15 Time 10:58 Sent To  
Notes
2008-01-15 10:59:57 
  
 ** DENIED2ND REVIEW **
  
 ** PLEASE SEE ALMOST EVERY COMMENT FROM THE PREVIOUS
 REVIEW IS THE EXACT SAME COMMENT WITHOUT ANY CHANGES OR
 CORRECTIONS MADE.
 ** THERE ARE RESPONSE LETTERS FOR PLUMBING REVIEW
 HOWEVER NOT FOR ELECTRICAL OR OTHER TRADES.
  
  
 1) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. PLEASE BE SURE
 ADDRESS COMMENTS. THIS IS ONLY AN NOTICE AT THIS TIME.
 ONE SET OF PLANS WILL BE RETAINED
  
 2) NOTE:SAME COMMENT:
 PLEASE SEE CODES TO BE STATED ON PLANS ARE NEEDED AS
 FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2003 NFPA-101
  
 3) NOTE:SAME COMMENT:
 PLEASE SEE WHAT APPEARS TO BE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER PER FAC 61G1-16.004 AND FS
 481.219. PLEASE SEE FS 481.219 AS STATED AS A *DESIGN
 FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY NOT
 DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM AS
 SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE PROVIDE
 THE CA NUMBER AS REQUIRED.
 PLEASE CONFIRM.
  
 4) NOTE: SAME COMMENT:
 PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW AND
 INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL
 BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL
 SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS
 INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON
 PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF
 MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE
 SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED.
 NEC 408.4, 310.16, 240.4 ETC
 FBC106.1.2, 106.3.5.1.2
  
 5) NOTE:SAME COMMENT: CALCULATIONS WERE ADJUSTED WITH
 SOME MINOR CHANGES HOWEVER THEYA RE NOT CODE COMPLIANT
 FOR COMMERCIAL.
  
 PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON PANEL ARE
 THAT FOR A RESIDENCE. PLEASE SEE 220.12, 220.14,
 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42 FOR
 CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%. PLEASE
 SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR SIGN
 CIRCUIT IS 1200VA.
 PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE
 SHOWN PER 220.43
 PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET
 COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT
 CALCULATIONS CAN NOT BE DONE AT THIS TIME.
  
 6) NOTE:SAME COMMENT:
 PLEASE SEE THE PLANS INDICATE TWO PANELS YET THE PLANS
 ONLY SHOW ONE?
 PLEASE COMPLETE AND CORRELATE.
 408.4, 240.24, ETC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 7) NOTE: SAME COMMENT:
 PLEASE SEE THE DRYER AS SHOWN ON PANEL SCHEDULE IS
 SHOWN AS 5KW YET THE BRANCH CIRCUIT IS SHOWN AS A
 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD EXCEEDS
 THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT A
 2-POLE CIRCUIT?
 PLEASE SEE 240.4, 310.16, ETC
 FBC 106.1.2
  
 8) NOTE: COMMENT OK FOR COOLER UNDER SEPARATE PERMIT.
  
 9) NOTE:SAME COMMENT:
 PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND .1.3.
 PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED
 SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS
 A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K
 SQ FT.
 PLEASE CLEARLY SHOW NEW WORK AND EXISTING.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME
 AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE
 COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON
 FIXTURES AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: SAME COMMENT:
 PLEASE CLARIFY WHAT APPEARS TO BE A FIRE ALARM DEVICE
 ON PLANS. PLANS INDICATE A FA IN A BOX HOWEVER AS THE
 SYMBOL LEGEND DOES NOT SHOW THIS IT IS UNCLEAR WHAT
 THIS IS?
 PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE
 SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR
 ADA.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 08:29 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 16:59 Sent To  
Notes
2007-12-23 08:29:58** DENIED**
  
  
 1) NOTE: PLEASE CLARIFY PROPOSED SCOPE OF WORK AND
 OCCUPANCY. THE PERMIT APPLICATION ORIGINALLY INDICATED
 A *MASSAGE THERAPY* FIT-OUT, THEN THAT WAS CROSSED OUT
 FOR * FOOD RETAIL*. THE PACKAGE CONTAINS A LETTER FROM
 GESULT DESIGN STUDIO WHICH IS ADDRESSED TO PALM BEACH
 COUNTY BLDG DEPT, AND SEEMS TO RESPOND TO COMMENTS.
 THIS LETTER SPECIFIES THE OCCUPANCY AS FRESH FRUIT
 BOUQUET CO.
 PLEASE INDICATE AND CORRELATEALL .
  
 2) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS
 2004 FBC W/2007 REVISIONS
 2005 NFPA-70 (SHOWS 2002)
 2003 NFPA-101
  
 3) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING
 CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004
 AND FS 481.219. PLEASE SEE FS 481.219 AS STATED AS A
 *DESIGN FIRM* WHICH IS NO LICENSED AS NOTED ABOVE MAY
 NOT DESIGN COMMERCIAL WORK AS SHOWN. IF THE DESIGN FIRM
 AS SHOWN IS PART OF THE ARCHITECT AS LISTED PLEASE
 PROVIDE THE CA NUMBER AS REQUIRED.
 PLEASE CONFIRM.
  
 4) NOTE: PLEASE SHOW ALL CIRCUITING ON PLANS FOR NEW
 AND INDICATE ALL WHICH EXISTS. PLEASE SEE 700.12F FOR
 CIRCUITING OF EMERGENCY AND EXIT LIGHTS AS THESE SHALL
 BE CIRCUITED TO THE LOCAL LIGHTING BRANCH CIRCUIT IN
 THAT AREA. PLEASE BE SURE ALL CIRCUITS ON PANEL
 SCHEDULE CORRELATE WITH PLANS. FOR EXAMPLE: PLANS
 INDICATE A WATER HEATER HOWEVER THIS IS NOT SHOWN ON
 PANEL SCHEDULE? PLEASE COMPLETE THE ABOVE FOR REVIEW OF
 MINIMUM CODE COMPLIANCE. CIRCUITS ON SCHEDULE ARE TO BE
 SPECIFIC TO AREAS/ITEMS IN WHICH THEY FEED.
 NEC 408.4, 310.16, 240.4 ETC
 FBC106.1.2, 106.3.5.1.2
  
 5) NOTE: PLEASE SEE THE LOAD CALCULATIONS AS SHOWN ON
 PANEL ARE THAT FOR A RESIDENCE. PLEASE SEE 220.12,
 220.14, 220.42, 220.44 ETC. PLEASE SEE 215.5, 230.42
 FOR CONTINUOUS LOADS WHICH ARE TO BE SHOWN AT 125%.
 PLEASE SEE 600.5 AS THE MINIMUM LOAD TO BE SHOWN FOR
 SIGN CIRCUIT IS 1200VA.
 PLEASE SEE THE MINIMUM VA FOR SHOW WINDOWS SHALL BE
 SHOWN PER 220.43
 PLEASE KNOW AT THIS TIME THE CALCULATIONS DO NOT MEET
 COMMERCIAL MINIMUM THEREFORE A REVIEW OF THE CORRECT
 CALCULATIONS CAN NOT BE DONE AT THIS TIME.
  
 6) NOTE: PLEASE SEE THE PLANS INDICATE TWO PANELS YET
 THE PLANS ONLY SHOW ONE?
 PLEASE COMPLETE AND CORRELATE.
 408.4, 240.24, ETC
 FBC 106.1.2 ADMIN SECTION FOR ADDITIONAL INFORMATION.
  
 7) NOTE: PLEASE SEE THE DRYER AS SHOWN ON PANEL
 SCHEDULE IS SHOWN AS 5KW YET THE BRANCH CIRCUIT IS
 SHOWN AS A 1-POLE 30AMP BREAKER. PLEASE KNOW THIS LOAD
 EXCEEDS THAT OF A 1-POLE CIRCUIT AT 30AMPS. IS THIS NOT
 A 2-POLE CIRCUIT?
 PLEASE SEE 240.4, 310.16, ETC
 FBC 106.1.2
  
 8) NOTE: PLEASE SEE PLANS MENTIONS COOLER IS TO BE
 INSTALLED BY OTHERS HOWEVER ELECTRICAL IS NEEDED AT
 THIS TIME UNLESS ALL WILL BE UNDER SEPARATE PERMITS OR
 REVISED AT A LATER DATE?
 240,220, 310, ETC
 FBC 106.1.2
  
 9) NOTE: PLEASE SEE FBC 13-415.1.ABC.1.1, .1.2 AND
 .1.3.
 PLEASE KNOW THAT ANY NEW LIGHTING CONTROLS INSTALLED
 SHALL MEET THE AUTOMATED CONTROLS AS REQUIRED. THIS IS
 A TENANT SPACE IN A *BUILDING* WHICH IS GREATER THAN 5K
 SQ FT.
 PLEASE CLEARLY SHOW NEW WORK AND EXISTING.
 PLEASE PROVIDE LIGHTING PERFORMANCE CALCULATIONS PER
 13-415.2.
 PLEASE SEE AS NEW LIGHTING IS BEING INSTALLED IN SOME
 AREAS THIS IS REQUIRED FOR LIGHTING DENSITIES. PLEASE
 COMPLETE THE FIXTURE LEGEND WITH ALL INFORMATION ON
 FIXTURES AS SHOWN.
 FBC 106.3.5.1.2, 106.1.2
  
 10) NOTE: PLEASE CLARIFY WHAT APPEARS TO BE A FIRE
 ALARM DEVICE ON PLANS. PLANS INDICATE A FA IN A BOX
 HOWEVER AS THE SYMBOL LEGEND DOES NOT SHOW THIS IT IS
 UNCLEAR WHAT THIS IS?
 PLEASE KNOW IF THIS IS A FIRE ALARM DEVICE(S) PLEASE
 SEE FBC 11-4.28.1, .2 AND .3(4) FOR MINIMUM LEVELS FOR
 ADA.
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status P Date 2008-03-31 Cont ID  
Sent By mawillia Date 2008-03-31 Time 11:56 Rev Time 0.00
Received By mawillia Date 2008-03-31 Time 11:30 Sent To  
Notes
2008-03-31 11:52:30*****APPROVED*****
  
  
 PLAN SHEETS A-1.2, A-1.3, E-1.1, AND FP-1.1 WERE
 STAMPED, INITIALED, AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status F Date 2008-02-13 Cont ID  
Sent By mwennerg Date 2008-02-13 Time 15:33 Rev Time 0.00
Received By mwennerg Date 2008-02-13 Time 15:33 Sent To  
Notes
2008-02-13 15:45:02***DENIED***
  
 1) OK
  
 2) RESPONSE INDICATES THAT FIRE EXTINGUISHERS ARE SHOWN
 ON PLAN. PLEASE NOTE UNABLE TO LOCATE.
  
 3) OK
  
 4) IF FIRE ALARM EQUIPMENT IS PART OF THE SCOPE OF THIS
 WORK, ALL APPLICABLE EQUIPMENT IS TO BE ILLUSTRATED ON
 PLANS.THE TERM FIRE ALARM CAN BE CONSIDERED GENERIC AND
 DOES NOT IDENTIFY THE SPECIFIC DEVICE SHOWN ON PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-01-16 Cont ID  
Sent By mwennerg Date 2008-01-16 Time 14:56 Rev Time 0.00
Received By mwennerg Date 2008-01-16 Time 14:56 Sent To  
Notes
2008-01-16 14:57:39***DENIED***
  
 THESE COMMENTS WERE TAKEN DIRECTLY FROM THE FIRST FIRE
 REVIEW.
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE.
  
 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE
 WITH FIRE SPRINKLER COVERAGE.
  
 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON
 PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mwennerg Date 2007-12-28 Time 10:37 Rev Time 0.00
Received By mwennerg Date 2007-12-28 Time 10:37 Sent To  
Notes
2007-12-28 10:44:38***DENIED***
  
 1) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL IF APPLICABLE.
  
 2) MINIMUM RATED 2A- 10B,CFIRE EXTINGUISHERS ARE
 REQUIRED TO BE MOUNTED AT DISTANCES NOT TO EXCEED 75'
 TRAVEL DISTANCE.
  
 3) STORAGE SHELVING SHALL NOT OBSTRUCT OR INTERFERE
 WITH FIRE SPRINKLER COVERAGE.
  
 4) LIFE SAFETY TO COMPLY WITH NFPA 101, 2003 EDITION.
  
 5) PLEASE CLARIFY FA AS THAT SYMBOL IS NOT REFLECTED ON
 PLANS.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 09:08 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 09:08 Sent To M
Notes
2008-06-16 09:09:02TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-04-03 Cont ID  
Sent By shill Date 2008-04-03 Time 16:47 Rev Time 0.00
Received By shill Date 2008-04-03 Time 16:47 Sent To E
Notes
2008-04-03 16:47:33TO "BTROBAUG" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 14:08 Rev Time 0.00
Received By shill Date 2008-03-19 Time 14:08 Sent To  
Notes
2008-03-19 14:11:30TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-31 Cont ID  
Sent By adarroug Date 2008-01-31 Time 09:00 Rev Time 0.00
Received By adarroug Date 2008-01-31 Time 09:00 Sent To  
Notes
2008-01-31 09:02:37TO "BOB"#12

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-10 Cont ID  
Sent By mmiller Date 2008-01-10 Time 16:08 Rev Time 0.00
Received By mmiller Date 2008-01-10 Time 16:08 Sent To  
Notes
2008-01-10 16:09:32SENT TO BOB # 05

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-12-29 Time   Rev Time 0.00
Received By adarroug Date 2007-12-19 Time 11:17 Sent To  
Notes
2007-12-21 17:11:20TO "BOB" # 412/21/07SPALMER
2007-12-19 11:22:18WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-16 Cont ID  
Sent By tgordon Date 2008-06-16 Time 14:30 Rev Time 0.30
Received By tgordon Date 2008-06-16 Time 14:30 Sent To  
Notes
2008-06-16 14:32:30RECIVED NOA FOR ROOF TOP CONDENSER UNIT STANDS FOR
 WALK-IN COOLER.
  
 *** FILED WITH PERMIT # 08040403 ***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-24 Cont ID  
Sent By tgordon Date 2008-03-24 Time 14:20 Rev Time 0.30
Received By tgordon Date 2008-03-24 Time 14:19 Sent To  
Notes
2008-03-24 14:25:43*** PROVISO ***
 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 10:35 Rev Time 0.30
Received By tgordon Date 2007-12-26 Time 10:35 Sent To  
Notes
2007-12-26 10:38:43NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 *** PROVISO ***
 1) ADDITIONAL MECHANICAL PERMITS REQUIRED FOR
 (A) WALK-IN-COOLER.
 (B) CLOTHES DRYER VENT.
 ** SUBMIT PLANS WITH PERMIT APPLICATION.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-03-24 Cont ID  
Sent By mperson Date 2008-03-24 Time 09:09 Rev Time 0.00
Received By mperson Date 2008-03-24 Time 09:09 Sent To  
Notes
2008-03-24 09:16:19****************PROVISO****************
 AIR CHAMBERS ARE NOT COMPLIANT WITH FBC PLUMBING
 CHAPTER 6, SECTION 604.9, WATER HAMMER AND SHALL NOT BE
 INSTALLED. REFERENCE PLUMBING GENERAL NOTES AND
 SPECIFICATIONS (NOTE # 4) ON SHEET P-2.1 AND COMPLY.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 3 Status F Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 10:32 Rev Time 0.00
Received By mperson Date 2008-02-05 Time 10:32 Sent To  
Notes
2008-02-05 10:44:48PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 3RD TIME:
  
 1. NOTE: PREVIOUS PLUMBING PLAN REVIEW COMMENTS HAVE
 BEEN ADDRESSED, HOWEVER UNTIL ELECTRICAL COMMENT #1
 ABOUT THE TITLE BLOCKARE ADDRESSED PLANS WILL REMAIN
 IN FAILED STATUS. PER FAC 61G1-16.004 AND FS 481.219.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-01-17 Cont ID  
Sent By mperson Date 2008-01-18 Time 16:37 Rev Time 0.00
Received By mperson Date 2008-01-18 Time 07:51 Sent To  
Notes
2008-01-17 16:58:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS PLAN REVIEW COMMENTS**
  
 1. **OK** COMMENT ADDRESSED.
  
 2. **OK** COMMENT ADDRESSED.
  
 3. NOTE: COMMENT RESPONSE NOTED, HOWEVER SEE NEW
 COMMENTS BELOW ORIGINAL COMMENT.
 **PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 **NEW COMMENTS FOR COMMENT #3**
  
 A} ADD COLD WATER SUPPLY AND WATER-HAMMER ARRESTOR FOR
 ICE MAKER "G". PER FBC PLUMBING SECTION *601.1 SCOPE
 AND SECTION *604.9 WATER HAMMER.
  
 B} INDICATE WATER-HAMMER ARRESTORS FOR WASHING MACHINE
 CLOSER TO THE WATER OUTLET PER MANUFACTURER'S
 RECOMMENDATIONS, NOT ON TOP OF RISER. PER FBC PLUMBING
 SECTION *601.1 SCOPE AND SECTION *604.9 WATER HAMMER.
  
 C} PLEASE CORRECT THE FOLLOWING: THE HOT AND COLD
 WATER ARE CROSSED (COLD SHOULD BE ON THE RIGHT AND HOT
 SHOULD BE ON THE ON LEFT) FOR THE WASHING MACHINE AND
 THE HAND SINK BY THE 3 COMP. SINK. PER FBC PLUMBING
 SECTION *601.1 SCOPE.
  
 D} PLEASE DELETE THE FOLLOWING: THE EXTRA COLD WATER
 FOR THE 3 COMP. SINK OR IDENTIFY WHAT IT IS FOR AND THE
 TEE FITTINGS FOR BOTH THE COLD AND HOT WATER AFTER THE
 VALVES TO THE 3 COMP. SINKS. PER FBC PLUMBING SECTION
 *601.1 SCOPE.
  
 E} PLEASE CLEARLY INDICATE THAT THERE IS AN EXISTING
 BACKFLOW PREVENTER OR A NEW ONE WILL BE INSTALLED AND
 THAT THE EXISTING WATER HEATER IS PROTECTED FROM
 EXPANSION CONTROL. PER FBC PLUMBING SECTIONS 608 AND
 607.3.
  
 4. **OK** COMMENT ADDRESSED.
  
 5. **OK** COMMENT ADDRESSED.
  
 6. **OK** COMMENT ADDRESSED.
  
 7. **OK** COMMENT ADDRESSED.
  
 8. **OK** COMMENT ADDRESSED.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By mperson Date 2007-12-27 Time 10:00 Rev Time 0.00
Received By mperson Date 2007-12-27 Time 10:00 Sent To  
Notes
2007-12-27 11:46:57PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET A1 SANITARY ISOMETRIC PLUMBING RISER DIAGRAM:
 THE TWO 3 COMPARTMENT SINKS SHALL DISCHARGE THROUGH AN
 INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP. PER
 *802.1.1, FOOD HANDLING. SIZING OF THE COMBINATION
 WASTE AND VENT SYSTEM SHALL BE PER SECTION *912, TABLE
 *912.3.
  
 2. A DRINKING FOUNTAIN IS REQUIRED PER TABLE *403.1(6)
 MERCANTILE AND SHALL BE ACCESSIBLE PER THE FOLLOWING
 REQUIREMENTS.
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELAVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED WORK FOR BOTH THE HOT AND
 COLD WATER INDICATING THE PIPE SIZES, VALVE LOCATIONS,
 LOCATION OF THE WATER SUPPLY LINE WITH BACKFLOW
 PREVENTER **608, THERMAL EXPANSION CONTROL FOR THE
 WATER HEATER **607.3, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 4. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: CLEARLY
 INDICATE ON THE RESUBMITTAL THE FOLLOWING FOR THE
 WASHING MACHINE.
  
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER.
  
 (B) 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS
 FOR RODDING.
 **INDICATE THE REQUIRED STANDPIPE.
  
 (C) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE 3".
  
 (D) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 **CLEANOUT FOR THE WASHING MACHINE SHALL BE LOCATED AT
 4' A.F.F.
  
 5. SHEET A1 SANITARY ISOMETRIC RISER DIAGRAM: PER
 *708.3.5 BUILDING DRAIN AND BUILDING SEWER JUNCTION.
 THERE SHALL BE A TWO-WAY CLEANOUT NEAR THE JUNCTION OF
 THE BUILDING DRAIN AND THE BUILDING SEWER. **CLEARLY
 INDICATE THAT THERE IS AN EXISTING ONE OR THAT A NEW
 ONE WILL BE PROVIDED ON THE RESUBMITTAL.
  
 6. SHEET A1 NEW FLOOR PLAN WALK-IN COOLER: CLEARLY
 INDICATE IF THIS COOLER WILL HAVE A CONENSATE DRAIN AND
 WHERE IT WILL DISCHARGE.
 314.2.1 CONDENSATE DISPOSAL.
 CONDENSATE FROM ALL COOLING COILS AND EVAPORATORS SHALL
 BE CONVEYED FROM THE DRAIN PAN OUTLET TO AN APPROVED
 PLACE OF DISPOSAL. CONDENSATE SHALL NOT DISCHARGE INTO
 A STREET, ALLEY OR OTHER AREAS SO AS TO CAUSE A
 NUISANCE.
  
 7. SHEET A1 EXISTING FLOOR PLAN DEMOLITION.
 PER FBC-2004 PLUMBING, SECTION 704.5 DEAD ENDS: IN THE
 REMOVAL OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS
 SHALL BE PROHIBITED. A PLUMBING PERMIT AND INSPECTION
 REQUIRED OF DEMO WORK PRIOR TO COVERING DEMO WORK WITH
 FINNISH WALLS, CIELINGS, OR POURED CONCRETE SLABS.
 **CLEARLYINDICATE THESE REQUIREMENTS ON THE
 RESUBMITTED PLANS.
  
 8. SHEET A1 PLUMBING NOTES #3 PLEASE DELETE AND ADD
 THE FOLLOWING: MINIMUM SLOPE OF HORIZONTAL DRAINAGE
 PIPE PER TABLE *704.1. PIPE SIZE 2-1/2" OR LESS MINIMUM
 SLOPE IS 1/4" PER FOOT, PIPE 3" TO 6" MINIMUM SLOPE IS
 1/8" PER FOOT, PIPE 8" OR LARGER MINIMUM SLOPE IS 1/16"
 PER FOOT.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-24 Cont ID  
Sent By choops Date 2007-12-24 Time 10:15 Rev Time 0.00
Received By choops Date 2007-12-24 Time 10:15 Sent To  
Notes
2007-12-24 10:15:47*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.