Plan Review Details - Permit 07120434
Plan Review Stops For Permit 07120434
Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-26 Cont ID  
Sent By mjacobs Date 2007-12-26 Time 16:51 Rev Time 0.00
Received By mjacobs Date 2007-12-26 Time 16:26 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 15:32 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 15:32 Sent To  
Notes
2007-12-22 15:34:58REDLINED PLANS.
  
 PLANS DO NOT SHOW ANY NEW CIRCUITS AND ALL ARE EXISTING
 OR EXISTING TO BE RE-LOCATED. PLEASE SUBMIT A REVISED
 PANEL SCHEDULE SHOWING ANY *NEW* CIRCUITS SHOWING OVER
 CURRENT PROTECTION, AND CONDUCTOR SIZES IF NEW ARE
 INSTALLED. NO INFORMATION IS NEEDED AT THIS TIME.
 408.4, 240.4, 310.16
 FBC 106.3.5.1.2, 106.1.2

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-28 Cont ID  
Sent By mwennerg Date 2007-12-28 Time 14:03 Rev Time 0.00
Received By mwennerg Date 2007-12-28 Time 14:03 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-04 Cont ID  
Sent By adarroug Date 2008-03-04 Time 10:57 Rev Time 0.00
Received By adarroug Date 2008-03-04 Time 10:57 Sent To P
Notes
2008-03-04 10:57:31TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-12 Cont ID  
Sent By adarroug Date 2008-02-12 Time 15:24 Rev Time 0.00
Received By adarroug Date 2008-02-12 Time 15:24 Sent To P
Notes
2008-02-12 15:25:27TO "P" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-28 Cont ID  
Sent By mwennerg Date 2007-12-28 Time 14:04 Rev Time 0.00
Received By mwennerg Date 2007-12-18 Time 12:05 Sent To  
Notes
2007-12-20 18:04:40SENT TO BOB # 15 AS OF 12/20/2007 MMILLER
2007-12-18 12:06:26WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-26 Cont ID  
Sent By tgordon Date 2007-12-26 Time 10:54 Rev Time 0.25
Received By tgordon Date 2007-12-26 Time 10:54 Sent To  
Notes
2007-12-26 10:56:56NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.
  
 *** PROVISO ***
 1) A MECHANICAL PERMIT WILL BE REQUIRED FOR CLOTHES
 DRYER VENT AND BATHROOM EXHAUST.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-07 Cont ID  
Sent By mperson Date 2008-03-07 Time 08:36 Rev Time 0.00
Received By mperson Date 2008-03-07 Time 08:36 Sent To PC
Notes
2008-03-07 08:50:16****************PROVISO****************
 NOTE: REVISION REQUIRED WITH THE FOLLOWING INFORMATION
 ON SHEET P101:
  
 A} A 4" AERATOR FITTING IS REQUIRED FOR THE RELOCATED
 WASHING MACHINE AND NEW MACERATING UNIT.
  
 B} THE 1-1/2" VENT FROM THE TOP OF THE MACERATING UNIT
 COLLECTION TANK SHALL TIE INTO THE 2" VENT 6" ABOVE THE
 WASHING MACHINE STANDPIPE INLET.
  
 C} THE 2" VENT SHALL BE REQUIRED TO TIE BACK INTO THE
 4" SOIL STACK A MINIMUM OF 36" ABOVE THE NEW 4" AERATOR
 FITTING FOR THE WASHING MACHINE AND MACERATING UNIT.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-15 Cont ID  
Sent By mperson Date 2008-02-15 Time 13:20 Rev Time 0.00
Received By mperson Date 2008-02-14 Time 13:20 Sent To PC
Notes
2008-02-14 14:26:26PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 **PREVIOUS REVIEW COMMENTS**
  
 1. **OK, COMMENT ADDRESSED**
  
 2. ** OK,COMMENT ADDRESSED**
  
 3. **OK, COMMENT ADDRESSED**
  
 4. **OK, COMMENT ADDRESSED**
  
 5. **NO COMMENT RESPONSE, NEW COMMENTS TO FOLLOW WITH
 THE REDESIGNED SYSTEM ADDING THE MACERATING UNIT**
  
 PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE NEW
 AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH IN
 REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER
 K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING
 WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR
 FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO
 THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT
 JOINT SYSTEMS.
  
 6. **NO COMMENT RESPONSE, AERATOR FITTING REQUIRED FOR
 THE WASHINGMACHINE AND MACERATING UNIT**
  
 NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL BE
 SUPPORTED. PER SECTION *308 PIPING SUPPORT.
  
 7. **OK, COMMENT ADDRESSED**
  
 **THE FOLLOWING ARE NEW COMMENTS FOR THE REDESIGNED
 PLUMBING SYSTEM WITH THE ADDITION OF THE MACERATING
 UNIT**
  
 8. SHEET P101 IS MISSING THE CERTIFICATE OF
 AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES. PER FLORIDA
 ADMINISTRATIVE CODE (2) 61G15-23.002 AND FLORIDA
 STATUTES 471.023 (2). PLEASE REFERENCE CERTIFICATE OF
 AUTHORIZTION NUMBER FOR TEELE & ASSOCIATES FROM DBPR
 WEB SITE ATTACHED TO THESE PLUMBING COMMENTS.
  
 9. PER CITY OF WPB AMENDMENTS TO CHAPTER 1, SECTION
 106.1 SUBMITTAL DOCUMENTS. CONSTRUCTION DOCUMENTS,
 SPECIAL INSPECTION AND STRUCTURAL OBSERVATION PROGRAMS,
 AND OTHER DATA SHALL BE SUBMITTED IN TWO OR MORE SETS
 WITH EACH APPLICATION FOR A PERMIT.
 **ONLY ONE COPY OF THE MANUFACTURE'R SPECIFICATION
 SHEETS FOR THE MACERATING UNIT WAS SUBMITTED. TWO
 COMPLETE COPIES OF SPECIFICATION SHEETS ARE REQUIRED.
  
 10. SHEET P101 SANITARY RISER: A} A 4" AERATOR FITTING
 IS REQUIRED FOR THE WASHING MACHINE AND MACERATING
 UNIT. BOTH THE WASHING MACHINE AND MACERATING UNIT CAN
 DRAIN INTO THE SAME AERATOR FITTING. PER CONINE
 MANUFACTURING DESIGN MANUAL #802.
 B} THE 1-1/2"VENT FROM THE COLLECTION TANK OF THE
 MACERATING UNIT SHALL BE REQUIRED TO TIE BACK INTO THE
 4" STACK36" ABOVE THE AERATOR FITTING AND AN 1-1/2
 VENT IS REQUIRED FOR THE 2" LINE FROM THE DISCHARGE OF
 THE MACERATING UNIT.
 NOTE: PER THE SUBMITTED MANUFACTURER SPECIFICATION
 PAGE #5 STATES, "WARNING: DO NOT USE AN AIR ADMITTANCE
 VALVE (CHEATER, MECHANICAL VENTS), WHICH ARE ONE-WAY
 VALVES. THE AIR PRESSUR IN AND OUTSIDE THE MACERATING
 PUMP UNIT MUST REMAIN CONSTANT." PER CONINE
 MANUFACTURING DESIGN MANUAL #802.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-26 Cont ID  
Sent By mperson Date 2007-12-26 Time 11:40 Rev Time 0.00
Received By mperson Date 2007-12-26 Time 11:39 Sent To  
Notes
2007-12-26 14:54:02PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET P101, ISOMETRIC SANITARY RISER DIAGRAM:
 CLEARLY INDICATE ALL PIPE SIZES PER THE FOLLOWING
 SECTION *106.3.5.1.3, PLUMBING AND SOVENT DESIGN MANUAL
 #802.
  
 A} SOVENT STACK = 4".
  
 B} AREATOR BOX (NEW & EXISTING) = 4" X 3".
  
 C} RELOCTED WASHING MACHINE HORIZONTAL BRANCH = 3".
  
 D} RELOCATED WASHING MACHINE VERTICAL DROP = 3".
  
 E} RELOCATED WASHING MACHINE TRAP = 2".
  
 2. SHEET P101, EXISTING FLOOR PLAN DETAIL: PLEASE
 CORRECT/ADD THE FOLLOWING PER SECTION *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 *106.1.2, ADDITIONAL DATA.
  
 A} PLEASE CORRECT THE SPELLING OF "SOLVENT" TO
 "SOVENT".
  
 B} PLEASE ADD THE FOLLOWING TO THE EXISTING SINK
 LOCATION. "EXISTING SOVENT STACK".
  
 3. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE THE
 "EXTEND EXISTING 2" BRANCH" IS LOCATED IS THAT
 RELOCATED FIXTURE A SINK OR A LAVATORY? PLEASE CLEARLY
 IDENTIFY ALL FIXTURES. PER SECTION *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND SECTION
 *106.1.2, ADDITIONAL DATA.
  
 4. SHEET P101, NEW FLOOR PLAN DETAIL: WHERE EXISTING
 WASHING MACHINE WASTE IS LOCATED IT STATES "CAP
 EXISTING AT WALL". PER *704.5 DEAD ENDS.IN THE REMOVAL
 OF ANY PART OF A DRAINAGE SYSTEM, DEAD ENDS SHALL BE
 PROHIBITED. PLEASE CLEARLY INDICATE THIS ON THE
 RESUBMITTAL.
  
 5. PLEASE CLARIFY HOW THE NEW WATER CLOSET WITH THE
 NEW AERATOR FITTING WILL BE INSTALLED TO MEET THE ROUGH
 IN REQUIREMENTS OF THE SPECIFIED KOHLER MODEL NUMBER
 K-3554 WHICH IS 4" A.F.F. AND HOW THE AERATOR FITTING
 WILL BE FIRE STOPPED. PLEASE REFERENCE THE AERATOR
 FITTING CUT SHEET WITH ROUGH-IN DIMENSIONS ATTACHED TO
 THESE COMMENTS. PER SECTION *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION *713, FIRE RESISTANT
 JOINT SYSTEMS.
  
 6. NOTE: DETAIL REQUIRED ON HOW AERATOR FITTING WILL
 BE SUPPORTED. PER SECTION *308 PIPING SUPPORT.
  
 7. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR THE PROPOSED NEW AND RELOCATED WORK FOR
 BOTH THE HOT AND COLD WATER INDICATING THE PIPE SIZES,
 VALVE LOCATIONS, AND LOCATION OF THE WATER-HAMMER
 ARRESTORS WHERE QUICK CLOSING VALVES ARE UTILIZED
 (EXAMPLES=WASHING MACHINES, DISHWASHERS, ICE MAKERS)
 **604.9.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-26 Cont ID  
Sent By choops Date 2007-12-26 Time 15:57 Rev Time 0.00
Received By choops Date 2007-12-26 Time 15:57 Sent To  
Notes
2007-12-26 15:57:50*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved