| 2008-01-02 16:53:33 | BUILDING PLAN REVIEW |
| | PERMIT: 07120427 |
| | ADD: 777 S FLAGLER DR 10TH FLOOR |
| | CONT: PAVARNI INTERIORS |
| | TEL: (561) 856-6655 |
| | |
| | FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| | W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS |
| | JAN. 02,2008 |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1A)--- VERY IMPORTANT STATEMENT --- |
| | PLEASE DO NOT IGNORE! |
| | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & |
| | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL |
| | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH |
| | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE |
| | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE |
| | FOUND |
| | WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR |
| | ANTICIPATED COOPERATION. |
| | |
| | 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS, |
| | REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR |
| | REVIEW FOR PERMIT. |
| | IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF |
| | YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A |
| | THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID |
| | DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1* |
| | /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH |
| | ADMINISTRATIVE CODE. |
| | |
| | 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004 |
| | DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN |
| | THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF |
| | MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY |
| | WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE |
| | SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS |
| | A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS |
| | EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC |
| | INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE |
| | SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND |
| | EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT |
| | WILL CONFORM TO THE PROVISIONS OF THIS CODE AND |
| | RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS |
| | DETERMINED BY THE BUILDING OFFICIAL. |
| | |
| | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) |
| | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC |
| | BUILDING WITH THE2007 SUPPLEMENTS. SHEET A00.00 UNDER |
| | THE BUILDING CODE SUMMARY INDICATES THE PLANS WERE |
| | PREPARED UNDER THE 2006 FBC SUPPLEMENTS, PLEASE |
| | CORRECT. |
| | |
| | 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED |
| | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE |
| | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT |
| | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING |
| | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) |
| | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE |
| | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| | |
| | 3) ARCHITECT OF RECORD STERHEN TURNER SWICEGOOD IS |
| | MISSING HIS PRINTED NAME AND LICENSE NUMBER IN THE |
| | TITLE BLOCK. THE NAME OF THE ARCHITECTURAL FIRM GENSLER |
| | ARCHITECT APPEARS TO BE EITHER A FIRM REQUIRING A |
| | CERTIFICATE OF AUTHORIZATION. |
| | 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A |
| | REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH |
| | MUST: |
| | - STATE THE FIRM NAME, ADDRESS AND TELEPHONE |
| | NUMBER |
| | - STATE THE FIRM LICENSE NUMBER |
| | - STATE PROJECT NAME OR IDENTIFICATION |
| | - STATE DATE PREPARED |
| | - INCLUDE AN ORIGINAL SIGNATURE AND DATE SEAL |
| | - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE |
| | PLANS. |
| | |
| | 4)SHEET A00.00 ALSO INDICATES THE WORK TO BE |
| | COMPLETED UNDER THIS PERMIT TO BE A LEVEL III |
| | ALTERATION. PLEASE SEE SSECTION 305.1 OF THE 2004 |
| | EXISTING BUILDING CODE FBC. FOR A LEVEL III ALTERATION |
| | TO TAKE PLACE 50% OF THE AGGREGATE AREA OF THE BUILDING |
| | AND WITHIN ANY 12-MONTH PERIOD.EITHER THIS IS THE |
| | FIRST OF A LARGE BUILDING RENOVATION OR A LEVEL II |
| | ALTERATION. PLEASE CLARIFY THE INTENT? |
| | |
| | 5) SHEET A00.00 BUILDING DATA: INDICATES THE BUILDING |
| | IS LOCATED IN A FIRE DISTRICT, THERE ARE NO LONGER ANY |
| | FIRE DISTRICTS IN THE CITY OF WEST PALM BEACH, THEY |
| | WERE REMOVED SOME YEARS AGO. PLEASE CORRECT. |
| | 106.1.2 ADDTIONAL INFORMATION REQUIRED. |
| | |
| | 6A)A00.31 INDICATES THE USE OF A WALL COVERING AND |
| | STRETCH FABRIC WALL SYSTEM BOTH USING KNOLL TEXTILE, |
| | SEQUELAS THE WALL FINISH, PLEASE PROVIDE ADDITIONAL |
| | MOUNTING INFORMATION OR THE STRETCH WALL SYSTEM,DOES |
| | THIS SYSTEM STRETCH THE FABRIC OVER A SOLID BACKING OR |
| | IS THE FABRIC MOUNTED INTO A FRAME, THEN STRETCHED THAT |
| | ALLOWA AIR BEHIND THE FABRIC? PLEASE SEE 803.6.1 FOR |
| | FLAME SPREAD CLASSIFICATION AND TEST PROTOCAL. |
| | |
| | 6B)SHEET A11.01 VARIOUS ELEVATIONS HAVE A NOTE # 17 |
| | INDICATING TACKABLE FABRIC WRAPPED PANELS AND A DETAIL |
| | OR CUT SECTION 4/ A12.01. WHEN REVIEWING THIS DETAIL IT |
| | IS OF A HEAD DETAIL OF TYPICAL DOOR, NOT THE PANELIZED |
| | WALL SYSTEM. PLEASE PROVIDE THE INFORMATION REQUESTED |
| | UNDER COMMENT 6A. SEE 803.6.1. |
| | |
| | 7) A01.10NOTE # 13 INDICATES CORNER DETAILS FOUNDON |
| | DETAIL 9/A12.-00, THIS SHEET IS MISSING. 106.1.2 |
| | ADDITIONAL INFORMATION REQUIRED. |
| | |
| | 8) A02.10 ROOMS 1026,1027 & CORRIDOR 10-H17 APPEAR TO |
| | BE MISSING THE 18" ON THE LATCH SIDE OF THE DOOR. |
| | 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE |
| | A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN |
| | 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND |
| | OPPOSITE STOP. 11-4.13.6 MANEUVERING CLEARENCES AT |
| | DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE |
| | NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN |
| | FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. |
| | |
| | 9)SHEET A12.01 & A12.02 WOOD BUCK DETAILS DO NOT |
| | INDICATE THE USE OF FIRE RETARDANT TREATED WOOD, SEE |
| | SECTION 603.1. |
| | |
| | 10)ASSUMPTIONS: |
| | 10A) ROOM 10-37 NO WORK BEING COMPLETED, AND FLOOR |
| | SYSTEM IS ALREADY DESIGNED FOR HEAVY STORAGE. |
| | 10B) ROOM 10-38 BREAK ROOM NO WORK BEING COMPLETED SINK |
| | ADA IS ALREADY CODE COMPLIANT. |
| | |
| | 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS |
| | OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF |
| | CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST |
| | RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT |
| | BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC |
| | REQUIREMENT, THE SPECIFIC |
| | REQUIREMENT SHALL BE APPLICABLE. |
| | |
| | |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER C. B. O. |
| | BUILDING PLAN REVIEW II |
| | |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |