Plan Review Details - Permit 07120427
Plan Review Stops For Permit 07120427
Review Stop AD ADDRESSING
Rev No 4 Status P Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 12:12 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop AD ADDRESSING
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 13:59 Rev Time 0.00
Received By dpalmer Date   Time   Sent To  
Notes
2008-04-03 13:59:55AS APPLIED ON APPLICATION AND PLANS, WORK IS FOR THE
 10TH FLOOR. NO SUITE OR UNIT. NO INFORMATION FOR EAST
 TOWER OR WEST TOWER?
 TITLE BLOCKS ALSO DO NOT SHOW LOCATION. THIS MAY BE
 ADDED BY HAND. SEE ELECTRICAL REVIEW COMMENTS.

Review Stop AD ADDRESSING
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By lursu Date 2008-02-21 Time 15:22 Rev Time 0.00
Received By lursu Date 2008-02-07 Time 08:12 Sent To  
Notes
2008-02-21 15:23:45PLEASE CLARIFY THE UNIT NUMBER OF THIS LOCATION.
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]
  

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By lursu Date 2007-12-27 Time 14:03 Rev Time 0.00
Received By jwitmer Date 2008-01-02 Time 16:49 Sent To  
Notes
2007-12-27 14:07:14***FAILED***
  
 PERMIT APPLICATION AND THE SITE PLANS MUST CORRELATE
 .REVIEW PERMIT APPLICATION TO CONTAIN THE WEST TOWER (
 IF THAT INDEED IS THE JOB LOCATION) WITH THE SUITE
 NUMBER TO FOLLOW, AND THE CORRECT OWNER INFORMATION .IS
 THE WORK DONE AT THE ENTIRE FLOOR 10 OR AT THE SPECIFIC
 UNIT?PLEASE CLARIFY.
  
 QUESTIONS/COMMENTS:
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-11 Cont ID  
Sent By jwitmer Date 2008-02-11 Time 16:55 Rev Time 1.33
Received By jwitmer Date 2008-02-11 Time 16:55 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By jwitmer Date 2008-01-02 Time 16:49 Rev Time 2.22
Received By jwitmer Date 2008-01-02 Time 16:49 Sent To  
Notes
2008-01-02 16:53:33BUILDING PLAN REVIEW
 PERMIT: 07120427
 ADD: 777 S FLAGLER DR 10TH FLOOR
 CONT: PAVARNI INTERIORS
 TEL: (561) 856-6655
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS
 JAN. 02,2008
 1ST REVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT.
 IF YOUR PROJECT WILL REQUIRE A RESIDENT INSPECTOR OR IF
 YOUR PROJECT IS A THRESHOLD BUILDING REQUIRING A
 THRESHOLD INSPECTOR THEN (3) THREE SETS OF ALL SAID
 DOCUMENTS WILL BE REQUIRED FOR PERMIT ISSUANCE. 106.1*
 /2004 SUBMITTAL DOCUMENTSWEST PALM BEACH
 ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS. SHEET A00.00 UNDER
 THE BUILDING CODE SUMMARY INDICATES THE PLANS WERE
 PREPARED UNDER THE 2006 FBC SUPPLEMENTS, PLEASE
 CORRECT.
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) ARCHITECT OF RECORD STERHEN TURNER SWICEGOOD IS
 MISSING HIS PRINTED NAME AND LICENSE NUMBER IN THE
 TITLE BLOCK. THE NAME OF THE ARCHITECTURAL FIRM GENSLER
 ARCHITECT APPEARS TO BE EITHER A FIRM REQUIRING A
 CERTIFICATE OF AUTHORIZATION.
 61G1-16.004FL. ADMIN. CODE.PLANS PREPARED BY A
 REGISTERED ARCHITECT SHALL INCLUDE A TITLE BLOCK WHICH
 MUST:
 - STATE THE FIRM NAME, ADDRESS AND TELEPHONE
 NUMBER
 - STATE THE FIRM LICENSE NUMBER
 - STATE PROJECT NAME OR IDENTIFICATION
 - STATE DATE PREPARED
 - INCLUDE AN ORIGINAL SIGNATURE AND DATE SEAL
 - INCLUDE THE PRINTED NAME OF THE ARCHITECT SEALING THE
 PLANS.
  
 4)SHEET A00.00 ALSO INDICATES THE WORK TO BE
 COMPLETED UNDER THIS PERMIT TO BE A LEVEL III
 ALTERATION. PLEASE SEE SSECTION 305.1 OF THE 2004
 EXISTING BUILDING CODE FBC. FOR A LEVEL III ALTERATION
 TO TAKE PLACE 50% OF THE AGGREGATE AREA OF THE BUILDING
 AND WITHIN ANY 12-MONTH PERIOD.EITHER THIS IS THE
 FIRST OF A LARGE BUILDING RENOVATION OR A LEVEL II
 ALTERATION. PLEASE CLARIFY THE INTENT?
  
 5) SHEET A00.00 BUILDING DATA: INDICATES THE BUILDING
 IS LOCATED IN A FIRE DISTRICT, THERE ARE NO LONGER ANY
 FIRE DISTRICTS IN THE CITY OF WEST PALM BEACH, THEY
 WERE REMOVED SOME YEARS AGO. PLEASE CORRECT.
 106.1.2 ADDTIONAL INFORMATION REQUIRED.
  
 6A)A00.31 INDICATES THE USE OF A WALL COVERING AND
 STRETCH FABRIC WALL SYSTEM BOTH USING KNOLL TEXTILE,
 SEQUELAS THE WALL FINISH, PLEASE PROVIDE ADDITIONAL
 MOUNTING INFORMATION OR THE STRETCH WALL SYSTEM,DOES
 THIS SYSTEM STRETCH THE FABRIC OVER A SOLID BACKING OR
 IS THE FABRIC MOUNTED INTO A FRAME, THEN STRETCHED THAT
 ALLOWA AIR BEHIND THE FABRIC? PLEASE SEE 803.6.1 FOR
 FLAME SPREAD CLASSIFICATION AND TEST PROTOCAL.
  
 6B)SHEET A11.01 VARIOUS ELEVATIONS HAVE A NOTE # 17
 INDICATING TACKABLE FABRIC WRAPPED PANELS AND A DETAIL
 OR CUT SECTION 4/ A12.01. WHEN REVIEWING THIS DETAIL IT
 IS OF A HEAD DETAIL OF TYPICAL DOOR, NOT THE PANELIZED
 WALL SYSTEM. PLEASE PROVIDE THE INFORMATION REQUESTED
 UNDER COMMENT 6A. SEE 803.6.1.
  
 7) A01.10NOTE # 13 INDICATES CORNER DETAILS FOUNDON
 DETAIL 9/A12.-00, THIS SHEET IS MISSING. 106.1.2
 ADDITIONAL INFORMATION REQUIRED.
  
 8) A02.10 ROOMS 1026,1027 & CORRIDOR 10-H17 APPEAR TO
 BE MISSING THE 18" ON THE LATCH SIDE OF THE DOOR.
 11-4.13.5 DOORWAY MIN CLEAR WIDTH . DOORWAYS SHALL HAVE
 A MINIMUM CLEAR WIDTH OF 32" WITH THE DOOR OPEN
 90-DEGREES, MEASURED BETWEEN THE FACE OF THE DOOR AND
 OPPOSITE STOP. 11-4.13.6 MANEUVERING CLEARENCES AT
 DOORS. MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE
 NOT AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN
 FIG. 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED
 CLEARANCES SHALL BE CLEAR & LEVEL.
  
 9)SHEET A12.01 & A12.02 WOOD BUCK DETAILS DO NOT
 INDICATE THE USE OF FIRE RETARDANT TREATED WOOD, SEE
 SECTION 603.1.
  
 10)ASSUMPTIONS:
 10A) ROOM 10-37 NO WORK BEING COMPLETED, AND FLOOR
 SYSTEM IS ALREADY DESIGNED FOR HEAVY STORAGE.
 10B) ROOM 10-38 BREAK ROOM NO WORK BEING COMPLETED SINK
 ADA IS ALREADY CODE COMPLIANT.
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-04-16 Cont ID  
Sent By dpalmer Date 2008-04-16 Time 12:11 Rev Time 0.00
Received By dpalmer Date 2008-04-16 Time 12:11 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-04-03 Cont ID  
Sent By dpalmer Date 2008-04-03 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2008-04-03 Time 14:27 Sent To PC
Notes
2008-04-03 14:27:42** DENIED 3RD REVIEW **
  
 1) NOTE: PLEASE SEE COMPLIANCE FOR LIGHTING PERFORMANCE
 CALCULATIONS STILL NEEDS TO BE MET. PLEASE SEE PLANS
 STILL SHOW METHOD *C* CALCULATIONS ON SHEETS E-0.3 AND
 E-0.4. THESE NEED TO BE SUBMITTED SEPARATELY. THESE
 NEED TO SHOW ALL LIGHTING AS SHOWN ON PLANS. PLEASE SEE
 THE NEW LIGHTING LEVELS PRINTED ON TABLE ON SHEET E-0.1
 NOW CONTAINS LOWER DESIGN WATTAGE THAN THE DESIGN
 WATTAGE ON THE TWO SHEETS ABOVE.
 THE NEW LIGHTING PLANS SUBMITTED NOW HAVE NUMEROUS
 FIXTURES THAT WERE ON PREVIOUS PLANS NOW DELETED FROM
 NEW PLANS YET THE WATTAGE HAS ONLY DECREASED A SMALL
 AMOUNT FROM THE INFORMATION PREVIOUSLY SUBMITTED.
 PLEASE SEE BOTH THE EXISTING SHEETS LEFT IN SETS AND
 THE NEW INFORMATION AND PLEASE BE SURE TO COORDINATE
 ALL.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 2) NOTE: PLEASE SEE THE ADDRESS OF THE PROJECT FOR
 SUITE/UNIT NUMBER STILL NEEDS TO BE DETERMINED. PLANS
 CALL FOR 10TH FLOOR YET IF THIS IS A SUITE/UNIT WHERE
 THE WORK IS BEING DONE THEN THE TITLE BLOCKS NEED TO
 SHOW THE SUITE OR UNIT. THERE ARE ALSO TWO TOWERS TO
 THIS SAME ADDRESS. IS THIS EAST OR WEST TOWER? PLEASE
 KNOW THAT ON ALL SHEETS WHICH DO NOT NEED TO BE
 CORRECTED OR CHANGED FOR ELECTRICAL COMMENTS THE TITLE
 BLOCKS MAY SIMPLY HAVE THE INFORMATION HAND WRITTEN IN
 A NEAT FASHION, STAMPED, PRINTED ETC. THIS IS REQUIRED
 OF ALL SHEETS AND ALL SETS WHETHER OR NOT COMMENT IS OR
 HAS BEEN MADE BY ANY OTHER TRADES.
 FOR EXAMPLE:
 SUITE #401, EAST TOWER.
  
 FAC 61G15-23.002, 61G1-16.004.
  
 3) NOTE: PLEASE KNOW DUE TO REPEAT COMMENTS SOME
 ELECTRICAL SHEETS HAVE BEEN RETAINED BY THIS OFFICE.
 PLEASE BE SURE COMMENTS ARE ADDRESS AND PLANS ARE
 ADJUSTED. ** IF THERE ARE QUESTIONS OR COMMENTS PLEASE
 CONTACT THIS REVIEWER DIRECTLY AT THE CONTACT
 INFORMATION BELOW.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-01 Cont ID  
Sent By dpalmer Date 2008-02-01 Time 09:44 Rev Time 0.00
Received By dpalmer Date 2008-02-01 Time 09:44 Sent To  
Notes
2008-02-01 09:44:41** DENIED 2ND REVIEW **
  
 1) NOTE: PLEASE SEE THE OWNER INFORMATION ON PERMIT
 APPLICATION IS NOT CORRECT. PLEASE ALSO KNOW THE
 SUITE/UNIT NUMBER HAS NOT YET BEEN DETERMINED AND
 COMPLETED. ONCE THIS IS DONE THE SUITE/UNIT NUMBER
 NEEDS TO BE ON TITLE BLOCKS. THIS MAY BE DONE BY HAND
 WITH OUT HAVING RE-PRINT SHEETS.
 PLEASE SEE NOTES FROM ADDRESSING AND/OR BUILDING
 REVIEWER.
 PLEASE KNOW THIS IS BEING NOTED FOR INFORMATION AS
 THESE WILL NEED TO BE CORRECTED.
  
 2) NOTE: PLEASE SUBMIT COMPLETED SEPARATE ENERGY
 CALCULATIONS. THESE ARE PRINTED ON SHEETS WHICH ARE OK;
 HOWEVER ALSO NEED SEPARATE FORMS SUBMITTED.
 PLEASE SEE THE FORMS REQUIRES OWNER/AGENT SIGNATURE,
 SIGNED, DATED AND SEALED BY THE DESIGNER OF RECORD.
 PLEASE SEE AT THIS TIME A NAME IS SHEET E-.03 WHICH
 INDICATES SOMEONE OTHER THAN THE DESIGNER OF RECORD AS
 THE PREPARER OF SAID DOCUMENTS.
 PLEASE KNOW AS THE SCOPE OF WORK IS REQUIRED TO BE DONE
 BY A LICENSED ARCHITECT/ENGINEER IN THE STATE OF
 FLORIDA; PLEASE PROVIDE INFORMATION FOR SAID PREPARER.
 IF THE PREPARER AS LISTED IS NOT A LICENSE ARCHITECT OR
 ENGINEER IN THE STATE PLEASE COMPLETE WITH THE DESIGNER
 OF RECORDS INFORMATION.
 FBC 13-103.1., FAC 61G15-23.002, FS 481.221, 471.025
 ETC
  
 3) NOTE: PLEASE SEE THE DESIGNATION ON THE INPUT DATA
 REPORT DOES NOT COORDINATE WITH THE ROOM/AREA
 DESIGNATIONS ON PLANS.
 PLEASE SEE FOR EXAMPLE: CONFERENCE ROOM IS NOTED, BUT
 IT IS UNCLEAR WHICH IS WHICH. THE IDR NOTES CONF #2,
 YET THE PLANS HAS OTHER DESIGNATIONS.
 PLEASE SEE THE IDR ALSO INDICATES *MANUAL ON/OFF*
 CONTROLS FOR MANY OF THESE ROOMS WHICH IS NOT POSSIBLE
 WHEN THESE ROOMS/LOCATIONS CONTAINS AUTOMATED TYPE
 DEVICES LISTED ON PLANS.
 13-415.1.ABC.1.1, .1.2, 13-415.2, 13-415.1.C,
 PLEASE COORDINATE ALL.
  
 4) NOTE: PLEASE CLARIFY THE CONF ROOM 10-19 WHICH SHOWS
 WHAT APPEARS AS CIRCUIT P1-29 TO THE EMERGENCY BATTERY
 BACK UP LIGHT? PLEASE CLARIFY THIS AS PLANS DO CONTAIN
 NOTES IN OTHER AREAS FOR THESE TYPES OF FIXTURES TO BE
 WIRED PER 700.12F.
  
 ** PLEASE BE SURE TO ADDRESS COMMENTS. IF THERE ARE ANY
 QUESTIONS, ANY COMMENTS NOT TYPED IN A CLEAR MANOR OR
 NOT UNDERSTOOD IN ANYWAY PLEASE DO NOT HESITATE IN
 CONTACTING THIS REVIEWER.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 17:08 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 17:08 Sent To  
Notes
2007-12-23 17:08:20** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED
 TO COORDINATE. PLEASE SEE APPLICATION DOES NOT INDICATE
 WHICH TOWER SCOPE OF WORK WILL BE DONE. PLEASE SEE
 PLANS CALL FOR WEST TOWER.
 AS THE SCOPE OF WORK DOES FALL UNDER A TENANT SPACE AND
 NOT THE ENTIRE FLOOR PLEASE KNOW THE PERMIT APPLICATION
 DOCUMENTATION WILL BE ROUTED TO THE ADDRESSING REVIEWER
 FOR SUITE/UNIT NUMBER DETERMINATION. PLEASE SE AWARE OF
 ANY POSSIBLE CHANGES
 PLEASE SEE THE OWNER INFORMATION ON PERMIT APPLICATION
 ALSO NEEDS TO BE ADJUSTED. THE TENANT IS LISTED AS
 OWNER OF BUILDING WHICH IS NOT THE CASE. PLEASE SEE
 SPACE FOR TENANT INFORMATION.
 PLEASE ADJUST AS NEEDED.
 FBC 106.5, 106.1.2,
 FAC 61G15-23.002
  
 2) NOTE: PLEASE SEE MISSING INFORMATION ON TITLE BLOCKS
 FOR ARCHITECTURAL FIRM AS REQUIRED PER FLORIDA
 ADMINISTRATIVE CODE 61G1-16.004 AND FLORIDA STATUTES
 481.219.
 PLEASE BE SURE THE PRINTED NAME, PRINTED LICENSE NUMBER
 OF ARCHITECT ALONG WITH THE MISSING CERTIFICATE OF
 AUTHORIZATION NUMBER IS PLACED ON ALL SHEETS WHICH
 CONTAIN THE TITLE BLOCKS FOR THE ARCHITECTURAL FIRM
 LISTED.
  
 3) NOTE: PLEASE SEE FS 471.025 AS THE PLANS ARE ALSO
 REQUIRED TO BE DATED WHEN SIGNING AND SEALING SAID
 DOCUMENTS.
 ELECTRICAL PLANS ARE NOT DATED.
  
 4) NOTE: PLEASE SEE THE FOLLOWING CODES ARE TO BE
 STATED ON PLANS AS THE LATEST ADOPTED EDITIONS BY THE
 STATE OF FLORIDA. SOME ARE ALREADY SHOWN, HOWEVER THIS
 IS REQUIRED ON ARCHITECTURAL AND ELECTRICAL SHEETS FOR
 THIS REVIEWER.
 PLEASE SEE SOME CODES LISTED ARE NOT YET ADOPTED BY THE
 STATE.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72 (SHOWS 2006)
 2003 NFPA-101 (SHOWS 2005)
  
 5) NOTE:PLEASE SHOW LIGHTING POWER DENSITIES FOR
 EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE
 ADDED.
 PLEASE SEE 13-415.2.
 PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED
 SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACES NOTES ON PLANS ACCORDINGLY.
 THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON.
  
 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY
 DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES
 SHOWN.
 PLEASE VERIFY ANY NEW CONTROLS FOR BATHROOMS. PLEASE
 PROVIDE MORE INFORMATION AND DETAILS FOR NEW LUTORN
 GRAFIK EQUIPMENT.
 SCHEDULING TIMES ETC.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
 PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES.
  
 8) NOTE: PLEASE SEE BASED ON PLANS AND PANEL SCHEDULES
 SUBMITTED PLEASE SEE BOTH PANEL *IG* AND PANEL *P*
 REQUIRE MAINS WITH OVER CURRENT PROTECTION ON THE
 SECONDARY SIDE OF THE TRANSFORMERS AS SHOWN. PLEASE
 KNOW THIS WAS REQUIRED IN THE NEC EVEN WHEN THE
 BUILDING WAS ORIGINALLY BUILT. PLEASE VERIFY IF THESE
 PANELS ALREADY CONTAIN MAINS AND THE PANELS WHICH ARE
 SHOWN AS MLO ARE ONLY A MISPRINT.
 PLEASE KNOW IF THESE PANELS DO NOT CONTAIN OVER CURRENT
 PROTECTION ON THE SECONDARY SIDE OF THE TRANSFORMER
 THIS IS A LIFE SAFETY AND FIRE HAZARD AND MAIN CIRCUIT
 BREAKERS OR DISCONNECTS WITH OCP WILL BE REQUIRED TO BE
 INSTALLED.
 PLEASE SEE NEC 240.21, 408.36, 310.16, 240.4, 90.4. **
 PLEASE VERIFY IN FIELD BEFORE RESUBMITTING PLANS.A
 FILED INSPECTION MAY BE SET UP TO VERIFY THESE BEFORE
 PERMIT ISSUANCE.
  
 9) NOTE: PLEASE SEE NOTES ON SHEET E-0.2 WIRING NOTE 3
 3.02 (D) AS ANY COLOR CODING FOR ANY NEW WIRING SHALL
 BE BROWN, PURPLE, YELLOW FOR 277/480V SYSTEMS. ORANGE
 PER THE NEC IS MARKING FOR A HIGH-LEG DELTA SYSTEM
 WHICH 277/480V IS NOT.
 PLEASE KNOW LOCAL COLOR CODING FOR DECADES WAS DONE BY
 LOCAL AMENDMENTS AND AS THE NEC DOES NOT PROVIDE COLOR
 CODING THE ABOVE COLORS WERE DETERMINED ON A CITY AND
 COUNTY WIDE BASIS. EVEN AS TECHNICAL AMENDMENTS ARE NO
 LONGER IN AFFECT, THESE COLORS WILL STILL BE ADHERED TO
 AS NEC DOES NOT PROVIDE.
 NEC 90.4
  
 10) NOTE: PLEASE PROVIDE NOTES FOR ALL DEVICES WHICH
 ARE NOTED FOR ACCESS CONTROLS AND DOORS LOCKING DEVICES
 WHICH ARE REQUIRED TO MEET NFPA-101 2003 7.2 PLEASE
 KNOW THAT NO DEVICES SHALL IMPEDED EGRESS DURING AN
 EMERGENCY OR POWER FAILURE.
 PLEASE SEE 7.2.1.5, 7.2.1.6.2 ETC
 PLEASE SEE POSSIBLE COMMENTS FROM FIRE MARSHAL
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-19 Cont ID  
Sent By mwennerg Date 2008-02-19 Time 13:31 Rev Time 0.00
Received By mwennerg Date 2008-02-19 Time 13:31 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By mwennerg Date 2008-01-08 Time 10:16 Rev Time 0.00
Received By mwennerg Date 2008-01-08 Time 10:16 Sent To  
Notes
2008-01-08 10:27:09***DENIED***
  
 1) THE ADOPTED CODE EDITION FOR FIRE PREVENTION CODE IS
 2004 EDITION. SHT A00.00
  
 2) NFPA 241, NOT 214 IS THE STANDARD FOR SAFEGUARDING
 CONSTRUCTION, ALTERATION AND DEMOLITION. SHT A00.00
  
 3) MAXIMUM TRAVEL DISTANCE INFORMATION IS DIFFICULT TO
 READ. SHT A00.20, 00.21, AND 00.22 NEXT TO COMM. RM.
  
 4) PLEASE PROVIDE MINIMUM INTERIOR FINISH
 CLASSIFICATION FOR WALLS AND CEILING.
  
 5) NFPA 101, AND NFPA 1, 2003 EDITION. SHT E-0.1.
  
 6) ACCESS CONTROLLED EGRESS DOORS SHALL COMPLY WITH
 NFPA 101, SEC. 7.2.1.6.2.
  
 7) SEPARATE SHOP DRAWINGS AND PERMITS REQUIRED FOR FIRE
 SPRINKLER AND FIRE ALARM REMODEL.
  
  
 MIKE WENNERGREN, ASSISTANT FIRE MARSHAL
 FIRE PLAN REVIEW
 FIRE PREVENTION (561) 804-4756

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-04-10 Cont ID  
Sent By adarroug Date 2008-04-10 Time 17:18 Rev Time 0.00
Received By adarroug Date 2008-04-10 Time 17:18 Sent To E
Notes
2008-04-10 17:18:58TO "DPALMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-26 Cont ID  
Sent By adarroug Date 2008-03-26 Time 16:28 Rev Time 0.00
Received By adarroug Date 2008-03-26 Time 16:28 Sent To E
Notes
2008-03-26 16:29:46TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-25 Cont ID  
Sent By shill Date 2008-01-25 Time 11:59 Rev Time 0.00
Received By shill Date 2008-01-25 Time 11:59 Sent To  
Notes
2008-01-25 12:02:11TO "COMM" BD#48

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-08 Cont ID  
Sent By mwennerg Date 2008-01-08 Time 10:35 Rev Time 0.00
Received By mwennerg Date 2007-12-18 Time 10:07 Sent To  
Notes
2007-12-18 10:07:24TO "COMM" BD#63

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2008-01-07 Cont ID  
Sent By rregueir Date 2008-01-07 Time 16:58 Rev Time 0.00
Received By rregueir Date 2008-01-07 Time 14:06 Sent To  
Notes
***NONE***