| 2007-12-23 15:45:21 | ** DENIEDREVIEW ** |
| | |
| | 8TH FLOOR/SUITE # 800 |
| | |
| | |
| | 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION HAS |
| | BEEN ROUTED TO THE ADDRESSING REVIEWER FOR CONFORMATION |
| | OF SUITE/UNIT # SHOWN ON PLANS. |
| | THE APPLICATION STATES 8TH FLOOR HOWEVER AS SCOPE OF |
| | WORK IS NOT FOR COMMON AREA AND FOR A TENANT, THE |
| | SUITE/UNIT NUMBER WILL BE ASSIGNED. |
| | |
| | 2) NOTE: PLEASE SEE POSSIBLE NOTES FROM BUILDING WITH |
| | RESPECT TO ANY DESIGNS BY LICENSED INTERIOR DESIGNER |
| | UNDER FS 481.2131 |
| | |
| | 3) NOTE: PLEASE SEE PLANS SUBMITTED ARE NOT SIGNED, |
| | DATED OR SEALED BY THE ELECTRICAL ENGINEER OF RECORD AS |
| | REQUIRED PER FAC 61G15-23.002, FS 471.025 |
| | |
| | 4) NOTE: PLEASE SHOW AND INDICATE ALL ROOM AND AREA |
| | DESIGNATIONS ON PLANS. PLEASE KNOW THAT SOME ITEMS CAN |
| | NOT BE REVIEWED FOR MINIMUM CODE AT THIS TIME. |
| | 240.4, 408.17, 110.26 ETC |
| | FBC 106.1.2 ADDITIONAL INFORMATION. |
| | |
| | 5) NOTE: PLEASE BE SURE ONCE ALL ROOMS AND AREAS ARE |
| | SHOWN TO PLEASE BE SURE ALL CIRCUITS ON PANEL SCHEDULES |
| | ARE SPECIFIC TO ROOMS AND AREAS IN WHICH THEY FEED. |
| | PLEASE SEE 408.4 OFTHE 2005 NEC. |
| | FBC 106.3.5.1.2 |
| | |
| | 6) NOTE: PLEASE SHOW LIGHTING POWER DENSITIES FOR |
| | EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE |
| | ADDED. |
| | PLEASE SEE 13-415.2. |
| | PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED |
| | SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE |
| | CALCULATIONS. |
| | |
| | 7)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND |
| | PLACES NOTES ON PLANS ACCORDINGLY. |
| | THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON. |
| | |
| | 8) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY |
| | DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES |
| | SHOWN. |
| | PLEASE SEE 13-415.1.ABC.1.1, .1.2. |
| | PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES. |
| | |
| | 9) NOTE: PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR |
| | MINIMUM DEVICES AND LEVELS OF DEVICES FOR ADA |
| | COMPLIANCE. |
| | PLEASE INDICATE ON PLANS EVEN AS ANY FIRE ALARM SYSTEM |
| | WORK IS REQUIRED UNDER SEPARATE PERMIT. |
| | THE BASE PLANS ARE REQUIRED TO SHOW MINIMUM DESIGN. |
| | |
| | 10) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTING |
| | FOR PANEL L4D. PLEASE SEE NOTES 4 AND 5 ABOVE AND |
| | COORDINATE. |
| | 408.4, 310.16, 240.4 ETC |
| | FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION. |
| | |
| | 11) NOTE: PLEASE SEE PANEL SCHEDULE FOR PANEL L4C |
| | INDICATES THIS AS 400AMP MLO, WHEN THE RISER SHOWS THIS |
| | AS 225AMP MLO. |
| | PLEASE COORDINATE AND ADJUST. |
| | FBC 106.1.2 |
| | |
| | 12) NOTE: PLEASE VERIFY PLANS SHOWING AN *IT ROOM*. IF |
| | THIS ROOM MEETS THE DEFINITIONS OF AN IT AS STATED IN |
| | 645.4, PLEASE SHOW. IF THIS DOES NOT PLEAS ADJUST |
| | DESIGNATION AS ROOM WILL BE REQUIRED TO BE COMPLY WITH |
| | MORE STRINGENT WIRING METHODS PER CHAPTERS 1-4 OF THE |
| | NEC. |
| | |
| | 13) NOTE: PLEASE SEE PLANS ON E-2 IN TRAINING ROOM 21 |
| | SHOWS A MDF, DISCONNECT AND TRANSFORMER YET THE RISER |
| | AND PANEL SCHEDULES DO NOT INCLUDE ANY OF THESE. |
| | PLEASE COMPLETE PLANS. |
| | 310.16, 240.4, 240.21, 408.4, 110.26, ETC |
| | FBC 106.3.5.1.2 |
| | |
| | |
| | |
| | *** IMPORTANT** |
| | AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW, |
| | THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH |
| | CAN NOT BE MADE AT THIS TIME. |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY |
| | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, |
| | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO |
| | TWO SETS/FOLDERS/BINDERS ETC. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |
| | |
| | |