Plan Review Details - Permit 07120418
Plan Review Stops For Permit 07120418
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-08-25 Cont ID  
Sent By mjacobs Date 2008-08-25 Time 09:06 Rev Time 0.00
Received By mjacobs Date 2008-08-25 Time 09:06 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-03-15 Cont ID  
Sent By mjacobs Date 2008-03-15 Time 08:27 Rev Time 0.00
Received By mjacobs Date 2008-03-15 Time 06:45 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By mjacobs Date 2008-01-04 Time 16:00 Rev Time 0.00
Received By mjacobs Date 2008-01-04 Time 13:30 Sent To  
Notes
2008-01-04 15:59:59BUILDING PLAN REVIEW
 PERMIT: 07120418
 ADD: 1700 PBL BLVD SUITE 500 & 510
 CONT: HOLT LEE CONST.
 TEL: (954)725-4881
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST
 ACTION: DENIED
 1-4-08
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY.
  
 4)THE APPLICATION INDICATES SUITES 500 & 510;
 THEREFORE THE ADDRESS ON EACH PAGE OF THE DRAWINGS
 SHALL REFLECT SUITE 500 AND 510.THIS INFORMATION IS
 REQUIRED ON THE DRAWINGS TO COMPLY WITH OUR RECORD
 RETENTION PROGRAM AS REQUIRED BY FBC 106.5.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-08-25 Cont ID  
Sent By dpalmer Date 2008-08-25 Time 14:19 Rev Time 0.00
Received By dpalmer Date 2008-08-25 Time 14:19 Sent To PC
Notes
2008-08-25 14:20:35REDUCED SCOPE OF WORK

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-06-16 Cont ID  
Sent By dpalmer Date 2008-06-16 Time 16:09 Rev Time 0.00
Received By dpalmer Date 2008-06-16 Time 16:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-05-19 Cont ID  
Sent By dpalmer Date 2008-05-19 Time 10:02 Rev Time 0.00
Received By dpalmer Date 2008-05-19 Time 10:02 Sent To PC
Notes
2008-05-19 10:07:58** DENIED**
  
 1) NOTE: PLANS BEING SUBMITTED NEED TO BE COORDINATED.
 PLEASE SEE THERE ARE SHEETS FOR SUITE #8000 IN THE SETS
 FOR SUITE 500 AND 510.
 PLEASE SEE THE RESPONSE MENTIONS SHEETS WERE REVISED
 HOWEVER SOME SHEETS ARE THE SAME AS PREVIOUS REVIEW
 DATED 1/18/08.
 PLEASE COORDINATE ALL PLANS AND RESUBMIT.
 *** AS A NOTE, PLEASEBE SURE TO GO OVER FIXTURE COUNT
 AS PREVIOUSLY NOTED. PLEASE SEE SHEETS AND COMMENTS
 UNDER SUITE #800 PLANS.
 13-415.2, 13-415.2.ABC.1.1, .1.2.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-14 Cont ID  
Sent By dpalmer Date 2008-03-14 Time 12:59 Rev Time 0.00
Received By dpalmer Date 2008-03-14 Time 12:59 Sent To  
Notes
2008-03-14 12:59:51** DENIED2ND REVIEW**
  
 ** PLEASE SEE THE NOTES BELOW WHICH ARE FROM THE FIRST
 REVIEW WHICH STILL NEED TO BE ADDRESSED. PLEASE ALSO
 SEE NEW NOTE DUE TO CHANGE ON PLANS.
  
 1) NOTE:PLEASE SEE PREVIOUS REVIEW NOTEAS THE
 TAPPED CONDUCTORS ON THE SECONDARY SIDE OF THE
 TRANSFORMER DO NOT MEET 240.21, 310.16, 240.4. RISER
 STILL SHOWS 500MCB AND A 400AMP MCB FOR THE OVER
 CURRENT PROTECTION.THIS IS A SAFETY AND FIRE HAZARD.
 PLEASE ADJUST BREAKER OR TAPPED CONDUCTORS. SINCE NO
 PANEL SCHEDULE OR LOAD WAS SUBMITTED FOR L1 AS
 REQUESTED ON PREVIOUS REVIEW FURTHER REVIEW AND
 DETERMINATION CAN NOT BE DONE AT THIS TIME.
 FBC 106.1.2
  
 2) NOTE: PLEASE SEE RISER AS THIS SHOWS A 30AMP BREAKER
 FEEDING PANELS L1A AND L1B. HOW IS THIS POSSIBLE WITH
 THE 350MCM AND THE LOAD ON BOTH OF THESE PANELS AT
 161.2 AMPS?
 THIS IS BEING ASSUMED TO BE A MISPRINT HOWEVER
 ASSUMPTION CAN NOT BE MADE TO BE FACT.
 PLEASE PROVIDE INFORMATION AND ADJUST.
 240.4, 408, 310.16 ETC
 FBC 106.1.2
  
 3) NOTE: PLEASE GO OVER COUNT ON FIXTURES PER 13-415.2,
 13-415.2.ABC.1.1.
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 16:08 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 15:51 Sent To  
Notes
2007-12-23 16:08:23** DENIEDREVIEW **
  
 SUITE(S) 500/510
  
 1) NOTE: PLEASE KNOW THE PLANS/PERMIT APPLICATION NEED
 TO COORDINATE. PLEASE SEE APPLICATION AND SCOPE ON
 PLANS APPEARS TO BE IN TWO SEPARATE SUITES/UNITS
 ALTHOUGH TITLE BLOCKS ON SHEETS ONLY INDICATE SUITE
 #500.?
 PLEASE ADJUST AS NEEDED.
 FBC 106.5, 106.1.2,
 FAC 61G15-23.002
  
 2) NOTE: PLEASE CORRELATE RISER AND PANELS.
 PLEASE SEE RISER SHOWS L1 WHICH CONTAINS A 400AMP MCB
 WITH 500MCM FEEDERS TO PANEL *L1A WHICH IS ONLY RATED
 AT 250AMP MLO. WHAT IS THE OVER CURRENT PROTECTION FROM
 L1 TO L1A?
 240.4, 310.16,ETC
 THE OCP IF 400AMP AT L1 IS TOO HIGH FOR THE 250AMP
 RATED PANEL.
 110.3, 90.7
  
 3) NOTE: PLEASE ALSO SEE PANEL L1A WHICH SHOWS THE
 FEEDERS AND FEED-THRU LUGS FROM THIS PANEL TO PANEL
 L1B. PANEL L1B IS ONLY RATED FOR 100AMPS AND IS A MLO
 PANEL AS SHOWN ON RISER.
 PLEASE SEE THE PANEL SCHEDULE SHOWN FOR L1B HOWEVER IS
 SHOWN AS 400AMP MLO??
 PLEASE CLARIFY ALL SERVICE AND RISER EQUIPMENT AND
 COORDINATE FOR MINIMUM CODE COMPLIANCE.
 PLEASE SEE 220,230,240,310.16,240.4, 90.7, 110.3 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION AND
 COORDINATION OF PLANS.
  
 4) NOTE: PLEASE SEE 700.12F AS EMERGENCY AND EXIT
 LIGHTS SHALL BE CIRCUITED TO THE LOCAL LIGHTING BRANCH
 CIRCUIT IN ANY ONE AREA.
  
 5) NOTE: PLEASE SHOW LIGHTING POWER DENSITIES FOR
 EXISTING AND NEW LIGHTING BEFORE NEW LIGHTING MAY BE
 ADDED.
 PLEASE SEE AREAS WHERE ALL NEW LIGHTING IS BEING ALSO
 NEEDS TO BE VERIFIED.
 PLEASE SEE 13-415.2.
 PLEASE KNOW AS THE SPACE ALREADY CONTAINS CONDITIONED
 SPACE, WE ONLY NEED THE LIGHTING PERFORMANCE
 CALCULATIONS.
  
 6)NOTE: PLEASE SEE 13-413.1.ABC.2.1 AND .2.2 AND
 PLACES NOTES ON PLANS ACCORDINGLY.
 THE NOTE ON E- #7 NEEDS TO BE EXPANDED UPON.
  
 7) NOTE: PLEASE INDICATE MAXIMUM TIMES ON OCCUPANCY
 DEVICES AS SHOWN ON PLANS ALONG WITH SWITCHING DEVICES
 SHOWN.
 PLEASE SEE 13-415.1.ABC.1.1, .1.2.
 PLANS SYMBOL LEGEND CAN BE USED TO INCLUDE TIMES.
  
 8) NOTE: (ONLY NOTED FOR NEW DEVICES BEING RELOCATED OR
 INSTALLED NEW).
 PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR MINIMUM
 DEVICES AND LEVELS OF DEVICES FOR ADA COMPLIANCE.
 PLEASE INDICATE ON PLANS EVEN AS ANY FIRE ALARM SYSTEM
 WORK IS REQUIRED UNDER SEPARATE PERMIT.
 THE BASE PLANS ARE REQUIRED TO SHOW MINIMUM DESIGN.
  
 9) NOTE: PLEASE SEE NO PANEL SCHEDULE WAS SUBMITTING
 FOR PANEL L1A. DUE TO THE NOTES ON RISER AND
 COORDINATION PLEAS SUBMIT.
 408.4, 310.16, 240.4, 240.21 ETC
 FBC 106.1.2, 106.3.5.1.2 FOR ADDITIONAL INFORMATION.
  
  
 *** IMPORTANT**
 AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR REVIEW,
 THERE MAY BE NEW COMMENTS ON THE FOLLOWING REVIEW WHICH
 CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-08-25 Cont ID  
Sent By mawillia Date 2008-08-25 Time 12:24 Rev Time 0.00
Received By mawillia Date 2008-08-25 Time 12:01 Sent To  
Notes
2008-08-25 12:24:35*****REVISION #2,APPROVED*****
  
 REVISED PLAN SHEETS A1, E-1,E-2, AND FP-1 WERE
 STAMPED, INITIALED, AND DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-04-01 Cont ID  
Sent By mawillia Date 2008-04-01 Time 19:48 Rev Time 0.00
Received By mawillia Date 2008-04-01 Time 19:21 Sent To  
Notes
2008-04-01 19:44:33*****PROVISO*****
  
 ALL COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED.PLAN SHEETS A1, FN1, AND FP-1 WERE
 STAMPED, INITIALED, AND DATED;HOWEVER, SHEETS E-1 AND
 E-2 TO BE FIRE-STAMPED WHEN ELECTRICAL PLAN EXAMINER'S
 COMMENT HAS BEEN SATISFIED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-05 Cont ID  
Sent By mawillia Date 2008-01-05 Time 23:20 Rev Time 0.00
Received By mawillia Date 2008-01-05 Time 22:29 Sent To  
Notes
2008-01-05 23:51:26*****DENIED*****
  
 1.THE PLANS SHOW WORK BEING DONE IN SUITE 500 AND
 510, HOWEVER THE SUITE NUMBER SHOWN IN THE TITLE BLOCK
 OF EACH SUBMITTED PLAN SHEET IS FOR SUITE 500 ONLY.
 PLEASE EXPLAIN.
  
 2.ON SHEET A1 IN THE DATA FOR THE SCOPE OF
 WORK/LOCATION MAP, OCCUPANCY CALC IS GIVEN FOR SUITE
 501.SHOULD THIS BE SUITE 510 INSTEAD?
  
 3.COULD NOT LOCATE PLAN SHEET FP1 AS INDICATED IN THE
 SHEET INDEX SECTION (SHEET A1).
  
 4.SHOW THE LOCATION OF THE 2A:BC RATED FIRE
 EXTINGUISHERS WHICH SATISFY THE 75' TRAVEL DISTANCE.
  
 5.SPECIFY THE INTERIOR FINISH MATERIAL FOR THE WALLS
 AND CEILING IN TERMS OF CLASS A, CLASS B, OR CLASS C.
  
 6.SUBMIT A LAYOUT OF THE FIRE SPRINKLER SYSTEM AS IT
 RELATES TO THE SCOPE OF WORK BEING CONDUCTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDIATING WHERE/HOW EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-08-05 Cont ID  
Sent By adarroug Date 2008-08-05 Time 10:08 Rev Time 0.00
Received By adarroug Date 2008-08-05 Time 10:08 Sent To  
Notes
2008-08-05 10:08:51TO "COMM" BD#20

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-10 Cont ID  
Sent By adarroug Date 2008-06-10 Time 08:53 Rev Time 0.00
Received By adarroug Date 2008-06-10 Time 08:53 Sent To E
Notes
2008-06-10 08:53:32TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-07 Cont ID  
Sent By adarroug Date 2008-05-07 Time 10:53 Rev Time 0.00
Received By adarroug Date 2008-05-07 Time 10:53 Sent To E
Notes
2008-05-07 10:53:57TO "DPALMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-03-06 Cont ID  
Sent By adarroug Date 2008-03-06 Time 09:26 Rev Time 0.00
Received By adarroug Date 2008-03-06 Time 09:26 Sent To  
Notes
2008-03-06 09:28:02TO "COMM" BD#41

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-06 Cont ID  
Sent By mawillia Date 2008-01-06 Time 16:32 Rev Time 0.00
Received By mawillia Date 2007-12-17 Time 16:50 Sent To  
Notes
2007-12-17 16:50:40TO "COMM" BD#3

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-08-21 Cont ID  
Sent By rregueir Date 2008-08-21 Time 13:26 Rev Time 0.00
Received By rregueir Date 2008-08-21 Time 11:33 Sent To  
Notes
2008-08-21 13:26:00PG AC-1 REV.2

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-03-26 Cont ID  
Sent By rregueir Date 2008-03-26 Time 15:01 Rev Time 0.00
Received By rregueir Date 2008-03-26 Time 14:36 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-05 Cont ID  
Sent By rregueir Date 2008-01-05 Time 14:58 Rev Time 0.00
Received By rregueir Date 2008-01-05 Time 14:15 Sent To  
Notes
2008-01-05 14:58:48REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ALL RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL
 BE PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL PER FBC, EB 609.1. O.A. CALCULATIONS AS
 SHOWN ON PLANS REFERENCE ASHRAE 62-89. THE CURRENT AND
 CORRECT REFERENCE STANDARD IS ASHRAE 62.1-2004. THE
 CALCULATIONS MAY BE BASED ON THIS STANDARD OR FBC, M
 TABLE 403.3. IF ASHRAE 62.1-2004 IS USED, INDICATE
 WHETHER THE AIRFLOW RATE OR IAQ METHOD IS USED. ALSO,
 NOTE #1 INDICATES THE CALCULATIONS ARE BASED ON THE
 MAX. ESTIMATED OCCUPANT RATES PER ARCHITECTURAL PLANS.
 ARCHITECTURAL PLANS PUT THE COMBINED OCCUPANCY AT 53
 PERSONS. THE OCCUPANCY MAY BE FIGURED BASED ON ASHRAE
 OR TABLE 403.3 RATHER THAN ARCHITECTURAL PLANS.
  
 2. AC-2: FIRE DAMPER INSTALLATION DETAIL DOES NOT
 APPEAR TO BE SPECIFIC TO ANY BRAND OR MANUFACTURER.
 FIRE DAMPERS LOCATED WITHIN AIR DISTRIBUTION SYSTEMS
 SHALL BE INSTALLED IN ACCORDANCE WITH THE
 MANUFACTURER?S INSTALLATION INSTRUCTIONS AND LISTING.
 IF THE DETAIL ON PLANS DOES NOT CONFORM TO THE
 MANUFACTURER?S INSTRUCTIONS, PLEASE REMOVE AND REPLACE
 WITH THE APPROPRIATE DETAIL OR A NOTE MAY BE PROVIDED
 WHICH DEFERS TO THE FIRE DAMPER MANUFACTURER?S
 INSTALLATION INSTRUCTIONS. SEE FBC, M 607.2.
 MANUFACTURER?S INSTALLATION INSTRUCTIONS SHALL BE
 AVAILABLE ON THE JOB SITE AT THE TIME OF INSPECTION IN
 ACCORDANCE WITH FBC, M 304.1.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-31 Cont ID  
Sent By choops Date 2007-12-31 Time 08:54 Rev Time 0.00
Received By choops Date 2007-12-31 Time 08:54 Sent To  
Notes
2007-12-31 08:54:38*ZONING REVIEW NOT REQUIRED - INTERIOR WORK ONLY, AND
 VALUE OF PROPOSED WORK DOES NOT EXCEED 50% OF THE
 IMPROVEMENT VALUE.