| 2007-12-22 16:56:11 | ** DENIED** |
| | |
| | * |
| | |
| | 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE |
| | NEEDED AS FOLLOWS |
| | 2004 FBC W/2007 REVISIONS |
| | 2005 NFPA-70 (SHOWS 2002) |
| | 2002 NFPA-72 |
| | |
| | 2) NOTE: PLEASE SEE WHAT APPEARS TO BE MISSING |
| | CERTIFICATE OF AUTHORIZATION NUMBER PER FAC 61G1-16.004 |
| | AND FS 481.219. |
| | PLEASE CONFIRM. |
| | |
| | 3) NOTE: PLEASE CLARIFY IF ALL CIRCUITS FROM EXISTING |
| | PANEL LOCATION WILL BE ROUTED TO NEW PANEL LOCATION. |
| | PLEASE SEE IF UNIT AND ALL BRANCH CIRCUIT CONDUCTORS |
| | ARE NOT BEING ROUTED AND RE-WIRED TO NEW PANEL LOCATION |
| | THE ONE INCH CONDUIT BEING SHOWN AS NEW TO BE INSTALLED |
| | IS NOT LARGE ENOUGH FOR PIPE FILL. |
| | PLEASE SEE TABLES IN CHAPTER NINE OF THE NEC. |
| | |
| | 4) NOTE: PLEASE SEE NOTE ON THE BOTTOM OF THE PANEL |
| | SCHEDULE MENTIONS ALL BEDROOM CIRCUITS TO BE ARC FAULT |
| | WHICH IS OK, HOWEVER PLEASE SEE ONLY CIRCUIT #12 IS |
| | SHOWN AS AFCI ON PANEL SCHEDULE. |
| | 210.12 OF THE 2005 NEC REQUIRE ALL OUTLETS INCLUDING |
| | LIGHTING AND SMOKE ALARMS. |
| | |
| | 5) NOTE: PLEASE SEE NFPA-72 DEFINITIONS AS THE DEVICES |
| | ON PLANS SHOW SMOKE DETECTORS WHICH ARE DEVICES WHICH |
| | DETECT AND DO NOT SOUND AN ALARM. IF THE DEVICES ARE |
| | UNITS WHICH DETECT AND SOUND AN ALARM PLEASE ADJUST |
| | DESIGNATION TO SA. |
| | ** NOTE ON LEFT OF PLANS LEND TO THESE AS BEING SMOKE |
| | ALARMS** |
| | |
| | 6) NOTE: PLEASE CLARIFY KITCHEN CIRCUITING AS THE |
| | KITCHEN ONLY INDICATES ONE SMALL APPLIANCE CIRCUIT. |
| | PLEASE SEE 210.52B1, 210.11C1. IF RE-WIRE OF BRANCH |
| | CIRCUITS TO PANEL IS BEING DONE, THIS WILL BE REQUIRED |
| | TO MEET THE MINIMUM. THIS IS A SAFETY ISSUE DUE TO OVER |
| | LOADING OF CIRCUIT IN KITCHEN IF ONLY ONE IS PRESENT. |
| | |
| | 7) NOTE: PLEASE SEE NEC 210.4B AS THE DISHWASHER AND |
| | DISPOSAL IS BEING SHOWN ON THE SAME YOKE YET THE PANEL |
| | SCHEDULE SHOWS BOTH OF THESE CIRCUITS ON SINGLE POLE |
| | BREAKERS. THIS WOULD BE REQUIRED TO BE A DOUBLE POLE |
| | BREAKER IF FEEDING A SINGLE YOKE/DEVICE. |
| | PLEASE ADJUST. |
| | |
| | 8) NOTE: PLEASE CORRELATE PANEL SCHEDULE AND LOAD |
| | CALCULATIONS. |
| | PLEASE SEE THE PANEL SCHEDULE INDICATES AN OVEN, YET |
| | NOT IN LOAD CALCULATIONS. |
| | PLEASE ALSO SEE THE OVEN IS NOT SHOWN ON PLANS. |
| | PLEASE SEE THE CALCULATIONS INDICATES A LAUNDRY |
| | CIRCUIT, HOWEVER NO LAUNDRY ON PLANS OR PANEL |
| | SCHEDULE. |
| | PLEASE SEE THE WATER HEATER IS SHOWN AS 3KW ON |
| | CALCULATIONS, YET THE PANEL SCHEDULE SHOWS THIS AS |
| | 4.5KW. |
| | PLEASE ALSO SEE THIS SAME WATER HEATER WITH A 4.5KW |
| | LOAD IS SHOWN ON A SINGLE POLE 20AMP BREAKER WITH #12 |
| | CONDUCTORS. |
| | PLEASE SEE 408.4, 240.4, 310.16 ETC AND ADJUST AND |
| | CORRELATE ALL. |
| | THE ABOVE WAS A FEW EXAMPLES, PLEASE BE SURE TO GO OVER |
| | ALL. |
| | |
| | 9) NOTE: PLEASE KNOW DEPENDING ON SCOPE WORK A NEW GFI |
| | RECEPTACLE MAY BE REQUIRED ALONG KITCHEN COUNTER SPACE |
| | AS THIS DOES NOT MEET 210.52C1. |
| | PLEASE SEE THE CODE HAS REQUIRED SPACE ALONG COUNTERS |
| | TO MEET 210.52C1 FOR DECADES. |
| | PLEASE SEE AS IT APPEARS THE EXISTING PANEL WAS PLACED |
| | INSIDE THE OLDER KITCHEN CABINETS WHICH WAS NEVER |
| | PERMITTED UNDER THE NEC, THE COUNTER SPACE/CABINETS |
| | APPEAR TO HAVE BEEN ADDED AT SOME POINT. |
| | IF SPACING EXISTS AND MEETS NEC, PLEASE SHOW. |
| | |
| | |
| | * ** IMPORTANT** |
| | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR |
| | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL |
| | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS |
| | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT |
| | LEAVE ANY OLD/VOIDED SHEETS IN SETS. |
| | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS |
| | SHOULD BE SUBMITTED FOR REFERENCE. |
| | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY |
| | DELAYS. |
| | |
| | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY |
| | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE |
| | DO NOT HESITATE IN CONTACTING THIS OFFICE. |
| | PLEASE SEE BELOW FOR CONTACT INFORMATION. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW II |
| | CONSTRUCTION SERVICES DEPT. |
| | CITY OF WEST PALM BEACH |
| | 561-805-6717 |
| | [email protected] |