| Plan Review Stops For Permit 07120350 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
P |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-01-25 |
Time |
15:21 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-01-25 |
Time |
15:21 |
Sent To |
|
|
| Notes |
| 2008-01-25 15:22:15 | PERMIT WAS ASSIGNED TO THE CORRECT ADDRESS AS 223 | | | CLEMATIS ST . | | | | | | QUESTIONS/COMMENTS | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
8 |
Status |
P |
Date |
2008-06-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-18 |
Time |
14:42 |
Rev Time |
0.55 |
| Received By |
jwitmer |
Date |
2008-06-18 |
Time |
14:42 |
Sent To |
|
|
| Notes |
| 2008-06-18 14:43:52 | REV# 7 SURFACE MOUNTED LIGHTS IN STAIRWELL, DO NOT | | | PENETRATE 1 HR CEILING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
7 |
Status |
P |
Date |
2008-06-06 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-06 |
Time |
15:23 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-06-06 |
Time |
15:23 |
Sent To |
PC |
|
| Notes |
| 2008-06-16 13:44:59 | 6/16/08--TO "BOB"#7 | | 2008-06-06 15:24:16 | REVISION, FRONT ENTRY FL# 8111 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
6 |
Status |
F |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-06-02 |
Time |
15:11 |
Rev Time |
1.22 |
| Received By |
jwitmer |
Date |
2008-06-02 |
Time |
15:11 |
Sent To |
PC |
|
| Notes |
| 2008-06-02 15:20:36 | BUILDING PLAN REVIEW | | | PERMIT: 07120350 | | | ADD:223 CLEMATIS ST | | | CONT: CASTLE FLORIDA | | | TEL: (561)441-0492/ MARK | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVISIONREVIEW | | | ACTION: DENIED | | | 1) THIS REVISION INDICATES THAT HIGH HAT FIXTURES ARE | | | GOING TO BE GOING THROUGH A 1 HR RATED CEILING, BUT NO | | | INFORMATION WAS SUBMITTED TO THE BUILDING DEPARTMENT AS | | | TO HOW TO MAINTAIN THE 1 HR RATING. | | | 711.5 PENETRATIONS.PENETRATIONS THROUGH | | | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL | | | COMPLY WITH SECTION 712. | | | | | | 712.4 HORIZONTAL ASSEMBLIES. | | | | | | PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE | | | CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE | | | PROTECTED IN ACCORDANCE WITH SECTION 707 . PENETRATIONS | | | PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL | | | COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4 . | | | EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR | | | UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO | | | HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1, | | | 2, 5, 7, 8 OR 9 IN SECTION 707.2 . | | | | | | 712.4.1 THROUGH PENETRATIONS. | | | THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED | | | HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION | | | 712.4.1.1 OR 712.4.1.2 . | | | | | | 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES. | | | PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN | | | APPROVED FIRE-RESISTANCE-RATED ASSEMBLY. | | | | | | 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM. | | | THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED | | | THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND | | | TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A | | | MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH | | | (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING | | | AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS | | | THAN THE REQUIRED RATING OF THE FLOOR PENETRATED. | | | EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED | | | WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING. | | | | | | | | | 712.4.2 MEMBRANE PENETRATIONS. | | | PENETRATIONS OF MEMBRANES THAT ARE PART OF A | | | FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLY SHALL COMPLY | | | WITH SECTION 712.4.1.1 OR 712.4.1.2 . WHERE | | | FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A MINIMUM | | | 1-HOUR FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL | | | BE INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE | | | WILL NOT BE REDUCED. | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
5 |
Status |
P |
Date |
2008-04-09 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-04-09 |
Time |
10:36 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2008-04-09 |
Time |
10:36 |
Sent To |
PC |
|
| Notes |
| 2008-04-09 10:56:24 | THRESHOLD BUILDING: | | | 1) FLOOR SHORING DETAILS AND INSPECTION LETTER | | | THRESHOLD INSPECTOR | | | 2) SHOP DRAWINGS STEEL PAN STAIRS |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-19 |
Time |
08:48 |
Rev Time |
1.33 |
| Received By |
jwitmer |
Date |
2008-02-19 |
Time |
08:48 |
Sent To |
|
|
| Notes |
| 2008-02-19 08:48:40 | REV # 4 |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-02-04 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-02-04 |
Time |
15:42 |
Rev Time |
2.22 |
| Received By |
jwitmer |
Date |
2008-02-04 |
Time |
15:42 |
Sent To |
|
|
| Notes |
| 2008-02-04 15:43:28 | BUILDING PROVISO: THRESHOLD INSPECTION REPORT IS TURNED | | | IN BEFORE ISSUANCE OF PERMIT AND A CURRENT NOC. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-01-18 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2008-01-18 |
Time |
11:12 |
Rev Time |
1.11 |
| Received By |
jwitmer |
Date |
2008-01-18 |
Time |
11:12 |
Sent To |
PC |
|
| Notes |
| 2008-01-18 11:13:03 | BUILDING PLAN REVIEW | | | PERMIT: 07120350 | | | ADD: 219 CLEMATIS ST | | | CONT: CASTLE FLORIDA | | | TEL: (561)756-2491 | | | | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2NDREVIEW | | | ACTION: DENIED | | | | | | | | | | | | 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT | | | ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 2) FROM THE PREVIOUS REVIEW, THE OWNERS HAVE UNIFIED | | | THE MONKEY CLUB BUILDING AND EVERYTHING WEST TO OLIVE | | | INTO ONE PROPERTY UNDER ONE PCN. THE SECOND ISSUE IS | | | THAT THEY HAVE ALSO | | | BROKE THROUGH THE 2 / 2HR RATED WALLS ALLOWING THE | | | SPACE WITHIN TO COMMUNICATE. BY REQUEST OF THE OWNERS | | | AND TENANT OF THE OLD MONKEY CLUB WE HAVE VISITED THE | | | SITE THIS IS FIRST HAND KNOWLEDGE OF WHAT IS TO BE | | | CONSIDERED A SINGLE BUILDING. | | | SHEET A-0 PROJECT INFORMATION, PLEASE CORRECT THE | | | BUILDING TYPE, THIS IS A 4 STORY BUILDING REQUIRING A | | | BLDG TYPE OF IIA FULLY SPRINKLERED BUILDING. PLEASE | | | NOTE THE CURRENT PLANS INDICATE UNPROTECTED STRUCTURAL | | | ELEMENTS, PLEASE SEE THE FIRE RATINGS FOR THE | | | STRUCTURAL ELEMENTS TABLE 601. | | | | | | 3-7) COMPLIED. | | | | | | 8) 2ND REQUEST,PLEASE CORRECT SHEET A-6.0, INDICATES | | | ON THE SECOND FLOOR THIS SPACE AS AN EXISTING | | | NIGHTCLUB, PLEASE CORRECT TO STORAGE.AGAIN THIS IS | | | KNOWLEDGE THAT YOU AS THE DESIGNER WOULD NOT HAVE | | | CURRENT INFORMATION, THE OPEN PERMIT THAT WAS FOR THIS | | | SPACE TO CREATE AN A-2 OCCUPANCY, NIGHTCLUB, THE TENANT | | | HAS DELETED THIS AREA FROM THE SCOPE OF WORK UNDER THIS | | | PERMIT WITH THE DELEETION OF ENCASING THE REAR | | | STAIRWAY.WE DO NOT INTEND TO ISSUE A PERMIT IF THE | | | REPRESENTATION IS NOT TRUELY REPRESENT THE CURRENT | | | INFORMATION ON HAND. | | | | | | | | | | | | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
jwitmer |
Date |
2007-12-21 |
Time |
11:30 |
Rev Time |
3.33 |
| Received By |
jwitmer |
Date |
2007-12-21 |
Time |
11:30 |
Sent To |
|
|
| Notes |
| 2007-12-21 11:42:57 | JIM WITMER C. B. O. | | | BUILDING PLAN REVIEW II | | | | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 | | | E-MAIL: [email protected] | | | | | | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS | | | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS | | | REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO | | | THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE | | | THEREFORE SUBJECT TO PUBLIC DISCLOSURE. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
6 |
Status |
P |
Date |
2008-09-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-09-10 |
Time |
09:08 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-09-10 |
Time |
09:08 |
Sent To |
PC |
|
| Notes |
| 2008-09-10 09:12:36 | ADDRESS ON PLANS SHOW 219 WHICH IS FOR ANOTHER SPACE TO | | | THE EAST OF STAIRS. PLANS WERE CHANGED BY REVIEWER TO | | | 223. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
5 |
Status |
P |
Date |
2008-06-19 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-06-19 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-06-19 |
Time |
10:09 |
Sent To |
PC |
|
| Notes |
| 2008-06-19 10:51:16 | | | | | | | REVISION #2 & 3, REVISED RECESS FIXTURE AND REPLACED | | | WITH SURFACE TO PRESERVE FIRE INTEGRITY OF CEILING IN | | | STAIRWELL./WRT. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
F |
Date |
2008-06-02 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-06-02 |
Time |
15:01 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-06-02 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2008-06-02 15:01:36 | ** DENIEDREVISION** | | | | | | | | | 1) NOTE: PLEASE SUPPLY INFORMATION WITH RESPECT TO | | | COVERING THE RECESSED LIGHTING AS SHOWN ON PLANS. | | | PLEASE SUPPLY INFORMATION ON HOW THESE MATS WILL BE | | | INSTALLED AND HOW THEY WILL AFFECT HEAT DISSIPATION. | | | PLEASE SUPPLY FIXTURE SPECS ON RATING OF RECESSED | | | FIXTURE WITH RESPECT TO HEAT AND AUTOMATIC SHUT OFF. | | | PLEASE KNOW INSTALLING A RECESSED LIGHT FIXTURE IN | | | AREAS OTHER THAN INTENDED DESIGN SPECIFICATIONS WILL | | | CREATE A FIRE/LIFE SAFETY HAZARD. | | | PLEASE REVIEW THE MANUFACTURES MINIMUM SPECIFICATIONS | | | AND PLEASE REVISE WITHIN ELECTRICAL PLANS. NEC 110.3, | | | 410 PART VII (ALL). | | | PLEASE SEE FBC CHAPTER 7 AND BUILDING REVIEW COMMENTS | | | FOR MAINTAINING CEILING RATINGS WITH RECESSED LIGHTING. | | | THIS IS ONLY NOTED AS BUILDING REVIEWER WILL NOTE. | | | | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT | | | HESITATE IN CONTACTING THIS OFFICE. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
P |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-09 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-09 |
Time |
16:07 |
Sent To |
|
|
| Notes |
| 2008-01-09 16:07:40 | SHEETS BROUGHT IN AND SETS COMPLETED BY CONTRACTOR. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-01-09 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-09 |
Time |
08:50 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-09 |
Time |
08:50 |
Sent To |
|
|
| Notes |
| 2008-01-09 08:50:50 | *** DENIED *** | | | | | | 1) NOTE: PLEASE SEE THE TWO NEW SETS ARE NOT COMPLETE | | | WITH ALL SHEETS. MISSING E-2, FP, AND SEVERAL A-SHEETS. | | | | | | THE OLD/VOIDED PREVIOUS SUBMITTED SINGLE SET WHICH WAS | | | BROUGHT BACK ONLY CONTAINS ONE OF EACH OF THE NEEDED | | | SHEETS | | | | | | ** CALLED AND LEFT MESSAGE ON JOHN SATEU VOICE MAIL TO | | | BRING IN SHEETS TO COMPLETE SETS. | | | | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-19 |
Time |
11:13 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-19 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2007-12-19 11:14:09 | ** DENIED ** | | | | | | | | | 1) NOTE: PLEASE SUBMIT LIGHTING PHOTO-METRICS MEETING | | | THE MINIMUM REQUIREMENTS OF NFPA-101 7.8.1.3 AND | | | 7.9.2.2. | | | PLEASE SEE A MINIMUM OF 10FT CANDLES UNDER NORMAL ARE | | | REQUIRED AND THEN IS PERMITTED DOWN TO 1FT CANDLE UNDER | | | EMERGENCY. | | | PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 FOR | | | REQUIRED LIGHTING LEVELS IN DESIGN. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | | | | | |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
P |
Date |
2008-01-14 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-14 |
Time |
14:08 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-14 |
Time |
13:49 |
Sent To |
|
|
| Notes |
| 2008-01-14 14:07:37 | ***** | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE | | | BEEN ADDRESSED;PLAN SHEETS A-1.0, A-2.0, A-6.0, E-1, | | | AND FP-1 WERE STAMPED, INTIALED, AND DATED. | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
|
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-28 |
Time |
16:40 |
Sent To |
|
|
| Notes |
| 2007-12-28 16:52:58 | *****DENIED***** | | | | | | 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 2.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE NEW | | | HANDRAILS AND/OR GUARDRAILS. | | | | | | 3.STAIRS SHALL HAVE HAVE HANDRAILS ON BOTH SIDES. | | | | | | 4.NEW HANDRAILS SHALL BE INSTALLED TO PROVIDE A | | | CLEARANCE OF NOT LESS THAN 2 1/4" BETWEEN THE HANDRAIL | | | AND THE WALL TO WHICH IT IS FASTENED. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHEAL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
10 |
Status |
N |
Date |
2008-09-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-09-03 |
Time |
11:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-09-03 |
Time |
11:07 |
Sent To |
E |
|
| Notes |
| 2008-09-03 11:07:53 | TO "DPALMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
9 |
Status |
N |
Date |
2008-06-16 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-16 |
Time |
13:42 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-16 |
Time |
13:42 |
Sent To |
|
|
| Notes |
| 2008-06-16 13:45:19 | TO "BOB"#7 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
8 |
Status |
N |
Date |
2008-06-04 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-06-04 |
Time |
16:20 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-06-04 |
Time |
16:20 |
Sent To |
B |
|
| Notes |
| 2008-06-04 16:21:03 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
7 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
13:17 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-12 |
Time |
13:17 |
Sent To |
B |
|
| Notes |
| 2008-05-23 16:25:43 | IN LUIS'S OFFICE5/23/08 | | 2008-05-12 13:17:54 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
6 |
Status |
N |
Date |
2008-03-21 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-21 |
Time |
12:41 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-21 |
Time |
12:40 |
Sent To |
B |
|
| Notes |
| 2008-03-21 12:41:21 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
5 |
Status |
N |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-20 |
Time |
16:53 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-20 |
Time |
16:53 |
Sent To |
B |
|
| Notes |
| 2008-03-20 16:53:44 | TO "JWITMER" DESK/SUBMITTAL |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-02-14 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-14 |
Time |
10:01 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-14 |
Time |
10:01 |
Sent To |
B |
|
| Notes |
| 2008-02-14 10:01:37 | TO "JWITMER" DESK/REV |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-28 |
Time |
10:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-28 |
Time |
10:25 |
Sent To |
B |
|
| Notes |
| 2008-01-28 10:29:29 | TO "JWITMER" DESK/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-08 |
Time |
11:57 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-08 |
Time |
11:57 |
Sent To |
|
|
| Notes |
| 2008-01-08 12:00:05 | TO "BOB"#4 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2007-12-28 |
Time |
16:40 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-14 |
Time |
11:41 |
Sent To |
|
|
| Notes |
| 2007-12-17 15:03:51 | TO "BOB"#1 | | 2007-12-14 11:44:45 | WAITING FOR "BOB"-PER "LMARTINEZ" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-19 |
Time |
11:15 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-19 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-19 |
Time |
11:14 |
Rev Time |
|
| Received By |
dpalmer |
Date |
|
Time |
|
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-18 |
Time |
13:29 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-18 |
Time |
13:29 |
Sent To |
|
|
| Notes |
| 2007-12-18 13:29:28 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|