Plan Review Details - Permit 07120350
Plan Review Stops For Permit 07120350
Review Stop AD ADDRESSING
Rev No 1 Status P Date 2008-01-25 Cont ID  
Sent By lursu Date 2008-01-25 Time 15:21 Rev Time 0.00
Received By lursu Date 2008-01-25 Time 15:21 Sent To  
Notes
2008-01-25 15:22:15PERMIT WAS ASSIGNED TO THE CORRECT ADDRESS AS 223
 CLEMATIS ST .
  
 QUESTIONS/COMMENTS
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 8 Status P Date 2008-06-18 Cont ID  
Sent By jwitmer Date 2008-06-18 Time 14:42 Rev Time 0.55
Received By jwitmer Date 2008-06-18 Time 14:42 Sent To  
Notes
2008-06-18 14:43:52REV# 7 SURFACE MOUNTED LIGHTS IN STAIRWELL, DO NOT
 PENETRATE 1 HR CEILING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 7 Status P Date 2008-06-06 Cont ID  
Sent By jwitmer Date 2008-06-06 Time 15:23 Rev Time 1.22
Received By jwitmer Date 2008-06-06 Time 15:23 Sent To PC
Notes
2008-06-16 13:44:596/16/08--TO "BOB"#7
2008-06-06 15:24:16REVISION, FRONT ENTRY FL# 8111

Review Stop B BUILDING (STRUCTURAL)
Rev No 6 Status F Date 2008-06-02 Cont ID  
Sent By jwitmer Date 2008-06-02 Time 15:11 Rev Time 1.22
Received By jwitmer Date 2008-06-02 Time 15:11 Sent To PC
Notes
2008-06-02 15:20:36BUILDING PLAN REVIEW
 PERMIT: 07120350
 ADD:223 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)441-0492/ MARK
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVISIONREVIEW
 ACTION: DENIED
 1) THIS REVISION INDICATES THAT HIGH HAT FIXTURES ARE
 GOING TO BE GOING THROUGH A 1 HR RATED CEILING, BUT NO
 INFORMATION WAS SUBMITTED TO THE BUILDING DEPARTMENT AS
 TO HOW TO MAINTAIN THE 1 HR RATING.
 711.5 PENETRATIONS.PENETRATIONS THROUGH
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLIES SHALL
 COMPLY WITH SECTION 712.
  
 712.4 HORIZONTAL ASSEMBLIES.
  
 PENETRATIONS OF A FLOOR, FLOOR/CEILING ASSEMBLY OR THE
 CEILING MEMBRANE OF A ROOF/CEILING ASSEMBLY SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 707 . PENETRATIONS
 PERMITTED BY EXCEPTIONS 3 AND 4 OF SECTION 707.2 SHALL
 COMPLY WITH SECTIONS 712.4.1 THROUGH 712.4.4 .
 EXCEPTION: PENETRATIONS LOCATED WITHIN THE SAME ROOM OR
 UNDIVIDED AREA AS FLOOR OPENINGS ARE NOT REQUIRED TO
 HAVE A SHAFT ENCLOSURE IN ACCORDANCE WITH EXCEPTION 1,
 2, 5, 7, 8 OR 9 IN SECTION 707.2 .
  
 712.4.1 THROUGH PENETRATIONS.
 THROUGH PENETRATIONS OF FIRE-RESISTANCE-RATED
 HORIZONTAL ASSEMBLIES SHALL COMPLY WITH SECTION
 712.4.1.1 OR 712.4.1.2 .
  
 712.4.1.1 FIRE-RESISTANCE-RATED ASSEMBLIES.
 PENETRATIONS SHALL BE INSTALLED AS TESTED IN AN
 APPROVED FIRE-RESISTANCE-RATED ASSEMBLY.
  
 712.4.1.2 THROUGH-PENETRATION FIRESTOP SYSTEM.
 THROUGH PENETRATIONS SHALL BE PROTECTED BY AN APPROVED
 THROUGH-PENETRATION FIRESTOP SYSTEM INSTALLED AND
 TESTED IN ACCORDANCE WITH ASTM E 814 OR UL 1479, WITH A
 MINIMUM POSITIVE PRESSURE DIFFERENTIAL OF 0.01 INCH
 (2.49 PA) OF WATER. THE SYSTEM SHALL HAVE AN F RATING
 AND A T RATING OF NOT LESS THAN 1 HOUR BUT NOT LESS
 THAN THE REQUIRED RATING OF THE FLOOR PENETRATED.
 EXCEPTION: FLOOR PENETRATIONS CONTAINED AND LOCATED
 WITHIN THE CAVITY OF A WALL DO NOT REQUIRE A T RATING.
  
  
 712.4.2 MEMBRANE PENETRATIONS.
 PENETRATIONS OF MEMBRANES THAT ARE PART OF A
 FIRE-RESISTANCE-RATED HORIZONTAL ASSEMBLY SHALL COMPLY
 WITH SECTION 712.4.1.1 OR 712.4.1.2 . WHERE
 FLOOR/CEILING ASSEMBLIES ARE REQUIRED TO HAVE A MINIMUM
 1-HOUR FIRE-RESISTANCE RATING, RECESSED FIXTURES SHALL
 BE INSTALLED SUCH THAT THE REQUIRED FIRE RESISTANCE
 WILL NOT BE REDUCED.
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 5 Status P Date 2008-04-09 Cont ID  
Sent By jwitmer Date 2008-04-09 Time 10:36 Rev Time 1.33
Received By jwitmer Date 2008-04-09 Time 10:36 Sent To PC
Notes
2008-04-09 10:56:24THRESHOLD BUILDING:
 1) FLOOR SHORING DETAILS AND INSPECTION LETTER
 THRESHOLD INSPECTOR
 2) SHOP DRAWINGS STEEL PAN STAIRS

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-02-19 Cont ID  
Sent By jwitmer Date 2008-02-19 Time 08:48 Rev Time 1.33
Received By jwitmer Date 2008-02-19 Time 08:48 Sent To  
Notes
2008-02-19 08:48:40REV # 4

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-02-04 Cont ID  
Sent By jwitmer Date 2008-02-04 Time 15:42 Rev Time 2.22
Received By jwitmer Date 2008-02-04 Time 15:42 Sent To  
Notes
2008-02-04 15:43:28BUILDING PROVISO: THRESHOLD INSPECTION REPORT IS TURNED
 IN BEFORE ISSUANCE OF PERMIT AND A CURRENT NOC.

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-01-18 Cont ID  
Sent By jwitmer Date 2008-01-18 Time 11:12 Rev Time 1.11
Received By jwitmer Date 2008-01-18 Time 11:12 Sent To PC
Notes
2008-01-18 11:13:03BUILDING PLAN REVIEW
 PERMIT: 07120350
 ADD: 219 CLEMATIS ST
 CONT: CASTLE FLORIDA
 TEL: (561)756-2491
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 2NDREVIEW
 ACTION: DENIED
  
  
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2) FROM THE PREVIOUS REVIEW, THE OWNERS HAVE UNIFIED
 THE MONKEY CLUB BUILDING AND EVERYTHING WEST TO OLIVE
 INTO ONE PROPERTY UNDER ONE PCN. THE SECOND ISSUE IS
 THAT THEY HAVE ALSO
 BROKE THROUGH THE 2 / 2HR RATED WALLS ALLOWING THE
 SPACE WITHIN TO COMMUNICATE. BY REQUEST OF THE OWNERS
 AND TENANT OF THE OLD MONKEY CLUB WE HAVE VISITED THE
 SITE THIS IS FIRST HAND KNOWLEDGE OF WHAT IS TO BE
 CONSIDERED A SINGLE BUILDING.
 SHEET A-0 PROJECT INFORMATION, PLEASE CORRECT THE
 BUILDING TYPE, THIS IS A 4 STORY BUILDING REQUIRING A
 BLDG TYPE OF IIA FULLY SPRINKLERED BUILDING. PLEASE
 NOTE THE CURRENT PLANS INDICATE UNPROTECTED STRUCTURAL
 ELEMENTS, PLEASE SEE THE FIRE RATINGS FOR THE
 STRUCTURAL ELEMENTS TABLE 601.
  
 3-7) COMPLIED.
  
 8) 2ND REQUEST,PLEASE CORRECT SHEET A-6.0, INDICATES
 ON THE SECOND FLOOR THIS SPACE AS AN EXISTING
 NIGHTCLUB, PLEASE CORRECT TO STORAGE.AGAIN THIS IS
 KNOWLEDGE THAT YOU AS THE DESIGNER WOULD NOT HAVE
 CURRENT INFORMATION, THE OPEN PERMIT THAT WAS FOR THIS
 SPACE TO CREATE AN A-2 OCCUPANCY, NIGHTCLUB, THE TENANT
 HAS DELETED THIS AREA FROM THE SCOPE OF WORK UNDER THIS
 PERMIT WITH THE DELEETION OF ENCASING THE REAR
 STAIRWAY.WE DO NOT INTEND TO ISSUE A PERMIT IF THE
 REPRESENTATION IS NOT TRUELY REPRESENT THE CURRENT
 INFORMATION ON HAND.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By jwitmer Date 2007-12-21 Time 11:30 Rev Time 3.33
Received By jwitmer Date 2007-12-21 Time 11:30 Sent To  
Notes
2007-12-21 11:42:57JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 6 Status P Date 2008-09-10 Cont ID  
Sent By dpalmer Date 2008-09-10 Time 09:08 Rev Time 0.00
Received By dpalmer Date 2008-09-10 Time 09:08 Sent To PC
Notes
2008-09-10 09:12:36ADDRESS ON PLANS SHOW 219 WHICH IS FOR ANOTHER SPACE TO
 THE EAST OF STAIRS. PLANS WERE CHANGED BY REVIEWER TO
 223.

Review Stop E ELECTRICAL
Rev No 5 Status P Date 2008-06-19 Cont ID  
Sent By btrobaug Date 2008-06-19 Time 10:45 Rev Time 0.00
Received By btrobaug Date 2008-06-19 Time 10:09 Sent To PC
Notes
2008-06-19 10:51:16 
  
 REVISION #2 & 3, REVISED RECESS FIXTURE AND REPLACED
 WITH SURFACE TO PRESERVE FIRE INTEGRITY OF CEILING IN
 STAIRWELL./WRT.

Review Stop E ELECTRICAL
Rev No 4 Status F Date 2008-06-02 Cont ID  
Sent By dpalmer Date 2008-06-02 Time 15:01 Rev Time 0.00
Received By dpalmer Date 2008-06-02 Time 15:01 Sent To  
Notes
2008-06-02 15:01:36** DENIEDREVISION**
  
  
 1) NOTE: PLEASE SUPPLY INFORMATION WITH RESPECT TO
 COVERING THE RECESSED LIGHTING AS SHOWN ON PLANS.
 PLEASE SUPPLY INFORMATION ON HOW THESE MATS WILL BE
 INSTALLED AND HOW THEY WILL AFFECT HEAT DISSIPATION.
 PLEASE SUPPLY FIXTURE SPECS ON RATING OF RECESSED
 FIXTURE WITH RESPECT TO HEAT AND AUTOMATIC SHUT OFF.
 PLEASE KNOW INSTALLING A RECESSED LIGHT FIXTURE IN
 AREAS OTHER THAN INTENDED DESIGN SPECIFICATIONS WILL
 CREATE A FIRE/LIFE SAFETY HAZARD.
 PLEASE REVIEW THE MANUFACTURES MINIMUM SPECIFICATIONS
 AND PLEASE REVISE WITHIN ELECTRICAL PLANS. NEC 110.3,
 410 PART VII (ALL).
 PLEASE SEE FBC CHAPTER 7 AND BUILDING REVIEW COMMENTS
 FOR MAINTAINING CEILING RATINGS WITH RECESSED LIGHTING.
 THIS IS ONLY NOTED AS BUILDING REVIEWER WILL NOTE.
  
  
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-01-09 Cont ID  
Sent By dpalmer Date 2008-01-09 Time 16:07 Rev Time 0.00
Received By dpalmer Date 2008-01-09 Time 16:07 Sent To  
Notes
2008-01-09 16:07:40SHEETS BROUGHT IN AND SETS COMPLETED BY CONTRACTOR.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-01-09 Cont ID  
Sent By dpalmer Date 2008-01-09 Time 08:50 Rev Time 0.00
Received By dpalmer Date 2008-01-09 Time 08:50 Sent To  
Notes
2008-01-09 08:50:50*** DENIED ***
  
 1) NOTE: PLEASE SEE THE TWO NEW SETS ARE NOT COMPLETE
 WITH ALL SHEETS. MISSING E-2, FP, AND SEVERAL A-SHEETS.
  
 THE OLD/VOIDED PREVIOUS SUBMITTED SINGLE SET WHICH WAS
 BROUGHT BACK ONLY CONTAINS ONE OF EACH OF THE NEEDED
 SHEETS
  
 ** CALLED AND LEFT MESSAGE ON JOHN SATEU VOICE MAIL TO
 BRING IN SHEETS TO COMPLETE SETS.
  
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 11:13 Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 11:13 Sent To  
Notes
2007-12-19 11:14:09** DENIED **
  
  
 1) NOTE: PLEASE SUBMIT LIGHTING PHOTO-METRICS MEETING
 THE MINIMUM REQUIREMENTS OF NFPA-101 7.8.1.3 AND
 7.9.2.2.
 PLEASE SEE A MINIMUM OF 10FT CANDLES UNDER NORMAL ARE
 REQUIRED AND THEN IS PERMITTED DOWN TO 1FT CANDLE UNDER
 EMERGENCY.
 PLEASE SEE FLORIDA ADMINISTRATIVE CODE 61G15-33.004 FOR
 REQUIRED LIGHTING LEVELS IN DESIGN.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  
  

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-01-14 Cont ID  
Sent By mawillia Date 2008-01-14 Time 14:08 Rev Time 0.00
Received By mawillia Date 2008-01-14 Time 13:49 Sent To  
Notes
2008-01-14 14:07:37*****
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A-1.0, A-2.0, A-6.0, E-1,
 AND FP-1 WERE STAMPED, INTIALED, AND DATED.
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time   Rev Time 0.00
Received By mawillia Date 2007-12-28 Time 16:40 Sent To  
Notes
2007-12-28 16:52:58*****DENIED*****
  
 1.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 2.PROVIDE PRESCRIPTIVE STRENGHTS FOR THE NEW
 HANDRAILS AND/OR GUARDRAILS.
  
 3.STAIRS SHALL HAVE HAVE HANDRAILS ON BOTH SIDES.
  
 4.NEW HANDRAILS SHALL BE INSTALLED TO PROVIDE A
 CLEARANCE OF NOT LESS THAN 2 1/4" BETWEEN THE HANDRAIL
 AND THE WALL TO WHICH IT IS FASTENED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHEAL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 10 Status N Date 2008-09-03 Cont ID  
Sent By adarroug Date 2008-09-03 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-09-03 Time 11:07 Sent To E
Notes
2008-09-03 11:07:53TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 9 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 13:42 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 13:42 Sent To  
Notes
2008-06-16 13:45:19TO "BOB"#7

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 16:20 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 16:20 Sent To B
Notes
2008-06-04 16:21:03TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 13:17 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 13:17 Sent To B
Notes
2008-05-23 16:25:43IN LUIS'S OFFICE5/23/08
2008-05-12 13:17:54TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-03-21 Cont ID  
Sent By adarroug Date 2008-03-21 Time 12:41 Rev Time 0.00
Received By adarroug Date 2008-03-21 Time 12:40 Sent To B
Notes
2008-03-21 12:41:21TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-03-20 Cont ID  
Sent By adarroug Date 2008-03-20 Time 16:53 Rev Time 0.00
Received By adarroug Date 2008-03-20 Time 16:53 Sent To B
Notes
2008-03-20 16:53:44TO "JWITMER" DESK/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-02-14 Cont ID  
Sent By adarroug Date 2008-02-14 Time 10:01 Rev Time 0.00
Received By adarroug Date 2008-02-14 Time 10:01 Sent To B
Notes
2008-02-14 10:01:37TO "JWITMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-01-28 Cont ID  
Sent By adarroug Date 2008-01-28 Time 10:29 Rev Time 0.00
Received By adarroug Date 2008-01-28 Time 10:25 Sent To B
Notes
2008-01-28 10:29:29TO "JWITMER" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-08 Cont ID  
Sent By shill Date 2008-01-08 Time 11:57 Rev Time 0.00
Received By shill Date 2008-01-08 Time 11:57 Sent To  
Notes
2008-01-08 12:00:05TO "BOB"#4

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-28 Cont ID  
Sent By mawillia Date 2007-12-28 Time 16:40 Rev Time 0.00
Received By mawillia Date 2007-12-14 Time 11:41 Sent To  
Notes
2007-12-17 15:03:51TO "BOB"#1
2007-12-14 11:44:45WAITING FOR "BOB"-PER "LMARTINEZ"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 11:15 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 11:14 Rev Time  
Received By dpalmer Date   Time   Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 13:29 Rev Time 0.00
Received By choops Date 2007-12-18 Time 13:29 Sent To  
Notes
2007-12-18 13:29:28*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.