Plan Review Details - Permit 07120346
Plan Review Stops For Permit 07120346
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mjacobs Date 2008-05-20 Time 12:21 Rev Time 0.00
Received By mjacobs Date 2008-05-20 Time 09:49 Sent To  
Notes
2008-05-20 12:05:55 
 1009.4 STAIRWAY LANDINGS.
 EXCEPTIONS:
 2.DOORS OPENING ONTO A LANDING SHALL NOT REDUCE THE
 LANDING TO LESS THAN ONE-HALF THE REQUIRED WIDTH. WHEN
 FULLY OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7
 INCHES INTO A LANDING .

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-22 Cont ID  
Sent By mjacobs Date 2007-12-22 Time 08:14 Rev Time 0.00
Received By mjacobs Date 2007-12-22 Time 06:55 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-05-22 Cont ID  
Sent By btrobaug Date 2008-05-22 Time 11:33 Rev Time 0.00
Received By btrobaug Date 2008-05-22 Time 11:09 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-19 Cont ID  
Sent By dpalmer Date 2007-12-19 Time 13:53 Rev Time 0.00
Received By dpalmer Date 2007-12-19 Time 13:53 Sent To  
Notes
***NONE***

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-05-20 Cont ID  
Sent By mwennerg Date 2008-05-20 Time 15:57 Rev Time 0.00
Received By mwennerg Date 2008-05-20 Time 15:57 Sent To  
Notes
2008-05-20 15:58:06SEPARATE SHOP DRAWINGS AND PERMIT REQUIRED FOR FIRE
 SPRINKLER REMODEL.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status P Date 2007-12-21 Cont ID  
Sent By mwennerg Date 2007-12-21 Time 16:00 Rev Time 0.00
Received By mwennerg Date 2007-12-21 Time 16:00 Sent To  
Notes
***NONE***

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-14 Cont ID  
Sent By adarroug Date 2008-05-14 Time 12:55 Rev Time 0.00
Received By adarroug Date 2008-05-14 Time 12:55 Sent To  
Notes
2008-05-14 12:55:15TO "BOB"#8

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-04-02 Cont ID  
Sent By adarroug Date 2008-04-02 Time 10:23 Rev Time 0.00
Received By adarroug Date 2008-04-02 Time 10:23 Sent To M
Notes
2008-04-02 10:23:45TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-12-22 Time   Rev Time 0.00
Received By adarroug Date 2007-12-14 Time 11:05 Sent To  
Notes
2007-12-17 09:39:41TO "BOB"#9
2007-12-14 11:16:44WAITING FOR "BOB"

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-05-14 Cont ID  
Sent By tgordon Date 2008-05-14 Time 15:49 Rev Time 0.40
Received By tgordon Date 2008-05-14 Time 15:49 Sent To  
Notes
2008-05-14 15:51:27REVISION TO MECHANICAL PLANS M-1, M-2, AND M-3.
  
 *** PROVISO ***
 1) 603.15 REGISTERS, GRILLES AND DIFFUSERS.
 DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME
 SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED
 PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT
 OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER.
 (PB-1).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-04-03 Cont ID  
Sent By tgordon Date 2008-04-03 Time 09:29 Rev Time 0.45
Received By tgordon Date 2008-04-03 Time 09:29 Sent To  
Notes
2008-04-03 09:32:26REVISION TO MECHANICAL PLANS M-1, M-2, AND M-3.
  
 *** PROVISO ***
 1) 603.15 REGISTERS, GRILLES AND DIFFUSERS.
 DUCT REGISTERS, GRILLES AND DIFFUSERS SHALL BE
 INSTALLED IN ACCORDANCE WITH THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS, AND SHALL HAVE A FLAME
 SPREAD RATING NOT OVER 25 WITHOUT EVIDENCE OF CONTINUED
 PROGRESSIVE COMBUSTION AND A SMOKE-DEVELOPED RATING NOT
 OVER 50 WHEN TESTED IN ACCORDANCE WITH ASTM E 84.
 BALANCING DAMPERS OR OTHER MEANS OF SUPPLY AIR
 ADJUSTMENT SHALL BE PROVIDED IN THE BRANCH DUCTS OR AT
 EACH INDIVIDUAL DUCT REGISTER, GRILLE OR DIFFUSER.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-17 Cont ID  
Sent By tgordon Date 2007-12-17 Time 14:45 Rev Time 0.30
Received By tgordon Date 2007-12-17 Time 14:45 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 13:17 Rev Time 0.00
Received By choops Date 2007-12-18 Time 13:17 Sent To  
Notes
2007-12-18 13:17:43*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.