Plan Review Details - Permit 07120321
Plan Review Stops For Permit 07120321
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-08-25 Cont ID  
Sent By amorse Date 2008-08-25 Time 16:01 Rev Time 0.00
Received By amorse Date 2008-08-25 Time 16:01 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-17 Cont ID  
Sent By amorse Date 2008-06-17 Time 17:33 Rev Time 0.00
Received By amorse Date 2008-06-17 Time 17:33 Sent To PC
Notes
2008-06-17 17:59:44 
 DENIED
  
 THE FOLLOWING COMMENTS FROM THE 1ST AND 2ND REVIEW WERE
 NOT ADDRESSED
  
 1ST REVIEW
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 11)NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF DECK
 ABOVE STUDY AND ON BALCONY,NEW DOOR UNIT WITH GLAZED
 SIDELITES AND CONNECTORS AND STRAPS. IN LUE OF PRODUCT
 APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE
 ON THE DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT
 APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE
 FLORIDA INDEX WITH CONNECTORS TO BE USED HIGHLIGHTED.
 *********AS STATED IN COMMENT # 1 OF THE SECOND REVIEW
 THE MIAMI-DADE COMPLIANCE REPORT THAT BELONGS TO THIS
 STATE APPROVAL IS NOT THE ONE SUBMITTED, NOA 07-0522.07
 BELONGS WITH THIS STATE APPROVAL. ******** ********NO
 PRODUCT APPROVAL WAS SUBMITTED FOR THE ROOF DECK OVER
 STUDY ALTHOUGH THIS IS A PATIO, AN APPROVED ROOFING
 APPLICATION IS STILL REQUIRED********** *********NO
 PRODUCT APPROVALS WERE SUBMITTED FOR FRAMING STRUCTURAL
 CONNECTORS********
  
  
 2ND REVIEW
  
 1)THE FLORIDA PRODUCT APPROVAL FOR THE NEW FRONT
 ENTRY DOOR WAS NOT SUBMITTED WITH THE CORRECT
 COMPLIANCE REPORT, IF THIS IS THE DOOR TO BE INSTALL
 PROVIDE THE "ARCHITECTURAL TESTING INC," REPORT THAT IS
 FOUND UNDER THE LINK. IF THE MODEL YOU HAVE CHOSEN IS
 NOT COVERED BY THE STATE AND IT IS THE ONE IN THE
 MIAMI-DADE REPORT,A LOCAL PRODUCT APPROVAL WILL BE
 GRANTED ON THE MIAMI-DADE NOA/COMPLIANCE REPORT.
 *********WILL THIS PRODUCT BE USED FOR THE NEW REAR
 ENTRY DOOR, IF SO PLEASE REMOVE THE FLORIDA SHEETS AND
 REVIEW AND APPROVE JUST THE MIAMI-DADE FOR LOCAL
 PRODUCT APPROVAL
  
 NEW COMMENTS
  
 1)THE NEW DRAWINGS SPECIFY A SOLID 2 1/4" PECKY
 CYPRESS DOOR PLEASE SUBMIT APPLICATION FOR SITE
 SPECIFIC PRODUCT APPROVAL THAT DOOR WILL MEET THE
 REQUIRED WIND LOADS
  
 2)PER THE PRODUCT APPROVAL FOR THE SIDELITE/TRANSOMS
 WHERE JOINED TOGETHER ABOVE THE DOOR MULLIONS ARE
 REQUIRED, PLEASE SUBMIT APPROVALS (FL# 10330) FOR
 HARTMAN APPROVED MULLIONS
  
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 ******ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICALAND ROOFING******
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-28 Cont ID  
Sent By amorse Date 2008-02-28 Time 16:47 Rev Time 0.00
Received By amorse Date 2008-02-28 Time 16:47 Sent To PC
Notes
2008-02-28 17:08:37 
  
 DENIED
  
 THE FOLLOWING COMMENTS FROM THE 1ST REVIEW WERE NOT
 ADDRESSED
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
 *******NOTE: FEES ARE DUE IN THE AMOUNT OF $226.63 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN
 REVIEW********
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY/SITE PLAN
 SHOWING THE PROPOSED BUILDING/ADDITION WITH ALL
 SETBACKS. *******AREA OF CONCERN IS NEW FRAMED WALL
 THAT IS INSTALLED IN LINE WITH EXISTING WALL THAT
 ENCROACHES INTO 25 FOOT MIN FRONT SETBACK*********
  
 11)NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF DECK
 ABOVE STUDY AND ON BALCONY,NEW DOOR UNIT WITH GLAZED
 SIDELITES AND CONNECTORS AND STRAPS. IN LUE OF PRODUCT
 APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE
 ON THE DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT
 APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE
 FLORIDA INDEX WITH CONNECTORS TO BE USED HIGHLIGHTED.
  
 19)PROVIDE A KEY PLAN (WITH EGRESS SHOWN), SHUTTER
 SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS
 SHALL BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE
 AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT
 INFORMATION SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION,
 MOUNTING CONNECTION METHOD, ANCHOR TYPE, SHUTTER SPAN
 (VERTICAL OR HORIZONTAL), ETC.) PLEASE SEE THE ATTACHED
 MEMO AND SCHEDULE.
  
 NEW COMMENTS
  
 1)THE FLORIDA PRODUCT APPROVAL FOR THE NEW FRONT
 ENTRY DOOR WAS NOT SUBMITTED WITH THE CORRECT
 COMPLIANCE REPORT, IF THIS IS THE DOOR TO BE INSTALL
 PROVIDE THE "ARCHITECTURAL TESTING INC," REPORT THAT IS
 FOUND UNDER THE LINK. IF THE MODEL YOU HAVE CHOSEN IS
 NOT COVERED BY THE STATE AND IT IS THE ONE IN THE
 MIAMI-DADE REPORT,A LOCAL PRODUCT APPROVAL WILL BE
 GRANTED ON THE MIAMI-DADE NOA/COMPLIANCE REPORT.
  
 2)PLEASE REMOVE THE CYPRESS ENTRY DOOR FRAME DETAIL
 FROM THE DRAWINGS AND PROVIDE FRAMED WALL DETAILS FOR
 NEW ENTRY DOOR
  
 3)PLEASE NOTE THAT ONE SET OF DRAWINGS IS MISSING THE
 ARCHITECTS SIGNATURE ON SHEET A-2
  
 4)PLANS THAT ARE REVISED AND NEW PAGES SHALL BE
 REVIEWED AND APPROVED BY THE HISTORIC PRESERVATION
 DIVISION
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 ******ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICALAND ROOFING******
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-08 Cont ID  
Sent By amorse Date 2008-01-08 Time 15:52 Rev Time 0.00
Received By amorse Date 2008-01-08 Time 15:52 Sent To PC
Notes
2008-01-08 16:04:32 
  
 DENIED
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)IN AN EXISTING BUILDING WHERE ALTERATIONS ARE BEING
 MADE A DESIGN PROFESSIONAL MUST ELECT THE LEVEL OF
 ALTERATION PER 301.5 OF EXISTING BUILDING CODE AND
 STATE ALONG WITH THE TYPE OF CONSTRUCTION ON THE
 DRAWINGS
  
 3)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 4)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $226.63 FOR
 INCREASED VALUE AND STATE RADON FEES THIS AMOUNT IS
 REQUIRED TO BE PAID PRIOR TO FURTHER PLAN REVIEW
  
 5)PROVIDE 2 COPIES OF A RECENT SURVEY SHOWING THE
 PROPOSED BUILDING/ADDITION WITH ALL SIDE AND REAR
 SETBACKS
  
 6)PROVIDE A SITE PLAN THAT SHOWS DRAINAGE IN
 COMPLIANCE WITH THE REQUIREMENTS OF R403.1 FBC RES.
  
 7)SUBMIT TWO COPIES OF ENERGY CALC'S PER 13-101.2.2
 FBC. BE SURE THAT THEY ARE SIGNED AND
 DATED BY PREPARER AND OWNER/AGENT PRIOR
 TO SUBMITTAL
  
 8)THE PERMIT APPLICATION SHALL INCLUDE TWO COPIES OF
 EACH PRODUCT APPROVAL THAT IS RELEVANT PER 9B-72. THESE
 SHOULD INCLUDE THE FLORIDA STATE APPROVAL COVER PAGES.
 ALL CAN BE FOUND ON WWW.FLORIDABUILDING.ORG *****NOTE
 ONLY ONE COPY OF EACH APPROVAL WAS SUBMITTED*****
  
 9)THOSE PRODUCTS WHICH ARE REGULATED BY DCA RULE
 9B-72 (PRODUCT APPROVALS) SHALL BE REVIEWED AND
 APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO
 SUBMITTAL FOR JURISDICTIONAL APPROVAL PER 106.3.3 FBC*
  
 10)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER
 SHEETS WHEN AVAILABLE. THEY CAN BE SEARCHED FOR ON
 WWW.FLORIDABUILDING.ORG.WHEN AVAILABLE AND NOT
 SUBMITTED APPLICATIONS WILL BE DENIED
  
 11)NO PRODUCT APPROVALS WERE SUBMITTED FOR ROOF DECK
 ABOVE STUDY AND ON BALCONY,NEW DOOR UNIT WITH GLAZED
 SIDELITES AND CONNECTORS AND STRAPS. IN LUE OF PRODUCT
 APPROVALS STRAPS/CONNECTORS MAY BE LISTED IN A SCHEDULE
 ON THE DRAWINGS COMPLETE WITH THE STATEWIDE PRODUCT
 APPROVAL NUMBERS OR SUBMIT SIMPSON TIE'S COMPLETE
 FLORIDA INDEX WITH CONNECTORS TO BE USED HIGHLIGHTED.
 THE DOOR UNITMAY RECEIVE LOCAL PRODUCT APPROVAL/SITE
 SPECIFIC, PLEASE SEE ENCLOSED APPLICATION
  
 12)ENTRY DOOR DOES NOT MEET EGRESS REQUIREMENTS PER
 R311.4.2 FBC RES
  
 13)HANDRAIL/GUARD AT BALCONY TO MEET REQUIREMENTS OF
 R312.2 AND SHALL NOT ALLOW PASSAGE OF 4" SPHERE
  
 14)PROVIDE STRUCTURAL SITE WALL AND FOUNDATION
 DETAILS, ALSO FRAMING DETAILS FOR NEW OPENINGS IN
 ADDITION
  
 15)PLYWOOD ROOF SHEATHING TO BE FASTENED PER
 R803.2.3.1 FBC RES 4" O/C IN 130 MPH OR GREATER IN ZONE
 3 OF ROOF
  
 16)PROVIDE ROOF PITCH
  
 17)SECTION DESIGNATIONS ON SHEETS A/03 AND A/04 ARE
 INCORRECTLY DIRECTING TO SHEET A/01 OR A/03
  
 18)EXTERIOR STAIRWAY IS REQUIRED TO COMPLY WITHTHE
 REQUIREMENTS OF R311.5 THRU R311.5.7 FBC RES
  
 19)PROVIDE A KEY PLAN (WITH EGRESS SHOWN), SHUTTER
 SCHEDULE AND THE PRODUCT APPROVALS. APPROVAL DRAWINGS
 CAN BE MARKED FOR MOUNTING METHOD AND CONNECTION TYPE
 AND THE SCHEDULE FILLED OUT WITH ALL PERTINENT
 INFORMATION SPECIFIC TO THE SITE (TYPE OF CONSTRUCTION,
 MOUNTING CONNECTION METHOD, ANCHOR TYPE, SHUTTER SPAN
 (VERTICAL OR HORIZONTAL), ETC.) PLEASE SEE THE ATTACHED
 MEMO AND SCHEDULE.
  
 20)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 ******ADDITIONAL PERMITS WILL BE REQUIRED FOR PLUMBING,
 ELECTRICALAND ROOFING******
  
 REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS OF
 NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF THE
 OLD PAGES ONLY FOR REFERENCE.
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 3 Status P Date 2008-06-12 Cont ID  
Sent By dpalmer Date 2008-06-12 Time 11:29 Rev Time 0.00
Received By dpalmer Date 2008-06-12 Time 11:29 Sent To B
Notes
2008-06-12 11:30:02ARCHITECT CAME IN A DATED PLANS.

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-06-11 Cont ID  
Sent By dpalmer Date 2008-06-11 Time 09:50 Rev Time 0.00
Received By dpalmer Date 2008-06-11 Time 09:50 Sent To B
Notes
2008-06-11 09:53:08TEMP FAILED STATUS AS ARCHITECT DID NOT DATE PLANS WHEN
 SIGNED AND SEALED AS REQUIRED BY FS 481.221.
 ARCHITECT MAY COME IN AND DATE PLANS PERSONALLY AND
 REVIEW STATUS WILL CHANGE TO A PASS.
  
 PERMITS FOR ELECTRICAL AND LOW VOLTAGE STILL REQUIRED.
 MAY REFERENCE THE PERMIT NUMBER FOR TURN AROUND PERMITS
 FOR EACH.
  

Review Stop E ELECTRICAL
Rev No 1 Status P Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 14:40 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 14:35 Sent To B
Notes
2007-12-23 14:41:18REDLINED NEC 2005
  
 SEPARATE PERMITS STILL REQUIRED FOR ELECTRICAL AND LOW
 VOLTAGE. THESE PLANS MAY BE REFERENCE FOR BOTH.

Review Stop HIST HISTORICAL
Rev No 1 Status P Date 2007-12-13 Cont ID  
Sent By ssherman Date 2007-12-13 Time 10:15 Rev Time 0.00
Received By ssherman Date 2007-12-13 Time 10:15 Sent To  
Notes
2007-12-13 10:15:21HISTORICAL APPROVAL PER GALINA JUDGE

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-07-23 Cont ID  
Sent By adarroug Date 2008-07-23 Time 10:28 Rev Time 0.00
Received By adarroug Date 2008-07-23 Time 10:28 Sent To B
Notes
2008-07-23 10:28:42TO "AMORSE" DESK/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-04 Cont ID  
Sent By adarroug Date 2008-06-04 Time 09:55 Rev Time 0.00
Received By adarroug Date 2008-06-04 Time 09:55 Sent To Z
Notes
2008-06-04 09:55:42TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-22 Cont ID  
Sent By adarroug Date 2008-02-22 Time 14:45 Rev Time 0.00
Received By adarroug Date 2008-02-22 Time 14:45 Sent To Z
Notes
2008-02-22 14:46:08TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2008-01-08 Time   Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 16:05 Sent To  
Notes
2007-12-13 16:05:28TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 1 Status N Date 2007-12-21 Cont ID  
Sent By tgordon Date 2007-12-21 Time 13:44 Rev Time 0.20
Received By tgordon Date 2007-12-21 Time 13:44 Sent To E
Notes
2007-12-21 13:45:03NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 1 Status N Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 14:39 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 14:41 Sent To  
Notes
2007-12-23 14:40:14NO PLUMB APPLIED FOR, NO PLUMB IN SCOPE.

Review Stop Z ZONING
Rev No 3 Status P Date 2008-06-09 Cont ID  
Sent By choops Date 2008-06-09 Time 10:18 Rev Time 0.00
Received By choops Date 2008-06-09 Time 10:18 Sent To E
Notes
2008-06-09 10:21:16***APPROVED - RESUB #2***
  
 PROVISOS:
 1)NEW FRONT PORCH MUST BE SETBACK A MINIMUM OF 25'
 FROM FRONT PROPERTY LINE AND SHALL BE SETBACK A MINIMUM
 OF 10' FROM THE EAST SIDE PROPERTY LINE.
 2)TOTAL IMPERMEABLE SURFACE WITHIN THE FRONT YARD
 (FRONT PROPERTY LINE TO FRONT BUILDING FACADE), SHALL
 NOT EXCEED 512.5 SQUARE FEET.
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-25 Cont ID  
Sent By choops Date 2008-02-25 Time 14:19 Rev Time 0.00
Received By choops Date 2008-02-25 Time 14:20 Sent To B
Notes
2008-02-25 14:20:57***FAILED - RESUB #1***
  
  
 REPEAT COMMENTS:
  
 1)SURVEYS AND/OR SITE PLAN SHALL INDICATE PROPOSED
 WORK WITH SETBACK DIMENSION TO ALL PROPERTY LINES.
 NOTE:ALL NEW CONSTRUCTION SHALL MEET CURRENT
 REGULATIONS, INCLUDING THE 25 FOOT FRONT SETBACK
 REQUIREMENT.
  
 NEW COMMENTS:
  
 1)NEWLY SUBMITTED PLANS SHALL BE APPROVED/RESTAMPED
 BY THE CITY'S HISTORIC PRESERVATION DEPARTMENT.
  
  
 NOTE:TOTAL IMPERMEABLE SURFACE WITHIN THE FRONT YARD
 (FRONT PROPERTY LINE TO FRONT BUILDING FACADE), SHALL
 NOT EXCEED 512.5 SQUARE FEET.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "B" - AM

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By choops Date 2007-12-14 Time 15:42 Rev Time 0.00
Received By choops Date 2007-12-14 Time 15:42 Sent To E
Notes
2007-12-14 16:01:44***FAILED***
  
  
 1)PROVIDE TWO (2) CURRENT SURVEYS SHOWING THE
 LOCATION OF THE PROPOSED WORK WITH SETBACK DIMENSION TO
 ALL PROPERTY LINES.NOTE:MUST MAINTAIN A MINIMUM
 FRONT SETBACK OF 25' TO THE OUTERMOST EDGE OF PROPOSED
 2ND STORY PORCH.
  
 2)PURSUANT TO SECTION 94-305(B)(7) OF THE ZONING AND
 LAND DEVELOPMENT REGULATIONS (ZLDRS):STEPS AND
 PORCHES.STEPS, OPEN UNCOVERED PORCHES OR STOOPS, AND
 OPEN TERRACES WHICH ARE THREE FEET OR LESS ABOVE GRADE
 MAY ENCROACH INTO ANY REQUIRED SETBACK AREA TO A POINT
 NOT CLOSER THAN TWO FEET TO THE PROPERTY LINE. ANY
 GRADE DIFFERENTIAL BETWEEN THE ENCROACHING STEP, PORCH,
 STOOP, OR TERRACE AND ADJACENT PROPERTY SHALL BE
 STRUCTURALLY RETAINED AND POSITIVELY DRAINED IN A
 MANNER THAT WILL PREVENT ANY DRAINAGE DISCHARGE TO ANY
 PROPERTY CONTIGUOUS TO THE SIDE OR REAR PROPERTY LINES.
 PLEASE PROVIDE A SECTION DETAIL OF THE PROPOSED
 RAMP/STAIRS IN RELATION TO THE GRADE OF THE PROPERTY.
  
 3)PROVIDE SQUARE FOOTAGE OF ALL PROPOSED AND
 EXISTING IMPERMEABLE SURFACE WITHIN THE FRONT YARD
 (FRONT OF BUILDING TO FRONT PROPERTY LINE).MUST
 MAINTAIN 75% OR 1,000 SQ.FT. WHICH EVER IS LESS, OF
 LANDSCAPING MATERIAL WITHIN THE FRONT YARD AS PER
 SECTION 94-482 OF THE ZLDRS.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - METAL RACK