Plan Review Details - Permit 07120318
Plan Review Stops For Permit 07120318
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-08 Cont ID  
Sent By mjacobs Date 2008-02-08 Time 10:43 Rev Time 0.00
Received By mjacobs Date 2008-02-08 Time 10:11 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status P Date 2007-12-19 Cont ID  
Sent By mjacobs Date 2007-12-19 Time 14:30 Rev Time 0.00
Received By mjacobs Date 2007-12-19 Time 10:17 Sent To  
Notes
2007-12-19 14:11:11PROVISOR:A PORTION OF THE MAIN COUNTER SHALL BE A
 MINIMUM OF 36 INCHES IN LENGTH AND SHALL BE A MAXIMUM
 HEIGHT OF 36 INCHES. FBC 11-7(2)(I).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By dpalmer Date 2008-02-06 Time 09:43 Rev Time 0.00
Received By dpalmer Date 2008-02-06 Time 09:43 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-22 Cont ID  
Sent By dpalmer Date 2007-12-22 Time 14:27 Rev Time 0.00
Received By dpalmer Date 2007-12-22 Time 14:27 Sent To  
Notes
2007-12-22 14:28:12** DENIED REVIEW **
  
 1) NOTE. PLEASE PROVIDE LIGHTING PERFORMANCE
 CALCULATIONS FOR NEW AREAS ONLY PER 13-415.2,
 13-415.2.B.1
 THIS IS ONLY FOR NEW LIGHTING BEING INSTALLED INCLUDING
 THOSE SHOWN FROM EXISTING CONTROLS.
  
 2) NOTE: PLEASE SEE COVER SHEET REFERENCES 2005 NFPA-72
 HOWEVER THE STATE IS STILL UNDER THE 2002 EDITION.
 PLEASE CLARIFY REFERENCE AS FA DEVICES NEW OR EXISTING
 COULD NOT BE LOCATED. IF SYSTEM EXISTS, PLEASE IDENTIFY
 DEVICES COMPLYING WITH FBC 11-4.28.1,.2,AND .3(4) FOR
 ADA.
 COULD NOT DETERMINE IF SYSTEM IS PRESENT, EXISTING, NEW
 OR IF APPLICABLE. PLEASE SEE POSSIBLE COMMENTS FROM
 FIRE MARSHAL.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By mawillia Date 2008-02-07 Time 15:08 Rev Time 0.00
Received By mawillia Date 2008-02-07 Time 14:51 Sent To  
Notes
2008-02-07 14:55:13*****APPROVED******
  
 PLAN SHEETS 2 AND 3 WERE STAMPED, INITIALED, AND
 DATED.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By mawillia Date 2007-12-27 Time 11:36 Rev Time 0.00
Received By mawillia Date 2007-12-27 Time 10:59 Sent To  
Notes
2007-12-27 11:36:18*****UNSAT******
  
  
 1.THE 2000 EDITION OF NFPA 241 SHALL BE REFERENCED.
 SEE SHEET 1, UNDERCODES FOR THIS PROJECT
  
 2.SINCE THE SCOPE OF WORK IS FOR SUITE 303 ONLY,
 OMIT/DELETE SUITE 304 FROM THE PROJECT SITE ADDRESS
 LOCATED IN THE TITLE BLOCK OF EACH SUBMITTED PLAN
 SHEET.
  
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-01 Cont ID  
Sent By adarroug Date 2008-02-01 Time 13:36 Rev Time 0.00
Received By adarroug Date 2008-02-01 Time 13:36 Sent To  
Notes
2008-02-01 13:38:50TO "BOB"#13

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-27 Cont ID  
Sent By mawillia Date 2007-12-27 Time 10:59 Rev Time 0.00
Received By mawillia Date 2007-12-13 Time 16:08 Sent To  
Notes
2007-12-13 16:13:26TO "BOB"#13

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-01 Cont ID  
Sent By tgordon Date 2008-02-01 Time 15:29 Rev Time 0.30
Received By tgordon Date 2008-02-01 Time 15:29 Sent To  
Notes
2008-02-01 15:30:12PLAN RESUBMITTED.

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-17 Cont ID  
Sent By tgordon Date 2007-12-17 Time 15:01 Rev Time 0.25
Received By tgordon Date 2007-12-17 Time 15:01 Sent To  
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By mperson Date 2008-02-07 Time 08:00 Rev Time 0.00
Received By mperson Date 2008-02-07 Time 08:00 Sent To  
Notes
2008-02-07 08:07:23****************PROVISO****************
 A} PER FBC PLUMBING, SECTION 704.5
 DEAD ENDS: IN THE INSTALLATION OR
 REMOVAL OF ANY PART OF A DRAINAGE
 SYSTEM, DEAD ENDS SHALL BE PROHIBITED.
 A PLUMBING PERMIT IS REQUIRED AND AN
 INSPECTION IS REQUIRED OF DEMO WORK PRIOR
 TO COVERING DEMO WORK WITH FINNISH
 WALLS, CIELINGS, OR POURED CONCRETE
 SLABS.
  
 B} PER FBC PLUMBING SECTION *802.2 DISHWASHING
 MACHINES SHALL DISCHARGE INTO A WYE-BRANCH FITTING ON
 THE TAILPIECE OF THE KITCHEN SINK.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By mperson Date 2007-12-18 Time 08:38 Rev Time 0.00
Received By mperson Date 2007-12-18 Time 08:38 Sent To  
Notes
2007-12-18 10:18:11PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. SHEET 4, PLUMBING FIXTURE SCHEDULE AND SHEET 6,
 POWER PLAN ARE INDICATING A DISPOSAL, HOWEVER THE
 DISPOSAL IS NOT BEING INDICATED ON SHEET 3, DETAIL "C"
 LOUNGE OR SHEET 2, STAFF LOUNGE. PLEASE CORRELATE ALL
 SHEETS TO REFLECT THE DISPOSAL. PER *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS. PLEASE PROVIDE
 THE FOLLOWING ADDITIONAL INFORMATION FOR THE STAFF
 LOUNGE SINK WTH DISPOSAL COMPLIANT WITH THE FOLLOWING.
  
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.3 KNEE CLEARANCE. MINIMUM 27" HIGH, 30" WIDE,
 AND 19" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.
 11-4.24.6 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.24.7 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR
 ELECTRONICALLY CONTROLLED ARE ACCEPTABLE DESIGNS.
  
 PLEASE PROVIDE MANUFACTURER'S SPECIFCATION SHEETS OF
 THE PROPOSED DISPOSAL AND FAUCET INDICATED ON SHEET 4,
 PLUMBING FIXTURE SCHEDULE THAT MEETS ADA REQUIREMENTS.
  
 2. SHEET 2, TOILET ROOM ELEVATION "A" PLEASE PROVIDE
 THE FOLLOWING THE FOLLOWING INFORMATION FOR THE
 LAVATORY COMPLIANT WITH THE FOLLOWING.
  
 **11-4.19 LAVATORIES AND MIRRORS (ELEVATION DETAIL
 REQUIRED WITH THE FOLLOWING INFORMATION)
 11-4.19.4 EXPOSED PIPES AND SURFACES. INSULATE TO
 PROTECT AGAINST CONTACT.
 11-4.19.5 FAUCETS. LEVER-OPERATED, PUSH-TYPE AND
 ELECTRONICALLY CONTROLLED ARE EXAMPLES.
  
 PLEASE PROVIDE MANFACTURER'S SPECIFICATION SHEET OF THE
 PROPOSED FAUCET INDICATED ON SHEET4,PLUMBING
 FIXTURE SCHEDULE THAT MEETS ADA REQUIREMENTS.
  
 3. SHEET 2, FLOOR PLAN, STAFF LOUNGE: INDICATES A DW
 BELOW (N.I.C.). IS DW A DISHWASHER? WHAT IS (N.I.C.)?
 NOTE: THESE ITEMS ARE NOT INDICATED IN THE LEGEND.
 PLEASE CLARIFY PER *106.1.1, INFORMATION ON
 CONSTRUCTION DOCUMENTS.
  
 4. SHEET 4, WATER RISER DIAGRAM: IF COMMENT #3 IS
 CLARIFIED AND DW IS A DISHWASHER PLEASE PROVIDE A WATER
 HAMMER ARRESTOR ON THE HOT WATER TO THE DISHWASHER. PER
 *604.9, WATER HAMMER.
  
 5. SHEET 4, WASTE RISER DIAGRAM: STAFF LOUNGE SINK
 DOES NOT REFLECT THE FLOOR PLAN. SINK IS A DOUBLE BOWL
 W/ DISPOSAL AND A POSSIBLE DISHWASHER. PER *106.1.1,
 INFORMATION ON CONSTRUCTION DOCUMENTS AND *701.1,
 SCOPE.
  
 NOTE: IF THERE IS A DISHWASHER IT SHALL DRAIN PER THE
 FOLLOWING *802.2 DISHWASHING MACHINES SHALL DISCHARGE
 INTO A WYE-BRANCH FITTING ON THE TAILPIECE OF THE
 KITCHEN SINK OR THE DISHWASHER CONNECTION OF A FOOD
 WASTE GRINDER AND BE INDICATED ON THE WASTE RISER
 DIAGRAM.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]
  
  
  
  

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-14 Cont ID  
Sent By choops Date 2007-12-14 Time 08:43 Rev Time 0.00
Received By choops Date 2007-12-14 Time 08:43 Sent To  
Notes
2007-12-14 08:43:47*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.