Plan Review Details - Permit 07120293
Plan Review Stops For Permit 07120293
Review Stop G GAS REVIEW
Rev No 3 Status F Date 2008-03-03 Cont ID  
Sent By mperson Date 2008-03-03 Time 11:35 Rev Time 0.00
Received By mperson Date 2008-03-03 Time 11:35 Sent To PC
Notes
2008-03-03 12:00:09PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 REVISION DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. THE GAS PIPING IS SIZED WRONG PER FBC FUEL GAS
 TABLE 402.4(2). SEE RED LINE CORRECTIONS TO GAS
 ISOMETRIC RISER DIAGRAM BECAUSE OF RELOCATED MP
 REGULATOR. PLEASE REFERENCE TABLE 402.4(2) ATTACHED TO
 THESE COMMENTS INDICATING THIS.
  
 2. PER FBC FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF THE RELOCATED MP REGULATOR.
  
 3. APPROVED MASTER PERMIT #07120290 IS INDICATING WORK
 FOR A GENERATOR, HOWEVER THE SUBMITTED REVISION IS
 INDICATING THE GENERATOR AS "FUTURE". PLEASE CLARIFY
 THIS PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 4. APPROVED MASTER PERMIT #07120290 IS INDICATING THE
 GENERATOR AS A 45 KW GENERATOR WITH 560,000 BTU'S,
 HOWEVER THE SUBMITTED REVISION IS INDICATING THE
 GENERATOR AS A 35 KW, WITH 480,000 BTU'S. PLEASE
 CLARIFY THIS PER FBC FUEL GAS SECTION 401.1 SCOPE.
  
 5. THE APPROVED GAS PLANS ARE INDICATING THE TOTAL
 BTU'SAS 1,682,000, HOWEVER THE SUBMITTED REVISION IS
 INDICATING THE TOTAL BTU'S AS 1,602,000. PLEASE
 REFERENCE A COPY OF THE APPROVED GAS PLANS ATTACHED TO
 THESE COMMENTS INDICATING THIS. PLEASE CLARIFY PER FBC
 FUEL GAS SECTION 401.1 SCOPE.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 NOTE: THERE IS ONLY ONE CORRECTED DRAWING
 IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS
 EXAMINER FOR REFERENCE FOR THE
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 15:43 Rev Time 0.00
Received By mperson Date 2008-02-05 Time 15:43 Sent To  
Notes
2008-02-05 15:44:36NOTE: GAS PERMIT ATTACHED TO GEN/RES PERMIT #07120290.

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-31 Cont ID  
Sent By mperson Date 2007-12-31 Time 08:56 Rev Time 0.00
Received By mperson Date 2007-12-31 Time 08:56 Sent To  
Notes
2007-12-31 08:57:05NOTE: REFERENCE GEN/RES PERMIT #07120290 FOR GAS
 COMMENTS.

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-29 Cont ID  
Sent By adarroug Date 2008-02-29 Time 11:09 Rev Time 0.00
Received By adarroug Date 2008-02-29 Time 11:09 Sent To G
Notes
2008-02-29 11:10:17TO "G" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-31 Cont ID  
Sent By mperson Date 2007-12-31 Time 08:57 Rev Time 0.00
Received By mperson Date 2007-12-13 Time 11:20 Sent To  
Notes
2007-12-13 11:21:04TO "Z" BOX W/GEN-RES APPL