| 2008-03-03 12:00:09 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | REVISION DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. |
| | |
| | 1. THE GAS PIPING IS SIZED WRONG PER FBC FUEL GAS |
| | TABLE 402.4(2). SEE RED LINE CORRECTIONS TO GAS |
| | ISOMETRIC RISER DIAGRAM BECAUSE OF RELOCATED MP |
| | REGULATOR. PLEASE REFERENCE TABLE 402.4(2) ATTACHED TO |
| | THESE COMMENTS INDICATING THIS. |
| | |
| | 2. PER FBC FUEL GAS, SECTION 409.4 MP REGULATOR |
| | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED |
| | IMMEDIATELY AHEAD OF THE RELOCATED MP REGULATOR. |
| | |
| | 3. APPROVED MASTER PERMIT #07120290 IS INDICATING WORK |
| | FOR A GENERATOR, HOWEVER THE SUBMITTED REVISION IS |
| | INDICATING THE GENERATOR AS "FUTURE". PLEASE CLARIFY |
| | THIS PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 4. APPROVED MASTER PERMIT #07120290 IS INDICATING THE |
| | GENERATOR AS A 45 KW GENERATOR WITH 560,000 BTU'S, |
| | HOWEVER THE SUBMITTED REVISION IS INDICATING THE |
| | GENERATOR AS A 35 KW, WITH 480,000 BTU'S. PLEASE |
| | CLARIFY THIS PER FBC FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | 5. THE APPROVED GAS PLANS ARE INDICATING THE TOTAL |
| | BTU'SAS 1,682,000, HOWEVER THE SUBMITTED REVISION IS |
| | INDICATING THE TOTAL BTU'S AS 1,602,000. PLEASE |
| | REFERENCE A COPY OF THE APPROVED GAS PLANS ATTACHED TO |
| | THESE COMMENTS INDICATING THIS. PLEASE CLARIFY PER FBC |
| | FUEL GAS SECTION 401.1 SCOPE. |
| | |
| | ********IMPORTANT INFORMATION******** |
| | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION |
| | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT |
| | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, |
| | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. |
| | THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | NOTE: THERE IS ONLY ONE CORRECTED DRAWING |
| | IN RED INK ON THE INDICATED PLAN SHEETS BY THIS PLANS |
| | EXAMINER FOR REFERENCE FOR THE |
| | RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |