Plan Review Details - Permit 07120290
Plan Review Stops For Permit 07120290
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By shill Date 2008-02-07 Time 13:51 Rev Time 0.00
Received By shill Date 2008-02-07 Time 13:51 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-03 Cont ID  
Sent By shill Date 2008-01-03 Time 10:46 Rev Time 0.00
Received By shill Date 2008-01-03 Time 10:46 Sent To  
Notes
2008-01-03 10:51:57****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVIDE A DETAIL FOR THE SLAB AND ANCHORING,
 FBC1609.1.3.PREFAB SLABS REQUIRE ENGINEERING.
  
 2.THIS PARCEL IS IN A FLOOD ZONE.WPB ADMIN CODE
 94-546(B) REQUIRES THAT THE TOP OF SLAB BE 6" ABOVE
 BFE.A FORM BOARD ELEVATION CERTIFICATE WILL BE
 REQUIRED. (INFORMATIONAL)
  
 3.THE SURVEY SHOWS THE FORM BOARD ELEVATION FOR THE
 HOUSE AT 7'.IS THIS CORRECT?THE HOUSE PERMIT
 REQUIRED 7'6".

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-02-08 Cont ID  
Sent By btrobaug Date 2008-02-05 Time 14:13 Rev Time 0.00
Received By btrobaug Date 2008-02-05 Time 13:46 Sent To P
Notes
2008-02-05 14:12:43 

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-28 Cont ID  
Sent By btrobaug Date 2007-12-28 Time 10:36 Rev Time 0.00
Received By btrobaug Date 2007-12-28 Time 10:22 Sent To G
Notes
2007-12-28 10:36:25 
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
  
 CITY OF WEST PALM BEACH RESIDENTIAL GENERATOR PLAN
 REVIEW
  
  
 ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO
 EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS,
 SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF
 ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER
 108.3 WPB AMENDMENTS.
  
 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED
 LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM
 PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED.CONTACT THE WPB ZONING DEPARTMENT
 FOR DETAILS REGARDING SETBACKS.
  
 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE
 THE FOLLOWING:
  
 A) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE
 EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE
 STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE
 RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF
 LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO
 110.9 FOR AIC RATING.
  
 B) MANUFACTURER SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 C) LOADS MUST NOT EXCEED GENERATOR OUTPUT. ONLY SUBMIT
 PANEL SCHEDULE AND CALCULATIONS FOR THE LOADS FED FROM
 THE GENERATOR.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
  
  
  
  

Review Stop G GAS REVIEW
Rev No 2 Status P Date 2008-02-05 Cont ID  
Sent By mperson Date 2008-02-05 Time 15:28 Rev Time 0.00
Received By mperson Date 2008-02-05 Time 15:28 Sent To M
Notes
***NONE***

Review Stop G GAS REVIEW
Rev No 1 Status F Date 2007-12-31 Cont ID  
Sent By mperson Date 2007-12-31 Time 08:30 Rev Time 0.00
Received By mperson Date 2007-12-31 Time 08:30 Sent To B
Notes
2007-12-31 08:47:13PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 GAS PLAN REVIEW:
 DENIED:
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 GAS PLAN REVIEW TO MEET CODE COMPLIANCE.
  
 1. TWO COPIES OF SURVEY AND SITE PLAN INDICATING THE
 PROPOSED LOCATION OF THE GENERATOR. GIVE DIMENSIONS
 FROM PROPRTY LINES AND ALL STRUCTURES. INDICATE ANY
 EASEMENTS INVOLVED. CONTACT THE WPB ZONING DEPARTMENT
 FOR DETAILS REGARDING DETBACKS.
  
 2. TWO COPIES OF MANUFACTURER'S INSTALLATION
 INSTRUCTIONS WITH SETBACK RECOMMENDATIONS FROM
 STRUCTURES.
  
 3. THE WATER HEATER SUBMITTAL DOES NOT HAVE A LISTING
 FROM A NATIONALLY RECOGNIZED TESTING LABORATORY
 (EXAMPLE= CSA, AGA). PLEASE PROVIDE THIS INFORMATION ON
 THE RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-29 Cont ID  
Sent By adarroug Date 2008-01-29 Time 16:07 Rev Time 0.00
Received By adarroug Date 2008-01-29 Time 16:07 Sent To Z
Notes
2008-01-29 16:07:25TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-08 Cont ID  
Sent By adarroug Date 2008-01-03 Time 16:05 Rev Time 0.00
Received By adarroug Date 2007-12-13 Time 11:13 Sent To  
Notes
2007-12-13 11:20:38TO "Z" BOX

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By tgordon Date 2008-02-06 Time 09:45 Rev Time 0.20
Received By tgordon Date 2008-02-06 Time 09:45 Sent To B
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By tgordon Date 2007-12-21 Time 10:59 Rev Time 0.25
Received By tgordon Date 2007-12-21 Time 10:59 Sent To E
Notes
2007-12-21 11:04:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SHOW OR STATE ON SITE PLAN DISTANCES TO BUILDING AND
 BUILDING OPENINGS (WINDOWS, DOORS, AND EAVE VENTS).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-31 Cont ID  
Sent By choops Date 2008-01-31 Time 08:55 Rev Time 0.00
Received By choops Date 2008-01-31 Time 08:55 Sent To E
Notes
2008-01-31 08:55:45***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - BT

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By choops Date 2007-12-18 Time 09:58 Rev Time 0.00
Received By choops Date 2007-12-18 Time 09:58 Sent To E
Notes
2007-12-18 09:59:30***FAILED***
  
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED
 GENERATOR EQUIPMENT TO THE PROPERTY LINES.AS PER
 SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT
 MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
 MUST MAINTAIN A MINIMUM SETBACK OF 11' TO REAR PROPERTY
 LINE, AND A MINIMUM OF 1' TO THE NORTH SIDE PROPERTY
 LINE.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
 SENT TO "E" - GEN. BOX