| Plan Review Stops For Permit 07120290 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
P |
Date |
2008-02-07 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-07 |
Time |
13:51 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-07 |
Time |
13:51 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-03 |
Time |
10:46 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-03 |
Time |
10:46 |
Sent To |
|
|
| Notes |
| 2008-01-03 10:51:57 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.PROVIDE A DETAIL FOR THE SLAB AND ANCHORING, | | | FBC1609.1.3.PREFAB SLABS REQUIRE ENGINEERING. | | | | | | 2.THIS PARCEL IS IN A FLOOD ZONE.WPB ADMIN CODE | | | 94-546(B) REQUIRES THAT THE TOP OF SLAB BE 6" ABOVE | | | BFE.A FORM BOARD ELEVATION CERTIFICATE WILL BE | | | REQUIRED. (INFORMATIONAL) | | | | | | 3.THE SURVEY SHOWS THE FORM BOARD ELEVATION FOR THE | | | HOUSE AT 7'.IS THIS CORRECT?THE HOUSE PERMIT | | | REQUIRED 7'6". |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-02-05 |
Time |
14:13 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-02-05 |
Time |
13:46 |
Sent To |
P |
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-28 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-28 |
Time |
10:36 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-28 |
Time |
10:22 |
Sent To |
G |
|
| Notes |
| 2007-12-28 10:36:25 | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | | | | CITY OF WEST PALM BEACH RESIDENTIAL GENERATOR PLAN | | | REVIEW | | | | | | | | | ALL PERMIT APPLICATIONS MUST BE SUBMITTED TOGETHER TO | | | EXPEDITE THE REVIEW PROCESS.TWO COPIES OF ALL PLANS, | | | SURVEYS AND SPECIFICATIONS ARE REQUIRED. THE COST OF | | | ALL EQUIPMENT AND LABOR MUST BE ENTERED AS VALUE PER | | | 108.3 WPB AMENDMENTS. | | | | | | 1} SURVEY AND SITE PLANS INDICATING THE PROPOSED | | | LOCATION OF THE GENERATOR. GIVE DIMENSIONS FROM | | | PROPERTY LINES AND ALL STRUCTURES. INDICATE ANY | | | EASEMENTS INVOLVED.CONTACT THE WPB ZONING DEPARTMENT | | | FOR DETAILS REGARDING SETBACKS. | | | | | | 2} AN APPLICATION FOR AN ELECTRICAL PERMIT MUST INCLUDE | | | THE FOLLOWING: | | | | | | A) SITE PLAN INDICATING THE PHYSICAL LOCATION OF THE | | | EQUIPMENT WITH REGARD TO THE SERVICE AND SEPARATE | | | STRUCTURES. NOTE: DISCONNECT REQUIRED TO BE SERVICE | | | RATED PER 225.36. THIS INCLUDES THE TRANSFER SWITCH IF | | | LOCATED AS A MAIN SERVICE DISCONNECTING MEANS. ALSO | | | 110.9 FOR AIC RATING. | | | | | | B) MANUFACTURER SETBACK RECOMMENDATIONS FROM | | | STRUCTURES. | | | | | | C) LOADS MUST NOT EXCEED GENERATOR OUTPUT. ONLY SUBMIT | | | PANEL SCHEDULE AND CALCULATIONS FOR THE LOADS FED FROM | | | THE GENERATOR. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 | | | | | | | | | | | | |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
2 |
Status |
P |
Date |
2008-02-05 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-05 |
Time |
15:28 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-05 |
Time |
15:28 |
Sent To |
M |
|
| Notes |
|
|
| Review Stop |
G |
GAS REVIEW |
| Rev No |
1 |
Status |
F |
Date |
2007-12-31 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2007-12-31 |
Time |
08:30 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2007-12-31 |
Time |
08:30 |
Sent To |
B |
|
| Notes |
| 2007-12-31 08:47:13 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | GAS PLAN REVIEW: | | | DENIED: | | | | | | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR | | | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. | | | | | | 1. TWO COPIES OF SURVEY AND SITE PLAN INDICATING THE | | | PROPOSED LOCATION OF THE GENERATOR. GIVE DIMENSIONS | | | FROM PROPRTY LINES AND ALL STRUCTURES. INDICATE ANY | | | EASEMENTS INVOLVED. CONTACT THE WPB ZONING DEPARTMENT | | | FOR DETAILS REGARDING DETBACKS. | | | | | | 2. TWO COPIES OF MANUFACTURER'S INSTALLATION | | | INSTRUCTIONS WITH SETBACK RECOMMENDATIONS FROM | | | STRUCTURES. | | | | | | 3. THE WATER HEATER SUBMITTAL DOES NOT HAVE A LISTING | | | FROM A NATIONALLY RECOGNIZED TESTING LABORATORY | | | (EXAMPLE= CSA, AGA). PLEASE PROVIDE THIS INFORMATION ON | | | THE RESUBMITTAL. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-29 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-29 |
Time |
16:07 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-01-29 |
Time |
16:07 |
Sent To |
Z |
|
| Notes |
| 2008-01-29 16:07:25 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-01-03 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-13 |
Time |
11:13 |
Sent To |
|
|
| Notes |
| 2007-12-13 11:20:38 | TO "Z" BOX |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
P |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-06 |
Time |
09:45 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2008-02-06 |
Time |
09:45 |
Sent To |
B |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-21 |
Time |
10:59 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2007-12-21 |
Time |
10:59 |
Sent To |
E |
|
| Notes |
| 2007-12-21 11:04:06 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SHOW OR STATE ON SITE PLAN DISTANCES TO BUILDING AND | | | BUILDING OPENINGS (WINDOWS, DOORS, AND EAVE VENTS). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-31 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-31 |
Time |
08:55 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-31 |
Time |
08:55 |
Sent To |
E |
|
| Notes |
| 2008-01-31 08:55:45 | ***APPROVED - RESUB #1*** | | | | | | | | | | | | | | | SENT TO "E" - BT |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-18 |
Time |
09:58 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-18 |
Time |
09:58 |
Sent To |
E |
|
| Notes |
| 2007-12-18 09:59:30 | ***FAILED*** | | | | | | | | | 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED | | | GENERATOR EQUIPMENT TO THE PROPERTY LINES.AS PER | | | SECTION 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT | | | MAY NOT PROJECT MORE THAN 4' INTO A REQUIRED SETBACK. | | | MUST MAINTAIN A MINIMUM SETBACK OF 11' TO REAR PROPERTY | | | LINE, AND A MINIMUM OF 1' TO THE NORTH SIDE PROPERTY | | | LINE. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | SENT TO "E" - GEN. BOX |
|
|