Plan Review Details - Permit 07120259
Plan Review Stops For Permit 07120259
Review Stop G GAS REVIEW
Rev No 1 Status P Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 13:06 Rev Time 0.00
Received By mperson Date 2007-12-17 Time 13:06 Sent To PC
Notes
2007-12-17 14:38:24IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 2,500 CUBIC FEET REQUIRED.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2007-12-17 Cont ID  
Sent By mperson Date 2007-12-17 Time 13:52 Rev Time 0.00
Received By mperson Date 2007-12-12 Time 16:19 Sent To  
Notes
2007-12-12 16:19:40TO "G" BOX