Plan Review Details - Permit 07120233
Plan Review Stops For Permit 07120233
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-07 Cont ID  
Sent By rmcdouga Date 2008-02-07 Time 16:57 Rev Time 0.00
Received By rmcdouga Date 2008-02-07 Time 16:57 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By rmcdouga Date 2008-01-04 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2008-01-04 Time 13:34 Sent To  
Notes
2008-01-04 13:34:172004 FBC W/2007 REVISIONS
 RESIDENTIAL REMODEL
  
 DENIED BY BUILDING
  
 1)A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2)SUBMIT TWO SETS OF PLANS THAT CLEARLY INDICATE THE
 SCOPE OF WORK. FBC 106.1.1* CITY AMENDMENTS INFORMATION
 ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 3) THE NAME AND ADDRESS OF THE PROJECT IS REQUIRED ON
 EACH PAGE OF THE PLANS. THE PRINTED NAME AND SIGNATURE
 OF THE PERSON RESPONSIBLE FOR THE PLANS IS ALSO
 REQUIRED. FBC 106.1.3* CITY AMENDMENTS.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 08:33 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 08:31 Sent To M
Notes
2008-01-28 08:44:18CHANGE OUT EXISTING MCB EXISTING SERVICE.
 INSTALL NEW SA'S
 INSTALL NEW TANKLESS WATER HEATER

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 14:01 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 14:01 Sent To Z
Notes
2007-12-23 14:02:01** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE: PLEASE SUBMIT COMPLETE PLANS FOR ALL MINIMUM
 CODE COMPLIANCE.
 PLEASE SUBMIT PANEL SCHEDULE SHOWING ALL CONDUCTORS,
 BRANCH CIRCUITS AND BREAKERS.
 PLEASE SUBMIT RISER DIAGRAM SHOWING ALL CONDUCTORS,
 OVER CURRENT PROTECTION, MAINS, GROUNDING ETC
 PLEASE SEENEC/ NFPA-70 408.4, 240.4, 310.16 ETC.
 PLEASE SHOW ALL MINIMUM CIRCUITS AS REQUIRED PER
 210.52, 210.11, 220.
 PLEASE SUBMIT LOAD CALCULATIONS FOR NEW AND
 EXISTING.220.87
 PLEASE SHOW ALL AFCI PROTECTED CIRCUITS PER 210.12.
 PLEASE SEE FBC R313 FOR REQUIRED SMOKE ALARMS DEVICES
 PLEASE COMPLETE THE SW LEGS FOR COMPLETION OF EGRESS
 LIGHTING CONTROLS PER 210.70,LS 101 7.8.
 PLEASE SUBMIT MANUFACTURES SPECS/CUT SHEETS FOR NEW
 TANK-LESS WATER HEATER UNIT.90.7, 110.3
 PLEASE SUBMIT COMPLETED PLANS. PLEASE KNOW PLANS ARE
 BEING ROUTED TO ZONING TO CONFIRM USE AS SHOWN.
  
  
  
 *** AS SOME ITEMS WERE NOT SUBMITTED COMPLETE FOR
 REVIEW, THERE MAY BE NEW COMMENTS ON THE FOLLOWING
 REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-18 Cont ID  
Sent By adarroug Date 2008-01-18 Time 12:25 Rev Time 0.00
Received By adarroug Date 2008-01-18 Time 12:25 Sent To Z
Notes
2008-01-18 12:25:38TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By rmcdouga Date 2008-01-04 Time 13:34 Rev Time 0.00
Received By rmcdouga Date 2007-12-13 Time 09:22 Sent To  
Notes
2007-12-13 09:22:53TO "SFR" "E"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By tgordon Date 2008-01-28 Time 09:25 Rev Time 0.30
Received By tgordon Date 2008-01-28 Time 09:25 Sent To P
Notes
2008-01-28 09:31:17*** PROVISO ***
 1) MECHANICAL INSPECTOR TO VERIFY MODEL NUMBER AND
 SEER, PER 2004 FBC 13-607.1.ABC.3.1.1.
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By tgordon Date 2007-12-21 Time 11:42 Rev Time 0.25
Received By tgordon Date 2007-12-21 Time 11:42 Sent To E
Notes
2007-12-21 11:48:06PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) NEED THE JOB ADDRESS ON ALL PAGES OF THE PLANS, PER
 2004 WPB AMEND. 106.1.3.
  
 2) NEED THE INFORMATION FOR THE A/C SYSTEM BEING
 INSTALLED (MODEL NUMBERS, BTU'S, SEER, ETC., PER 2004
 WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By jleech Date 2008-02-06 Time 13:32 Rev Time 0.00
Received By jleech Date 2008-02-06 Time 13:32 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By jleech Date 2007-12-24 Time 09:31 Rev Time 0.00
Received By jleech Date 2007-12-24 Time 09:31 Sent To B
Notes
2007-12-24 09:36:39NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW. PLEASE
 SHOW FIXTURE LOCATION AND A DISCRIPTIN OF WORK TO BE
 DONE. WAS THERE AN EXISTING W/H IF SO WHERE WAS IT
 LOCATED. SUBMIT AMANUFATURE CUT SHEET FOR THE
 HEATER.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2008-02-13 Cont ID  
Sent By choops Date 2008-02-13 Time 11:40 Rev Time 0.00
Received By choops Date 2008-02-13 Time 11:40 Sent To PC
Notes
2008-02-13 11:40:43***APPROVED - RESUB #1 (CONTRACTOR (AMY) BROUGHT IN
 REQUESTED INFORMATION

Review Stop Z ZONING
Rev No 2 Status F Date 2008-01-24 Cont ID  
Sent By choops Date 2008-01-24 Time 10:20 Rev Time 0.00
Received By choops Date 2008-01-24 Time 10:20 Sent To E
Notes
2008-01-24 10:22:13***FAILED - RESUB #1***
  
  
 REPEAT COMMENT:
  
 1)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO ALL PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By choops Date 2007-12-24 Time 08:09 Rev Time 0.00
Received By choops Date 2007-12-24 Time 08:09 Sent To P
Notes
2007-12-24 08:15:56***FAILED***
  
  
 1)PROVIDE TWO (2) COPIES OF A CURRENT SURVEY.
  
 2)INDICATE SETBACK DIMENSIONS FROM PROPOSED A/C
 EQUIPMENT TO THE PROPERTY LINES.AS PER SECTION
 94-305(B)(4) OF THE ZLDRS: MECHANICAL EQUIPMENT MAY NOT
 PROJECT MORE THAN 4' INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720