Plan Review Details - Permit 07120230
Plan Review Stops For Permit 07120230
Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-04-09 Cont ID  
Sent By jwitmer Date 2008-04-09 Time 11:42 Rev Time 0.50
Received By jwitmer Date 2008-04-09 Time 11:42 Sent To  
Notes
2008-04-09 11:43:42NOTE: RECORDED REVISED EASEMENT FOR WATER FEATURE AT
 ECOPLEX

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By jwitmer Date 2008-01-24 Time 13:15 Rev Time 0.55
Received By jwitmer Date 2008-01-24 Time 13:15 Sent To PC
Notes
2008-01-24 13:18:06BUILDING PLAN REVIEW
 PERMIT: 07120230
 ADD: 1641 WORTHINGTON RD
 CONT: URDL'S WATERFALL CREATION
 TEL: (561)441-0401
  
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 BUILDING PROVISOS:
  
 1)PLEASE PROVIDE DOCUMENTS FOR CROSS EASEMENTS OR UNITY
 OF TITLE BETWEEN PARCELS AFFECTED BY THIS PERMIT.
 106.1.2 ADITIONAL INFORMATION REQUIRED.
  
 2) THE PROPERTY LISTED ON THE PERMIT APPLICATION FALLS
 WITH A "A9" FLOOD ZONE WITH MINIMUM HEIGTH REQUIREMENTS
 FOR ELECTRICAL. THE MINIMUM HEIGTH FOR THE ELECTRICAL
 BASE PAD IS 13'-6", PLEASE INDICATE THE HEIGTH ON SHEET
 F1, THE HYDROLIC PROFILE DETAIL. FBC BUILDING 3110.1.2
 / CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED BEFORE A
 CERTIFICATE OF COMPLETION WILL BE ISSUED.
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
  
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By jwitmer Date 2008-01-04 Time 11:19 Rev Time 2.22
Received By jwitmer Date 2008-01-04 Time 11:19 Sent To PC
Notes
2008-01-04 11:32:13BUILDING PLAN REVIEW
 PERMIT:07120230
 ADD: 1641 WORTHINGTON RD
 CONT: URDL'S WATERFALL CREATIONS
 TEL: (561)441-0401
 FL BLD CODE= 2004 FLORIDA BUILDING CODE W/ 2007 FBC
 REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR
 ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE2007 SUPPLEMENTS.
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) PLEASE PROVIDE DOCUMENTS FOR CROSS EASEMENTS OR
 UNITY OF TITLE BETWEEN PARCELS AFFECTED BY THIS PERMIT.
 106.1.2 ADITIONAL INFORMATION REQUIRED.
  
 4) THE PROPERTY LISTED ON THE PERMIT APPLICATION FALLS
 WITH A "A9" FLOOD ZONE WITH MINIMUM HEIGTH REQUIREMENTS
 FOR ELECTRICAL. THE MINIMUM HEIGTH FOR THE ELECTRICAL
 BASE PAD IS 13'-6", PLEASE INDICATE THE HEIGTH ON SHEET
 F1, THE HYDROLIC PROFILE DETAIL. FBC BUILDING 3110.1.2
 / CITY OF WPB CODE OF ORDINANCES SECTION 94-546.
 STRUCTURE IS LOCATED IN AN "A" FLOOD ZONE. A FLOOD
 ELEVATION CERTIFICATE WILL BE REQUIRED BEFORE A
 CERTIFICATE OF COMPLETION WILL BE ISSUED.
  
  
  
  
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 2 Status N Date 2008-01-17 Cont ID  
Sent By dpalmer Date 2008-01-17 Time 14:20 Rev Time 0.00
Received By dpalmer Date 2008-01-17 Time 14:20 Sent To  
Notes
2008-01-17 14:29:11** PROVISO**
  
 ** NO REVIEW DONE OF ANY PROPOSED ELECTRICAL**
  
 1) NOTE: NO ELECTRICAL ON PLANS AND NO ELECTRICAL
 APPLIED FOR.
 ALL BONDING FOR STRUCTURALAND SHALL BE IN ACCORDANCE
 TO NEC 680.26. PLANS FOR GROUNDING AND BONDING DETAILS
 STILL REQUIRED ALONG WITH SEPARATE PERMIT APPLICATION.
 AS STRUCTURE IS NOT ON LEGAL PROPERTY OF BASE
 PLANS/BUILDING PERMITS THE LEGAL EASEMENTS AND OTHER
 DOCUMENTS ARE TO BE FORTHCOMING.
 NO CO UNTIL DOCUMENTS ARE PROVIDED.
  
 2) NOTE: PLEASE SUBMIT DETAIL FOR BONDING FOR FOUNTAIN
 AND ANY ELECTRICAL DETAILS FOR WORK IN OR ON EASEMENT
 AREA/PROPERTY.
  
 3) NOTE: PLANS NOTE BONDING IS ON PERMITTED PLANS,
 HOWEVER THIS IS NOT THE CASE. PLEASE ALSO KNOW AS THIS
 STRUCTURE IS ON A SEPARATE PROPERTY AS NOTED ABOVE IN
 NOTE #1, SEPARATE PERMIT FOR ELECTRICAL IS REQUIRED.
  
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PAM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By dpalmer Date 2007-12-21 Time 12:49 Rev Time 0.00
Received By dpalmer Date 2007-12-21 Time 12:49 Sent To  
Notes
2007-12-21 12:49:14** DENIED **
  
 1) NOTE: PLEASE VERIFY AND SHOW BONDING OF ANY
 STRUCTURAL STEEL WHICH IS PART OF FOUNTAIN PER NEC
 680.26.
 THE ELECTRICAL PUMP WAS PART OF THE BASE BUILDING
 DESIGN HOWEVER SHOULD BE NOTED ON PLANS. THESE PLANS
 SHOW A NEW PUMP BUT DO NOT INDICATE IF THIS IS THE SAME
 FROM BASE BUILDING SITE AND ELECTRICAL PLANS.
  
 2) NOTE: PLEASE KNOW AT THIS TIME LIGHTING AND ANY
 ELECTRICAL NOT PART OF THIS PROPERTY NEEDS TOVERIFY
 EASEMENT ETC PREVIOUSLY MENTIONED AND NOTED TO OWNER
 AND BASE BUILDING CONTRACTOR BY MR. ROBERT BROWN.
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 09:30 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 09:30 Sent To  
Notes
2008-03-25 17:43:17SENT TO PLANNING IN-BOX.(SUBMITTAL REMOVED FROM "P"
 BOX AND ROUTED TO PLANNER INSTEAD).
2008-03-25 09:30:40TO "P" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-16 Cont ID  
Sent By adarroug Date 2008-01-16 Time 12:34 Rev Time 0.00
Received By adarroug Date 2008-01-16 Time 12:34 Sent To  
Notes
2008-01-16 12:35:06TO "COMM" BD#25

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By jwitmer Date 2008-01-04 Time 11:19 Rev Time 0.00
Received By jwitmer Date 2007-12-13 Time 08:49 Sent To  
Notes
2007-12-13 08:49:34TO "COMM" BD#5

Review Stop P PLUMBING
Rev No 1 Status P Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 16:53 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 16:53 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-28 Cont ID  
Sent By jroach Date 2008-03-28 Time 10:23 Rev Time 0.00
Received By jroach Date 2008-03-28 Time 10:23 Sent To B
Notes
2008-03-28 10:24:50AS REQUIRED PRIOR TO FINAL INSPECTION, EASEMENT HAS
 BEEN RECORDED AND RECEIVED.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-22 Cont ID  
Sent By jroach Date 2008-01-22 Time 17:42 Rev Time 0.00
Received By jroach Date 2008-01-22 Time 17:42 Sent To  
Notes
2008-01-22 17:43:45***PROVISO***
  
 1) PER ATTACHED EMAIL, EASEMENT SHALL BE RECORDED PRIOR
 TO THE ISSUANCE OF A CO/FINAL INSPECTION.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-27 Cont ID  
Sent By jroach Date 2007-12-27 Time 15:13 Rev Time 0.00
Received By jroach Date 2007-12-27 Time 15:13 Sent To  
Notes
2007-12-27 15:15:06***FAILED***
  
 1) SEE NOTE FROM ELECTRICAL PLAN REVIEWER DEWEY PALMER
 REGARDING REQUIRED EASEMENT.OTHERWISE, THERE ARE NO
 ZONING OBJECTIONS TO THIS PERMIT.
  
 QUESTIONS/COMMENTS, CONTACT JOHN ROACH, SENIOR PLANNER,
 AT (561) 822-1435.