Plan Review Details - Permit 07120223
Plan Review Stops For Permit 07120223
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status P Date 2008-02-08 Cont ID  
Sent By amorse Date 2008-02-08 Time 17:38 Rev Time 0.00
Received By amorse Date 2008-02-08 Time 17:38 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-31 Cont ID  
Sent By amorse Date 2007-12-31 Time 09:42 Rev Time 0.00
Received By amorse Date 2007-12-31 Time 09:42 Sent To PC
Notes
2007-12-31 09:49:56 
 DENIED
  
  
 1)PLANS AND SPECIFICATIONS DESIGN PARAMETERS SHALL
 COMPLY WITH THE 2004 FLORIDA BLDG CODE WITH 2006
 AMENDMENTS PER 106.1.1 FBC*
  
 2)THE CLAIMED VALUATION ON THE PERMIT APPLICATION IS
 LOW. FOR PERMITTING PURPOSES, VALUATION OF BUILDINGS
 AND SYSTEMS SHALL BE THE TOTAL REPLACEMENT COST
 EXCLUDING LAND VALUE. OUR VALUATION REFERENCE IS ICC
 (BVD), MARSHALL-SWIFT AND MEANS COST ANALYSIS SERVICES
 PER 108.3 FBC*
  
 3)THE STATE OF FLORIDA REQUIRES COLLECTION OF A RADON
 SURCHARGE ON ALL NEW CONSTRUCTION COMPUTED ON UNDER
 ROOF FLOOR SPACE PER 10D-91 FAC. THESE FEES WILL BE
 ADDED TO THE PERMIT APPLICATION FEES
  
 NOTE: FEES ARE DUE IN THE AMOUNT OF $3,782.59 FOR
 REMAINING FEES, INCREASED VALUE AND STATE RADON FEES
 THIS AMOUNT IS REQUIRED TO BE PAID PRIOR TO FURTHER
 PLAN REVIEW
  
 4)SURVEY AND SITE PLAN SIDE AND REAR SETBACK
 MEASUREMENTS DO NOT MATCH EACH OTHER
  
 5)PROVIDE CORRECT PROJECT ADDRESS ON THE DRAWINGS
 (USE OF LABEL IS ACCEPTABLE), ALSO CLARIFY BUILDER AND
 OWNER INFORMATION ON ENERGY CALC'S THEY STATE KOLTER
 HOMES AS THE BUILDER
  
 6)THE CITY OF WEST PALM BEACH REQUIRES THE FLORIDA
 STATE PRODUCT APPROVAL COVER SHEETS WHEN AVAILABLE.
 THEY CAN BE SEARCHED FOR ON WWW.FLORIDABUILDING.ORG.
 WHEN AVAILABLE AND NOT SUBMITTED APPLICATIONS WILL BE
 DENIED
  
 7) SUBMIT 2 COPIES OF ENGINEERED TRUSS DRAWINGS THAT
 COMPLY WITH R802.10.1 FBC WITH PERMIT APPLICATION OR
 BEFORE INSTALLATION THAT HAVE BEEN REVIEWED AND
 APPROVED BY THE DESIGNER OF RECORD ***PLEASE NOTE THAT
 FLORIDA SHEETS WERE NOT SUBMITTED FOR PGT AND WAYNE
 DALTON PRODUCTS AND THE FL#'S ARE WRITTEN AT THE TOP OF
 THESE PRODUCT NOA'S***
  
 8)PRODUCT APPROVALS WERE NOT SUBMITTED FOR MULLIONS
 THAT WILL BE USED ON SEVERAL DOOR AND WINDOW
 INSTALLATIONS, ALSO PRODUCT APPROVAL FOR CASEMENT
 WINDOWS WERE SUBMITTED BUT NONE ARE PRESENT ON THE
 DRAWINGS, PLEASE CLARIFY
  
 9)THE FIXED WINDOW IN THE DINING ROOM AREA IS 51 SQ
 FT. AND EXCEEDS THE MAX ALLOWABLE SIZE OF 30.28 SQ FT.
 IN THE FIXED WINDOW PRODUCT APPROVAL
  
 10)CORRECT SECTION AND COLUMN DESIGNATIONS ON SHEETS
 A/2 AND A/3 THAT REFER TO A SHEET 7 AND THAT ALSO HAVE
 DETAIL AND SHEET NUMBERS REVERSED
  
 11)CLARIFYFOUNDATIONFOR SCREEN WALL, SCHEDULE ON
 A/2 STATES 12" X 24" FOOTING AND DETAIL OFBLOCK PIERS
 ON SHEET A/5 SHOWS 30" X 30" PAD
  
 12)CLARIFY SECTION J-6 ON SHEET A/2 AT GARAGE WALL
 WITH DETAIL ON A/6
  
 13)CLARIFY DETAILS FOR FRAMED WALLS FROM MAIN ROOF AT
 FRONT PORCH TO RAISED ROOF, ARE THESEDETAILS J-6, O-6
 AND N-6 IF SO SHOW THEORIENTATION OF SECTIONS ON THE
 FLOOR OR ROOF PLAN. SHOW THAT BEAM ABOVE IS FRAMED INTO
 ENTIRE PERIMETER WALL AS SHOWN ON ROOF FRAMING PLAN AND
 IS IT BOXED OUT ON THE INSIDE ALL THE WAY AROUND AS
 STATED ON SAME PLAN
  
 14)REMOVE ALL OLD PAGES AND RESUBMIT 2 COMPLETE SETS
 OF NEW DRAWINGS WITH REVISIONS AND INCLUDE 1 COPY OF
 THE OLD PAGES ONLY FOR REFERENCE. PLEASE RE-SUBMIT ANY
 PAGES WITH THE IMPACT FEE STAMP
  
 15)A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT IS REQUIRED PRIOR TO
 A PERMIT BEING ISSUED
  
 NOTE: FBC = FLORIDA BUILDING CODE 2004 W/2006
 AMENDMENTS
 FBC* = WEST PALM BEACH ADMINISTRATIVE
 AMENDMENTS TO FBC
 FAC = FLORIDA ADMINISTRATIVE CODE
 FS = FLORIDA STATUTES
 FBC RES. = FLORIDA BUILDING CODE
 RESIDENTIAL 2004 W/2006 AMENDMENTS
  
 BLDG PLAN REVIEW
 ADRIAN MORSE
 561-805-6716
  
  
  
  
  
  
  
  
  
  
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-11-24 Cont ID  
Sent By dpalmer Date 2008-11-24 Time 14:18 Rev Time 0.00
Received By dpalmer Date 2008-11-24 Time 14:18 Sent To PC
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-11-21 Cont ID  
Sent By dpalmer Date 2008-11-21 Time 09:28 Rev Time 0.00
Received By dpalmer Date 2008-11-21 Time 09:28 Sent To PC
Notes
2008-11-21 09:29:09 
  
  
 ** FAILED REVISION **
  
  
  
 1) NOTE: PLEASE SEE ITEM REDLINED ON ISSUED PLANS FROM
 1/28/08 THE 2005 NEC WAS REVISED TO REQUIRE ALL
 RECEPTACLES IN LAUNDRY ROOMS TO BE GFI/GFI PROTECTED
 WITHIN 6FT OF THE LAUNDRY SINK EVEN IF THESE ARE
 DEDICATED RECEPTACLES.
 THE PLANS WERE REDLINED FOR THE IRONING BOARD
 RECEPTACLE TO MEET 210.8A7
  
 2) NOTE: PLEASE LIST/IDENTIFY THE ARC FAULT BREAKERS ON
 PANEL SCHEDULES.
 210.12,408.4
  
 3) NOTE: PLEASE VERIFY THE CONDUITS FROM METER TO
 MAINS. ARE THESE OVERHEAD AS SHOWN ON RISER OR
 UNDERGROUND?
 IF OVER HEAD THEN OCP IS REQUIRED ON THE OUTSIDE.
 IF IN SLAB PLEASE SHOW.
 230.70
  
 4) NOTE: PLEASE SEE 210.11C2, 220.52
  
 5) NOTE: PLEASE SEE THE INCORRECT NFPA-72 IS STATED ON
 PLANS. SHOWS 2005 AND NEEDS TO 2002. THIS WAS REDLINED
 ON ORIGINAL PLANS.
  
  
 **IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC. SHOULD BE PLACED
 INTO TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 IF THERE ARE ANY QUESTIONS; OR IF COMMENTS ARE NOT
 TYPED IN A CLEAR MANNER PLEASE DO NOT HESITATE TO
 CONTACT THIS REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By dpalmer Date 2008-01-28 Time 09:06 Rev Time 0.00
Received By dpalmer Date 2008-01-28 Time 09:03 Sent To P
Notes
2008-01-28 09:09:30REDLINED PLANS.
  
 PREVIOUS REVIEW 210.8A7, ALL RECEPTACLES EVEN DEDICATED
 15/20AMP 125V WITHIN 6FT OF LAUNDRY SINK SHALL BE GFI.;
 THIS INCLUDES IRONING BOARD RECEPT. MOST WERE OK.
 PLANS CHANGED CODES, HOWEVER NFPA-72 WAS CHANGED TO
 2005 WHEN PREVIOUS REVIEWS REQUESTS 2002 NFPA-72 AS
 ADOPTED BY FS 553.79 AND THE FLORIDA BUILDING
 COMMISSION. THIS WAS REDLINED ON PLANS.

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-23 Cont ID  
Sent By dpalmer Date 2007-12-23 Time 13:16 Rev Time 0.00
Received By dpalmer Date 2007-12-23 Time 13:16 Sent To P
Notes
2007-12-23 13:16:23** DENIEDREVIEW **
  
  
 1) NOTE: PLEASE SEE CODES TO BE STATED ON PLANS ARE
 NEEDED AS FOLLOWS:
 2005 NFPA-70
 2002 NFPA-72
  
 2) NOTE: PLEASE SEE 2005 NEC AS ALL RECEPTACLES IN A
 LAUNDRY ROOM WITHIN 6FT OF LAUNDRY SINK ARE TO BE GFI.
 THIS INCLUDES WASHING MACHINE. BASED ON THE SCALE OF
 ELECTRICAL PLANS, THE SINK EDGE IS AT 6FT OR LESS.
 PLEASE SEE 210.8A7
  
 3) NOTE: PLEASE SEE BEDROOM #3 AS ALL OUTLETS WHICH ARE
 15AMP OR 20AMP SHALL BE AFCI PROTECTED PER 210.12. THIS
 INCLUDES THE GFI AND OTHER DEDICATED RECEPTACLES SHOWN
 IN THIS ROOM.
  
 4) NOTE: PLEASE SEE PANEL SCHEDULE/LOAD CALCULATIONS
 ARE STILL SHOWING 3-#6 CONDUCTORS FOR AH UNITS AND C
 UNITS. THESE ARE TWO POLE UNITS AND IT IS PERMITTED TO
 INSTALLED #6 FOR THE EQUIPMENT GROUNDING CONDUCTORS
 HOWEVER NOT REQUIRED. IF SHOWN ON PLANS, THIS IS WHAT
 WILL BE REQUIRED TO BE INSTALLED.
 NO CHANGE IS NEEDED FOR EQUIPMENT GROUNDING IF #6
 CONDUCTORS WILL BE INSTALLED. THIS IS NOTED FOR
 INFORMATION ONLY.
  
 5) NOTE: PLEASE SEE MISSING LIVING ROOM RECEPTACLE
 ALONG MORE THAN 2FT OF WALL SPACE. (REDLINED ON ONE
 SET) (WALL NEAR KITCHEN DOORWAY ENTERING FROM BRKFST
 RM.
 210.52
  
 6) NOTE: PLEASE SEE NFPA-72 11.8.3. IF THE TRAY CEILING
 IN OFFICE WHICH IS ALSO CONSIDERED AN ADAPTABLE BEDROOM
 IS 12INCHES OR HIGHER, THE SA IS REQUIRED AT THE HIGH
 POINT OF ELEVATION. (ONLY IF TRY IS 12 INCHES OR
 GREATER). BASED ON PLANS AND ELEVATIONS SHOWN THIS IS
 THE CASE. PLEASE ADJUST LOCATION.
  
 7) NOTE: PLEASE CORRELATE ELECTRICAL PLANS AND
 MECHANICAL PLANS FOR NUMBER OF A/C UNITS AND SIZE OF
 HEAT STRIPS.
 PLEASE SEE MECHANICAL PLANS CALL FOR 1-5KW, 1-10KW AND
 1-7.5KW WHEREAS THE ELECTRICAL PANEL SCHEDULE/LOAD
 CALCULATIONS ONLY INDICATE TWO SYSTEMS AND BOTH AT 10KW
 EACH FOR HEAT.
 THIS WILL AFFECT CIRCUITING, LOADS, OVER CURRENT
 PROTECTION ETC.
 408.4, 240.4, 310.16, 220, ETC
 FBC 106.3.5.4
  
 8) NOTE: PLEASE COORDINATE PLANS AND RISER AS PLANS
 SHOW TWO MAIN DISCONNECTS OUTSIDE AND RISER ONLY SHOWS
 TWO PANELS INSIDE.?
 PLEASE COORDINATE.
 FBC 106.1.2, 106.3.5.4
 NEC 230.70, 230.71, 230.72
  
 9) NOTE: PLEASE VERIFY IF THE LOAD ON POOL PANEL ARE
 ALREADY FIGURED AT 125%.
 215.3, 230.42 ETC
  
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop I INCOMING/PROCESSING
Rev No 8 Status N Date 2008-11-24 Cont ID  
Sent By adarroug Date 2008-11-24 Time 11:07 Rev Time 0.00
Received By adarroug Date 2008-11-24 Time 11:07 Sent To E
Notes
2008-11-24 11:07:44TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 7 Status N Date 2008-11-18 Cont ID  
Sent By adarroug Date 2008-11-18 Time 13:57 Rev Time 0.00
Received By adarroug Date 2008-11-18 Time 13:57 Sent To E
Notes
2008-11-18 13:57:24TO "DPALMER" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 6 Status N Date 2008-11-04 Cont ID  
Sent By adarroug Date 2008-11-04 Time 16:39 Rev Time 0.00
Received By adarroug Date 2008-11-04 Time 16:39 Sent To L
Notes
2008-11-04 16:40:03TO "Z" BOX/SUBMITTAL--LANDSCAPING REVIEW

Review Stop I INCOMING/PROCESSING
Rev No 5 Status N Date 2008-10-17 Cont ID  
Sent By adarroug Date 2008-10-17 Time 11:46 Rev Time 0.00
Received By adarroug Date 2008-10-17 Time 11:46 Sent To Z
Notes
2008-10-17 11:47:16TO "Z" BOX/SUBMITTAL

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-18 Cont ID  
Sent By adarroug Date 2008-06-18 Time 13:36 Rev Time 0.00
Received By adarroug Date 2008-06-18 Time 13:36 Sent To M
Notes
2008-06-18 13:36:55TO "TGORDON" DESK/REV

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-06-06 Cont ID  
Sent By adarroug Date 2008-06-06 Time 11:19 Rev Time 0.00
Received By adarroug Date 2008-06-06 Time 11:19 Sent To M
Notes
2008-06-06 11:20:06TO "M" BOX/REV

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-22 Cont ID  
Sent By adarroug Date 2008-01-22 Time 11:53 Rev Time 0.00
Received By adarroug Date 2008-01-22 Time 11:53 Sent To Z
Notes
2008-01-22 11:53:37TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date   Cont ID  
Sent By   Date 2007-12-31 Time   Rev Time 0.00
Received By adarroug Date 2007-12-12 Time 09:19 Sent To  
Notes
2007-12-12 09:21:00TO "SFR" "Z"

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2008-11-13 Cont ID  
Sent By rkussner Date 2008-11-13 Time 09:49 Rev Time 0.00
Received By rkussner Date 2008-11-13 Time 09:49 Sent To PC
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-11-05 Cont ID  
Sent By rkussner Date 2008-11-05 Time 15:58 Rev Time 0.00
Received By rkussner Date 2008-11-05 Time 15:58 Sent To PC
Notes
2008-11-05 16:01:10***LANDSCAPE REVIEW FAILED***
  
 1. PLEASE SHOW THE REQUIRED STREET TREES ON THE
 LANDSCAPE PLAN.
  
 2. PLEASE CLARIFY LANDSCAPE CALCULATIONS.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-10-27 Cont ID  
Sent By rkussner Date 2008-10-27 Time 09:02 Rev Time 0.00
Received By rkussner Date 2008-10-27 Time 09:02 Sent To PC
Notes
2008-10-27 09:07:16***LANDSCAPE REVIEW FAILED***
  
 1. SUBMIT 2ND COPY OF LANDSCAPE PLAN.
  
 2. COMPLETE THE REQUIRED CALCULATIONS---TREES REQUIRED
 AND PROVIDED, SHRUBS REQUIRED AND PROVIDED, ETC.
  
 3. IDENTIFY AND PROVIDE THE REQUIRED STREET TREES.

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-06-23 Cont ID  
Sent By tgordon Date 2008-06-23 Time 08:35 Rev Time 0.30
Received By tgordon Date 2008-06-23 Time 08:35 Sent To  
Notes
2008-06-23 08:36:08REVISION TO MECH. PLAN.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-06-09 Cont ID  
Sent By tgordon Date 2008-06-09 Time 09:47 Rev Time 0.45
Received By tgordon Date 2008-06-09 Time 09:47 Sent To  
Notes
2008-06-09 10:00:18PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 REVISION TO MECHANICAL PLANS.
 *** DENIED ***
 1) COOLING LOAD CALCULATION ON FILE ARE CALLING FOR
 51,426 TOTAL COOLING BTU'S FOR SYSTEM 1, REVISED
 MECHANICAL PLAN IS SHOWING MODEL NUMBERS FOR A 3 TON
 SYSTEM AROUND 33,800 TOTAL COOLING BTU'S. (SEE ARI
 CERTIFICATE ATTACHED). PLEASE CORRECT PLANS OR REVISE
 COOLING LOAD CAL'S PER 2004 FBC 13-607.1.ABC.1.1.
  
 2) THE SUPPLY AIR DUCT FROM AIR HANDLER #2 TO THE
 MIXING BOX OVER THE MASTER BATHROOM NEEDS TO BE SIZED,
 PER WPB AMEND. 106.3.5.4 (10).
  
 3) PLEASE SHOW THE JOB ADDRESS ON THE PLAN, PER WPB
 AMEND.106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status P Date 2007-12-21 Cont ID  
Sent By tgordon Date 2007-12-21 Time 12:22 Rev Time 0.40
Received By tgordon Date 2007-12-21 Time 12:22 Sent To E
Notes
***NONE***

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-02-06 Cont ID  
Sent By jleech Date 2008-02-06 Time 09:33 Rev Time 0.00
Received By jleech Date 2008-02-06 Time 09:33 Sent To B
Notes
***NONE***

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-24 Cont ID  
Sent By jleech Date 2007-12-24 Time 08:45 Rev Time 0.00
Received By jleech Date 2007-12-24 Time 08:40 Sent To B
Notes
2007-12-24 09:01:36DENIED;
 1. L.T. IS NOT ON THE SAME WALL AS W/M. SEPARATE BRANCH
 DRAIN REQUIRED.
 2. NO BIDET SHOWN ON RISER DIAGRAM, BUT SHOWN ON FLOOR
 PLANS.
 3. DELETE W/H DIAGRAM ON SHEET A-4. INFORMATION ON
 DIAGRAM IS NOT CORRECT. T&P WILL DISCHARGE TO THE
 GARAGE FLOOR,HEATER IS GAS WITH A RECIRCULATION SYSTEM,
 AND NO WATER HEATER PAN IS REQUIRED.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By choops Date 2008-01-24 Time 15:39 Rev Time 0.00
Received By choops Date 2008-01-24 Time 15:39 Sent To E
Notes
2008-01-24 15:39:47***APPROVED - RESUB #1***
  
  
  
  
 SENT TO "E" - DP

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By choops Date 2007-12-12 Time 16:38 Rev Time 0.00
Received By choops Date 2007-12-12 Time 16:38 Sent To E
Notes
2007-12-12 16:41:55***FAILED***
  
  
 1)PROPOSED DRIVEWAY DOES NOT MATCH FROM SURVEY TO
 SHEET A6.PLEASE CLARIFY.
  
 2)PROPOSED A/C UNITS DO NOT MATCH FROM SHEETS A2/A4
 TO A6.PLEASE CLARIFY.
  
 3)PLEASE SUBMIT A LANDSCAPE PLAN SHOWING COMPLIANCE
 WITH SECTION 94-442 AND 94-445 OF THE ZONING AND LAND
 DEVELOPMENT REGULATIONS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720