Plan Review Details - Permit 07120219
| Plan Review Stops For Permit 07120219 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-21 |
Time |
14:42 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-21 |
Time |
14:42 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-18 |
Time |
17:29 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-18 |
Time |
17:29 |
Sent To |
|
|
| Notes |
| 2007-12-18 17:31:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | PREVIOUS LIST: | | | | | | 1.)TWO DIFFERENT ASSEMBLIES WERE SELECTED (PAGE 33, | | | PAGE 34).ENHANCED FASTENING WHICH YOU HAVE SPECIFIED, | | | 4" OC, IS NOT COMPLIANT FOR FASTENING 2 ON EITHER | | | SYSTEM.PLEASE INDICATE WHICH FASTENER YOU ARE USING | | | (MUST BE FASTENING #1 FOR SYSTEM E2 FOR 2 FIELD ROWS | | | 4"OC), SELECT ANOTHER SYSTEM, OR SPECIFY ADDITIONAL | | | ROWS FOR ENHANCED FASTENING. | | | | | | CONTRACTOR SELECTED SYSTEM 2.THERE ARE STILL TWO | | | DIFFERENT ASSEMBLIES IN THE PACKAGE.PLEASE CHOOSE | | | ONLY ONE ASSEMBLY.SPECIFY ENHANCED FASTENING FOR | | | ZONES 2 AND 3.YOU HAD SPECIFIED 4" OC, BUT THIS WAS | | | CROSSED OFF.THIS IS NOT COMPLIANT FOR THE ASSEMBLY | | | YOU HAVE SELECTED.PLEASE SPECIFY ENHANCED FASTENING. | | | |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-11 |
Time |
14:52 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-11 |
Time |
14:52 |
Sent To |
|
|
| Notes |
| 2007-12-11 14:56:08 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)TWO DIFFERENT ASSEMBLIES WERE SELECTED (PAGE 33, | | | PAGE 34).ENHANCED FASTENING WHICH YOU HAVE SPECIFIED, | | | 4" OC, IS NOT COMPLIANT FOR FASTENING 2 ON EITHER | | | SYSTEM.PLEASE INDICATE WHICH FASTENER YOU ARE USING | | | (MUST BE FASTENING #1 FOR SYSTEM E2 FOR 2 FIELD ROWS | | | 4"OC), SELECT ANOTHER SYSTEM, OR SPECIFY ADDITIONAL | | | ROWS FOR ENHANCED FASTENING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-10 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2007-12-10 |
Time |
17:59 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-10 |
Time |
17:59 |
Sent To |
|
|
| Notes |
| 2007-12-10 18:00:27 | ****CORRECTIONS**** | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 | | | EXISTING BUILDING CODE | | | FBC*CITY OF WEST PALM BEACH | | | AMENDMENTS TO THE FBC2004 | | | | | | 1.)FOR THE LOW SLOPE ROOF, SPECIFY THE ENHANCED | | | FASTENING FOR CORNER AND PERIMETER ZONES.THIS IS TO | | | BE EITHER WRITTEN ON THE PRODUCT APPROVAL OR SUBMITTED | | | ON LETTERHEAD, TWO SETS (NOT WRITTEN ON THE RESUB | | | SHEET). | | | |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-13 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2007-12-13 |
Time |
11:23 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2007-12-13 |
Time |
11:23 |
Sent To |
B |
|
| Notes |
| 2007-12-13 11:23:42 | TO "SHILL' DESK/RESUB |
|
|
|