Plan Review Details - Permit 07120184
Plan Review Stops For Permit 07120184
Review Stop AD ADDRESSING
Rev No 1 Status N Date 2008-08-05 Cont ID  
Sent By lursu Date 2008-08-05 Time 08:25 Rev Time 0.00
Received By lursu Date 2008-08-05 Time 08:25 Sent To  
Notes
2008-08-05 08:26:39THE SITE ADDRESS OF 8150 OKEECHOBEE BLVD MUST CHNAGE TO
 8180 OKEECHOBEE BLVD

Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-07-30 Cont ID  
Sent By shill Date 2008-07-30 Time 13:59 Rev Time 0.00
Received By shill Date 2008-07-30 Time 13:59 Sent To  
Notes
2008-07-30 14:01:07****PROVISOS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PROVISO - ROOF ENHANCED FASTENING AND ROOF TILE
 PRODUCT APPROVAL AND FASTENING UNDER SEPARATE PERMIT
 ENGINEERED CALCULATIONS REQUIRED (FLAT)
 NOA 06-0626.02, JOHN MANVILLE MODIFIED OVER STEEL DECK
 SUBMITTED
 ASSEMBLY PAGE 7
  
 2.PROVISO - ROOF ACCESS LADDER UNDER TENANT BUILDOUT
 PERMIT
  
 3.PROVIDE CROSS ACCESS AGREEMENT PRIOR TO CO ***CO
 HOLD PLACED ON PERMIT***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-06-04 Cont ID  
Sent By shill Date 2008-06-04 Time 15:06 Rev Time 0.00
Received By shill Date 2008-06-04 Time 15:06 Sent To  
Notes
2008-06-04 15:07:00****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.ADDRESSED.
  
 2.PRODUCT APPROVALS, SOILS, SPECS HAVE BEEN STAMPED
 AS REVIEWED.WHEN RESUBMITTING, PLEASE INCLUDE BOTH
 SETS IN THE RESUBMITTAL (INFORMATIONAL ONLY).
  
 3.A DATE IS REQUIRED FOR THE ARCHITECT'S SEAL.IF
 POSSIBLE, PLEASE DATE THE SHEETS WHICH HAVE ALREADY
 BEEN SUBMITTED AS THEY HAVE BEEN STAMPED AS REVIEWED
 AND CODE COMPLIANT.FS481.
  
 4.THE PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS (INFORMATIONAL ONLY):
  
 1.PROVISO - ROOF ENHANCED FASTENING AND ROOF TILE
 PRODUCT APPROVAL AND FASTENING UNDER SEPARATE PERMIT
 ENGINEERED CALCULATIONS REQUIRED (FLAT)
 NOA 06-0626.02, JOHN MANVILLE MODIFIED OVER STEEL DECK
 SUBMITTED
 ASSEMBLY PAGE 7
  
 2.PROVISO - ROOF ACCESS LADDER UNDER TENANT BUILDOUT
 PERMIT

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-03-31 Cont ID  
Sent By shill Date 2008-03-31 Time 07:43 Rev Time 0.00
Received By shill Date 2008-03-31 Time 07:43 Sent To  
Notes
2008-03-31 07:46:33****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.PLEASE PROVIDE THE IMPACT FEE RECEIPT.THE PLANS
 ARE STAMPED BUT THE RECEIPT IS ALSO REQUIRED PRIOR TO
 PERMIT ISSUANCE.
  
 2.PRODUCT APPROVALS, SOILS, SPECS HAVE BEEN STAMPED
 AS REVIEWED.WHEN RESUBMITTING, PLEASE INCLUDE BOTH
 SETS IN THE RESUBMITTAL (INFORMATIONAL ONLY).
  
 3.A DATE IS REQUIRED FOR THE ARCHITECT'S SEAL.IF
 POSSIBLE, PLEASE DATE THE SHEETS WHICH HAVE ALREADY
 BEEN SUBMITTED AS THEY HAVE BEEN STAMPED AS REVIEWED
 AND CODE COMPLIANT.FS481.
  
 4.THE PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS (INFORMATIONAL ONLY):
  
 1.PROVISO - ROOF ENHANCED FASTENING AND ROOF TILE
 PRODUCT APPROVAL AND FASTENING UNDER SEPARATE PERMIT
 ENGINEERED CALCULATIONS REQUIRED (FLAT)
 NOA 06-0626.02, JOHN MANVILLE MODIFIED OVER STEEL DECK
 SUBMITTED
 ASSEMBLY PAGE 7
  
 2.PROVISO - ROOF ACCESS LADDER UNDER TENANT BUILDOUT
 PERMIT
  

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By jwitmer Date 2008-01-02 Time 15:59 Rev Time 3.33
Received By jwitmer Date 2008-01-02 Time 15:59 Sent To  
Notes
2008-01-02 16:20:22BUILDING PLAN REVIEW
 PERMIT: 07120184
 ADD: 8150 OKEECHOBEE BLVD. (SHELL BUILDING)
 CONT: HALLMARK & SONS, INC.
 TEL: (561)644-3498
  
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS * WEST PALM BEACH AMENDMENTS
  
 JAN.02,2008
 1STREVIEW
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B)PLEASE SUBMIT 2 OF ALL SURVEYS, PLANS, REPORTS,
 REVISIONS , PRODUCT APPROVALS AND OR SUBMITTALS FOR
 REVIEW FOR PERMIT. IF YOUR PROJECT WILL REQUIRE A
 RESIDENT INSPECTOR OR IF YOUR PROJECT IS A THRESHOLD
 BUILDING REQUIRING A THRESHOLD INSPECTOR THEN (3) THREE
 SETS OF ALL SAID DOCUMENTS WILL BE REQUIRED FOR PERMIT
 ISSUANCE. 106.1* /2004 SUBMITTAL DOCUMENTSWEST PALM
 BEACH ADMINISTRATIVE CODE.
  
 1C) 106.1.1* W.P.B. ADMINISTRATIVE CODE/2004
 DRAWINGS & SPECIFICATIONS SHALL CONTAIN INFORMATION, IN
 THE FORM OF NOTES OR OTHERWISE, AS TO THE QUALITY OF
 MATERIALS, WHERE QUALITY IS ESSENTIAL TO CONFORMITY
 WITH THE TECHNICAL CODES. SUCH INFORMATION SHALL BE
 SPECIFIC TO THE TECHNICAL CODES "SHALL NOT BE CITED AS
 A WHOLE OR IN PART, NOR THE TERM "LEGAL" OR ITS
 EQUIVALENT BE USED AS A SUBSTITUTE FOR SPECIFIC
 INFORMATION". CONSTRUCTION DOCUMENTS SHALL BE
 SUFFICIENT CLARITY TO INDICATE THE LOCATION, NATURE AND
 EXTENT OF THE WORK PROPOSED AND SHOW IN DETAIL THAT IT
 WILL CONFORM TO THE PROVISIONS OF THIS CODE AND
 RELEVANT LAWS, ORDINANCES, RULES AND REGULATIONS, AS
 DETERMINED BY THE BUILDING OFFICIAL.
  
 1D ) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1E) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 SUPPLEMENTS. PLEASE CORRECT THE
 DESIGN CRITERIA FOUND ON BOTH A-1 & S-3. PLANS ARE
 INDICATE THE 2004 BASE FBC WITH 2007 SUPPLEMENTS .
  
 2) .FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS NOT
 ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 3) 109.3.10* IMPACT OF CONSTRUCTION. ALL CONSTRUCTION
 ACTIVITY REGULATED BY THIS CODE SHALL BE PERFORMED IN A
 MANNER SO AS NOT TO ADVERSELY IMPACT THE CONDITION OF
 ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS PERMITTED TO
 AFFECT SAID PROPERTY PURSUANT TO A CONSENT BY THE
 APPLICABLE PROPERTY OWNER, UNDER TERMS & CONDITIONS
 AGREEABLE TO THE APPLICABLE PROPERTY OWNER. THIS
 INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF DUST,
 NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE
 POSITIVE PATTERNS OF THE AFFECTED SITES. ACCORDINGLY,
 DEVELOPERS, CONTRACTORS, AND OWNERS OF ALL NEW
 RESIDENTIAL DEVELOPMENT, INCLUDING ADDITIONS, POOLS,
 PATIOS, DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ
 FT OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 4) 109.3.10.1 HURRICANE PROTECTION. IT SHALL BE
 UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION RELATED
 MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE OR
 OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24 HRS.
 AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO REMOVE OR SECURE THE
 CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS WITHIN 24
 HRS AFTER A HURRICANE WATCH HAS BEEN ISSUED SHALL BE
 SUBJECT TO A FINE NOT TO EXCEED $500.00.IN ADDITION
 TO THE ABOVE, A LICENSED CONTRACTOR WHO VIOLATES THIS
 SECTION SHALL BE SUBJECT TO DISCIPLINE PURSUANT TO
 SECTION 113 OF THIS CHAPTER.
  
 5) THE STRUCTURAL PLANS INDICATE THAT SOILS TEST WERE
 COMPLETED, PLEASE PROVIDE (2) ORIGINAL SIGNED & SEALED
 SETS OF THE SOILS REPORTS COMPLETED BY ALLTERRA
 ENGINEERING & TESTING DATED NOV. 8, 2007 REPORT#
 07-372.1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 6) 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS
 REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE
 PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS
 SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF
 GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE
 ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES
 POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH
 AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS
 OF SSTD 12, ASTM E 1886 ANDASTM E 1996, OR MIAMI-DADE
 TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1.
 GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE
 SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE TEST.
 2.GLAZED OPENINGS LOCATED MORE THAN 30 FEET (9.1
 M) ABOVE GRADE SHALL MEET THE PROVISIONS OF THE SMALL
 MISSILE TEST.
  
 6A) FL BLD CODE 1609.1.4: COMPONENTS & CLADDING,
 PROVIDE 2 COPIES, 3 IF THRESHOLD OR RESIDENT INSPECTOR
 OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE AS
 FOLLOWS:
 A) TRUSS ANCHORS
 B) ROOF ASSEMBLIES FOR FLAT ROOF AND ROOF TILE
  
 C) IF PRE-MANUFACTURED A/C STANDS ARE USED, ME1
 INDICATES ROOF CURBS TO BE USED WITH DOWN DRAFT UNITS.
 D) PASS THROUGH WINDOW
  
 6B)PRODUCT APPROVALS SUBMITTED WITH PERMIT
 APPLICATION AFTER OCTOBER 1, 2003 ARE REQUIRED TO
 COMPLY WITH THE FLORIDA PRODUCT APPROVAL SYSTEM. FOR
 INFORMATION PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH STATEWIDE
 APPROVAL ARE REQUIRED TO BE SUBMITTED WITH A COVER
 SHEET THAT LISTS THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE STATEWIDE APPROVAL,
 SUBMIT AN APPLICATION FOR LOCAL PRODUCT APPROVAL OR
 SITE SPECIFIC FORM PER RULE 9B-72. SEE ATTACHMENT.
 WWW.FLORIDABUILDING.ORG
  
 6C)WPB ADMIN CODE 106.3* PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 7A) NOTE THERE HAS BEEN NO ROOFING REPORTS SUBMITTED,
 IF THEY ARE GOING TO BE SUBMITTED FOR REVIEW THIS IS
 WHAT WILL BE REQUIRED FOR THE FLAT ROOF: 106.1.1.2FOR
 ROOFING ASSEMBLIES REQUIRED BY THIS CODE, THE
 CONSTRUCTION DOCUMENTS SHALL ILLUSTRATE, DESCRIBE, AND
 DELINEATE THE TYPE OF ROOFING SYSTEMS, MATERIALS,
 FASTENING REQUIREMENTS, FLASHING REQUIREMENTS AND WIND
 RESISTANCE RATING THAT ARE REQUIRED TO BE INSTALLED.
 FLAT ROOF:
 ____ CONTRACTOR DID NOT PROVIDE THE MEAN ROOF HEIGHT.
  
 ___ CONTRACTOR DID NOT INDICATE THE ROOF PITCH.
  
 ___ CONTRACTOR FAILED TO INDICATE WHICH SUB-SYSTEM
 SHALLBE INSTALLED.
  
 ___ THE SYSTEM PROVIDED HAS A LOW PRESSURE FOR ZONE
 _2&3__ .
  
 SINCE THE ROOFING REPORT DOESN'THAVE THE SUBSYSTEM
 HIGHLIGHTED THE NEXT 2 ITEMS ARE HIGHLIGHTED.
  
 ___ THE SYSTEM PROVIDED STATESLIMITATION# 7, SHOULD
 THE FASTENERRESISTANCE BE LESS THAN THAT REQUIRED,
 AS DETERMINED BY THEBUILDING OFFICIAL, A REVISED
 FASTENERSPACING, PREPARED , SIGNED AND SEALED BY A
 FLORIDA REGISTEREDPROFESSIONAL ENGINEER,
 REGISTEREDARCHITECT OR REGISTERED ROOF CONSULTANT
 MAY BE SUBMITTED.
  
 ___THE SYSTEM PROVIDED INDICATESLIMITATION# 9,
 NO ENHANCEDFASTENING ALLOWED.
  
 7B)PLEASE SUBMIT INFORMATION ON HOW THE RIDGE TILE
 ARE GOING TO BE SECURED TO THE ROOFING SYSTEM. 1507.3.7
 ATTACHMENT. CLAY AND CONCRETE ROOF TILES SHALL BE
 FASTENED IN ACCORDANCE WITH SECTION 1609 OR IN
 ACCORDANCE WITH FRSA/RTI INSTALLATION MANUAL. 1507.3.8
 APPLICATION. TILE SHALL BE APPLIED ACCORDING TO THE
 MANUFACTURER'S INSTALLATION INSTRUCTIONS OR
 RECOMMENDATIONS OF THE FRSA/RTI 07320- 04.
  
 9) SHEET A2.0 INDICATES THE USE OF EFIS MOLDINGS,
 PLEASE PROVIDE INFORMATION HOW THE FOAM WILL BE
 ATTACHED TO THE BUILDING. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 10) BOTH SHEETS A-3 AND A-4 BOTH INDICATE A PITCHED
 ROOF AND PARAPET WALL AROUND THE ENTIRE PERIMETER OF
 THE BUILDING. PLEASE INDICATE HOW ACCESS TO THE ROOF
 TOP MECHANICAL UNITS WILL OCCUR? PLEASE SEE 306.5
 MECHANICAL CODE, FBC. NOTE IF THIS IS TO BE
 ACCOMPLISHED THROUGH A ROOF TOP ACCESS HATCH, CURRENTLY
 THERE ARE NO DEVISES THAT MEET THE REQUIREMENTS OF RULE
 9B-72 (31-A). IF AN AFFIXED EXTERIOR LADDER IS TO BE
 INSTALLED PLEASE PROVIDE MANUFACTURES SPEC. FBC
 BUILDING 1209.3 MECHANICAL APPLIANCES. ACCESS TO
 MECHANICAL APPLIANCES INSTALLED IN UNDER-FLOOR AREAS,
 IN ATTIC SPACES AND ON ROOFS OR ELEVATED STRUCTURES
 SHALL BE IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL .
  
 11) PLEASE PROVIDE ATTIC ACCESS TO TRUSSED ROOF
 SECTION, 1209.2 ATTIC SPACES.
 AN OPENING NOT LESS THAN 20 INCHES BY 30 INCHES (559 MM
 BY 762 MM) SHALL BE PROVIDED TO ANY ATTIC AREA HAVING A
 CLEAR HEIGHT OF OVER 30 INCHES (762 MM). A 30-INCH (762
 MM) MINIMUM CLEAR HEADROOM IN THE ATTIC SPACE SHALL BE
 PROVIDED AT OR ABOVE THE ACCESS OPENING.
  
  
 102.1* WHERE, IN ANY SPECIFIC CASE, DIFFERENT SECTIONS
 OF THIS CODE SPECIFY DIFFERENT MATERIALS, METHODS OF
 CONSTRUCTION OR OTHER REQUIREMENTS, THE MOST
 RESTRICTIVE SHALL GOVERN. WHERE THERE IS A CONFLICT
 BETWEEN A GENERAL REQUIREMENT AND A SPECIFIC
 REQUIREMENT, THE SPECIFIC
 REQUIREMENT SHALL BE APPLICABLE.
  
  
  
  
 BUILDING PLAN REVIEW
 JIM WITMER C. B. O.
 BUILDING PLAN REVIEW II
  
 TEL: (561)805-6715
 FAX: (561)659-8026
 E-MAIL: [email protected]
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-07-03 Cont ID  
Sent By dpalmer Date 2008-07-03 Time 16:32 Rev Time 0.00
Received By dpalmer Date 2008-07-03 Time 16:32 Sent To  
Notes
2008-07-03 16:32:58ADDRESS OF 8150 IS CORRECT. WILL ONLY CHANGE AFTER C OF
 O.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-06-03 Cont ID  
Sent By dpalmer Date 2008-06-03 Time 15:43 Rev Time 0.00
Received By dpalmer Date 2008-06-03 Time 15:43 Sent To  
Notes
2008-06-03 15:43:55** DENIED 3RD REVIEW **
  
  
 ** NEW NOTES**
  
 1) NOTE: PLEASE SEE BOTH SETS OF ELECTRICAL PLANS/MEP
 ARE IN FACT PHOTO-COPIES OF SIGNED, DATED AND SEALED
 PLANS. NEED TO SUBMIT ORIGINAL SIGNED, DATED AND SEALED
 PLANS FOR REVIEW AND STAMPING.
 FS 471.025, FAC 61G15-23.002
  
  
 ** IMPORTANT**
 ONCE AUDIT/REVIEWS ARE COMPLETE AND PLANS ARE PICKED UP
 FOR CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE
 ALL OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING.
 DO NOT LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE AUDIT/REVIEW PROCESS AND AVOID
 ANY DELAYS.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS OR COMMENTS PLEASE DO NOT
 HESITATE IN CONTACTING THIS OFFICE.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By dpalmer Date 2008-03-05 Time 20:42 Rev Time 0.00
Received By dpalmer Date 2008-03-05 Time 20:42 Sent To  
Notes
2008-03-05 20:42:312008-03-05 20:42:31
  
 ** DENIED2ND REVIEW **
  
  
 1) NOTE: PLEASE SEE FBC 13-400.3.B AS THIS REQUIRES
 VERSION 2.5. IT WAS CONFIRMED WITH THE FLORIDA BUILDING
 COMMISSION/ DEPARTMENT OF COMMUNITY AFFAIRS THAT 3.0 IS
 NOT PERMITTED AND ONLY THE ADOPTED 2.5 MAY BE USED.
 THIS IS STILL PENDING REVIEW AND COORDINATION FROM
 OTHER TRADES FOR ENERGY CALCULATIONS.
 PLEASE SEE PREVIOUS REVIEW WHICH REQUESTED THE OWNER
 AGENT SIGN CALCULATIONS AS REQUIRED ON CERTIFICATION
 SHEETS.
 PLEASE ALSO BE SURE THE ENGINEER OF RECORD SIGNS AND
 SEALS THESE SAME SHEETS. 13-103.1.1.1, FS 471.025.
 (ENGINEER DID SEAL, SIGN COVER)
  
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By dpalmer Date 2007-12-12 Time 15:17 Rev Time 0.00
Received By dpalmer Date 2007-12-12 Time 15:17 Sent To  
Notes
2007-12-12 15:18:07** DENIED **
  
 ** APPLIED SHELL FOR STARBUCKS.
  
  
 1) NOTE: PLEASE BE SURE THE ELECTRICAL SHEETS CONTAIN
 THE RELEVANT CODES FOR DESIGN. PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE BE SURE THE APPLIED ADDRESS AND
 LOCATION IS LISTED IN TITLE BLOCKS. APPLIED ADDRESS FOR
 THIS LOCATION IS 8150 OKEECHOBEE BLVD.
 FAC 61G15-23.002, FBC 106.5, 106.1.2
  
 3) NOTE: PLEASE CLARIFY APPLIED SHELL PERMIT AS THIS
 LIST THE OCCUPANT AS BEING *STARBUCKS* HOWEVER AS A
 SHELL THE TENANT MAY NOT BE KNOWN AT THIS TIME. IS THIS
 POSSIBLE FUTURE TENANT?
 PLEASE KNOW THAT IF ANY INTERIOR WORK COMMENCES BEFORE
 CO OF SHELL THIS WILL AFFECT THE ASSUMPTIONS IN THE
 ENERGY CALCULATIONS AS SUBMITTED AS WELL AS THE LOAD
 CALCULATIONS FOR KNOWN ELECTRICAL APPLIANCES FOR
 BUILDING.
 THIS COMMENT IS FOR CLARIFICATION AND INFORMATIONAL
 PURPOSE AT THIS TIME.
 FBC 106.1.2 ADDITIONAL INFORMATION AND COORDINATION.
  
 4) NOTE: PLEASE SEE THE ENERGY CALCULATIONS AS
 SUBMITTED CONTAIN AN ADDENDUM TO THE CALCULATIONS.
 PLEASE KNOW THAT ANY CHANGES TO THE REPORT MUST BE
 INCLUDED IN THE FLA-COM PROGRAM.
 PLEASE BE SURE TO COORDINATE ALL ELECTRICAL LIGHTING ON
 PLANS WITH THAT OF THE LIGHTING IN THE INPUT DATA
 REPORTS.
 PLEASE SEE FOR EXAMPLE: EXTERIOR LIGHTING ON THE INPUT
 DATA REPORT SHOWS A TOTAL OF ONE LIGHT FIXTURE AT
 26WATTS. HOW IS THIS POSSIBLE WHEN THE PLANS CLEARLY
 SHOW AS MANY AS 5 EXTERIOR LIGHT FIXTURES AND THREE
 DIFFERENT TYPES OF FIXTURES?
  
 PLEASE BE SURE TO MAKE ADJUSTMENTS.
 THEINTERIOR LIGHTING ON THE IDR IS ASSUMPTIONS AT
 THIS TIME.
 13-415.2, 13-415.B.1
  
 5) NOTE: PLEASE BE SURE TO ADD NOTES ON PLANS FOR
 13-413.1.ABC.1.1 AND .2.2. (PART OF THIS SEEMS TO BE ON
 ME2 HOWEVER PART OF THE NOTE IS UNCLEAR)
  
 6) NOTE: PLEASE BE SURE THE OWNER AGENT IS SIGNED ON
 THE CERTIFICATION SHEETS ON THE ENERGY CALCULATIONS.
 PLEAS ALSO BE SURE THE ENGINEER SIGNS, DATES AND SEALS
 THE CERTIFICATION SHEET. (PAGE 3).
 13-103.1.1.1, FS 471.025
  
 7) NOTE: PLEASE CLARIFY LOCATIONS FOR A/C DISCONNECTS
 REQUIRED PER 440.11.
  
 8) NOTE: PLEASE SEE POSSIBLE COMMENTS FOR THE APPLIED
 VALUE AS THE VALUE SEEMS LOW PER FBC 108.3.
 THE APPLIED VALUE IS TO INCLUDE ALL LABOR, MATERIALS,
 EQUIPMENT, DESIGN COST, EVEN IF ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
 PLEASE SEE POSSIBLE COMMENTS FROM OTHER TRADES.
  
 9) NOTE: PLEASE CLARIFY WHERE SITE LIGHTING IS BEING
 FED FROM AND HOW THIS IS FIGURED INTO CALCULATIONS.
  
 10) NOTE: THIS NOTE ADDED. CLARIFY CONTINUOUS LOADS
 FIGURED AT 125% ALREADYOR TO BE ADJUSTED.
  
  
  
 ** PLEASE KNOW AS THERE IS SOME INFORMATION NOT YET
 SUBMITTED FOR REVIEW THERE MAY BE NEW COMMENTS ON THE
 FOLLOWING REVIEW WHICH CAN NOT BE MADE AT THIS TIME.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
  

Review Stop ENG ENGINEERING CSD
Rev No 3 Status P Date 2008-07-11 Cont ID  
Sent By rchokshi Date 2008-07-11 Time 09:04 Rev Time 0.00
Received By rchokshi Date 2008-07-11 Time 08:48 Sent To  
Notes
***NONE***

Review Stop ENG ENGINEERING CSD
Rev No 2 Status F Date 2008-03-10 Cont ID  
Sent By rchokshi Date 2008-03-10 Time 14:10 Rev Time 0.00
Received By rchokshi Date 2008-03-10 Time 13:57 Sent To  
Notes
2008-03-10 14:10:21FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 3.ORDINANCE NO. 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS.STORM
 WATER CALS MUST BE APPROVED FROM 100045TH STREET
 ENGINEERING SERVICES BY JONATHAN BRAMLEY, ENGINEERING
 DIRECTOR
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop ENG ENGINEERING CSD
Rev No 1 Status F Date 2007-12-14 Cont ID  
Sent By rchokshi Date 2007-12-14 Time 13:07 Rev Time 0.00
Received By rchokshi Date 2007-12-14 Time 12:50 Sent To  
Notes
2007-12-14 13:01:51FAILED FOR FOLLOWING REASONS:
  
 1. PLEASE PROVIDE A COPY OF NOTICE OF INTENT (NOI).
 PLEASE APPLY AT FDEP, NPDES STORMWATER SECTION FOR
 NOI.
 YOU CAN GET NOI INFO FROM
 WWW.DEP.STATE.FL.US/WATER/STORMWATER/NPDES/
 NOTICE OF INTENT DEP FORM 62-621.300(4)(B),
 EFFECTIVE MAY 1, 2003
  
 2. PLEASE SHOW ON DRAWINGS THE POLLUTION PREVENTION
 DETAILS,CLOTHES USED FOR SILT FENCE ETC., PLANS SHOWING
 SILT FENCE AROUND THE SITE & STORM CATCH BASIN DRAINS
 DURING CONSTRUCTION AND ALL DEMOLITION PHASE.HEIGHT
 OF FENCE SHOULD BE HIGH ENOUGH PER FDEP TO STOP DUST
 PARTICLES.
  
 ORDINANCE NO. 4060-07:
  
 ALL DEMOLITION AND NEW CONSTRUCTION PERMITS, WITH
 EXCEPTION OF SINGLE FAMILY, DUPLEX AND ACCESSORY
 APARTMENT, SHALL POST BONDS OR DEPOSITS FOR THE
 FOLLOWING:
  
 1. EROSION CONTROL, AND
 2. LAND STABILIZATION
  
 THE AMOUNT OF THE EROSION CONTROL AND LAND
 STABILIZATION BONDS SHALL BE DETERMINED BY THE ENGINEER
 OF RECORD USING THE CURRENT CITY COST SCHEDULE AND
 VERIFIED BY THE CITY'S ENGINEERING SERVICES DEPT.
 PLEASE CONTACT BRIAN MOREE, ENG SERVICES CONSTRUCTION
 SUPERVISOR, AT 561- 494 -1040 FOR MORE INFORMATION.
  
 UPON VERTICAL CONSTRUCTION COMMENCEMENT, PAYMENT IN
 FULL OF ALL APPLICABLE FEES, AND COMPLIANCE WITH ALL
 TERMS AND CONDITIONS OF ANY POSTED BOND, THE PERMITTEE
 MAY REQUEST RELEASE OF THE BONDS OR DEPOSITS.
  
 A COPY OF ORDINANCE NO. 4060-07 MAY BE OBTAINED FROM
 THE CITY CLERK'S OFFICE LOCATED ON THE FIRST FLOOR.
  
 3. PLEASE SHOW ON DRAWING ALL CITY STANDARDS NOTES FOR
 SIDEWALK, DRIVEWAY, APPROACH, PARKINGS, HANDICAP
 PARKINGS, DUMPSTER ENCLOSURE, YOU CAN GET A C D FOR ALL
 CITY STANDARDS NOTES FROM 1000, 45 STREET, ENGINEERING
 SERVICES, PHONE# 494-1040
  
 4. PLEASE SHOW ON DRAWINGSDUMPSTER & ITS ENCLOSURE
 DETAILS PER CITY OF WPB, &LOCATION ON DWG, LOCATION
 MUST BE ACCESSIBLE FOR PICKUP TRUCK.
  
 5. PLEASE SHOW ON CALCULATION THAT YOU HAVE CONSIDERED
 FLOOD ZONE AREA, & 5,10, 25, 100 YEAR FLOOD CRITERIA
 AND CROWN OF THE ROAD WHEN YOU DETERMINE THE FIRST
 FLOOR ELEVATION. FIRST FLOOR ELEVATION SHOULD BE
 ATLEAST 1 FOOT HIGHER THAN HIGHEST CROWN OF THE ROAD.
  
 6. PLEASE SHOW ON DRAINAGE DRAWINGTHE SITE AREA,
 GREEN, LAKE,PARKING AREA, IMPERVIOUS,PERVIOUS AREAYOU
 ARE DEVELOPING FOR THIS PROJECT . PLEASEMAKE SURE
 THESE AREAS SHOWN ON DRAINAGE DRAWINGS MUST MATCH WITH
 AND USED IN STORM WATER QUALITY CALCULATIONS. PLEASE
 PROVIDE A COPY OF THESE CALCULATIONS.
  
 7. PLEASE SHOW ALL STORM WATER PIPES AROUND YOUR SITE
 SO, WE CANSEE THE LAYOUT OF STORM WATER PIPES FROM
 ALL OTHER STORM WATER PIPES. PLEASE SHOW DETAIL OF THE
 CONTROL STRUCTURESWITH ELEVATIONS, NOTCHES, BLEEDING
 ELEVATION, ETC ON DRAWINGS, CALCULATION FOR
 EXFILTRATION TRENCHES, PLEASE SHOW DRY DETENTION/WET
 DETENTION AREAS IN STORM WATER CALS IF YOU HAVE ALL
 THESE. PLEASE RESUBMIT GEO-TECH REPORT AND ALL
 ENVRONMENTAL REPORT.
  
 8. ALSO PLEASE SHOW ALL CATCH BASINS NEAREST,AROUND
 YOUR SITE FOR STORM WATER DRAIN SO YOUR SITE DO NOT GET
 FLOODED AND HAVE ENOUGH DRAINS.
  
 9. PLEASE PROVIDE A COPY OF SFWMD PERMIT,, &STORM
 WATER QUALITY CALCULATIONS. STORM WATER CALS MUST BE
 APPROVED FROM 100045TH STREET ENGINEERING SERVICES.
  
  
 PLEASE RESPOND EACH ITEM IN DETAIL TO EXPEDITE YOUR
 PERMITTING PROCESS
  
 RASIK CHOKSHI805-6723

Review Stop FIRE FIRE DEPARTMENT
Rev No 4 Status N Date 2008-07-21 Cont ID  
Sent By mwennerg Date 2008-07-21 Time 09:57 Rev Time 0.00
Received By mwennerg Date 2008-07-21 Time 09:57 Sent To  
Notes
2008-07-21 09:58:33AS PER LAST REVIEW, PLANS APPROVED AND STAMPED BY MIKE
 WILLIAMS.

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status N Date 2008-06-09 Cont ID  
Sent By mwennerg Date 2008-06-09 Time 15:02 Rev Time 0.00
Received By mwennerg Date 2008-06-09 Time 15:01 Sent To  
Notes
2008-06-09 15:02:30PLANS APPROVED AND STAMPED ON 3/22/08

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status P Date 2008-03-22 Cont ID  
Sent By mawillia Date 2008-03-22 Time 17:03 Rev Time 0.00
Received By mawillia Date 2008-03-22 Time 16:40 Sent To  
Notes
2008-03-22 17:03:19*****APPROVED*****
  
 THE COMMENTS FORM THE PREVIOUS FIRE PLAN REVIEW HAVE
 BEEN ADDRESSED;PLAN SHEETS A1.0, A3.0, AND ME1 WERE
 STAMPED, INITIALED AND DATED.

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By mawillia Date 2008-01-04 Time 20:42 Rev Time 0.00
Received By mawillia Date 2008-01-04 Time 19:09 Sent To  
Notes
2008-01-04 19:10:31*****DENIED*****
  
 1.THE NUMERICAL ADDRESS OF THE PROJECT SITE SHALL BE
 IN THE TITLE BLOCK OF EACH SUBMITTED PLAN SHEET.
  
 2.SHOW THE LOCATION OF THE NEAREST EXISTING AND/OR
 PROPOSED FIRE HYDRANT(S) TO THE NEW STRUCTURE.
  
 2.ON SHEET A1.0 IN THE DESIGN STANDARDS/APPLICABLE
 CODES, THERE SEEMS TO BE AN INTERMINGLE OF THE FIRE
 CODES. AMEND TO READ AS SUCH:FLORIDA FIRE PREVENTION
 CODE (2004 EDITION);NFPA 1, UNIFORM FIRE CODE, 2003
 EDITION
  
 3.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 4.THE SCOPE OF WORK SHALL NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE
 PROPERTY/DEVELOPMENT OR VICINITY THEREOF (INCLUDING
 STREETS, ALLEYS, FIRE LANES).
  
 5.ON THE APPROPRIATE EXTERIOR ELEVATION, SHOW/DISPLAY
 THE NUMERICAL ADDRESS FOR THIS STRUCTURE.THE ADDRESS
 NUMBERS SHALL BE AT LEAST 8" IN HEIGHT AND AT LEAST 1"
 IN STROKE/WIDTH.IF A MONUMENT SIGN IS USED OR WILL BE
 USED FOR MULTIPLE COMMERCIAL STRUCTURES IN THE
 DEVELOPMENT, THE ADDRESS RANGE FOR THE DEVELOPMENT
 SHALL BE POSTED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE IN THE PLAN EACH ITEM WAS
 ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-06-16 Cont ID  
Sent By adarroug Date 2008-06-16 Time 13:24 Rev Time 0.00
Received By adarroug Date 2008-06-16 Time 13:24 Sent To  
Notes
2008-06-16 13:30:21TO "COMM" BD#2--PLANS ON RACK/LARGE FOLDED PLANS

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-05-13 Cont ID  
Sent By adarroug Date 2008-05-13 Time 11:27 Rev Time 0.00
Received By adarroug Date 2008-05-13 Time 11:27 Sent To  
Notes
2008-05-13 11:32:30TO "COMM" BD#27

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-20 Cont ID  
Sent By adarroug Date 2008-02-20 Time 08:48 Rev Time 0.00
Received By adarroug Date 2008-02-20 Time 08:48 Sent To  
Notes
2008-02-20 08:48:40TO "COMM" BD#56--2 APPL'S

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-04 Cont ID  
Sent By mawillia Date 2008-01-04 Time 19:10 Rev Time 0.00
Received By mawillia Date 2007-12-10 Time 10:43 Sent To  
Notes
2007-12-10 10:44:01TO "COMM" BD#62

Review Stop L LANDSCAPING
Rev No 3 Status P Date 2008-06-18 Cont ID  
Sent By rkussner Date 2008-06-18 Time 16:20 Rev Time 0.00
Received By rkussner Date 2008-06-18 Time 16:20 Sent To  
Notes
***NONE***

Review Stop L LANDSCAPING
Rev No 2 Status F Date 2008-05-15 Cont ID  
Sent By rkussner Date 2008-05-15 Time 15:52 Rev Time 0.00
Received By rkussner Date 2008-06-18 Time 16:17 Sent To  
Notes
2008-05-15 15:57:291. PREVIOUS COMMENT REQUIRED THAT STREET LIGHTS BE
 REMOVED FROM LANDSCAPE ISLANDS BECAUSE OF THE CONFLICTS
 WITH TREES.INSTEAD OF RELOCATTING THE STREET LIGHTS,
 THE TREES WERE SHIFTED WITHIN THE ISLANDS.THIS IS NOT
 ACCEPTABLE.THE TREES SHALL BE CENTERED WITHIN THE
 LANDSCAPE ISLANDS.WHEN THE TREES WITHIN ISLANDS
 ADJACENT TO THE PERIMETER ARE SHIFTED, THE PERIMETER
 TREES MAY NEED TO BE REPOSITIONED TO MAINTAIN THE
 MAXIMUM SPACING OF 30 FEET.
  
 2.THERE IS A GAP OF APPROXIMATELY 45 FEET ALONG THE
 PERIMETER LANDSCAPE STRIP ADJACENT TO OKEECHOBEE
 BOULEVARD.AN ADDITIONAL TREE WILL NEED TO BE ADDED.

Review Stop L LANDSCAPING
Rev No 1 Status F Date 2008-02-29 Cont ID  
Sent By rkussner Date 2008-02-29 Time 17:27 Rev Time 0.00
Received By rkussner Date 2008-02-29 Time 17:10 Sent To  
Notes
2008-02-29 17:16:03LANDSCAPE COMMENTS:
  
 1.TO TAKE CREDIT FOR THE 5 POINTS (XERISCAPE
 REQUIREMENTS) YOU MUST USE A MOISTURE SENSOR OTHER THAN
 A RAIN SWITCH.
 2.PROVIDE SOD AND IRRIGAION IN RIGHT-OF-WAY.
 3.PROVIDE LANDSCAPE SCREENING AROUND TRANSFORMER
 WITHOUT BLOCKING ACCESS.
 4.ELIMINATE CONFLICTS BETWEEN LIGHT POLES AND TREES.
 LIGHT POLES SHALL NOT BE LOCATED IN LANDSCAPE ISLANDS.
 5.PROVIDE VERTICAL LANDSCAPE ELEMENTS ALONG
 FOUNDATION OF BUILDING TO ACCENTUATE THE ARCHITECTURE.

Review Stop M MECHANICAL (A/C)
Rev No 5 Status P Date 2008-07-03 Cont ID  
Sent By rregueir Date 2008-07-03 Time 16:53 Rev Time 0.00
Received By rregueir Date 2008-07-03 Time 16:40 Sent To  
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 4 Status F Date 2008-06-04 Cont ID  
Sent By rregueir Date 2008-06-04 Time 13:29 Rev Time 0.00
Received By rregueir Date 2008-06-04 Time 13:25 Sent To  
Notes
2008-06-04 13:29:11SEE MECH REVIEW COMMENTS DATED 5/29/08.
  
 CONTRACTOR CALLED AND INFORMED THAT THE ME SHEETS WILL
 NOT BE ABLE TO BE REPLACED IN A TIMELY MANNER AND
 THEREFOR HAS REQUESTED THAT REVIEWS PROCEED.
  
 ALL PREVIOUS MECHANICAL REVIEW COMMENTS HAVE BEEN
 ADDRESSED. HOWEVER, SINCE THE ME PAGES ARE NOT SIGNED
 AND SEALED AS REQUIRED FAC 61G15-23.002, PLANS CAN NOT
 BE REVIEWED OR STAMPED FOR CODE COMPLIANCE. PLEASE
 CORRECT AND RESUBMIT.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2008-05-29 Cont ID  
Sent By rregueir Date 2008-05-29 Time 15:04 Rev Time 0.00
Received By rregueir Date 2008-05-29 Time 15:03 Sent To  
Notes
2008-06-04 13:25:02PLAN REVIEWS ON HOLD PER CONTRACTOR REQUEST. THE ME
 PAGES SUBMITTED ARE NOT SIGNED AND SEALED BY THE DESIGN
 PROFESSIONAL. CONTRACTOR TO PROVIDE NEW SHEETS.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-03-16 Cont ID  
Sent By rregueir Date 2008-03-16 Time 16:31 Rev Time 0.00
Received By rregueir Date 2008-03-16 Time 16:28 Sent To  
Notes
2008-03-16 16:31:20PLANS HAVE BEEN STAMPED. HOWEVER, REVIEW WILL REMAIN IN
 "FAIL" STATUS PENDING SUBMITTAL OF CORRECTED ENERGY
 CALCULATIONS. THE CORRECT FORM IS 400B-04 V2.5. SEE
 FBCB 13-400.3.A.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By rregueir Date 2008-01-04 Time 13:48 Rev Time 0.00
Received By rregueir Date 2008-01-04 Time 10:27 Sent To  
Notes
2008-01-04 13:48:52REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. ENERGY CALCULATIONS: METHOD B FOR SHELL BUILDING HAS
 BEEN SUBMITTED WITH ASSUMPTIONS FOR FEATURES TO BE
 INSTALLED AT A LATER DATE. THESE ASSUMPTIONS (AND THE
 COMPLIANCE FORM) ARE MISSING HVAC EQUIPMENT. PLANS
 INDICATE THIS IS TO BE INSTALLED AT A LATER DATE AND
 SHALL BE INCLUDED IN THE ASSUMPTIONS AS WELL AS THE
 CALCULATIONS IN ACCORDANCE WITH FBC 13-101.1.6. THE
 SIZE OF HVAC EQUIPMENT SHOULD BE DETERMINED AT THIS
 TIME TO DEMONSTRATE RELATIVE ACCURACY OF ASSUMPTIONS
 BEING MADE. THIS SHALL BE DEMONSTRATED WITH COOLING
 LOAD CALCULATIONS IN ACCORDANCE WITH FBC
 13-407.1.ABC.1. PROVIDE MISSING INFORMATION AND
 RESUBMIT ENERGY CALCULATIONS WITH THIS INFORMATION
 INCLUDED.
  
 2. TOP OF PARAPET WALL IS SHOWN AT 21 FEET. WHERE
 EQUIPMENT AND APPLIANCES REQUIRING ACCESS ARE INSTALLED
 ONELEVATED STRUCTURES AT A HEIGHT EXCEEDING 16 FEET,
 SUCH ACCESS SHALL BE PROVIDED BY A PERMANENT APPROVED
 MEANS OF ACCESS, THE EXTENT OF WHICH SHALL BE FROM
 GRADE OR FLOOR LEVEL TO THE EQUIPMENT AND APPLIANCES?
 LEVEL SERVICE SPACE. SUCH ACCESS SHALL NOT REQUIRE
 CLIMBING OVER OBSTRUCTIONS GREATER THAN 30 INCHES HIGH.
 FBC, M 306.5.
 PERMANENT LADDERS INSTALLED TO PROVIDE THE REQUIRED
 ACCESS SHALL COMPLY WITH THE FOLLOWING MINIMUM DESIGN
 CRITERIA:
 A. THE SIDE RAILING SHALL EXTEND ABOVE THE PARAPET OR
 ROOF EDGE NOT LESS THAN 30 INCHES.
 B. LADDERS SHALL HAVE RUNG SPACING NOT TO EXCEED 14
 INCHES ON CENTER.
 C. LADDERS SHALL HAVE A TOE SPACING NOT LESS THAN 6
 INCHES DEEP.
 D. THERE SHALL BE A MINIMUM OF 18 INCHES BETWEEN
 RAILS.
 E. RUNGS SHALL HAVE A MINIMUM 0.75-INCH DIAMETER AND BE
 CAPABLE OF WITHSTANDING A 300-POUND LOAD.
 F. LADDERS SHALL BE PROTECTED AGAINST CORROSION BY
 APPROVED MEANS.
  
 3. PROVIDE STRUCTURAL DETAIL FOR ATTACHMENT OF A/C ROOF
 CURBS TO BUILDING TO MEET WIND LOAD REQUIREMENTS IN
 ACCORDANCE WITH FBC, M 301.13. THE PROPOSED A/C
 EQUIPMENT LISTED ON PG ME1 MAY BE USED FOR THESE
 CALCULATIONS. SEE ALSO PG S-3 "SPECIALTY ENGINEERED
 PRODUCTS" NOTE 1(B). PROVIDE THE REQUESTED INFORMATION
 FOR BUILDING PLAN REVIEW.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 4 Status P Date 2008-07-15 Cont ID  
Sent By kstevens Date 2008-07-15 Time 08:41 Rev Time 0.00
Received By kstevens Date 2008-07-15 Time 08:41 Sent To  
Notes
2008-07-15 08:42:29PASSED/PROVISO-- AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-05-28 Cont ID  
Sent By kstevens Date 2008-05-28 Time 16:20 Rev Time 0.00
Received By kstevens Date 2008-05-28 Time 15:50 Sent To  
Notes
2008-05-28 16:20:51PASSED/PROVISO-- AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.

Review Stop P PLUMBING
Rev No 2 Status P Date 2008-03-18 Cont ID  
Sent By kstevens Date 2008-03-18 Time 12:05 Rev Time 0.00
Received By kstevens Date 2008-03-18 Time 12:05 Sent To  
Notes
2008-03-18 12:34:16PASSED/PROVISO-- AN RPZV BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-19 Cont ID  
Sent By kstevens Date 2007-12-19 Time 18:00 Rev Time 0.00
Received By kstevens Date 2007-12-19 Time 18:00 Sent To  
Notes
2007-12-19 18:08:49DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT ME1 SUBMIT A STORM ISOMETRIC RISER DIAGRAM
 SHOWING ALL PIPE SIZES, OFFSETS, AND CLEANOUTS REQUIRED
 BY SECTIONS 106.3.5.1.3, 1101.8, 1106 & 1107 & TABLE
 1106.3.
  
 2. IF THE GREASE INTERCEPTOR WILL BE INSTALLED AT THE
 TIME OF THE SHELL, THE INTERCEPTOR SHALL BE SIZED BY
 THE UTILITY DEPT., INDUSTRIAL PRETREATMENT,
 ENVIRONMENTAL COMPLIANCE. PLEASE CONTACT RODNEY COMPO,
 (561) 822-2272, E-MAIL [email protected], OR CALVIN
 WILLIAMS, (561) 822-2284, E-MAIL [email protected].
 THEY WILL GIVE YOU A WRITTEN DETERMINATION AS TO THE
 SIZE OF THE GREASE INTERCEPTOR REQUIRED. ARTICLE III
 SECTION 90-124(7)(F). PLEASE CLARIFY WHEN THE GREASE
 INTERCEPTOR WILL BE INSTALLED.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 4 Status P Date 2008-06-18 Cont ID  
Sent By adavila Date 2008-06-18 Time 16:31 Rev Time 0.00
Received By adavila Date 2008-06-18 Time 11:27 Sent To  
Notes
2008-06-18 11:27:47PER ERIC SCHNEIDER, PRINCIPAL PLANNER.
  
 PROVISO PROVIDE A COPY OF THE RECORDED CROSS-ACCESS
 AGREEMENT FOR THE NEIGHBORING PROPERTY FOR THE
 OKEECHOBEE BOULEVARD ENTRANCE DRIVEWAY PRIOR TO
 OBTAINING A CO.

Review Stop Z ZONING
Rev No 3 Status F Date 2008-05-16 Cont ID  
Sent By adavila Date 2008-05-16 Time 12:39 Rev Time 0.00
Received By adavila Date 2008-05-16 Time 12:39 Sent To  
Notes
2008-05-16 12:39:35PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.BUILDING PLAN (SHEET ME3) DOES NOT MATCH THE SITE
 AND LANDSCAPE PLANS.ALL PLANS SHALL SHOW THE SAME
 CONDITIONS.PLEASE REVISE.
  
 2.REPEAT COMMENT - LANDSCAPE CODE DATA HAS NOT BEEN
 UPDATED TO REFLECT THE NEW TREE QUANTITIES.PLEASE
 REVISE.
 A.ACCORDING TO THE LANDSCAPE CODE DATA, 98 SHADE
 TREES WILL BE PROVIDED.HOWEVER, THE PLANTING SCHEDULE
 SHOWS A TOTAL OF 72 SHADE TREES AND 34 PALMS.
  
 3.PLEASE NOTE THAT ALL SIGNS SHALL BE REVIEWED AND
 APPROVED ON A SEPARATE PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-29 Cont ID  
Sent By adavila Date 2008-02-29 Time 17:37 Rev Time 0.00
Received By adavila Date 2008-02-27 Time 12:08 Sent To  
Notes
2008-02-29 17:38:02PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1.REPEAT COMMENT - LANDSCAPE CODE DATA HAS NOT BEEN
 UPDATED TO REFLECT THE NEW TREE QUANTITIES.PLEASE
 REVISE.
  
 2.FPL TRANSFORMER SHALL BE SCREENED WITH LANDSCAPING
 AT ITS NEW LOCATION.
  
 3.ALL WALLS/FENCES SHALL BE APPROVED ON A SEPARATE
 PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-17 Cont ID  
Sent By adavila Date 2007-12-17 Time 10:53 Rev Time 0.00
Received By adavila Date 2007-12-12 Time 11:24 Sent To  
Notes
2007-12-12 11:24:551 COPY OF SET OF PLANS.
  
  
 PLANNING AND ZONING DEPARTMENT
  
 ***FAILED***
  
 1. PER THE TREE ALTERATION PERMIT ISSUED ON OCTOBER 23,
 2007, ?AN ADDITIONAL SHADE OR FLOWERING TREE SHALL BE
 PLANTED ON THE INTERIOR LANDSCAPE ISLAND OF THE PARKING
 ROW ALONG THE WEST SIDE OF THE RETAIL BUILDING. LIGHT
 POLE SHALL BE RELOCATED SO NOT TO INTERFERE WITH THE
 TREE. THE APPROVED LANDSCAPE PLAN SHALL BE REVISED TO
 REFLECT NEW CONDITIONS.?PROVIDE A REVISED LANDSCAPE
 PLAN REFLECTING THIS CONDITION.
  
 2. ACCORDING TO THE SURVEY, ALONG THE NORTH PROPERTY
 LINE THERE IS A 15 FOOT LANDSCAPE AND SIGN EASEMENT;
 HOWEVER, THE SURVEY ALSO SHOWS A 15 FOOT UTILITY
 EASEMENT.PLEASE PROVIDE THE LOCATION OF THE UTILITY
 LINES TO SHOW THAT THERE IS NO CONFLICT BETWEEN THE
 LINES AND THE PROPOSED LANDSCAPE.
  
 3. IT APPEARS THAT MORE TREES, TO INCLUDE PALM TREES,
 ARE BEING PROVIDED ON THE SITE THAN WHAT IS SHOWN ON
 THE APPROVED LANDSCAPE PLANS; HOWEVER, THE LANDSCAPE
 CODE DATA HAS NOT BEEN UPDATED TO REFLECT THE NEW TREE
 QUANTITIES.PLEASE REVISE.NOTE: STAFF IS IN FAVOR OF
 THE PROVISION OF ADDITIONAL TREES.
  
 4. IT APPEARS THAT FOUR (4) OF THE REQUIRED FLOWERING
 TREES ARE BEING SUBSTITUTED WITH PALM TREES.THE
 LANDSCAPE PLAN SHALL SHOW THE RATIO OF SUBSTITUTION OF
 PALM TREES.PLEASE NOTE THAT PER SECTION 94-442(C) OF
 THE ZONING AND LAND DEVELOPMENT REGULATIONS, PALM TREES
 MAY BE SUBSTITUTED FOR NOT MORE THAN 35 PERCENT OF THE
 SHADE OR FLOWERING TREES REQUIRED.PLEASE PROVIDE A
 TABLE TO SHOW THIS.
  
 5. PLEASE NOTE THAT ALL SIGNS SHALL BE APPROVED ON A
 SEPARATE PERMIT.
  
 6. A NOTARIZED LETTER WAIVING THE WALL REQUIREMENT FROM
 THE RESIDENTIAL PROPERTY OWNER(S) WEST OF THE SITE HAS
 NOT BEEN SUBMITTED TO THE PLANNING AND ZONING
 DEPARTMENT.THEREFORE, A WALL SHALL BE PROVIDED ALONG
 THE WEST PROPERTY LINE.ALL WALLS/FENCES SHALL BE
 APPROVED ON A SEPARATE PERMIT.
  
 7. PLEASE NOTE THAT AN IRRIGATION PLAN SHALL BE
 SUBMITTED WITH THE IRRIGATION PERMIT.
  
 COMMENTS/QUESTIONS, CONTACT ANDREINA DAVILA Q. OR ERIC
 SCHNEIDER, PRINCIPAL PLANNER, AT 822-1435.