| Plan Review Stops For Permit 07120174 |
| Review Stop |
AD |
ADDRESSING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-28 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-01-28 |
Time |
09:12 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-01-28 |
Time |
09:12 |
Sent To |
|
|
| Notes |
| 2008-01-28 09:14:36 | LOCATION WORK TO BE DONE FOR THE ENTIRE STRUCTURE , | | | ISSUE CLARIFIED ON JAN 25TH BY THE AFFINITI ARCHITECTS | | | @ 561-750-0445, EXT. | | | 117,[email protected] . | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
AD |
ADDRESSING |
| Rev No |
1 |
Status |
F |
Date |
2008-01-25 |
|
|
Cont ID |
|
| Sent By |
lursu |
Date |
2008-01-25 |
Time |
08:00 |
Rev Time |
0.00 |
| Received By |
lursu |
Date |
2008-01-25 |
Time |
08:00 |
Sent To |
|
|
| Notes |
| 2008-01-25 08:01:22 | PLEASE SPECIFY THE WORK LOCATION , WHICH FLOOR OR UNIT | | | WILL BE UNDER IMPROVEMENT? | | | | | | QUESTIONS/COMMENTS | | | | | | LACRAMIOARA URSU | | | MIS - GIS SUPPORT SPECIALIST | | | CITY OF WEST PALM BEACH | | | OFFICE:822-1239 | | | FAX: 822-1249 | | | E-MAIL:[email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
P |
Date |
2008-03-19 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-03-19 |
Time |
10:26 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-03-19 |
Time |
10:26 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-02-12 |
Time |
11:01 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-02-12 |
Time |
11:01 |
Sent To |
|
|
| Notes |
| 2008-02-12 11:05:37 | ****CORRECTIONS**** (REVISED 2/22/08) | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* | | | CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC | | | FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1. ADDRESSED. | | | | | | 2. ADDRESSED; 2/22/08. | | | | | | 3.SUBMIT PRODUCT APPROVALS FOR THE GREENHECK ESD 603D | | | LOUVER (SPECIFIED ON MECHANICAL PLAN), STOREFRONT, | | | OVERHEAD DOORS. | | | | | | SHOPS FOR THE LOUVER WAS SUBMITTED WHICH REFERS TO A | | | MIAMIDADE NOA.NO OTHER INFORMATION PROVIDED.PLEASE | | | SUBMIT PRODUCT APPROVALS FOR LOUVERS, STOREFRONT, | | | OVERHEAD DOORS, FAC9B72.PLEASE INCLUDE FLORIDA STATE | | | PRODUCT APPROVALS (WWW.FLORIDABUILDING.ORG) AND THE | | | ASSOCIATED DOCUMENTATION (EVALUATION REPORT AND | | | INSTALLATION INSTRUCTIONS OR THE MIAMIDADE NOA). | | | | | | 4.PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF | | | RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | | FBC*106.3.3. | | | | | | ARCHITECT REVIEWED LOUVER SHOPS, BUT PLEASE ALSO HAVE | | | THE STOREFRONT AND OVERHEAD DOORS REVIEWED PRIOR TO | | | SUBMITTAL. | | | | | | 5.ADDRESSED. | | | | | | NEW COMMENT: | | | | | | 6.THE NEW SHEETS LACK A DATE AT THE ARCHITECT'S | | | SIGNATURE AND SEAL.PLEASE SEE FS481 AND FAC61G16-23; | | | ALSO THE PRINTED NAME OF THE PERSON SEALING THE PLAN IS | | | REQUIRED TO BE ON EACH SHEET.PLEASE INCLUDE REQUIRED | | | INFORMATION WHEN RESUBMITTING. |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-11 |
Time |
11:40 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-11 |
Time |
11:40 |
Sent To |
|
|
| Notes |
| 2008-01-11 11:47:10 | ****CORRECTIONS**** | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | 561-805-6724 [email protected] | | | | | | FBCFLORIDA BUILDING CODE 2004 | | | FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING | | | CODE | | | FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL | | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 | | | | | | FAC FLORIDA ADMINISTRATIVE CODE | | | FSFLORIDA STATUTE | | | | | | 1.BUSINESS OCCUPANCY IS DECLARED; PLEASE REVISE TO | | | INCLUDE S2 FOR THE ENCLOSED PARKING GARAGE, FBC311.3. | | | | | | 2.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3. | | | | | | 3.SUBMIT PRODUCT APPROVALS FOR THE GREENHECK ESD 603D | | | LOUVER (SPECIFIED ON MECHANICAL PLAN), STOREFRONT, | | | OVERHEAD DOORS. | | | | | | 4.PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF | | | RECORD (SHOP DRAWING REVIEW STAMP OR LETTER), | | | FBC*106.3.3. | | | | | | 5.DECLARE GOVERNING CODE, INCLUDING 2007 AMENDMENTS | | | (EFFECTIVE JULY 1, 2007). | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
P |
Date |
2008-01-24 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-01-24 |
Time |
16:16 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-01-24 |
Time |
16:16 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-21 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-21 |
Time |
12:27 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-20 |
Time |
20:05 |
Sent To |
|
|
| Notes |
| 2007-12-21 14:19:05 | NOTE ADDED 12/21, | | | | | | DOES BUILDING CONTAIN A FIRE ALARM SYSTEM? | | | IF SO, PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR | | | MINIMUM LEVELS FOR STROBE AND HORN DEVICES FOR ADA | | | COMPLIANCE. | | 2007-12-21 12:27:43 | ** DENIED ** | | | | | | | | | | | | 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES | | | ARE LISTED ON THE ELECTRICAL PLANS. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | 2002 NFPA-72 (WHERE APPLICABLE) | | | | | | 2) NOTE: PLEASE PROVIDE COMPLETE DETAILS AND | | | INFORMATION FOR THE COMPLETE LIGHTING CONTROL SYSTEM. | | | PLANS INDICATE THERE WILL BE A LUTRON XPS PANEL HOWEVER | | | NO PANEL WAS SHOWN, NO DETAIL, NO SCHEDULING ETC. | | | PLEASE SEE SOME AREAS/ROOMS WHICH ARE NOT SHOWING ANY | | | LIGHTING CONTROLS. PLEASE SEE FOR EXAMPLE. ROOMS 137, | | | 138, ACCENT LIGHTING ETC. | | | 13-415.1.ABC.1.1, .1.2 AND .1.3. | | | | | | 3) NOTE: PLEASE SPECIFY THE METHOD OF LIGHTING BEING | | | DESIGNED PER 13-415.2. PLANS APPEARS TO SHOW TABLE | | | *C*? | | | PLEASE VERIFY THE LIGHTING LEGEND AS THERE ARE FIXTURES | | | ON TABLE WITH OUT DESIGNATIONS AFTER *F* FIXTURE AND | | | NOT LOCATED ON PLANS. | | | | | | 4) NOTE: PLEASE SEE THE NEW SERVICE MAIN/METERAS | | | SHOWN IS NOT PERMITTED PER 230.2. | | | PLEASE SEE 230.2 AS THIS DOES NOT FALL UNDER EXCEPTION | | | TO PERMIT A SEPARATE METER FOR THE SINGLE TENANT. | | | PLEASE CONTACT THIS OFFICE TO GO OVER IF NEEDED OR | | | REVISE PLANS ACCORDINGLY. | | | | | | 5) NOTE: PLEASE PROVIDE A SCHEDULE FOR THE EXISTING MDP | | | SHOWING THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES | | | FOR PANELS. | | | 240.4, 310.16 | | | (NEED TO VERIFY FOR CODE COMPLIANCE AND LIFE SAFETY) | | | FBC ADMIN 106.1.2 | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] | | 2007-12-20 20:05:41 | 2007-12-20 20:05:41 | | | IN ELEC FOR REVIEW |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-03-19 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-19 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-19 |
Time |
18:55 |
Sent To |
|
|
| Notes |
| 2008-03-19 19:19:14 | *****APPROVED***** | | | | | | THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE | | | BEEN ADDRESSED;PLAN SHEETS A4.0, A5.0, E-2, AND FS-1 | | | & FS-2 WERE STAMPED, INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-02-06 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-02-06 |
Time |
19:19 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-02-06 |
Time |
18:51 |
Sent To |
|
|
| Notes |
| 2008-02-06 19:13:17 | *****UNSAT***** | | | | | | THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE | | | PLAN REVIEW STILL NEED TO BE ADDRESSED: | | | | | | | | | 08.YOUR RESPONSE INDICATED THAT THIS BUILDING DOES | | | HAVE A FIRE ALARM SYSTEM.PLEASE SHOW A LAYOUT OF THE | | | FIRE ALARM DEVICES FOR THIS SITE. | | | | | | 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL | | | FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER | | | PIPE APPEAR TO BE THE SAME. | | | | | | 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER | | | EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS | | | REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON | | | SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT | | | SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET | | | FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT | | | CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE | | | GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-01-02 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-02 |
Time |
16:36 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-02 |
Time |
13:06 |
Sent To |
|
|
| Notes |
| 2008-01-02 13:54:52 | *****DENIED***** | | | | | | | | | 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 02.THE SCOPE OF WORK SHALL NO NOT HINDER OR INTERFERE | | | WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR | | | VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE | | | LANES). | | | | | | 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS | | | SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY | | | AS NECESSARY FOR SAFE OPERATION. | | | | | | 04.WILL THE BUILDING OR PORTION OF THE BUILDING BE | | | OCCUPIED DURING THE SCOPE OF WORK?IF THE BUILDING OR | | | PORTION OF THE BUIDLING IS TO BE OCCUPIED DURING THIS | | | SCOPE OF WORK, THIS WILL DONE ONLY WHERE REQUIRED MEANS | | | OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN | | | PLACE AND MAINTAINED. | | | | | | 05.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.AMEND | | | SHEET A-4.0 TO REFLECT AS SUCH. | | | | | | 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A | | | 5.0), DISPLAY/SHOW THE NUMERICAL ADDRESS FOR THIS | | | BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS | | | SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE | | | FRONTING OR FACING UPON THE STREET OR PRINCIPAL | | | VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE READILY | | | VISIBLE TO APPROACHING VEHICLES.ALSO, THE NUMBERS | | | SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1" | | | IN WIDTH. | | | | | | 07.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE | | | REFERENCED. | | | | | | 08.IT IS NOT INDICATED IF THIS BUILDING HAS A FIRE | | | ALARM SYSTEM OR NOT.HOW IS THE FIRE DEPARTMENT | | | NOTIFIED IF THE ACTIVATION OF OF A FIRE SPRINKLER | | | OCCURS DURING NON-BUSINESS HOURS? | | | | | | 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL | | | FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER | | | APPEAR TO BE THE SAME. | | | | | | 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER | | | EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS | | | REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON | | | SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT | | | SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET | | | FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT | | | CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE | | | GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND. | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE | | | LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-03 |
Time |
12:29 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-03 |
Time |
12:29 |
Sent To |
|
|
| Notes |
| 2008-03-03 12:31:43 | TO "COMM" BD#10 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-01-17 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-17 |
Time |
16:44 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2008-01-17 |
Time |
16:44 |
Sent To |
|
|
| Notes |
| 2008-01-17 16:51:04 | TO "COMM" BD#36 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-11 |
|
|
Cont ID |
|
| Sent By |
shill |
Date |
2008-01-11 |
Time |
11:47 |
Rev Time |
0.00 |
| Received By |
shill |
Date |
2007-12-07 |
Time |
11:04 |
Sent To |
|
|
| Notes |
| 2007-12-07 11:07:41 | TO "COMM" BD#56 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
P |
Date |
2008-03-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-03-22 |
Time |
14:58 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-03-22 |
Time |
14:37 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-11 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2008-02-11 |
Time |
18:17 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2008-02-11 |
Time |
16:52 |
Sent To |
|
|
| Notes |
| 2008-02-11 18:17:32 | REVIEW #: 2ND | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. | | | | | | 1. THIS APPEARS TO BE A LEVEL 3 ALTERATION IN | | | ACCORDANCE WITH FBC, EB 305.1. SEE BUILDING PLAN REVIEW | | | COMMENTS. | | | | | | 2. OK | | | | | | 3. THERE IS NO INDICATION THAT THE DUCT SMOKE DETECTORS | | | WILL BE TIED INTO THE BUILDING FIRE ALARM SYSTEM AS | | | REQUIRED BY FBC, M 606.4.1. THERE IS NO REQUIREMENT FOR | | | THE DETECTORS TO BE INTERCONNECTED OR FOR ALL DETECTORS | | | TO SHUT DOWN AT ONCE, BUT THIS CONFIGURATION IS | | | ACCEPTABLE AS A DESIGN CHOICE. | | | | | | 4. OK | | | | | | 5. NOTE #28: THIS NOTE IS NOT SUFFICIENT TO DEMONSTRATE | | | CODE COMPLIANCE. IF THERE IS A SPRAY FOAM PLASTIC | | | INSULATION WHICH IS TESTED AND LISTED FOR USE IN A | | | PLENUM, PLEASE SUBMIT THE DOCUMENTATION FOR REVIEW | | | PRIOR TO PERMIT ISSUANCE. FBC, M 60.2.1.5 AND FBC | | | 2603.4. | | | | | | 6. OK | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-22 |
|
|
Cont ID |
|
| Sent By |
rregueir |
Date |
2007-12-22 |
Time |
13:11 |
Rev Time |
0.00 |
| Received By |
rregueir |
Date |
2007-12-22 |
Time |
09:43 |
Sent To |
|
|
| Notes |
| 2007-12-22 13:10:59 | REVIEW #: 1ST | | | ACTION: DENIED | | | | | | FBC 2004 CODE FAMILY W/ 2007 REVISIONS | | | FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH | | | | | | 1. EXISTING BUILDING: THE LEVEL OF ALTERATION IS NOT | | | DECLARED ON PLANS. THE DESIGN PROFESSIONAL OR OWNER | | | MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION | | | PURSUANT TO SECTIONS 303, 304 AND 305 OF THIS CODE IN | | | ACCORDANCE WITH FBC, EB 301.5. FOR THE PURPOSE OF | | | MECHANICAL REVIEW THE PROPOSED SCOPE OF WORK WILL BE | | | CONSIDERED A LEVEL 3 ALTERATION AS DEFINED IN FBC, EB | | | 305.1. LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE | | | PROVISIONS OF CHAPTERS 5 AND 6 FOR LEVEL 1 AND 2 | | | ALTERATIONS, RESPECTIVELY, AS WELL AS THE PROVISIONS OF | | | CHAPTER 7 IN ACCORDANCE WITH FBC, EB 305.2. | | | | | | 2. OUTSIDE AIR CALCULATIONS HAVE NOT BEEN PROVIDED. ALL | | | RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL BE | | | PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR | | | EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE, | | | MECHANICAL. SHOW COMPLIANCE WITH FBC, M 403.3 OR ASHRAE | | | 62.1-2004 FOR ALL HABITABLE SPACES IN ACCORDANCE WITH | | | FBC, EB 609.1. | | | | | | 3. HVAC GENERAL NOTE #27 ON M-2: FAN SHUT-DOWN BY SMOKE | | | DETECTOR IS REQUIRED FOR ALL AIR HANDLERS IN THIS SPACE | | | SINCE ALL UNITS SHARE A COMMON RETURN PLENUM IN | | | ACCORDANCE WITH FBC, M 606.2.2. SMOKE DETECTORS SHALL | | | BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN | | | ACCORDANCE WITH FBC, M 606.4.1. | | | | | | 4. FIRE DAMPER DETAIL ON M-2: FIRE DAMPERS LOCATED | | | WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER?S | | | INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M | | | 607.2. | | | NOTE: IT IS LIKELY THAT MANUFACTURER?S INSTRUCTIONS | | | WILL NOT CORRESPOND WITH THE DETAIL ON PLANS. | | | | | | 5. PG A-3.2: ROOF DECK NOTE AT WALL SECTIONS CALLS FOR | | | ICYNENE INSULATION TO BE APPLIED TO THE UNDERSIDE OF | | | THE ROOF DECK. THIS SPACE IS BEING USED AS A RETURN AIR | | | PLENUM. FOAM PLASTIC INSULATION (SUCH AS ICYNENE) USED | | | IN A PLENUM SHALL BE IN COMPLIANCE WITH FBC, M | | | 602.2.1.5. SEE ALSO FBC 2603.4. | | | | | | 6. PG M-2 GARAGE VENTILATION: THE FAN IS SHOWN TO BE | | | OPERATED BY A CO2 SENSOR SET AT 900 PARTS PER MILLION | | | (PPM). MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED | | | PARKING GARAGES ARE NOT REQUIRED TO OPERATE | | | CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE | | | AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF | | | CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY | | | APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH | | | FBC, M 404.1. ALSO, AUTOMATIC OPERATION OF THE SYSTEM | | | SHALL NOT REDUCE THE VENTILATION RATE BELOW0.05 CFM | | | PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL | | | BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM | | | PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M | | | 404.2. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] | | | |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-20 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-03-20 |
Time |
13:20 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-03-20 |
Time |
13:20 |
Sent To |
|
|
| Notes |
| 2008-03-20 13:30:56 | ****************PROVISO**************** | | | NOTE: THE BACKFLOW PREVENTER FOR THE ICE MAKER SHALL BE | | | LOCATED ON THE OUTLET SIDE OF THE ICE MAKER SHUT OFF | | | VALVE. PER FBC PLUMBING SECTION 601.1 SCOPE AND SECTION | | | 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS. | | | | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | (561) 805-6730 | | | FAX (561) 805-6731 | | | E-MAIL: [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-21 |
|
|
Cont ID |
|
| Sent By |
mperson |
Date |
2008-02-21 |
Time |
09:11 |
Rev Time |
0.00 |
| Received By |
mperson |
Date |
2008-02-21 |
Time |
09:11 |
Sent To |
PC |
|
| Notes |
| 2008-02-21 11:59:20 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH | | | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO | | | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE | | | (F.A.C.), AND FLORIDA STATUTES (F.S.). | | | | | | PLUMBING PLAN REVIEW: | | | DENIED 2ND TIME: | | | | | | THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH | | | THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S | | | RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW COMMENTS | | | WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW | | | COMMENTS. | | | | | | 1. **RESPONSE NOTED, HOWEVER WATER COOLERS ARE NOT | | | COMPLIANT** | | | SHEET A-3.0 PER TABLE 403.1.2 DRINKING FOUNTAINS ARE | | | REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING | | | FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTION 11-4.15 AND ALL SUBSECTIONS. | | | | | | **PER FBC PLUMBING TABLE 403.1.2 WITH AN OCCUPANCY | | | LOAD OF 146 PERSONS BEING INDICATED ON SHEET A-1.0, A | | | MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED AND | | | SHALL BE COMPLIANT WITH CHAPTER 11 FLORIDA | | | ACCESSIBILITY CODE SECTION 11-4.15 AND ALL | | | SUBSECTIONS. | | | | | | | | | **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS | | | (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING | | | INFORMATION) | | | 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET | | | MAXIMUM. | | | 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN | | | TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT | | | OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN | | | ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3" | | | OF THE FRONT OF FOUNTAIN. | | | 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE | | | MOUNTED NEAR FRONT EDGE. | | | 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR | | | SPACE. | | | 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS | | | PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN | | | WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS | | | IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE | | | TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS | | | CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR | | | BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED | | | ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR). | | | | | | 2. **RESPONSE NOTED, HOWEVER SEE NOTE: BELOW PREVIOUS | | | COMMENT** | | | SHEET A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE, | | | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.24 AND ALL SUB SECTIONS. | | | | | | **NOTE: SHEET A-3.2 DETAIL 2, KITCHEN: PER CHAPTER 11 | | | FLORIDA ACCESSIBILITY CODE PLEASE SHOW COMPLIANCE TO | | | 11-4.24 SUBSECTIONS. | | | | | | **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE | | | FOLLOWING INFORMATION) | | | 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP. | | | 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR | | | SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE | | | SINK.**CLEARLY INDICATE THAT CLEAR FLOOR SPACE SHALL | | | EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK. 11-4.24.7 | | | FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR ELECTRONICALLY | | | CONTROLLED ARE ACCEPTABLE DESIGNS.**CLEARLY INDICATE | | | FAUCET TYPE. | | | | | | 3. **OK** COMMENT ADDRESSED. | | | | | | 4. **OK** COMMENT ADDRESSED. | | | | | | 5. **COMMENT RESPONSE NOTED, HOWEVER SEE NOT: BELOW | | | PREVIOUS COMMENT** | | | SHEET P-1 SHOW THE LOCATION OF THE SANITARY BUILDING | | | DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE | | | CONNECTED TO. SECTION 106.1.2 ADDITIONAL DATA. | | | | | | **NOTE: SHEET P-1 IS INDICATING THE SANITARY WASTE, | | | VENT AND POTABLE WATER TO THE SINK AS EXISTING (REMOVED | | | SINK) HOWEVER THERE IS NO INDICATION ON THE DEMO PLAN | | | SHEET A-2.0 THAT THERE WAS AN EXISTING SINK LOCATED IN | | | THIS AREA. PLEASE CLARIFY THIS. PER CITY OF WPB | | | AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON | | | CONSTRUCTION DOCUMENTS AND SECTION 106.1.2 ADDITIONAL | | | DATA. | | | | | | **THE FOLLOWING IS A NEW COMMENT** | | | | | | 6. SHEETS A-1.0, A-3.0, A-3.1, A-3.2, A-4.0 AND A-5.0 | | | ARE MISSING A DATE AT THE ARCHITECTS SIGNATURE AND SEAL | | | AS WELL AS THE PRINTED NAME AND LICENSE NUMBER OF THE | | | PERSON SIGNING AND SEALING EACH SHEET, ALSO SHEETS | | | A-2.0 AND A-6.0 ARE MISSING THE PRINTED NAME OF THE | | | PERSON RESPONSIBLE OF SIGNING AND SEALING SHEETS. PER | | | FS 481 AND FAC61G16-23. | | | | | | ********IMPORTANT INFORMATION******** | | | WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION | | | AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A | | | TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT | | | NUMBER, WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | | CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | END OF COMMENTS: | | | | | | REVIEW BY: MIKE PERSON | | | PLUMBING PLANS EXAMINER | | | PHONE= (561) 805-6730 | | | FAX= (561) 805-6731 | | | E-MAIL= [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-20 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-20 |
Time |
16:35 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-20 |
Time |
16:35 |
Sent To |
|
|
| Notes |
| 2007-12-20 16:40:52 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FBC-2004 CHAPTER 11 | | | | | | 1. SHT A-3.0 PER TABLE 403.1 2 DRINKING FOUNTAINS ARE | | | REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING | | | FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH | | | SECTION 11-4.15 AND ALL SUBSECTIONS. | | | | | | 2. SHT A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE. | | | PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION | | | 11-4.24 AND ALL SUBSECTIONS. | | | | | | 3. SHT A-3.1 DETAIL 5. THE WATER CLOSET SHALL BE 1'6" | | | OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE | | | FIGURE 11-28. | | | | | | 4. SHT A-3.1 DETAIL 1 THE ACCESSIBLE WATER CLOSETS | | | SHALL BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE | | | FIXTURE. SEE FIG. 11-28. | | | | | | 5. SHT P-1 SHOW THE LOCATION OF THE SANITARY BUILDING | | | DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE | | | CONNECTED TO. SECTION 106.1.2. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, | | | IDENTIFYING THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] | | | | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2008-03-03 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-03 |
Time |
13:25 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-03 |
Time |
13:25 |
Sent To |
|
|
| Notes |
| 2008-03-03 13:26:18 | ***APPROVED - RESUB #2 (RESTAMPED PLANS)*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
P |
Date |
2008-01-23 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-01-23 |
Time |
16:10 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-01-23 |
Time |
16:09 |
Sent To |
|
|
| Notes |
| 2008-01-23 16:10:16 | ***APPROVED - RESUB #1*** |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-11 |
Time |
10:13 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-11 |
Time |
10:12 |
Sent To |
|
|
| Notes |
| 2007-12-11 10:24:55 | ***FAILED*** | | | | | | | | | 1)PROVIDE A STRIPING DETAIL SHOWING COMPLIANCE WITH | | | THE PROVIDED SAMPLE DETAIL (SEE PERMIT PACKAGE). | | | | | | 2)SITE PLAN SHOWS A CONCRETE SIGN.IS THIS PROPOSED | | | OR EXISTING?PLEASE CLARIFY. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|