Plan Review Details - Permit 07120174
Plan Review Stops For Permit 07120174
Review Stop AD ADDRESSING
Rev No 2 Status P Date 2008-01-28 Cont ID  
Sent By lursu Date 2008-01-28 Time 09:12 Rev Time 0.00
Received By lursu Date 2008-01-28 Time 09:12 Sent To  
Notes
2008-01-28 09:14:36LOCATION WORK TO BE DONE FOR THE ENTIRE STRUCTURE ,
 ISSUE CLARIFIED ON JAN 25TH BY THE AFFINITI ARCHITECTS
 @ 561-750-0445, EXT.
 117,[email protected] .
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop AD ADDRESSING
Rev No 1 Status F Date 2008-01-25 Cont ID  
Sent By lursu Date 2008-01-25 Time 08:00 Rev Time 0.00
Received By lursu Date 2008-01-25 Time 08:00 Sent To  
Notes
2008-01-25 08:01:22PLEASE SPECIFY THE WORK LOCATION , WHICH FLOOR OR UNIT
 WILL BE UNDER IMPROVEMENT?
  
 QUESTIONS/COMMENTS
  
 LACRAMIOARA URSU
 MIS - GIS SUPPORT SPECIALIST
 CITY OF WEST PALM BEACH
 OFFICE:822-1239
 FAX: 822-1249
 E-MAIL:[email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status P Date 2008-03-19 Cont ID  
Sent By shill Date 2008-03-19 Time 10:26 Rev Time 0.00
Received By shill Date 2008-03-19 Time 10:26 Sent To  
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-12 Cont ID  
Sent By shill Date 2008-02-12 Time 11:01 Rev Time 0.00
Received By shill Date 2008-02-12 Time 11:01 Sent To  
Notes
2008-02-12 11:05:37****CORRECTIONS**** (REVISED 2/22/08)
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL FBC*
 CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 FAC
 FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1. ADDRESSED.
  
 2. ADDRESSED; 2/22/08.
  
 3.SUBMIT PRODUCT APPROVALS FOR THE GREENHECK ESD 603D
 LOUVER (SPECIFIED ON MECHANICAL PLAN), STOREFRONT,
 OVERHEAD DOORS.
  
 SHOPS FOR THE LOUVER WAS SUBMITTED WHICH REFERS TO A
 MIAMIDADE NOA.NO OTHER INFORMATION PROVIDED.PLEASE
 SUBMIT PRODUCT APPROVALS FOR LOUVERS, STOREFRONT,
 OVERHEAD DOORS, FAC9B72.PLEASE INCLUDE FLORIDA STATE
 PRODUCT APPROVALS (WWW.FLORIDABUILDING.ORG) AND THE
 ASSOCIATED DOCUMENTATION (EVALUATION REPORT AND
 INSTALLATION INSTRUCTIONS OR THE MIAMIDADE NOA).
  
 4.PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 ARCHITECT REVIEWED LOUVER SHOPS, BUT PLEASE ALSO HAVE
 THE STOREFRONT AND OVERHEAD DOORS REVIEWED PRIOR TO
 SUBMITTAL.
  
 5.ADDRESSED.
  
 NEW COMMENT:
  
 6.THE NEW SHEETS LACK A DATE AT THE ARCHITECT'S
 SIGNATURE AND SEAL.PLEASE SEE FS481 AND FAC61G16-23;
 ALSO THE PRINTED NAME OF THE PERSON SEALING THE PLAN IS
 REQUIRED TO BE ON EACH SHEET.PLEASE INCLUDE REQUIRED
 INFORMATION WHEN RESUBMITTING.

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-11 Cont ID  
Sent By shill Date 2008-01-11 Time 11:40 Rev Time 0.00
Received By shill Date 2008-01-11 Time 11:40 Sent To  
Notes
2008-01-11 11:47:10****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBCFLORIDA BUILDING CODE 2004
 FBC EBFLORIDA BUILDING CODE 2004 EXISTING BUILDING
 CODE
 FBC RFLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 FAC FLORIDA ADMINISTRATIVE CODE
 FSFLORIDA STATUTE
  
 1.BUSINESS OCCUPANCY IS DECLARED; PLEASE REVISE TO
 INCLUDE S2 FOR THE ENCLOSED PARKING GARAGE, FBC311.3.
  
 2.DECLARE LEVEL OF ALTERATION, FBC EB CHAPTER 3.
  
 3.SUBMIT PRODUCT APPROVALS FOR THE GREENHECK ESD 603D
 LOUVER (SPECIFIED ON MECHANICAL PLAN), STOREFRONT,
 OVERHEAD DOORS.
  
 4.PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER OF
 RECORD (SHOP DRAWING REVIEW STAMP OR LETTER),
 FBC*106.3.3.
  
 5.DECLARE GOVERNING CODE, INCLUDING 2007 AMENDMENTS
 (EFFECTIVE JULY 1, 2007).
  

Review Stop E ELECTRICAL
Rev No 2 Status P Date 2008-01-24 Cont ID  
Sent By dpalmer Date 2008-01-24 Time 16:16 Rev Time 0.00
Received By dpalmer Date 2008-01-24 Time 16:16 Sent To  
Notes
***NONE***

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-21 Cont ID  
Sent By dpalmer Date 2007-12-21 Time 12:27 Rev Time 0.00
Received By dpalmer Date 2007-12-20 Time 20:05 Sent To  
Notes
2007-12-21 14:19:05NOTE ADDED 12/21,
  
 DOES BUILDING CONTAIN A FIRE ALARM SYSTEM?
 IF SO, PLEASE SEE FBC 11-4.28.1,.2 AND .3(4) FOR
 MINIMUM LEVELS FOR STROBE AND HORN DEVICES FOR ADA
 COMPLIANCE.
2007-12-21 12:27:43** DENIED **
  
  
  
 1) NOTE: PLEASE BE SURE THE FOLLOWING RELEVANT CODES
 ARE LISTED ON THE ELECTRICAL PLANS.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
 2002 NFPA-72 (WHERE APPLICABLE)
  
 2) NOTE: PLEASE PROVIDE COMPLETE DETAILS AND
 INFORMATION FOR THE COMPLETE LIGHTING CONTROL SYSTEM.
 PLANS INDICATE THERE WILL BE A LUTRON XPS PANEL HOWEVER
 NO PANEL WAS SHOWN, NO DETAIL, NO SCHEDULING ETC.
 PLEASE SEE SOME AREAS/ROOMS WHICH ARE NOT SHOWING ANY
 LIGHTING CONTROLS. PLEASE SEE FOR EXAMPLE. ROOMS 137,
 138, ACCENT LIGHTING ETC.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 3) NOTE: PLEASE SPECIFY THE METHOD OF LIGHTING BEING
 DESIGNED PER 13-415.2. PLANS APPEARS TO SHOW TABLE
 *C*?
 PLEASE VERIFY THE LIGHTING LEGEND AS THERE ARE FIXTURES
 ON TABLE WITH OUT DESIGNATIONS AFTER *F* FIXTURE AND
 NOT LOCATED ON PLANS.
  
 4) NOTE: PLEASE SEE THE NEW SERVICE MAIN/METERAS
 SHOWN IS NOT PERMITTED PER 230.2.
 PLEASE SEE 230.2 AS THIS DOES NOT FALL UNDER EXCEPTION
 TO PERMIT A SEPARATE METER FOR THE SINGLE TENANT.
 PLEASE CONTACT THIS OFFICE TO GO OVER IF NEEDED OR
 REVISE PLANS ACCORDINGLY.
  
 5) NOTE: PLEASE PROVIDE A SCHEDULE FOR THE EXISTING MDP
 SHOWING THE OVER CURRENT PROTECTION AND CONDUCTOR SIZES
 FOR PANELS.
 240.4, 310.16
 (NEED TO VERIFY FOR CODE COMPLIANCE AND LIFE SAFETY)
 FBC ADMIN 106.1.2
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]
2007-12-20 20:05:412007-12-20 20:05:41
 IN ELEC FOR REVIEW

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-03-19 Cont ID  
Sent By mawillia Date 2008-03-19 Time 19:19 Rev Time 0.00
Received By mawillia Date 2008-03-19 Time 18:55 Sent To  
Notes
2008-03-19 19:19:14*****APPROVED*****
  
 THE COMMENTS FROM THE PREVIOUS FIRE PLAN REVIEWS HAVE
 BEEN ADDRESSED;PLAN SHEETS A4.0, A5.0, E-2, AND FS-1
 & FS-2 WERE STAMPED, INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-02-06 Cont ID  
Sent By mawillia Date 2008-02-06 Time 19:19 Rev Time 0.00
Received By mawillia Date 2008-02-06 Time 18:51 Sent To  
Notes
2008-02-06 19:13:17*****UNSAT*****
  
 THE FOLLOWING COMMENTS TAKEN FROM THE PREVIOUS FIRE
 PLAN REVIEW STILL NEED TO BE ADDRESSED:
  
  
 08.YOUR RESPONSE INDICATED THAT THIS BUILDING DOES
 HAVE A FIRE ALARM SYSTEM.PLEASE SHOW A LAYOUT OF THE
 FIRE ALARM DEVICES FOR THIS SITE.
  
 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL
 FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER
 PIPE APPEAR TO BE THE SAME.
  
 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER
 EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS
 REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON
 SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT
 SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET
 FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT
 CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE
 GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-02 Cont ID  
Sent By mawillia Date 2008-01-02 Time 16:36 Rev Time 0.00
Received By mawillia Date 2008-01-02 Time 13:06 Sent To  
Notes
2008-01-02 13:54:52*****DENIED*****
  
  
 01.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 02.THE SCOPE OF WORK SHALL NO NOT HINDER OR INTERFERE
 WITH EMERGENCY RESPONSE ACCESS TO THE SAID PROPERTY OR
 VICINITY THEREOF (INCLUDING STREETS, ALLEYS, FIRE
 LANES).
  
 03.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS
 SHALL BE REMOVED FROM THE SITE DAILY OR MORE FREQUENTLY
 AS NECESSARY FOR SAFE OPERATION.
  
 04.WILL THE BUILDING OR PORTION OF THE BUILDING BE
 OCCUPIED DURING THE SCOPE OF WORK?IF THE BUILDING OR
 PORTION OF THE BUIDLING IS TO BE OCCUPIED DURING THIS
 SCOPE OF WORK, THIS WILL DONE ONLY WHERE REQUIRED MEANS
 OF EGRESS AND REQUIRED FIRE PROTECTION FEATURES ARE IN
 PLACE AND MAINTAINED.
  
 05.FIRE EXTINGUISHERS TO BE 2A:10BC RATED.AMEND
 SHEET A-4.0 TO REFLECT AS SUCH.
  
 06.ON THE APPROPIATE EXTERIOR ELEVATION (SHEET A
 5.0), DISPLAY/SHOW THE NUMERICAL ADDRESS FOR THIS
 BUILDING.AS PER WEST PALM BEACH CODE, THE ADDRESS
 SHALL BE POSTED ON THAT PORTION OF THE STRUCTURE
 FRONTING OR FACING UPON THE STREET OR PRINCIPAL
 VEHICULAR ACCESS TO THE PREMISES, SO AS TO BE READILY
 VISIBLE TO APPROACHING VEHICLES.ALSO, THE NUMBERS
 SHALL BE NO LESS THAN 6" IN HEIGHT AND NO LESS THAN 1"
 IN WIDTH.
  
 07.NFPA 101, LIFE SAFETY CODE, 2003 EDITION SHALL BE
 REFERENCED.
  
 08.IT IS NOT INDICATED IF THIS BUILDING HAS A FIRE
 ALARM SYSTEM OR NOT.HOW IS THE FIRE DEPARTMENT
 NOTIFIED IF THE ACTIVATION OF OF A FIRE SPRINKLER
 OCCURS DURING NON-BUSINESS HOURS?
  
 09.ON SHEET FS-1 UNDER THE SYMBOL LEGEND, THE SYMBOL
 FOR THE NEW SPRINKLER PIPE AND THE EXISTING SPRINKLER
 APPEAR TO BE THE SAME.
  
 10.IT IS NOTED ON SHEET FS-1, THAT ALL SPRINKLER
 EQUIPMENT AT THE SITE IS EXISTING - NO MODIFICATIONS
 REQUIRED.HOWEVER, IN THE FIRE SPRINKLER SCHEDULE ON
 SHEET FS-1, THERE ARE 89 NEW SEMI RECESSED PENDENT
 SPRINKLERS WHICH ARE SHOWN IN THE OFFICE AREA ON SHEET
 FS-2 AND ALSO THE REMOVAL OF EXISTING HEADS THAT
 CURRENTLY PROTECT UNDER OVERHEAD DOORS SHOWN IN THE
 GARAGE AREA (SHEET FS-2).PLEASE EXPLAIN OR AMEND.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS, INCLUDE A RESPONSE
 LETTER INDICATING WHERE EACH ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-03 Cont ID  
Sent By adarroug Date 2008-03-03 Time 12:29 Rev Time 0.00
Received By adarroug Date 2008-03-03 Time 12:29 Sent To  
Notes
2008-03-03 12:31:43TO "COMM" BD#10

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-01-17 Cont ID  
Sent By shill Date 2008-01-17 Time 16:44 Rev Time 0.00
Received By shill Date 2008-01-17 Time 16:44 Sent To  
Notes
2008-01-17 16:51:04TO "COMM" BD#36

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-11 Cont ID  
Sent By shill Date 2008-01-11 Time 11:47 Rev Time 0.00
Received By shill Date 2007-12-07 Time 11:04 Sent To  
Notes
2007-12-07 11:07:41TO "COMM" BD#56

Review Stop M MECHANICAL (A/C)
Rev No 3 Status P Date 2008-03-22 Cont ID  
Sent By rregueir Date 2008-03-22 Time 14:58 Rev Time 0.00
Received By rregueir Date 2008-03-22 Time 14:37 Sent To PC
Notes
***NONE***

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-11 Cont ID  
Sent By rregueir Date 2008-02-11 Time 18:17 Rev Time 0.00
Received By rregueir Date 2008-02-11 Time 16:52 Sent To  
Notes
2008-02-11 18:17:32REVIEW #: 2ND
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 1. THIS APPEARS TO BE A LEVEL 3 ALTERATION IN
 ACCORDANCE WITH FBC, EB 305.1. SEE BUILDING PLAN REVIEW
 COMMENTS.
  
 2. OK
  
 3. THERE IS NO INDICATION THAT THE DUCT SMOKE DETECTORS
 WILL BE TIED INTO THE BUILDING FIRE ALARM SYSTEM AS
 REQUIRED BY FBC, M 606.4.1. THERE IS NO REQUIREMENT FOR
 THE DETECTORS TO BE INTERCONNECTED OR FOR ALL DETECTORS
 TO SHUT DOWN AT ONCE, BUT THIS CONFIGURATION IS
 ACCEPTABLE AS A DESIGN CHOICE.
  
 4. OK
  
 5. NOTE #28: THIS NOTE IS NOT SUFFICIENT TO DEMONSTRATE
 CODE COMPLIANCE. IF THERE IS A SPRAY FOAM PLASTIC
 INSULATION WHICH IS TESTED AND LISTED FOR USE IN A
 PLENUM, PLEASE SUBMIT THE DOCUMENTATION FOR REVIEW
 PRIOR TO PERMIT ISSUANCE. FBC, M 60.2.1.5 AND FBC
 2603.4.
  
 6. OK
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-22 Cont ID  
Sent By rregueir Date 2007-12-22 Time 13:11 Rev Time 0.00
Received By rregueir Date 2007-12-22 Time 09:43 Sent To  
Notes
2007-12-22 13:10:59REVIEW #: 1ST
 ACTION: DENIED
  
 FBC 2004 CODE FAMILY W/ 2007 REVISIONS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 1. EXISTING BUILDING: THE LEVEL OF ALTERATION IS NOT
 DECLARED ON PLANS. THE DESIGN PROFESSIONAL OR OWNER
 MUST ELECT ONE OR A COMBINATION OF LEVELS OF ALTERATION
 PURSUANT TO SECTIONS 303, 304 AND 305 OF THIS CODE IN
 ACCORDANCE WITH FBC, EB 301.5. FOR THE PURPOSE OF
 MECHANICAL REVIEW THE PROPOSED SCOPE OF WORK WILL BE
 CONSIDERED A LEVEL 3 ALTERATION AS DEFINED IN FBC, EB
 305.1. LEVEL 3 ALTERATIONS SHALL COMPLY WITH THE
 PROVISIONS OF CHAPTERS 5 AND 6 FOR LEVEL 1 AND 2
 ALTERATIONS, RESPECTIVELY, AS WELL AS THE PROVISIONS OF
 CHAPTER 7 IN ACCORDANCE WITH FBC, EB 305.2.
  
 2. OUTSIDE AIR CALCULATIONS HAVE NOT BEEN PROVIDED. ALL
 RECONFIGURED SPACES INTENDED FOR OCCUPANCY SHALL BE
 PROVIDED WITH NATURAL OR MECHANICAL VENTILATION OR
 EXHAUST IN ACCORDANCE WITH THE FLORIDA BUILDING CODE,
 MECHANICAL. SHOW COMPLIANCE WITH FBC, M 403.3 OR ASHRAE
 62.1-2004 FOR ALL HABITABLE SPACES IN ACCORDANCE WITH
 FBC, EB 609.1.
  
 3. HVAC GENERAL NOTE #27 ON M-2: FAN SHUT-DOWN BY SMOKE
 DETECTOR IS REQUIRED FOR ALL AIR HANDLERS IN THIS SPACE
 SINCE ALL UNITS SHARE A COMMON RETURN PLENUM IN
 ACCORDANCE WITH FBC, M 606.2.2. SMOKE DETECTORS SHALL
 BE CONNECTED TO THE BUILDING FIRE ALARM SYSTEM IN
 ACCORDANCE WITH FBC, M 606.4.1.
  
 4. FIRE DAMPER DETAIL ON M-2: FIRE DAMPERS LOCATED
 WITHIN AIR DISTRIBUTION SYSTEMS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE MANUFACTURER?S
 INSTALLATION INSTRUCTIONS AND LISTING PER FBC, M
 607.2.
 NOTE: IT IS LIKELY THAT MANUFACTURER?S INSTRUCTIONS
 WILL NOT CORRESPOND WITH THE DETAIL ON PLANS.
  
 5. PG A-3.2: ROOF DECK NOTE AT WALL SECTIONS CALLS FOR
 ICYNENE INSULATION TO BE APPLIED TO THE UNDERSIDE OF
 THE ROOF DECK. THIS SPACE IS BEING USED AS A RETURN AIR
 PLENUM. FOAM PLASTIC INSULATION (SUCH AS ICYNENE) USED
 IN A PLENUM SHALL BE IN COMPLIANCE WITH FBC, M
 602.2.1.5. SEE ALSO FBC 2603.4.
  
 6. PG M-2 GARAGE VENTILATION: THE FAN IS SHOWN TO BE
 OPERATED BY A CO2 SENSOR SET AT 900 PARTS PER MILLION
 (PPM). MECHANICAL VENTILATION SYSTEMS FOR ENCLOSED
 PARKING GARAGES ARE NOT REQUIRED TO OPERATE
 CONTINUOUSLY WHERE THE SYSTEM IS ARRANGED TO OPERATE
 AUTOMATICALLY UPON DETECTION OF A CONCENTRATION OF
 CARBON MONOXIDE OF 25 PARTS PER MILLION (PPM) BY
 APPROVED AUTOMATIC DETECTION DEVICES IN ACCORDANCE WITH
 FBC, M 404.1. ALSO, AUTOMATIC OPERATION OF THE SYSTEM
 SHALL NOT REDUCE THE VENTILATION RATE BELOW0.05 CFM
 PER SQUARE FOOT OF THE FLOOR AREA AND THE SYSTEM SHALL
 BE CAPABLE OF PRODUCING A VENTILATION RATE OF 1.5 CFM
 PER SQUARE FOOT OF FLOOR AREA IN ACCORDANCE WITH FBC, M
 404.2.
  
 IF YOU HAVE ANY QUESTIONS PLEASE CONTACT:
 RONALD J. REGUEIRO
 561.805.6719
 [email protected]
  

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-03-20 Cont ID  
Sent By mperson Date 2008-03-20 Time 13:20 Rev Time 0.00
Received By mperson Date 2008-03-20 Time 13:20 Sent To  
Notes
2008-03-20 13:30:56****************PROVISO****************
 NOTE: THE BACKFLOW PREVENTER FOR THE ICE MAKER SHALL BE
 LOCATED ON THE OUTLET SIDE OF THE ICE MAKER SHUT OFF
 VALVE. PER FBC PLUMBING SECTION 601.1 SCOPE AND SECTION
 608.3 DEVICES, APPURTENANCES, APPLIANCES AND APPARATUS.
  
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL: [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-02-21 Cont ID  
Sent By mperson Date 2008-02-21 Time 09:11 Rev Time 0.00
Received By mperson Date 2008-02-21 Time 09:11 Sent To PC
Notes
2008-02-21 11:59:20PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH
 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO
 CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE
 (F.A.C.), AND FLORIDA STATUTES (F.S.).
  
 PLUMBING PLAN REVIEW:
 DENIED 2ND TIME:
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 THE PREVIOUS REVIEW COMMENTS AS WELL AS THE DESIGNER'S
 RESPONSES FOR THE PURPOSE OF CONTINUITY. NEW COMMENTS
 WILL BE SO NOTED FOLLOWING THE PREVIOUS REVIEW
 COMMENTS.
  
 1. **RESPONSE NOTED, HOWEVER WATER COOLERS ARE NOT
 COMPLIANT**
 SHEET A-3.0 PER TABLE 403.1.2 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
  
 **PER FBC PLUMBING TABLE 403.1.2 WITH AN OCCUPANCY
 LOAD OF 146 PERSONS BEING INDICATED ON SHEET A-1.0, A
 MINIMUM OF TWO DRINKING FOUNTAINS ARE REQUIRED AND
 SHALL BE COMPLIANT WITH CHAPTER 11 FLORIDA
 ACCESSIBILITY CODE SECTION 11-4.15 AND ALL
 SUBSECTIONS.
  
  
 **11-4.15 DRINKING FOUNTAINS AND WATER COOLERS
 (ELEVATION DETAIL REQUIRED WITH THE FOLLOWING
 INFORMATION)
 11-4.15.2 SPOUT HEIGHT. SPOUT HEIGHT 36" TO OUTLET
 MAXIMUM.
 11-4.15.3 SPOUT LOCATION. FRONT OF UNIT, WATER FLOW IN
 TRAJECTORY THAT IS PARALLEL OR NEARLY PARALLEL TO FRONT
 OF THE UNIT, WATER FLOW MINIMUM OF 4" HIGH. ON AN
 ACCESSIBLE OVAL OR ROUND BOWL FLOW OF WAER IS WITHIN 3"
 OF THE FRONT OF FOUNTAIN.
 11-4.15.4 CONTROLS. SHALL BE FRONT MOUNTED OR SIDE
 MOUNTED NEAR FRONT EDGE.
 11-4.15.5 CLEARANCES. KNEE 27" HIGH, & 30" X 48" FLOOR
 SPACE.
 11-4.1.3(10)(A) WHERE ONLY ONE DRINKING FOUNTAIN IS
 PROVIDED ON A FLOOR, THERE SHALL BE A DRINKING FOUNTAIN
 WHICH IS ACCESSIBLE TO INDIVIDUALS WHO USE WHEELCHAIRS
 IN ACCORDANCE WITH SECTION 11-4.15 AND ONE ACCESSIBLE
 TO THOSE WHO HAVE DIFFICULTY BENDING OR STOOPING.(THIS
 CAN BE ACCOMMODATED BY THE USE OF A HI-LO FOUNTAIN OR
 BY SUCH OTHER MEANS AS WOULD ACHIEVE THE REQUIRED
 ACCESSIBILITY FOR EACH GROUP ON EACH FLOOR).
  
 2. **RESPONSE NOTED, HOWEVER SEE NOTE: BELOW PREVIOUS
 COMMENT**
 SHEET A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE,
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUB SECTIONS.
  
 **NOTE: SHEET A-3.2 DETAIL 2, KITCHEN: PER CHAPTER 11
 FLORIDA ACCESSIBILITY CODE PLEASE SHOW COMPLIANCE TO
 11-4.24 SUBSECTIONS.
  
 **11-4.24 SINKS (ELEVATION DETAIL REQUIRED WITH THE
 FOLLOWING INFORMATION)
 11-4.24.4 DEPTH. MAXIMUM 6-1/2" DEEP.
 11-4.24.5 CLEAR FLOOR SPACE. 30" X 48" AND CLEAR FLOOR
 SPACE SHALL EXTEND A MAXIMUM OF 19" UNDERNEATH THE
 SINK.**CLEARLY INDICATE THAT CLEAR FLOOR SPACE SHALL
 EXTEND A MAXIMUM OF 19" UNDERNEATH THE SINK. 11-4.24.7
 FAUCETS. LEVER-OPERATED, PUSH-TYPE, OR ELECTRONICALLY
 CONTROLLED ARE ACCEPTABLE DESIGNS.**CLEARLY INDICATE
 FAUCET TYPE.
  
 3. **OK** COMMENT ADDRESSED.
  
 4. **OK** COMMENT ADDRESSED.
  
 5. **COMMENT RESPONSE NOTED, HOWEVER SEE NOT: BELOW
 PREVIOUS COMMENT**
 SHEET P-1 SHOW THE LOCATION OF THE SANITARY BUILDING
 DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE
 CONNECTED TO. SECTION 106.1.2 ADDITIONAL DATA.
  
 **NOTE: SHEET P-1 IS INDICATING THE SANITARY WASTE,
 VENT AND POTABLE WATER TO THE SINK AS EXISTING (REMOVED
 SINK) HOWEVER THERE IS NO INDICATION ON THE DEMO PLAN
 SHEET A-2.0 THAT THERE WAS AN EXISTING SINK LOCATED IN
 THIS AREA. PLEASE CLARIFY THIS. PER CITY OF WPB
 AMENDMENTS TO CHAPTER 1, SECTION 106.1.1 INFORMATION ON
 CONSTRUCTION DOCUMENTS AND SECTION 106.1.2 ADDITIONAL
 DATA.
  
 **THE FOLLOWING IS A NEW COMMENT**
  
 6. SHEETS A-1.0, A-3.0, A-3.1, A-3.2, A-4.0 AND A-5.0
 ARE MISSING A DATE AT THE ARCHITECTS SIGNATURE AND SEAL
 AS WELL AS THE PRINTED NAME AND LICENSE NUMBER OF THE
 PERSON SIGNING AND SEALING EACH SHEET, ALSO SHEETS
 A-2.0 AND A-6.0 ARE MISSING THE PRINTED NAME OF THE
 PERSON RESPONSIBLE OF SIGNING AND SEALING SHEETS. PER
 FS 481 AND FAC61G16-23.
  
 ********IMPORTANT INFORMATION********
 WHEN RESUBMITTING PLANS, PLEASE INDICATE THE REVISION
 AND REMOVE & REPLACE ANY PAGES AS NECESSARY. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER
 PHONE= (561) 805-6730
 FAX= (561) 805-6731
 E-MAIL= [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-20 Cont ID  
Sent By kstevens Date 2007-12-20 Time 16:35 Rev Time 0.00
Received By kstevens Date 2007-12-20 Time 16:35 Sent To  
Notes
2007-12-20 16:40:52DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
  
 1. SHT A-3.0 PER TABLE 403.1 2 DRINKING FOUNTAINS ARE
 REQUIRED. PLEASE INDICATE THE LOCATION OF EACH DRINKING
 FOUNTAIN. SUBMIT A DETAIL SHOWING COMPLIANCE WITH
 SECTION 11-4.15 AND ALL SUBSECTIONS.
  
 2. SHT A-3.0 THE KITCHEN SINK SHALL BE ACCESSIBLE.
 PLEASE SUBMIT A DETAIL SHOWING COMPLIANCE WITH SECTION
 11-4.24 AND ALL SUBSECTIONS.
  
 3. SHT A-3.1 DETAIL 5. THE WATER CLOSET SHALL BE 1'6"
 OFF THE WALL TO THE CENTERLINE OF THE FIXTURE. SEE
 FIGURE 11-28.
  
 4. SHT A-3.1 DETAIL 1 THE ACCESSIBLE WATER CLOSETS
 SHALL BE 1'6" OFF THE WALL TO THE CENTERLINE OF THE
 FIXTURE. SEE FIG. 11-28.
  
 5. SHT P-1 SHOW THE LOCATION OF THE SANITARY BUILDING
 DRAIN AND THE WATER MAIN THAT THE KITCHEN SINK WILL BE
 CONNECTED TO. SECTION 106.1.2.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]
  
  

Review Stop Z ZONING
Rev No 3 Status P Date 2008-03-03 Cont ID  
Sent By choops Date 2008-03-03 Time 13:25 Rev Time 0.00
Received By choops Date 2008-03-03 Time 13:25 Sent To  
Notes
2008-03-03 13:26:18***APPROVED - RESUB #2 (RESTAMPED PLANS)***

Review Stop Z ZONING
Rev No 2 Status P Date 2008-01-23 Cont ID  
Sent By choops Date 2008-01-23 Time 16:10 Rev Time 0.00
Received By choops Date 2008-01-23 Time 16:09 Sent To  
Notes
2008-01-23 16:10:16***APPROVED - RESUB #1***

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-11 Cont ID  
Sent By choops Date 2007-12-11 Time 10:13 Rev Time 0.00
Received By choops Date 2007-12-11 Time 10:12 Sent To  
Notes
2007-12-11 10:24:55***FAILED***
  
  
 1)PROVIDE A STRIPING DETAIL SHOWING COMPLIANCE WITH
 THE PROVIDED SAMPLE DETAIL (SEE PERMIT PACKAGE).
  
 2)SITE PLAN SHOWS A CONCRETE SIGN.IS THIS PROPOSED
 OR EXISTING?PLEASE CLARIFY.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved