Plan Review Details - Permit 07120109
Plan Review Stops For Permit 07120109
Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-05-19 Cont ID  
Sent By rmcdouga Date 2008-05-19 Time 14:40 Rev Time 0.00
Received By rmcdouga Date 2008-05-19 Time 14:40 Sent To  
Notes
2008-05-19 14:38:002004 FBC W/2007 REVISIONS
  
 2 STORY POOL HOUSE
  
 DENIED BY BUILDING
  
 ***********REPEAT COMMENTS ************
  
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, AN
 ELEVATION CERTIFICATE WILL BE REQUIRED. THE MINIMUM
 ELEVATION IS 7.5 ' BFE.
  
 4) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS DESIGNED
 TO COMPLY WITH THE 2004 FLORIDA BUILDING CODE AND ASCE
 7-02. THE PLANS ARE REQUIRED TO CLEARLY INDICATE ALL OF
 THE WORK THAT HAS BEEN COMPLETED. THE PLANS SHALL ALSO
 CLEARLY INDICATE THE PROPOSED WORK. ANY OF THE WORK HAS
 BEEN DONE BUT HAS NOT BEEN INSPECTED AND APPROVED BY
 THE CITY CONSTRUCTION SERVICES DEPARTMENT IS TO BE
 SPECIFIED AS PROPOSED WORK ON THE PLANS AND WILL
 REQUIRE FIELD INSPECTIONS AND APPROVALS. FBC 106.1.1*
 CITY AMENDMENTS INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 5) THE PERMIT VALUE IS TO INCLUDE THE COST OF LABOR AND
 MATERIAL THAT IS NEEDED TO COMPLETE THE PROJECT. PLEASE
 REVISE THE VALUE ON THE PERMIT APPLICATION TO INCLUDE
 LABOR AND MATERIAL COSTS FOR THE REMAINING WORK.
  
 6)SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS,
 GLASS BLOCK, STORM PANELS, DOORS, ROOFING MATERIALS,
 ETC. AS REQUIRED BY DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9B-72. TWO COPIES OF ALL SUBMITTALS ARE REQUIRED.
  
 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC CHAPTER 13.
  
 9) THE CURRENT BUILDING CODE IS THE 2004 FLORIDA
 BUILDING CODE WITH 2007 REVISIONS. THE 2004 FBC
 REFERENCES ASCE7-02. PLEASE UPDATE THE PLANS TO REFLECT
 THE APPLICABLE CODES AND STANDARDS.
  
 NOTE:ADDITIONAL COMMENTS MAY BE GENERATED WHEN THESE
 COMMENTS ARE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2008-01-07 Cont ID  
Sent By rmcdouga Date 2008-01-07 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2008-01-04 Time 16:28 Sent To  
Notes
2008-01-04 16:57:572004 FBC W/2007 REVISIONS
  
 2 STORY POOL HOUSE
  
 DENIED BY BUILDING
  
 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT
 MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, AN
 ELEVATION CERTIFICATE WILL BE REQUIRED. THE MINIMUM
 ELEVATION IS 7.5 ' BFE.
  
 4) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS DESIGNED
 TO COMPLY WITH THE 2004 FLORIDA BUILDING CODE AND ASCE
 7-02. THE PLANS ARE REQUIRED TO CLEARLY INDICATE ALL OF
 THE WORK THAT HAS BEEN COMPLETED. THE PLANS SHALL ALSO
 CLEARLY INDICATE THE PROPOSED WORK. ANY OF THE WORK HAS
 BEEN DONE BUT HAS NOT BEEN INSPECTED AND APPROVED BY
 THE CITY CONSTRUCTION SERVICES DEPARTMENT IS TO BE
 SPECIFIED AS PROPOSED WORK ON THE PLANS AND WILL
 REQUIRE FIELD INSPECTIONS AND APPROVALS. FBC 106.1.1*
 CITY AMENDMENTS INFORMATION ON CONSTRUCTION DOCUMENTS.
 CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN
 UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE
 PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING
 OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT
 CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF
 THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT
 LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED
 BY THE BUILDING OFFICIAL.
  
 5) THE PERMIT VALUE IS TO INCLUDE THE COST OF LABOR AND
 MATERIAL THAT IS NEEDED TO COMPLETE THE PROJECT. PLEASE
 REVISE THE VALUE ON THE PERMIT APPLICATION TO INCLUDE
 LABOR AND MATERIAL COSTS FOR THE REMAINING WORK.
  
 6)SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS,
 GLASS BLOCK, STORM PANELS, DOORS, ROOFING MATERIALS,
 ETC. AS REQUIRED BY DEPARTMENT OF COMMUNITY AFFAIRS
 RULE 9B-72. TWO COPIES OF ALL SUBMITTALS ARE REQUIRED.
  
 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE
 PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED
 BY FBC CHAPTER 13.
  
 9) THE CURRENT BUILDING CODE IS THE 2004 FLORIDA
 BUILDING CODE WITH 2007 REVISIONS. THE 2004 FBC
 REFERENCES ASCE7-02. PLEASE UPDATE THE PLANS TO REFLECT
 THE APPLICABLE CODES AND STANDARDS.
  
 NOTE:ADDITIONAL COMMENTS MAY BE GENERATED WHEN THESE
 COMMENTS ARE ADDRESSED.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-05-13 Cont ID  
Sent By btrobaug Date 2008-05-13 Time 15:22 Rev Time 0.00
Received By btrobaug Date 2008-05-13 Time 15:17 Sent To M
Notes
2008-05-13 15:22:40 
  
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS
 AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE
 FOLLOWING:
  
 SAME COMMENTS AS LAST REVIEW:
  
 1} NOT ENOUGH INFORMATION SUBMITTED FOR REVIEW. 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO
 BE SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 THE PLANS SUBMITTED ARE NOT SIGNED AND SEALEDAND ARE
 COPIES. SUBMIT TWO SETS OF NEW PLANS, AND DOCUMENTS
 PERTAINING TO SAME. SEE BUILDING COMMENTS.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By btrobaug Date 2007-12-12 Time 08:10 Rev Time 0.00
Received By btrobaug Date 2007-12-12 Time 07:41 Sent To M
Notes
2007-12-12 08:10:32 
  
 THIS REVIEW WAS DONE UNDER THESE CURRENT CODE
 CYCLES:
  
 THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004
 RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002,
 NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND
 NONCOMPLIANT WITH THE FOLLOWING:
  
 1} NOT ENOUGH INFORMATION SUBMITTED FOR REVIEW. 106.1.1
 INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION
 DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE
 MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO
 BE SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL.
 CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY
 TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES,
 RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING
 OFFICIAL (SEE ALSO SECTION 106.3.5).
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-05-12 Cont ID  
Sent By adarroug Date 2008-05-12 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-05-12 Time 11:11 Sent To Z
Notes
2008-05-12 11:11:51TO "Z" BOX/RESUB

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-07 Cont ID  
Sent By rmcdouga Date 2008-01-07 Time 08:27 Rev Time 0.00
Received By rmcdouga Date 2007-12-06 Time 12:22 Sent To  
Notes
2007-12-06 12:22:19TO "SFR" "Z"

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-05-13 Cont ID  
Sent By tgordon Date 2008-05-13 Time 16:12 Rev Time 0.45
Received By tgordon Date 2008-05-13 Time 16:12 Sent To P
Notes
2008-05-13 16:29:32PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** THIS REVIEW IS FOR PERMIT # 07120109, NOT FOR
 PREVIOUS APPLIED OR ISSUED PERMITS ***
  
 *** DENIED ***
 1) AS NOTED IN LAST REVIEW 12-12-07. SUBMIT ENERGY
 CALCULATIONS FOR REVIEW, SEE 2004 FBC 13-101.2.1.
  
 2) AS NOTED IN LAST REVIEW 12-12-07. SUBMITCOOLING
 LOAD CALCULATIONS (MANUAL J CALCULATIONS) FOR REVIEW,
 SEE 2004 FBC 13-607.1.ABC.1.
  
 3) PLEASE SUBMIT TWO NEW SETS OF MECHANICAL PLANS WITH
 OUT THE OLD CITY STAMPS AS THIS IS FOR A NEW PERMIT
 #07120112, PER 2004 FBC 106.1.1.
  
 4) PLEASE BE ADVISED THE REVISED MECHANICAL PLANS WILL
 NEED THE PRINTED NAME AND SIGNATURE OF THE PERSON
 RESPONSIBLE FOR THE DESIGN, AND CONTRACTOR INFORMATION
 IF APPLICABLE ON THEM, SEE W.P.B. AMEND. 106.1.3.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By tgordon Date 2007-12-12 Time 08:50 Rev Time 0.30
Received By tgordon Date 2007-12-12 Time 08:50 Sent To P
Notes
2007-12-12 08:57:43PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) SUBMIT ENERGY CALCULATIONS FOR REVIEW, SEE 2004 FBC
 13-101.2.1.
  
 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J
 CALCULATIONS) FOR REVIEW, SEE 2004 FBC 13-607.1.ABC.1.
  
 3) MECHANICAL PERMIT #07120112 HAS BEEN APPLIED FOR BUT
 NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE
 SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY
 OF WPB AMEND. 106.3.5.4 (10).
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-05-14 Cont ID  
Sent By jleech Date 2008-05-14 Time 14:31 Rev Time 0.00
Received By jleech Date 2008-05-14 Time 14:23 Sent To  
Notes
2008-05-14 14:36:46DENIED;
 1. 2 COPIES OF PLANS REQUIRED .
 2. SECOND REQUEST. SANITARY RISER DIAGRAM REQUIRED PER
 CHAPTER 1 OF THE FBC- BUILDING. NOT ENOUGH INFORMASION
 TO DO A PLUMBING PLAN REVIEW.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-15 Cont ID  
Sent By jleech Date 2007-12-15 Time 13:09 Rev Time 0.00
Received By jleech Date 2007-12-15 Time 13:09 Sent To B
Notes
2007-12-15 13:15:45DENIED;
 1. TWO STS OF PLANS ARE REQUIRED.
 2. NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW. A
 SANITARY RISER DIAGRAM IS REQUIRED SHOWING ALL SANITARY
 AVENT PIPE SIZES.SEE WPB AMENDMENTS TO THE FBC CHAPTER
 1 ADMINISTRATION CODE SECTION 106.3.5.4 (9).
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH
 805-6695

Review Stop Z ZONING
Rev No 3 Status P Date 2009-04-30 Cont ID  
Sent By ajones Date 2009-04-30 Time 17:08 Rev Time 0.00
Received By ajones Date 2009-04-30 Time 17:08 Sent To  
Notes
***NONE***

Review Stop Z ZONING
Rev No 2 Status F Date 2008-05-12 Cont ID  
Sent By choops Date 2008-05-12 Time 15:45 Rev Time 0.00
Received By choops Date 2008-05-12 Time 15:45 Sent To E
Notes
2008-05-12 15:45:46***FAILED - RESUB #1***
  
  
 NO NEW PLANS SUBMITTED
  
  
 REPEAT COMMENTS:
  
 1)PROVIDE TWO (2) CURRENT COPIES OF A SURVEY SHOWING
 THE LOCATION OF THE PROPOSED STRUCTURE WITH SETBACK
 DIMENSIONS FROM ALL PROPERTY LINES. NOTE: PURSUANT TO
 SECTION 94-304(B)(2) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS:
 SETBACKS.
 FRONT: 25 FEET.
 SIDE: FIVE FEET FROM THE LOT LINES.
 CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. REAR:
 FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE OF THE
 ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS
 GREATER.
  
 2)INDICATE HEIGHT DIMENSIONS ON ELEVATIONS FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.NOTE:
 PURSUANT TO SECTION 94-304(B)(4) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS: HEIGHT.ACCESSORY
 STRUCTURES SHALL NOT EXCEED 25 FEET.
  
 3)SHOW ANY PROPOSED A/C EQUIPMENT AND INDICATE
 SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT TO THE
 PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF THE
 ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 4' INTO A REQUIRED SETBACK.
  
 4)ACCESSORY STRUCTURE EXCEEDS MAXIMUM SQUARE FOOTAGE
 ALLOWABLE.PURSUANT TO SECTION 94-304(B)(1) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS: MAXIMUM
 SQUARE FOOTAGE.THE TOTAL FLOOR AREA OF ALL ROOFED
 ACCESSORY BUILDINGS ON A PROPERTY (INCLUDING ANY OTHER
 ACCESSORY STRUCTURES THAT MAY EXIST) SHALL NOT EXCEED
 75 PERCENT OF THE GROSS FLOOR AREA OF THE PRIMARY
 STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 SQUARE
 FEET.
  
  
 NOTE:ACCESSORY APARTMENTS/DWELLING UNITS ARE
 PROHIBITED WITHIN THE SF7 ZONING DISTRICT.STRUCTURE
 SHALL SERVE AS A POOL CABANA ONLY.NO DWELLING UNIT
 PERMITTED.NO RENTAL LICENSE SHALL BE GRANTED IN THE
 FUTURE.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720
  
  
  
  
 SENT TO "E" - BT
  

Review Stop Z ZONING
Rev No 1 Status F Date 2007-12-07 Cont ID  
Sent By choops Date 2007-12-07 Time 16:33 Rev Time 0.00
Received By choops Date 2007-12-07 Time 16:33 Sent To E
Notes
2007-12-07 16:43:20***FAILED***
  
  
 1)PROVIDE TWO (2) CURRENT COPIES OF A SURVEY SHOWING
 THE LOCATION OF THE PROPOSED STRUCTURE WITH SETBACK
 DIMENSIONS FROM ALL PROPERTY LINES. NOTE: PURSUANT TO
 SECTION 94-304(B)(2) OF THE CITY'S ZONING AND LAND
 DEVELOPMENT REGULATIONS:
 SETBACKS.
 FRONT: 25 FEET.
 SIDE: FIVE FEET FROM THE LOT LINES.
 CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. REAR:
 FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE OF THE
 ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS
 GREATER.
  
 2)INDICATE HEIGHT DIMENSIONS ON ELEVATIONS FROM
 GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.NOTE:
 PURSUANT TO SECTION 94-304(B)(4) OF THE CITY'S ZONING
 AND LAND DEVELOPMENT REGULATIONS: HEIGHT.ACCESSORY
 STRUCTURES SHALL NOT EXCEED 25 FEET.
  
 3)SHOW ANY PROPOSED A/C EQUIPMENT AND INDICATE
 SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT TO THE
 PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF THE
 ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN
 4' INTO A REQUIRED SETBACK.
  
 4)ACCESSORY STRUCTURE EXCEEDS MAXIMUM SQUARE FOOTAGE
 ALLOWABLE.PURSUANT TO SECTION 94-304(B)(1) OF THE
 CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS: MAXIMUM
 SQUARE FOOTAGE.THE TOTAL FLOOR AREA OF ALL ROOFED
 ACCESSORY BUILDINGS ON A PROPERTY (INCLUDING ANY OTHER
 ACCESSORY STRUCTURES THAT MAY EXIST) SHALL NOT EXCEED
 75 PERCENT OF THE GROSS FLOOR AREA OF THE PRIMARY
 STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 SQUARE
 FEET.
  
 NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY
 GENERATE ADDITIONAL COMMENTS.
  
  
 QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS,
 ZONING TECHNICIAN (561)805-6720