| Plan Review Stops For Permit 07120109 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-19 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-05-19 |
Time |
14:40 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-05-19 |
Time |
14:40 |
Sent To |
|
|
| Notes |
| 2008-05-19 14:38:00 | 2004 FBC W/2007 REVISIONS | | | | | | 2 STORY POOL HOUSE | | | | | | DENIED BY BUILDING | | | | | | ***********REPEAT COMMENTS ************ | | | | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, AN | | | ELEVATION CERTIFICATE WILL BE REQUIRED. THE MINIMUM | | | ELEVATION IS 7.5 ' BFE. | | | | | | 4) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS DESIGNED | | | TO COMPLY WITH THE 2004 FLORIDA BUILDING CODE AND ASCE | | | 7-02. THE PLANS ARE REQUIRED TO CLEARLY INDICATE ALL OF | | | THE WORK THAT HAS BEEN COMPLETED. THE PLANS SHALL ALSO | | | CLEARLY INDICATE THE PROPOSED WORK. ANY OF THE WORK HAS | | | BEEN DONE BUT HAS NOT BEEN INSPECTED AND APPROVED BY | | | THE CITY CONSTRUCTION SERVICES DEPARTMENT IS TO BE | | | SPECIFIED AS PROPOSED WORK ON THE PLANS AND WILL | | | REQUIRE FIELD INSPECTIONS AND APPROVALS. FBC 106.1.1* | | | CITY AMENDMENTS INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE | | | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. | | | | | | 5) THE PERMIT VALUE IS TO INCLUDE THE COST OF LABOR AND | | | MATERIAL THAT IS NEEDED TO COMPLETE THE PROJECT. PLEASE | | | REVISE THE VALUE ON THE PERMIT APPLICATION TO INCLUDE | | | LABOR AND MATERIAL COSTS FOR THE REMAINING WORK. | | | | | | 6)SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS, | | | GLASS BLOCK, STORM PANELS, DOORS, ROOFING MATERIALS, | | | ETC. AS REQUIRED BY DEPARTMENT OF COMMUNITY AFFAIRS | | | RULE 9B-72. TWO COPIES OF ALL SUBMITTALS ARE REQUIRED. | | | | | | 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC CHAPTER 13. | | | | | | 9) THE CURRENT BUILDING CODE IS THE 2004 FLORIDA | | | BUILDING CODE WITH 2007 REVISIONS. THE 2004 FBC | | | REFERENCES ASCE7-02. PLEASE UPDATE THE PLANS TO REFLECT | | | THE APPLICABLE CODES AND STANDARDS. | | | | | | NOTE:ADDITIONAL COMMENTS MAY BE GENERATED WHEN THESE | | | COMMENTS ARE ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-07 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2008-01-04 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2008-01-04 16:57:57 | 2004 FBC W/2007 REVISIONS | | | | | | 2 STORY POOL HOUSE | | | | | | DENIED BY BUILDING | | | | | | 1) A RECORDED COPY OF THE NOTICE OF COMMENCEMENT | | | MUST BE SUBMITTED BEFORE A | | | PERMIT CAN BE ISSUED. | | | | | | 2) IMPACT FEES MUST BE PAID TO PALM | | | BEACH COUNTY, PLANS STAMPED BY THEM AND | | | COPY OF RECEIPT SUBMITTED TO CITY OF | | | WEST PALM BEACH BUILDING DEPARTMENT, | | | BEFORE A BUILDING PERMIT CAN BE ISSUED. | | | | | | 3) STRUCTURE IS LOCATED IN AN A5 FLOOD ZONE, AN | | | ELEVATION CERTIFICATE WILL BE REQUIRED. THE MINIMUM | | | ELEVATION IS 7.5 ' BFE. | | | | | | 4) SUBMIT TWO SETS OF SIGNED AND SEALED PLANS DESIGNED | | | TO COMPLY WITH THE 2004 FLORIDA BUILDING CODE AND ASCE | | | 7-02. THE PLANS ARE REQUIRED TO CLEARLY INDICATE ALL OF | | | THE WORK THAT HAS BEEN COMPLETED. THE PLANS SHALL ALSO | | | CLEARLY INDICATE THE PROPOSED WORK. ANY OF THE WORK HAS | | | BEEN DONE BUT HAS NOT BEEN INSPECTED AND APPROVED BY | | | THE CITY CONSTRUCTION SERVICES DEPARTMENT IS TO BE | | | SPECIFIED AS PROPOSED WORK ON THE PLANS AND WILL | | | REQUIRE FIELD INSPECTIONS AND APPROVALS. FBC 106.1.1* | | | CITY AMENDMENTS INFORMATION ON CONSTRUCTION DOCUMENTS. | | | CONSTRUCTION DOCUMENTS SHALL BE DIMENSIONED AND DRAWN | | | UPON SUITABLE MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE | | | PERMITTED TO BE SUBMITTED WHEN APPROVED BY THE BUILDING | | | OFFICIAL. CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT | | | CLARITY TO INDICATE THE LOCATION, NATURE AND EXTENT OF | | | THE WORK PROPOSED AND SHOW IN DETAIL THAT IT WILL | | | CONFORM TO THE PROVISIONS OF THIS CODE AND RELEVANT | | | LAWS, ORDINANCES, RULES AND REGULATIONS, AS DETERMINED | | | BY THE BUILDING OFFICIAL. | | | | | | 5) THE PERMIT VALUE IS TO INCLUDE THE COST OF LABOR AND | | | MATERIAL THAT IS NEEDED TO COMPLETE THE PROJECT. PLEASE | | | REVISE THE VALUE ON THE PERMIT APPLICATION TO INCLUDE | | | LABOR AND MATERIAL COSTS FOR THE REMAINING WORK. | | | | | | 6)SUBMIT PRODUCT APPROVALS FOR EXTERIOR WINDOWS, | | | GLASS BLOCK, STORM PANELS, DOORS, ROOFING MATERIALS, | | | ETC. AS REQUIRED BY DEPARTMENT OF COMMUNITY AFFAIRS | | | RULE 9B-72. TWO COPIES OF ALL SUBMITTALS ARE REQUIRED. | | | | | | 7) FBC 106.3* CITY AMENDMENTS PRODUCT APPROVALS. THOSE | | | PRODUCT WHICH ARE REGULATED BY DCA RULE 9B-72 SHALL BE | | | REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF | | | RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL. | | | | | | 8) SUBMIT TWO COPIES OF ENERGY CALCULATIONS AS REQUIRED | | | BY FBC CHAPTER 13. | | | | | | 9) THE CURRENT BUILDING CODE IS THE 2004 FLORIDA | | | BUILDING CODE WITH 2007 REVISIONS. THE 2004 FBC | | | REFERENCES ASCE7-02. PLEASE UPDATE THE PLANS TO REFLECT | | | THE APPLICABLE CODES AND STANDARDS. | | | | | | NOTE:ADDITIONAL COMMENTS MAY BE GENERATED WHEN THESE | | | COMMENTS ARE ADDRESSED. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2008-05-13 |
Time |
15:22 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2008-05-13 |
Time |
15:17 |
Sent To |
M |
|
| Notes |
| 2008-05-13 15:22:40 | | | | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, 2004 FBC AS | | | AMENDED, CHAPTER 1.AND FOUND NONCOMPLIANT WITH THE | | | FOLLOWING: | | | | | | SAME COMMENTS AS LAST REVIEW: | | | | | | 1} NOT ENOUGH INFORMATION SUBMITTED FOR REVIEW. 106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO | | | BE SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL (SEE ALSO SECTION 106.3.5). | | | | | | THE PLANS SUBMITTED ARE NOT SIGNED AND SEALEDAND ARE | | | COPIES. SUBMIT TWO SETS OF NEW PLANS, AND DOCUMENTS | | | PERTAINING TO SAME. SEE BUILDING COMMENTS. | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
btrobaug |
Date |
2007-12-12 |
Time |
08:10 |
Rev Time |
0.00 |
| Received By |
btrobaug |
Date |
2007-12-12 |
Time |
07:41 |
Sent To |
M |
|
| Notes |
| 2007-12-12 08:10:32 | | | | | | | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE | | | CYCLES: | | | | | | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 | | | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, | | | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND | | | NONCOMPLIANT WITH THE FOLLOWING: | | | | | | 1} NOT ENOUGH INFORMATION SUBMITTED FOR REVIEW. 106.1.1 | | | INFORMATION ON CONSTRUCTION DOCUMENTS. CONSTRUCTION | | | DOCUMENTS SHALL BE DIMENSIONED AND DRAWN UPON SUITABLE | | | MATERIAL. ELECTRONIC MEDIA DOCUMENTS ARE PERMITTED TO | | | BE SUBMITTED WHEN APPROVED BY THE BUILDING OFFICIAL. | | | CONSTRUCTION DOCUMENTS SHALL BE OF SUFFICIENT CLARITY | | | TO INDICATE THE LOCATION, NATURE AND EXTENT OF THE WORK | | | PROPOSED AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THIS CODE AND RELEVANT LAWS, ORDINANCES, | | | RULES AND REGULATIONS, AS DETERMINED BY THE BUILDING | | | OFFICIAL (SEE ALSO SECTION 106.3.5). | | | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLANS EXAMINER | | | CITY OF WEST PALM BEACH | | | 561/805-6718 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-12 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-12 |
Time |
11:11 |
Sent To |
Z |
|
| Notes |
| 2008-05-12 11:11:51 | TO "Z" BOX/RESUB |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-07 |
|
|
Cont ID |
|
| Sent By |
rmcdouga |
Date |
2008-01-07 |
Time |
08:27 |
Rev Time |
0.00 |
| Received By |
rmcdouga |
Date |
2007-12-06 |
Time |
12:22 |
Sent To |
|
|
| Notes |
| 2007-12-06 12:22:19 | TO "SFR" "Z" |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-05-13 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-05-13 |
Time |
16:12 |
Rev Time |
0.45 |
| Received By |
tgordon |
Date |
2008-05-13 |
Time |
16:12 |
Sent To |
P |
|
| Notes |
| 2008-05-13 16:29:32 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** THIS REVIEW IS FOR PERMIT # 07120109, NOT FOR | | | PREVIOUS APPLIED OR ISSUED PERMITS *** | | | | | | *** DENIED *** | | | 1) AS NOTED IN LAST REVIEW 12-12-07. SUBMIT ENERGY | | | CALCULATIONS FOR REVIEW, SEE 2004 FBC 13-101.2.1. | | | | | | 2) AS NOTED IN LAST REVIEW 12-12-07. SUBMITCOOLING | | | LOAD CALCULATIONS (MANUAL J CALCULATIONS) FOR REVIEW, | | | SEE 2004 FBC 13-607.1.ABC.1. | | | | | | 3) PLEASE SUBMIT TWO NEW SETS OF MECHANICAL PLANS WITH | | | OUT THE OLD CITY STAMPS AS THIS IS FOR A NEW PERMIT | | | #07120112, PER 2004 FBC 106.1.1. | | | | | | 4) PLEASE BE ADVISED THE REVISED MECHANICAL PLANS WILL | | | NEED THE PRINTED NAME AND SIGNATURE OF THE PERSON | | | RESPONSIBLE FOR THE DESIGN, AND CONTRACTOR INFORMATION | | | IF APPLICABLE ON THEM, SEE W.P.B. AMEND. 106.1.3. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-12 |
Time |
08:50 |
Rev Time |
0.30 |
| Received By |
tgordon |
Date |
2007-12-12 |
Time |
08:50 |
Sent To |
P |
|
| Notes |
| 2007-12-12 08:57:43 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) SUBMIT ENERGY CALCULATIONS FOR REVIEW, SEE 2004 FBC | | | 13-101.2.1. | | | | | | 2) SUBMITCOOLING LOAD CALCULATIONS (MANUAL J | | | CALCULATIONS) FOR REVIEW, SEE 2004 FBC 13-607.1.ABC.1. | | | | | | 3) MECHANICAL PERMIT #07120112 HAS BEEN APPLIED FOR BUT | | | NO MECHANICAL PLANS WERE SUBMITTED FOR REVIEW. PLEASE | | | SUBMIT MECHANICAL PLANS FOR REVIEW, PER 2004 FBC CITY | | | OF WPB AMEND. 106.3.5.4 (10). | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-05-14 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2008-05-14 |
Time |
14:31 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2008-05-14 |
Time |
14:23 |
Sent To |
|
|
| Notes |
| 2008-05-14 14:36:46 | DENIED; | | | 1. 2 COPIES OF PLANS REQUIRED . | | | 2. SECOND REQUEST. SANITARY RISER DIAGRAM REQUIRED PER | | | CHAPTER 1 OF THE FBC- BUILDING. NOT ENOUGH INFORMASION | | | TO DO A PLUMBING PLAN REVIEW. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-15 |
|
|
Cont ID |
|
| Sent By |
jleech |
Date |
2007-12-15 |
Time |
13:09 |
Rev Time |
0.00 |
| Received By |
jleech |
Date |
2007-12-15 |
Time |
13:09 |
Sent To |
B |
|
| Notes |
| 2007-12-15 13:15:45 | DENIED; | | | 1. TWO STS OF PLANS ARE REQUIRED. | | | 2. NOT ENOUGH INFORMATION TO DO A PLUMBING REVIEW. A | | | SANITARY RISER DIAGRAM IS REQUIRED SHOWING ALL SANITARY | | | AVENT PIPE SIZES.SEE WPB AMENDMENTS TO THE FBC CHAPTER | | | 1 ADMINISTRATION CODE SECTION 106.3.5.4 (9). | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
P |
Date |
2009-04-30 |
|
|
Cont ID |
|
| Sent By |
ajones |
Date |
2009-04-30 |
Time |
17:08 |
Rev Time |
0.00 |
| Received By |
ajones |
Date |
2009-04-30 |
Time |
17:08 |
Sent To |
|
|
| Notes |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-05-12 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-05-12 |
Time |
15:45 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-05-12 |
Time |
15:45 |
Sent To |
E |
|
| Notes |
| 2008-05-12 15:45:46 | ***FAILED - RESUB #1*** | | | | | | | | | NO NEW PLANS SUBMITTED | | | | | | | | | REPEAT COMMENTS: | | | | | | 1)PROVIDE TWO (2) CURRENT COPIES OF A SURVEY SHOWING | | | THE LOCATION OF THE PROPOSED STRUCTURE WITH SETBACK | | | DIMENSIONS FROM ALL PROPERTY LINES. NOTE: PURSUANT TO | | | SECTION 94-304(B)(2) OF THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS: | | | SETBACKS. | | | FRONT: 25 FEET. | | | SIDE: FIVE FEET FROM THE LOT LINES. | | | CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. REAR: | | | FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE OF THE | | | ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS | | | GREATER. | | | | | | 2)INDICATE HEIGHT DIMENSIONS ON ELEVATIONS FROM | | | GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.NOTE: | | | PURSUANT TO SECTION 94-304(B)(4) OF THE CITY'S ZONING | | | AND LAND DEVELOPMENT REGULATIONS: HEIGHT.ACCESSORY | | | STRUCTURES SHALL NOT EXCEED 25 FEET. | | | | | | 3)SHOW ANY PROPOSED A/C EQUIPMENT AND INDICATE | | | SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT TO THE | | | PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF THE | | | ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN | | | 4' INTO A REQUIRED SETBACK. | | | | | | 4)ACCESSORY STRUCTURE EXCEEDS MAXIMUM SQUARE FOOTAGE | | | ALLOWABLE.PURSUANT TO SECTION 94-304(B)(1) OF THE | | | CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS: MAXIMUM | | | SQUARE FOOTAGE.THE TOTAL FLOOR AREA OF ALL ROOFED | | | ACCESSORY BUILDINGS ON A PROPERTY (INCLUDING ANY OTHER | | | ACCESSORY STRUCTURES THAT MAY EXIST) SHALL NOT EXCEED | | | 75 PERCENT OF THE GROSS FLOOR AREA OF THE PRIMARY | | | STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 SQUARE | | | FEET. | | | | | | | | | NOTE:ACCESSORY APARTMENTS/DWELLING UNITS ARE | | | PROHIBITED WITHIN THE SF7 ZONING DISTRICT.STRUCTURE | | | SHALL SERVE AS A POOL CABANA ONLY.NO DWELLING UNIT | | | PERMITTED.NO RENTAL LICENSE SHALL BE GRANTED IN THE | | | FUTURE. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 | | | | | | | | | | | | | | | SENT TO "E" - BT | | | |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-07 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-07 |
Time |
16:33 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-07 |
Time |
16:33 |
Sent To |
E |
|
| Notes |
| 2007-12-07 16:43:20 | ***FAILED*** | | | | | | | | | 1)PROVIDE TWO (2) CURRENT COPIES OF A SURVEY SHOWING | | | THE LOCATION OF THE PROPOSED STRUCTURE WITH SETBACK | | | DIMENSIONS FROM ALL PROPERTY LINES. NOTE: PURSUANT TO | | | SECTION 94-304(B)(2) OF THE CITY'S ZONING AND LAND | | | DEVELOPMENT REGULATIONS: | | | SETBACKS. | | | FRONT: 25 FEET. | | | SIDE: FIVE FEET FROM THE LOT LINES. | | | CORNER: SAME AS REQUIRED FOR PRINCIPAL STRUCTURE. REAR: | | | FIVE FEET MINIMUM OR 15 FEET FROM THE CENTERLINE OF THE | | | ALLEY TO A GARAGE DOOR FACING THE ALLEY, WHICHEVER IS | | | GREATER. | | | | | | 2)INDICATE HEIGHT DIMENSIONS ON ELEVATIONS FROM | | | GRADE TO THE MIDPOINT OF THE ROOF'S PITCH.NOTE: | | | PURSUANT TO SECTION 94-304(B)(4) OF THE CITY'S ZONING | | | AND LAND DEVELOPMENT REGULATIONS: HEIGHT.ACCESSORY | | | STRUCTURES SHALL NOT EXCEED 25 FEET. | | | | | | 3)SHOW ANY PROPOSED A/C EQUIPMENT AND INDICATE | | | SETBACK DIMENSIONS FROM PROPOSED A/C EQUIPMENT TO THE | | | PROPERTY LINES.AS PER SECTION 94-305(B)(4) OF THE | | | ZLDRS: MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN | | | 4' INTO A REQUIRED SETBACK. | | | | | | 4)ACCESSORY STRUCTURE EXCEEDS MAXIMUM SQUARE FOOTAGE | | | ALLOWABLE.PURSUANT TO SECTION 94-304(B)(1) OF THE | | | CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS: MAXIMUM | | | SQUARE FOOTAGE.THE TOTAL FLOOR AREA OF ALL ROOFED | | | ACCESSORY BUILDINGS ON A PROPERTY (INCLUDING ANY OTHER | | | ACCESSORY STRUCTURES THAT MAY EXIST) SHALL NOT EXCEED | | | 75 PERCENT OF THE GROSS FLOOR AREA OF THE PRIMARY | | | STRUCTURE WITH A MAXIMUM FLOOR AREA OF 1,000 SQUARE | | | FEET. | | | | | | NOTE:THE SUBMITTAL OF THE REQUESTED INFORMATION MAY | | | GENERATE ADDITIONAL COMMENTS. | | | | | | | | | QUESTIONS/COMMENTS, CONTACT CHRIS HOOPS, | | | ZONING TECHNICIAN (561)805-6720 |
|
|