| 2007-12-13 10:04:00 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODES WITH |
| | 2007 REVISIONS, CITY OF WEST PALM BEACH AMENDMENTS TO |
| | CHAPTER 1 (W.P.B.), FLORIDA ADMINISTRATIVE CODE |
| | (F.A.C.), AND FLORIDA STATUTES (F.S.). |
| | |
| | GAS PLAN REVIEW: |
| | DENIED: |
| | |
| | THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| | GAS PLAN REVIEW TO MEET CODE COMPLIANCE. PLEASE |
| | INDICATE THE FOLLOWING ON THE REQUIRED GAS ISOMETRIC. |
| | PLEASE REFERENCE THE CITY OF WEST PALM BEACH GAS PERMIT |
| | APPLICATION REQUIREMENTS FOR PERMIT APPLICATIONS |
| | ATTACHED TO THESE COMMENTS. |
| | |
| | 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| | CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| | AND CORRESPONDING LENGTHS PER FBC-2004 |
| | FUEL GAS CODE. |
| | **THE SUBMITTED GAS ISOMETRIC IS INCOMPLETE, AND DOES |
| | NOT INDICATE THE CORRESPONDING LENGTHS FOR THE CUT |
| | SECTIONS OF PIPE. PLEASE RESUBMIT WITH A COMPLETE RISER |
| | DIAGRAM OF THE PROPOSED GAS FOR THE GENERATOR FROM |
| | METER TO GENERATOR WITH THE REQUIRED INFORMATION. |
| | |
| | 2. SHOW TYPE OF PIPING MATERIAL BEING |
| | INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| | NUMBER OF CORRUGATED STAINLESS STEEL |
| | TUBING FOR EACH PIPE SIZE BEING USED. |
| | **THE INCOMPLETE GAS ISOMETRIC RISER DIAGRAM DOES NOT |
| | INDICATE PIPE SIZES. |
| | |
| | 3. TYPE OF GAS, (LP OR NATURAL) |
| | **THE SUBMITTED GAS RISER DOES NOT INDICATE THE GAS |
| | TYPE. |
| | |
| | 4. BTU LOAD OF EACH APPLIANCE AND THE |
| | TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| | THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| | THRU 402.6.1 AND TABLES 402.4(1) THRU |
| | 402.4(33). |
| | **THE SUBMITTED GAS RISER DOES NOT INDICATE THE BTU |
| | LOADS. |
| | |
| | 5. SHOW THE DISTANCE FROM THE POINT OF |
| | DELIVERY, (METER), TO THE MOST REMOTE |
| | OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| | FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| | OF CAPACITY TABLES A.3.1(4). |
| | **PLEASE REFERENCE COMMENT ONE AND COMPLY. |
| | |
| | 6. INDICATE THE DELIVERY PRESSURE (PSI) |
| | PER FBC-2004 FUEL GAS CODE SEC. 402.2. |
| | NATURAL GAS SPECIFY .5 PSI OR 2 PSI. |
| | **THE SUBMITTED GAS RISER DOES NOT INDICATE THIS. |
| | |
| | **IMPROTANT** |
| | THE ABOVE INFORMATION NEEDS TO BE ON THE GAS ISOMETRIC |
| | RISER DIAGRAM, PLEASE COMPLY ON THE RESUBMITTAL. |
| | |
| | END OF COMMENTS: |
| | |
| | REVIEW BY: MIKE PERSON |
| | PLUMBING PLANS EXAMINER |
| | (561) 805-6730 |
| | FAX (561) 805-6731 |
| | E-MAIL: [email protected] |