| 2007-12-12 14:32:39 | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING: |
| | |
| | 1} PROVIDE EMERGENCY ILLUMINATION PER NFPA-101 7.8 |
| | (2003), AND CIRCUITED PER 700.12 NEC (F)(4). INDICATE |
| | SAME ON PLANS. |
| | |
| | 2}INDICATE PANEL DESIGNATION AND CIRCUIT NUMBERS FOR |
| | DEVICES AND LIGHTS. 106.3.5 FBC. |
| | |
| | 3}LIGHTING SYSTEM MUST COMPLY WITH CHAPTER 12 FBC |
| | 13-400.0.C.4 RENOVATED BUILDINGS. |
| | RENOVATED BUILDINGS SHALL, WHEN APPLICABLE (SEE SECTION |
| | 202), MEET THE EFFICIENCIES LISTED ON FORM 400C FOR |
| | COMPONENTS BEING CHANGED OR SHALL COMPLY WITH THE |
| | ENVELOPE OR SYSTEMS CRITERIA IN METHOD B OF FLA/COM FOR |
| | THE COMPONENTS BEING CHANGED. EXISTING BUILDINGS NOT |
| | MEETING THE DEFINITION OF A RENOVATION IN WHICH NEW |
| | HEATING, COOLING, WATER HEATING, ELECTRICAL OR LIGHTING |
| | SYSTEMS ARE INSTALLED SHALL MEET THE BASIC PRESCRIPTIVE |
| | MINIMUM EFFICIENCIES LISTED IN THIS CODE FOR THE |
| | SYSTEM(S) BEING CHANGED. |
| | 13-415.2.ABC.1 PERFORMANCE CALCULATION PROCEDURES, |
| | GENERAL. |
| | THE INTERIOR LIGHTING POWER ALLOWANCE FOR A BUILDING OR |
| | A SEPARATELY METERED OR PERMITTED PORTION OF A BUILDING |
| | SHALL BE DETERMINED BY EITHER THE BUILDING AREA METHOD |
| | DESCRIBED IN SECTION 415.2.C.1 OR THE SPACE-BY-SPACE |
| | METHOD DESCRIBED IN SECTION 415.2.B.1. TRADE-OFFS OF |
| | INTERIOR LIGHTING POWER ALLOWANCE AMONG PORTIONS OF THE |
| | BUILDING FOR WHICH A DIFFERENT METHOD OF CALCULATION |
| | HAS BEEN USED ARE NOT PERMITTED. THE INSTALLED INTERIOR |
| | LIGHTING POWER IDENTIFIED IN ACCORDANCE WITH SECTION |
| | 415.2.ABC.1.1 SHALL NOT EXCEED THE INTERIOR LIGHTING |
| | POWER ALLOWANCE DEVELOPED IN ACCORDANCE WITH SECTION |
| | 415.2.C.1 OR 415.2.B.1 |
| | |
| | ALSO SEE 13-415.1.ABC.1.2 SPACE CONTROL. |
| | EACH SPACE ENCLOSED BY CEILING-HEIGHT PARTITIONS SHALL |
| | HAVE AT LEAST ONE CONTROL DEVICE TO INDEPENDENTLY |
| | CONTROL THE GENERAL LIGHTING WITHIN THE SPACE. EACH |
| | MANUAL DEVICE SHALL BE READILY ACCESSIBLE AND LOCATED |
| | SO THE OCCUPANTS CAN SEE THE CONTROLLED LIGHTING. |
| | SUBMIT LIGHTING DENSITIES AND FIXTURE SCHEDULES |
| | INDICATING COMPLIANCE WITH THIS CHAPTER. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |