| 2007-12-11 14:13:11 | |
| | |
| | |
| | THIS REVIEW WAS DONE UNDER THESE CURRENT CODE |
| | CYCLES: |
| | |
| | THE 2004 FLORIDA BUILDING CODE, 2006 REVISIONS, 2004 |
| | RESIDENTIAL BUILDING CODE, 2005 NEC, NFPA-72 2002, |
| | NFPA-101 2003, 2004 FBC AS AMENDED, CHAPTER 1.AND FOUND |
| | NONCOMPLIANT WITH THE FOLLOWING:ALL COMMENTS RELATE TO |
| | SHEET E-1, UNLESS OTHERWISE NOTED. ALL CODE ARTICLES |
| | REFERENCED ARE 2005 NEC UNLESS OTHERWISE NOTED. |
| | |
| | 1} THE RISER DIAGRAM INDICATES A 150 AMP MAIN, THE |
| | DISCONNECT (NOT SHOWN) INDICATED ON THE FLOOR PLAN IS |
| | 200 AMP. IF THIS IS A METER/ MAIN CHANGE THE RISER TO |
| | REFLECT A METER/ MAIN. |
| | |
| | 2} VERIFY THE 4/0 SERVICE CONDUCTORS SHOWN ON THE RISER |
| | ARE WHAT THE DESIGNER INTENDED WHEN A MINIMUM OF #1 CU |
| | IS ALL THATS REQUIRED FOR A 150 AMP SERVICE PER |
| | 310.15./0 CAN BE USED BUT WILL REQUIRE A REVISION TO |
| | CHANGE AFTER PERMITTING. |
| | |
| | 3} 210.52(B) (3) KITCHEN RECEPTACLE REQUIREMENTS: |
| | RECEPTACLES INSTALLED IN A KITCHEN TO SERVE COUNTERTOP |
| | SURFACES SHALL BE SUPPLIED BY NOT FEWER THAN TWO |
| | SMALL-APPLIANCE BRANCH CIRCUITS, EITHER OR BOTH OF |
| | WHICH SHALL ALSO BE PERMITTED TO SUPPLY RECEPTACLE |
| | OUTLETS IN THE SAME KITCHEN AND IN OTHER ROOMS |
| | SPECIFIED IN 210.52(B) (1). ADDITIONAL SMALL-APPLIANCE |
| | BRANCH CIRCUITS SHALL BE PERMITTED TO SUPPLY RECEPTACLE |
| | OUTLETS IN THE KITCHEN AND OTHER ROOMS SPECIFIED IN |
| | 210.52(B)(1). NO SMALL-APPLIANCE BRANCH CIRCUIT SHALL |
| | SERVE MORE THAN ONE KITCHEN.BECAUSE THE COUNTERTOP |
| | RECEPTACLE OUTLETS GENERALLY SUPPLY MORE OF THE |
| | PORTABLE COOKING APPLIANCES THAN THE WALL RECEPTACLES |
| | IN THE KITCHEN AND DINING AREAS, THE COUNTER AREAS MUST |
| | BE SUPPLIED BY NO FEWER THAN TWO SMALL-APPLIANCE BRANCH |
| | CIRCUITS. *THE INTENT OF THIS ARTICLE IS NOT MET WITH |
| | CIRCUIT #22 AS THE ONLY CIRCUIT SERVING THE |
| | COUNTERTOP. |
| | |
| | 4} 210.11(C) (2) LAUNDRY BRANCH CIRCUITS IN ADDITION TO |
| | THE NUMBER OF BRANCH CIRCUITS REQUIRED BY OTHER PARTS |
| | OF THIS SECTION, AT LEAST ONE ADDITIONAL 20-AMPERE |
| | BRANCH CIRCUIT SHALL BE PROVIDED TO SUPPLY THE LAUNDRY |
| | RECEPTACLE OUTLET(S) REQUIRED BY 210.52(F). THIS |
| | CIRCUIT SHALL HAVE NO OTHER OUTLETS.* CIRCUIT #13 DOES |
| | NOT COMPLY, ALSO THE DINING ROOM IS REQUIRED TO BE ON A |
| | SMALL APPLIANCE CIRCUIT PER 210.11(C)(1). THE LIVING |
| | ROOM IS NOT. |
| | |
| | 5} A RECEPTACLE IS REQUIRED IN THE GARAGE PER |
| | 210.52(G), GFCI PROTECTED PER 210.8(A)(2). |
| | |
| | 6} 210.52(E) REQUIRES A RECEPTACLE IN THE FRONT OUTSIDE |
| | OF THE RESIDENCE. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLANS EXAMINER |
| | CITY OF WEST PALM BEACH |
| | 561/805-6718 |
| | |
| | |