Plan Review Details - Permit 07120059
Plan Review Stops For Permit 07120059
Review Stop B BUILDING (STRUCTURAL)
Rev No 4 Status P Date 2008-05-29 Cont ID  
Sent By mjacobs Date 2008-05-29 Time 10:37 Rev Time 0.00
Received By mjacobs Date 2008-05-28 Time 17:34 Sent To PC
Notes
***NONE***

Review Stop B BUILDING (STRUCTURAL)
Rev No 3 Status F Date 2008-04-14 Cont ID  
Sent By mjacobs Date 2008-04-14 Time 07:50 Rev Time 0.00
Received By mjacobs Date 2008-04-09 Time 12:33 Sent To  
Notes
2008-04-10 09:56:38BUILDING PLAN REVIEW #3 4-9-08
 PERMIT: 07120059
 ADD: 2995 45TH STREET #562
 CONT: R.D. LANGE CONST. INC.
 TEL: (863)661-6305
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 3RD
 ACTION: DENIED
  
 NOTE: THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)OK
  
 **NOTED** SHEET COV-0 STATES PRODUCT APPROVAL NUMBERS
 FL4553/ FL1610.1 AND FL5115 HOWEVER, NONE OF THESE
 SHEETS WERE SUBMITTED. IF THESE ARE THE PRODUCT
 APPROVALS WHICH WILL BE USED ON THE PROJECT, PROVIDE
 THE STATE COVER SHEET ALONG WITH THE INSTALLATION
 REPORT INDICATING WHICH SYSTEM OR ITEMS WILL BE USED.
 SUBMIT THE STATE COVER SHEET WITH THE CORRECT
 INSTALLATION REPORTS. THE STATE COVER SHEET AND REPORT
 SHALL BE BOUND TOGETHER TO AVOID CONFUSION.
  
 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT
 APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT
 TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS
 ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED
 PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30
 FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
  
 4)OK.
 5)OK.
 6)OK
 7)OK
 8)OK
 9)OK
 10) OK
 11) OK
  
 **NEW**
 GENERATOR INFORMATION REMOVED FROM PLANS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By mjacobs Date 2008-02-19 Time 14:24 Rev Time 0.00
Received By mjacobs Date 2008-02-19 Time 07:58 Sent To  
Notes
2008-02-19 14:24:51BUILDING PLAN REVIEW
 PERMIT: 07120059
 ADD: 2995 45TH STREET #562
 CONT: R.D. LANGE CONST. INC.
 TEL: (863)661-6305
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 2ND 2-19-08
 ACTION: DENIED
  
 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE
 INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH
 REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS
 NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR
 OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS
 OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER
 INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN
 ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9.
  
 **NOTED** HOWEVER, FL#2484-R1 IS MISSING THE
 INSTALLATION REPORT. FL#3393 CODE VERSION IS 2001. WE
 ARE PRESENTLY UNDER THE 2004 CODE VERSION. TWO APPROVED
 AND COMPLETE SEPARATE SETS OF PRODUCT APPROVALS SHALL
 BE SUBMITTED. IF THE GLAZING IS NON-IMPACT, PROVIDE THE
 PRODUCT APPROVAL FOR THE IMPACT PROTECTION (SHUTTERS).
 PLEASE MAKE SURE THAT THE INSTALLATION REPORT IS
 ATTATCHED TO EACH PRODUCT APPROVAL.**
 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT
 APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT
 TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS
 ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED
 PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30
 FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
  
 4)OK.
 5)OK.
 6)OK
 7)OK
 8)OK
 9)OK
 10) OK
 11) OK
  
 **NEW**
 A) 61G1-16.004 TITLE BLOCK FOR MARK DAVID SHALL INCLUDE
 THE FOLLOWING INFORMATION.
 A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR
 INTERIOR DESIGN DRAWINGS AND SPECIFICATION
 IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A
 MINIMUM, CONTAIN THE FOLLOWING INFORMATION:
 (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER.
 (2) FIRM LICENSE NUMBER.
 (3) NAME OR IDENTIFICATION OF PROJECT.
 (4) DATE PREPARED.
 (5) A SPACE FOR THE SIGNATURE AND DATED SEAL.
 (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING
 THE DOCUMENT.
  
 B)PROVIDE THE ENGINEERING CALCULATIONS FOR THE
 GENERATOR.THE CALCULATIONS SHALL INCLUDE THE ANCHORAGE
 AGAINST OVERTURNING, UPLIFT AND SLIDING PER 1609.1.3.
 INDICATE ON THE PLANS THE ELEVATION FOR THE GENERATOR
 SLAB.ALL INFORMATION REGUARDING THE SLAB NEEDS TO BE
 SHOWN ON THE PLANS ALONG WITH WIND DESIGN CRITERIA PER
 1603.1.4.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 FAX (561) 805-6676
 [email protected]

Review Stop B BUILDING (STRUCTURAL)
Rev No 1 Status F Date 2007-12-12 Cont ID  
Sent By mjacobs Date 2007-12-12 Time 12:55 Rev Time 0.00
Received By mjacobs Date 2007-12-12 Time 06:43 Sent To  
Notes
2007-12-12 12:55:55 
 BUILDING PLAN REVIEW
 PERMIT: 07120059
 ADD: 2995 45TH STREET #562
 CONT: R.D. LANGE CONST. INC.
 TEL: (863)661-6305
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2007 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW: 1ST 12/12/07
 ACTION: DENIED
  
 1A)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION &
 REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL
 LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH
 A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE
 SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE
 FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR
 YOUR ANTICIPATED COOPERATION.
  
 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED
 WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE
 WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT
 ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING
 THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6)
 THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE
 CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW)
 AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC
 BUILDING WITH THE 2007 REVISIONS.
  
 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE
 INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH
 REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS
 NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR
 OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS
 OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE
 DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER
 INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN
 ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9.
  
  
 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS
 THAT ARE REGULATED BY DCA
 RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY
 THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR
 JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL
 FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT
 APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT
 TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS
 ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED
 PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30
 FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE
 TEST.
  
 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION;
 PROVIDE INFORMATION BASED ON INTERIOR FINISH
 REQUIREMENTS BASED ON OCCUPANCY. SHEET A-1 REFERS TO
 SHEET F-3 FOR THE DOOR, FRAME AND FINISH SCHEDULE
 HOWEVER; SHEET F-3 IS MISSING FROM THE DRAWINGS.
  
 5)SHEET A-1 REFERENCES A-3 AND A-4 FOR ADDITIONAL
 INFORMATION, THESE PAGES ARE NOT WITH THE SETS OF PLANS
 SUBMITTED.
  
 6)FBC 105.9 EACH BUILDING WHICH REQUIRES A PERMIT FOR
 RENOVATION SHALL CONTAIN AN ASBESTOS NOTIFICATION
 STATEMENT WHICH INDICATES THE OWNER?S OPERATOR?S
 RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION
 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT
 OF PROTECTION OF HIS OR HER INTENTIONS TO REMOVE
 ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH STATE AND
 FEDERAL LAW.
  
 7)THE COUNTER AND CHECK-OUT AISLES SHALL MEET THE
 REQUIREMENTS OF FBC 11-7. SHOW THE ELEVATION DETAILS OF
 THE ACCESSIBLE COUNTER WHERE A POTION OF THE MAIN
 COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A
 MAXIMUM HEIGHT OF 36 INCHES.
  
 8)2004 FBC EXISTING
 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE
 OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO
 SECTIONS 303, 304 AND 305 OF THIS CODE.
  
 9)1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND
 LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS
 GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM
 OF THE BUILDING:
 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR
 (KM/HR).
 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING
 CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7
 AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7.
 3.WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS
 UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND
 DIRECTION SHALL BE INDICATED.
 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF
 DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT.
 5.COMPONENTS AND CLADDING. THE DESIGN WIND
 PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE
 SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS
 NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL.
  
 10)SUBMIT A WALL LEGEND WITH THE DIFFERENT TYPES OF
 WALL TO BE INSTALLED AT THIS PROJECT. CONSTRUCTION
 DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE
 THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED
 AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE
 PROVISIONS OF THE CODE.
  
 11) A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING ALL
 MEANS OF EGRESS WHICH INCLUDE THE EXIT ACCESS, THE EXIT
 AND THE EXIT DISCHARGE. PER CH. 10
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 (561)805-6726
 [email protected]
  

Review Stop E ELECTRICAL
Rev No 4 Status P Date 2008-05-28 Cont ID  
Sent By dpalmer Date 2008-05-28 Time 14:49 Rev Time 0.00
Received By dpalmer Date 2008-05-28 Time 14:49 Sent To  
Notes
2008-05-28 14:50:01MUST USE SE RATED TRANSFER SWITCH AS INDICATED.

Review Stop E ELECTRICAL
Rev No 3 Status F Date 2008-03-26 Cont ID  
Sent By dpalmer Date 2008-03-26 Time 12:39 Rev Time 0.00
Received By dpalmer Date 2008-03-26 Time 12:39 Sent To  
Notes
2008-03-26 12:39:39** DENIEDREVIEW**
  
 ** PLANS HAVE NOW BEEN COMPLETELY REVISED WHICH HAS
 CREATE NEW COMMENTS.
  
 1) NOTE: PLEASE PROVIDE INFORMATION ON THE EQUIPMENT
 WHICH IS NOW BEING PROPOSED WHICH IS LISTED AS A
 TRANSFER SWITCH AND BEING SERVICE ENTRANCE RATED.
 PLEASE SEE THE STATUTES REQUIRES A TRANSFER SWITCH
 WHICH IS ALSO DEFINED IN THE CODE. THIS MUST PROVIDE A
 FAIL-SAFE OPERATION FOR THOSE TWO SIDES OF INCOMING
 POWER FROM NORMAL AND EMERGENCY SO THAT IT IS NOT
 POSSIBLE FOR POWER TO BE FED INTO SERVICE AT ANY
 ONE-TIME. AS A*KEYED INTERLOCK*WHICH IS ONLY NOW
 BEING SHOWN, THIS DOES NOT PROVIDE THIS OPERATION.
 702.6, 100, 110.3, 90.7 ETC.
  
 THIS IS A LIFE SAFETY, FIRE AND PROPERTY HAZARD.
  
  
  
 ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR
 CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL
 OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS
 INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT
 LEAVE ANY OLD/VOIDED SHEETS IN SETS.
 PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY
 ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS,
 SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO
 TWO SETS/FOLDERS/BINDERS ETC.
 PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS
 SHOULD BE SUBMITTED FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY
 DELAYS.
  
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 2 Status F Date 2008-02-10 Cont ID  
Sent By dpalmer Date 2008-02-10 Time 10:24 Rev Time 0.00
Received By dpalmer Date 2008-02-10 Time 10:24 Sent To  
Notes
2008-02-11 10:25:22** DENIED 2ND REVIEW **
  
 ** PLEASE SEE NEW NOTES BASED ON CHANGES MADE TO
 PLANS.
  
 1) NOTE: PLEASE SEE THE CODE REFERENCES ON PLANS STILL
 INDICATE THE 2002 NEC/ NFPA-70.
 PLEASE SEE THIS WAS DONE ON ELECTRICAL SHEETS HOWEVER
 PLEASE SEE SHEET COV -0.
 PLEASE ALSO BE SURE TO ADD NFPA-110 2002 FOR NEW
 GENERATOR.
 FBC 106.1.2 FOR COORDINATION.
  
 2) NOTE: PLEASE KNOW PLANS HAVE BEEN REVISED WITH NEW
 GENERATOR AS REQUIRED HOWEVER PLEASE SEE COMMENTS FROM
 OTHER TRADES WHICH WILL AFFECT PLANS.
 PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR NEW
 PROPOSED GENERATOR, TRANSFER SWITCH AND SUB BASE FUEL
 TANK.
 THE FUEL TANK WILL BE UNDER REVIEW OF FIRE MARSHAL AND
 MECHANICAL REVIEW.
 PLEASE INDICATE THE ELEVATION LEVEL OF ANY OF THE
 REQUIRED EPSS SYSTEM EQUIPMENT INCLUDING GENERATOR PER
 CHAPTER 7 OF NFPA 7.2.3
 110.3, 90.7, NFPA-110
  
 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE
 SCOPE OF WORK NOW ON PLANS NEEDS TO BE UPDATED PER FBC
 108.3
 PLEASE KNOW AS THE PLANS INCLUDE THE GENERATOR ETC THE
 COST INCLUDING LABOR, EQUIPMENT, MATERIALS, DESIGN COST
 ETC IS REQUIRED WHETHER OR NOT ANY OF THESE ITEMS ARE
 OWNER SUPPLIED.
  
 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES. AS MENTIONED
 IF ANY NEW LIGHTING WILL BE PROPOSED AS STATED ON
 ARCHITECTURAL PLANS. THESE MUST COMPLY WITH CHAPTER 13
 OF THE 2004 FBC W/2007 REVISIONS.
 PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR
 REQUIRED LIGHTING PERFORMANCE CALCULATIONS.
  
 5) NOTE: PLEASE VERIFY GROUNDING AT THE GENERATOR. 250
 THERE IS NO INFORMATION ON TRANSFER SWITCH WHICH IS
 NEEDED.
 IS THIS SERVICE ENTRANCE RATED AS REQUIRED?
 IS THIS 3 OR 4-POLE? THIS WILL AFFECT THE GROUNDING AT
 THE GENERATOR.
 PLEASE SEE MANY QUESTIONS ARE OUTSTANDING WHICH MAY
 AFFECT REVIEW NOTES ON THE FOLLOWING REVIEW.
 230.70, 230.71, 250.20,250.50 ETC
 FBC 106.3.5.1.2 AND 106.1.2 FOR ADDITIONAL INFORMATION
 AND COORDINATION.
  
 ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF
 THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN
 CONTACTING THIS OFFICE/REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPARTMENT
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop E ELECTRICAL
Rev No 1 Status F Date 2007-12-17 Cont ID  
Sent By dpalmer Date 2007-12-17 Time 12:09 Rev Time 0.00
Received By dpalmer Date 2007-12-13 Time 11:21 Sent To  
Notes
2007-12-17 12:10:11** DENIED **
  
  
 ** FIRST REVIEW UNDER NEW PERMIT APPLICATION.
 PREVIOUS REVIEWS DONE UNDER EXPIRED PERMIT #06110708.
  
  
 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE AFFECTIVE
 AS OF DECEMBER 8TH, 2006.
 PLANS REFLECT PREVIOUS CODES. PLEASE LIST THE
 FOLLOWING.
 2004 FBC W/2007 REVISIONS.
 2005 NFPA-70
 2003 NFPA-101
  
 2) NOTE: PLEASE SEE PREVIOUS NOTES UNDER REVIEW OF
 EXPIRED PERMIT MENTIONS THE HOUSE BILL 7121 WHICH
 REQUIRES A LEGALLY REQUIRED STAND-BY GENERATOR SYSTEM.
 PLEASE SEE THE PLANS ONLY INCLUDE A SYSTEM WHICH IS
 PORTABLE.
 WHEN PERMITTING OF SUBSTANTIALLY REMODELED OR NEW GAS
 STATIONS REQUIRE AN ON-SITE SYSTEM WITH A MINIMUM OF 72
 HRS ON-SITE FUEL.
 PLEASE ALSO SEE THAT IN ORDER TO USE A *KIRK-KEYED*
 SYSTEM AS PROPOSED A LETTER FROM A CORPORATE
 OFFICER/OWNER WOULD NEED TO ACCOMPANY PLANS THAT THE
 CONNECTION AND DISCONNECT OF SYSTEM WOULD ONLY BE
 PERFORMED BY QUALIFIED PERSONNEL.
 PLEASE SEE *LEGALLY REQUIRED* IN NEC 701 AS THIS DOES
 NOT PERMIT THIS KIRK KEY SYSTEM.
  
 3) NOTE: PLEASE SEE MISSING PRINTED NAME AND PRINTED
 LICENSE NUMBER FOR ENGINEER OF RECORD REQUIRED ON TITLE
 BLOCKS.
 FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE THE RESPONSE FROM DESIGN TEAM
 MENTIONED CLARIFICATION WAS NEEDED ON FBC AND CHAPTER
 13. DEPENDING ON THE SCOPE OF WORK, THIS IS WHAT WILL
 DETERMINE WHAT PARTS OF CHAPTER 13 APPLY.
 PLEASE SEE A-2 WHICH MENTIONS TO SEE ELECTRICAL PLANS
 FOR NEW LIGHTING, HOWEVER COULD NOT LOCATE ANY LIGHTING
 ON PLANS SUBMITTED.
 ANY NEW LIGHTING BEING INSTALLED IS TO MEET 13-415.2.
 NOTE ON A-2 MENTIONS NEWER LIGHTING TO REMAIN AND OLDER
 LIGHTING TO BE REPLACE. THIS NEEDS TO BE CLARIFIED IN
 SCOPE AT THIS TIME.
  
 ** AS THERE WILL BE SEVERAL CHANGES PLEASE KNOW THERE
 MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS
 TIME.
  
 ** ON PREVIOUS REVIEW THE NOTES MENTIONED IF THERE ARE
 ANY QUESTIONS OR COMMENTS TO PLEASE CONTACT THIS
 REVIEWER OR OFFICE.
 ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY
 COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE
 DO NOT HESITATE IN CONTACTING THIS OFFICE.
 PLEASE SEE BELOW FOR CONTACT INFORMATION.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]

Review Stop FIRE FIRE DEPARTMENT
Rev No 3 Status P Date 2008-04-15 Cont ID  
Sent By mawillia Date 2008-04-15 Time 15:49 Rev Time 0.00
Received By mawillia Date 2008-04-15 Time 15:01 Sent To  
Notes
2008-04-15 15:24:31*****APPROVED*****
  
 PLAN SHEETS A-1, A-2, LS-1, AND F-3 WERE STAMPED,
 INITIALED, AND DATED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW / WPBFR
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 2 Status F Date 2008-03-05 Cont ID  
Sent By mawillia Date 2008-03-05 Time 16:48 Rev Time 0.00
Received By mawillia Date 2008-03-05 Time 16:28 Sent To  
Notes
2008-03-05 16:47:34*****PROVISO*****
  
 THE PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED;
 HOWEVER THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED
 WHEN THE OTHER REVIEWERS HAVE BEEN SATISFIED.
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW / WPBFR
 561-805-6722

Review Stop FIRE FIRE DEPARTMENT
Rev No 1 Status F Date 2008-01-04 Cont ID  
Sent By mawillia Date 2008-01-04 Time 07:34 Rev Time 0.00
Received By mawillia Date 2008-01-03 Time 21:27 Sent To  
Notes
2008-01-03 22:30:44*****DENIED*****
  
  
 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR
 DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241.
  
 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL
 BE REMOVED FROM THE SITE AT THE END OF THE SHIFT OR
 MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION.
  
 3.WILL THE BUILDING OR PORTION OF THE BUILDING BE
 OCCUPIED DURING THE SCOPE OF WORK?IF SO, HOW WILL THE
 REQUIRED MEANS OF EGRESS BE MAINTAINED?
  
 4.PROVIDE A LIFE SAFETY PLAN SHEET SHOWING TRAVEL
 DISTANCE TO THE EXITS.
  
 5AN ADDITIONAL DEVICE DIRECTING PERSONS TO THE REAR
 EXIT MAY BE NEEDED IF THE EXIT/EMERGENCY LIGHT ABOVE
 THE REAR DOOR IS NOT VISIBLE.
  
 6INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION
 FOR THE NEW CEILING TILES IN TERMS OF CLASS A, B, OR
 C.
  
 7ON THE APPROPIATE PLAN SHEETS, RECTIFY THE
 DISCREPANCY OF THE DOOR SWING IN THE FOOD PREP AREA
 NEAR THE OVEN (FOR EXAMPLE SEE SHEET D-1, A-1, F-1 AS
 COMPARED TO E-2, E-4, P-1, P-4 .THE REFERENCED DOOR
 SHOULD NOT OPEN INTO THE PATH OF THE REAR EXIT ACCESS
 CORRIDOR.
  
 8PROVIDE DETAIL ON THE TYPES OF FOOD THAT WILL BE
 PREPARED ON THE ROLLER GRILLS AND PLEASE EXPLAIN "HOT
 SANDWICHES".
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING,
 INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH
 ITEM WAS ADDRESSED
  
  
 CAPT. MICHAEL A. WILLIAMS
 FIRE PLAN REVIEW / WPBFR
 561-805-6722

Review Stop I INCOMING/PROCESSING
Rev No 4 Status N Date 2008-05-15 Cont ID  
Sent By adarroug Date 2008-05-15 Time 08:54 Rev Time 0.00
Received By adarroug Date 2008-05-15 Time 08:54 Sent To  
Notes
2008-05-15 08:54:49TO "COMM" BD#12

Review Stop I INCOMING/PROCESSING
Rev No 3 Status N Date 2008-03-25 Cont ID  
Sent By adarroug Date 2008-03-25 Time 14:37 Rev Time 0.00
Received By adarroug Date 2008-03-25 Time 14:37 Sent To  
Notes
2008-03-25 14:37:27TO "COMM" BD#47

Review Stop I INCOMING/PROCESSING
Rev No 2 Status N Date 2008-02-08 Cont ID  
Sent By adarroug Date 2008-02-08 Time 11:11 Rev Time 0.00
Received By adarroug Date 2008-02-08 Time 11:11 Sent To  
Notes
2008-02-08 11:13:59TO "COMM" BD#5

Review Stop I INCOMING/PROCESSING
Rev No 1 Status N Date 2008-01-03 Cont ID  
Sent By mawillia Date 2008-01-03 Time 22:33 Rev Time 0.00
Received By mawillia Date 2007-12-10 Time 09:49 Sent To  
Notes
2007-12-10 09:49:14TO "BOB"#18

Review Stop M MECHANICAL (A/C)
Rev No 3 Status N Date 2008-03-26 Cont ID  
Sent By tgordon Date 2008-03-26 Time 16:04 Rev Time 0.25
Received By tgordon Date 2008-03-26 Time 16:04 Sent To  
Notes
2008-03-26 16:07:58GENERATOR AND FUEL STORAGE TANK REMOVED FROM PLANS.
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop M MECHANICAL (A/C)
Rev No 2 Status F Date 2008-02-12 Cont ID  
Sent By tgordon Date 2008-02-12 Time 11:09 Rev Time 1.30
Received By tgordon Date 2008-02-12 Time 11:09 Sent To  
Notes
2008-02-12 11:20:04PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM
 BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF
 THE PURPOSED DIESEL GENERATOR AND 1,200 GALLON FUEL
 STORAGE TANK, SEE 2004 FBC/M 1301.2.
  
 *** INFORMATIONAL ***
 A 1,200 GAL. FUEL TANK MUST BE 15 FT. FROM PROPERTY
 LINE THAT IS OR CAN BE BUILT UPON. ALSO 5 FT. FROM
 NEAREST SIDE OF ANY PUBLIC WAY. SEE 2003 N.F.P.A. 30
 CHAPTER 4 TABLE 4.3.2.1.1(B).
  
 ALSO THE PLAN WILL NEED TO GO TO PALM BEACH COUNTY
 DEPT. OF ENVIRONMENTAL RESOURCES MANAGEMENT (PHONE
 #561-233-2400) BEFORE RETURNING FOR A MECHANICAL
 REVIEW.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729
 E-MAIL; [email protected]

Review Stop M MECHANICAL (A/C)
Rev No 1 Status F Date 2008-02-12 Cont ID  
Sent By tgordon Date 2007-12-11 Time 09:08 Rev Time 0.20
Received By tgordon Date 2007-12-11 Time 09:08 Sent To  
Notes
2007-12-11 09:09:17SEE REVIEW NOTES FOR 02/12/08.
  
 NO MECHANICAL PLANS SUBMITTED, AND NO
 MECHANICAL PERMIT NUMBER APPLIED FOR AT
 THIS TIME.

Review Stop P PLUMBING
Rev No 3 Status P Date 2008-04-14 Cont ID  
Sent By kstevens Date 2008-04-14 Time 10:39 Rev Time 0.00
Received By kstevens Date 2008-04-14 Time 10:39 Sent To  
Notes
2008-04-14 11:03:12PER ENGINEER ONLY BOLD TYPE THIS PERMIT ON SHT P-2
 PLUMBING FIXTURE SCHEDULE.

Review Stop P PLUMBING
Rev No 2 Status F Date 2008-03-15 Cont ID  
Sent By kstevens Date 2008-03-15 Time 10:33 Rev Time 0.00
Received By kstevens Date 2008-03-15 Time 10:33 Sent To  
Notes
2008-03-15 10:39:36DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 ****FROM PREVIOUS REVIEW:
  
 1. ALL SHEETS WITH AN ARCHITECTURAL TITLE BLOCK
 REQUIRES THE FIRM ADDRESS. THE ADDRESS ON THE TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED SHEET).
 PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE BLOCK
 INFORMATION CORRELATE. FAC 61G1-16.004(1) & FS 481.219
 & 481.2055.
 ****RESPONSE NOTED, BUT NOT ALL SHEETS HAVE BEEN
 CHANGED. SEE SHEETS GR-1, A-1.1, A-2, F-1 & F-2.
  
 2. OK
 3. OK
 4. OK
 5. OK
 6. SHT P-2 PLUMBING FIXTURE SCHEDULE INDICATES A P-10
 TRAP PRIMER. THIS IS NOT INDICATED ON THE FLOOR PLAN,
 SANITARY RISER DIAGRAM NOR ON THE WATER RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
 ****RESPONSE NOTED, BUT THE TRAP PRIMER INFORMATION IS
 STILL INDICATED.
  
 7. OK
 8. OK
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
 ****NO RESPONSE, ONE SET OF VOIDED SHEETS WAS NOT
 SUBMITTED.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop P PLUMBING
Rev No 1 Status F Date 2007-12-18 Cont ID  
Sent By kstevens Date 2007-12-18 Time 08:16 Rev Time 0.00
Received By kstevens Date 2007-12-17 Time 18:59 Sent To  
Notes
2007-12-18 08:51:06DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS WITH AN ARCHITECTURAL TITLE BLOCK
 REQUIRES THE FIRM ADDRESS. THE ADDRESS ON THE TITLE
 BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD ON THE
 FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED SHEET).
 PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE BLOCK
 INFORMATION CORRELATE. FAC 61G1-16.004(1) & FS 481.219
 & 481.2055.
  
 2. PLUMBING SHEETS THE ENGINEER SHALL LEGIBLY INDICATE
 THEIR NAME ON EACH SHEET. FAC 61G15-23.002(2) & FS
 471.025.
  
 3. SHT P-1 KEY NOTES 20 & 21 NOT FOUND ON THE FLOOR
 PLAN. PLEASE CORRELATE. SECTION 106.1.1.
  
 4. SHT P-1 SHOWS A NEW 1-1/2" WATER SUPPLY CONNECTION
 OUTSIDE THE BUILDING, BUT THE WATER SUPPLY TO THE
 BUILDING IS SHOWN BY THE 3 COMPARTMENT SINK. PLEASE
 CLARIFY.SECTION 106.1.2.WILL THERE BE ANOTHER METER
 & BACKFLOW?
  
 5. SHT P-2 SANITARY RISER DIAGRAM ITEM P-4 IF THE SINK
 IS NOT INDIRECT WASTED, THEN IT SHALL BE VENTED.
 SECTION 901.2.1.
  
 6. SHT P-2 PLUMBING FIXTURE SCHEDULE INDICATES A P-10
 TRAP PRIMER. THIS IS NOT INDICATED ON THE FLOOR PLAN,
 SANITARY RISER DIAGRAM NOR ON THE WATER RISER DIAGRAM.
 PLEASE CLARIFY. SECTION 106.1.1.
  
 7. SHT P-2 THE P-11 WATER FILTER SHALL MEET THE
 REQUIREMENTS OF NSF-42. PLEASE SUBMIT THE MANUF
 SPECIFICATIONS. SECTION 611.1.
  
 8. SHT P-3 WATER MANIFOLD/FILTER DETAIL SHOWS A 1-1/2"
 C.W. TO MEN'S REST ROOM. THIS IS NOT REFLECTED ON THE
 WATER RISER DIAGRAM. PLEASE CORRELATE. SECTION
 106.1.1.
  
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUMBER,
 WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING
 THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE
 ALL VOID SHEETS FROM ALL PLANS AND PLACE
 ONE SET OF THEM LOOSELY ON TOP OF THE
 COLLATED PLANS TO BE REVIEWED.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]

Review Stop Z ZONING
Rev No 3 Status N Date 2008-03-26 Cont ID  
Sent By choops Date 2008-03-26 Time 14:04 Rev Time 0.00
Received By choops Date 2008-03-26 Time 14:04 Sent To  
Notes
2008-03-26 14:06:43***N/R - RESUB #2***
  
 *ZONING REVIEW NOT REQUIRED - GENERATOR HAS BEEN
 REMOVED FROM PLANS.

Review Stop Z ZONING
Rev No 2 Status F Date 2008-02-19 Cont ID  
Sent By choops Date 2008-02-19 Time 16:05 Rev Time 0.00
Received By choops Date 2008-02-19 Time 16:05 Sent To  
Notes
2008-02-19 16:15:06***FAILED - RESUB #1***
  
  
 1)AS THE PLANS NOW SHOW A NEWLY PROPOSED DIESEL
 GENERATOR, PRIOR TO THE ISSUANCE OF A BUILDING PERMIT,
 A MINOR AMENDMENT TO THE NORTHPOINT COMMERCIAL PLANNED
 DEVELOPMENT SHALL BE SUBMITTED TO AND APPROVED BY THE
 PLANNING AND ZONING DEPARTMENT.
  
 NOTE:PROPOSED GENERATOR IS REQUIRED TO BE SCREENED
 AND LANDSCAPED IN ACCORDANCE WITH SECTION 94-444(B) OF
 THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS
 (ZLDRS).
  
 NOTE:AS PER SECTION 94-305(B)(4) OF THE ZLDRS:
 MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET
 INTO A REQUIRED SETBACK.
  
  
 QUESTIONS/COMMENTS, PLEASE CONTACT ERIC SCHNEIDER
 PLANNING AND ZONING DEPARTMENT 822-1435

Review Stop Z ZONING
Rev No 1 Status N Date 2007-12-11 Cont ID  
Sent By choops Date 2007-12-11 Time 10:45 Rev Time 0.00
Received By choops Date 2007-12-11 Time 10:45 Sent To  
Notes
2007-12-11 10:45:48*ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK
 DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE.