| Plan Review Stops For Permit 07120059 |
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
4 |
Status |
P |
Date |
2008-05-29 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-05-29 |
Time |
10:37 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-05-28 |
Time |
17:34 |
Sent To |
PC |
|
| Notes |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
3 |
Status |
F |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-04-14 |
Time |
07:50 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-04-09 |
Time |
12:33 |
Sent To |
|
|
| Notes |
| 2008-04-10 09:56:38 | BUILDING PLAN REVIEW #3 4-9-08 | | | PERMIT: 07120059 | | | ADD: 2995 45TH STREET #562 | | | CONT: R.D. LANGE CONST. INC. | | | TEL: (863)661-6305 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 3RD | | | ACTION: DENIED | | | | | | NOTE: THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 2)OK | | | | | | **NOTED** SHEET COV-0 STATES PRODUCT APPROVAL NUMBERS | | | FL4553/ FL1610.1 AND FL5115 HOWEVER, NONE OF THESE | | | SHEETS WERE SUBMITTED. IF THESE ARE THE PRODUCT | | | APPROVALS WHICH WILL BE USED ON THE PROJECT, PROVIDE | | | THE STATE COVER SHEET ALONG WITH THE INSTALLATION | | | REPORT INDICATING WHICH SYSTEM OR ITEMS WILL BE USED. | | | SUBMIT THE STATE COVER SHEET WITH THE CORRECT | | | INSTALLATION REPORTS. THE STATE COVER SHEET AND REPORT | | | SHALL BE BOUND TOGETHER TO AVOID CONFUSION. | | | | | | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS | | | THAT ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL | | | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT | | | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT | | | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS | | | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED | | | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE | | | TEST. | | | | | | 4)OK. | | | 5)OK. | | | 6)OK | | | 7)OK | | | 8)OK | | | 9)OK | | | 10) OK | | | 11) OK | | | | | | **NEW** | | | GENERATOR INFORMATION REMOVED FROM PLANS. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2008-02-19 |
Time |
14:24 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2008-02-19 |
Time |
07:58 |
Sent To |
|
|
| Notes |
| 2008-02-19 14:24:51 | BUILDING PLAN REVIEW | | | PERMIT: 07120059 | | | ADD: 2995 45TH STREET #562 | | | CONT: R.D. LANGE CONST. INC. | | | TEL: (863)661-6305 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 2ND 2-19-08 | | | ACTION: DENIED | | | | | | 1B) FL S S 713.13 NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE | | | INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH | | | REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS | | | NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR | | | OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS | | | OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE | | | DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER | | | INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN | | | ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9. | | | | | | **NOTED** HOWEVER, FL#2484-R1 IS MISSING THE | | | INSTALLATION REPORT. FL#3393 CODE VERSION IS 2001. WE | | | ARE PRESENTLY UNDER THE 2004 CODE VERSION. TWO APPROVED | | | AND COMPLETE SEPARATE SETS OF PRODUCT APPROVALS SHALL | | | BE SUBMITTED. IF THE GLAZING IS NON-IMPACT, PROVIDE THE | | | PRODUCT APPROVAL FOR THE IMPACT PROTECTION (SHUTTERS). | | | PLEASE MAKE SURE THAT THE INSTALLATION REPORT IS | | | ATTATCHED TO EACH PRODUCT APPROVAL.** | | | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS | | | THAT ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL | | | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT | | | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT | | | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS | | | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED | | | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE | | | TEST. | | | | | | 4)OK. | | | 5)OK. | | | 6)OK | | | 7)OK | | | 8)OK | | | 9)OK | | | 10) OK | | | 11) OK | | | | | | **NEW** | | | A) 61G1-16.004 TITLE BLOCK FOR MARK DAVID SHALL INCLUDE | | | THE FOLLOWING INFORMATION. | | | A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR | | | INTERIOR DESIGN DRAWINGS AND SPECIFICATION | | | IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A | | | MINIMUM, CONTAIN THE FOLLOWING INFORMATION: | | | (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. | | | (2) FIRM LICENSE NUMBER. | | | (3) NAME OR IDENTIFICATION OF PROJECT. | | | (4) DATE PREPARED. | | | (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. | | | (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING | | | THE DOCUMENT. | | | | | | B)PROVIDE THE ENGINEERING CALCULATIONS FOR THE | | | GENERATOR.THE CALCULATIONS SHALL INCLUDE THE ANCHORAGE | | | AGAINST OVERTURNING, UPLIFT AND SLIDING PER 1609.1.3. | | | INDICATE ON THE PLANS THE ELEVATION FOR THE GENERATOR | | | SLAB.ALL INFORMATION REGUARDING THE SLAB NEEDS TO BE | | | SHOWN ON THE PLANS ALONG WITH WIND DESIGN CRITERIA PER | | | 1603.1.4. | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | FAX (561) 805-6676 | | | [email protected] |
|
|
| Review Stop |
B |
BUILDING (STRUCTURAL) |
| Rev No |
1 |
Status |
F |
Date |
2007-12-12 |
|
|
Cont ID |
|
| Sent By |
mjacobs |
Date |
2007-12-12 |
Time |
12:55 |
Rev Time |
0.00 |
| Received By |
mjacobs |
Date |
2007-12-12 |
Time |
06:43 |
Sent To |
|
|
| Notes |
| 2007-12-12 12:55:55 | | | | BUILDING PLAN REVIEW | | | PERMIT: 07120059 | | | ADD: 2995 45TH STREET #562 | | | CONT: R.D. LANGE CONST. INC. | | | TEL: (863)661-6305 | | | FL BLD CODE= 2004 FLORIDA BUILDING CODE | | | W/ 2007 FBC REVISIONS | | | * WEST PALM BEACH AMENDMENTS | | | | | | REVIEW: 1ST 12/12/07 | | | ACTION: DENIED | | | | | | 1A)--- VERY IMPORTANT STATEMENT --- | | | PLEASE DO NOT IGNORE! | | | WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION & | | | REMOVE & REPLACE ANY PAGES AS NECESSARY. A TRANSMITTAL | | | LETTER LISTING THE ORIGINAL REVIEW COMMENT NUMBER, WITH | | | A DESCRIPTION OF THE REVISION MADE, IDENTIFYING THE | | | SHEET OR SPECIFICATION PAGE WHERE THE CHANGES CAN BE | | | FOUND WILL HELP TO EXPEDITE YOUR PERMIT. THANK YOU FOR | | | YOUR ANTICIPATED COOPERATION. | | | | | | 1B) FL S S 713.13NOTICE OF COMMENCEMENT, TO BE FILED | | | WITH THE CLERK OF THE COURT.NOTE: 713.13(2) IF THE | | | WORK DESCRIBED IN THE NOTICE OF COMMENCEMENT IS NOT | | | ACTUALLY COMMENCED WITHIN 90 DAYS AFTER THE RECORDING | | | THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: 713.13(6) | | | THE POSTING OF THE NOTICE OF COMMENCEMENT AT THE | | | CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. | | | | | | 1C) PLANS SUBMITTED FOR PERMIT (FIRST TIME REVIEW) | | | AFTER JULY 1ST, 2007 SHALL BE REVIEWED TO THE 2004 FBC | | | BUILDING WITH THE 2007 REVISIONS. | | | | | | 2)NOTE: A ?DEMOLITION PERMIT? IS REQUIRED FOR THE | | | INTERIOR DEMOLITION. EACH EXISTING BUILDING WHICH | | | REQUIRES A PERMIT SHALL CONTAIN AN ASBESTOS | | | NOTIFICATION STATEMENT WHICH INDICATES THE OWNER?S OR | | | OPERATOR?S RESPONSIBILITY TO COMPLY WITH THE PROVISIONS | | | OF SECTION 469.003, FLORIDA STATUTES, AND TO NOTIFY THE | | | DEPARTMENT OF ENVIRONMENTAL PROTECTION OF HIS OR HER | | | INTENTIONS TO REMOVE ASBESTOS, WHEN APPLICABLE, IN | | | ACCORDANCE WITH STATE AND FEDERAL LAW. FBC: 105.9. | | | | | | | | | 3)106.3.3* PRODUCT APPROVALS- 2004 THOSE PRODUCTS | | | THAT ARE REGULATED BY DCA | | | RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN WRITING BY | | | THE DESIGNER OF RECORD PRIOR TO SUBMITTAL FOR | | | JURISDICTIONAL APPROVAL. SUBMIT THE PRODUCT APPROVAL | | | FOR THE STOREFRONT, MULLIONS AND DOORS. ON THE PRODUCT | | | APPROVALS CIRCLE OR HI-LIGHT EACH ITEM THAT IS RELEVANT | | | TO THE INSTALLATION. IF THE NEW STOREFRONT AND DOORS | | | ARE NON-IMPACT, HURRICANE PROTECTION WILL BE REQUIRED | | | PER FBC: 1609.1.4 GLAZED OPENINGS LOCATED WITHIN 30 | | | FEET SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE | | | TEST. | | | | | | 4)TABLE 803.5 MINIMUM INTERIOR FINISH CLASSIFICATION; | | | PROVIDE INFORMATION BASED ON INTERIOR FINISH | | | REQUIREMENTS BASED ON OCCUPANCY. SHEET A-1 REFERS TO | | | SHEET F-3 FOR THE DOOR, FRAME AND FINISH SCHEDULE | | | HOWEVER; SHEET F-3 IS MISSING FROM THE DRAWINGS. | | | | | | 5)SHEET A-1 REFERENCES A-3 AND A-4 FOR ADDITIONAL | | | INFORMATION, THESE PAGES ARE NOT WITH THE SETS OF PLANS | | | SUBMITTED. | | | | | | 6)FBC 105.9 EACH BUILDING WHICH REQUIRES A PERMIT FOR | | | RENOVATION SHALL CONTAIN AN ASBESTOS NOTIFICATION | | | STATEMENT WHICH INDICATES THE OWNER?S OPERATOR?S | | | RESPONSIBILITY TO COMPLY WITH THE PROVISIONS OF SECTION | | | 469.003, FLORIDA STATUTES, AND TO NOTIFY THE DEPARTMENT | | | OF PROTECTION OF HIS OR HER INTENTIONS TO REMOVE | | | ASBESTOS, WHEN APPLICABLE, IN ACCORDANCE WITH STATE AND | | | FEDERAL LAW. | | | | | | 7)THE COUNTER AND CHECK-OUT AISLES SHALL MEET THE | | | REQUIREMENTS OF FBC 11-7. SHOW THE ELEVATION DETAILS OF | | | THE ACCESSIBLE COUNTER WHERE A POTION OF THE MAIN | | | COUNTER SHALL BE A MINIMUM OF 36 INCHES IN LENGTH AND A | | | MAXIMUM HEIGHT OF 36 INCHES. | | | | | | 8)2004 FBC EXISTING | | | 301.5 A DESIGN PROFESSIONAL OR AN OWNER MUST ELECT ONE | | | OR A COMBINATION OF LEVELS OF ALTERATION PURSUANT TO | | | SECTIONS 303, 304 AND 305 OF THIS CODE. | | | | | | 9)1603.1.4 THE FOLLOWING INFORMATION RELATED TO WIND | | | LOADS SHALL BE SHOWN, REGARDLESS OF WHETHER WIND LOADS | | | GOVERN THE DESIGN OF THE LATERAL-FORCE-RESISTING SYSTEM | | | OF THE BUILDING: | | | 1.BASIC WIND SPEED (3-SECOND GUST), MILES PER HOUR | | | (KM/HR). | | | 2.WIND IMPORTANCE FACTOR, I W , AND BUILDING | | | CLASSIFICATION FROM TABLE 1604.5 OR TABLE 6-1, ASCE 7 | | | AND BUILDING CLASSIFICATION IN TABLE 1-1, ASCE 7. | | | 3.WIND EXPOSURE, IF MORE THAN ONE WIND EXPOSURE IS | | | UTILIZED, THE WIND EXPOSURE AND APPLICABLE WIND | | | DIRECTION SHALL BE INDICATED. | | | 4.THE APPLICABLE ENCLOSURE CLASSIFICATIONS AND, IF | | | DESIGNING WITH ASCE 7, INTERNAL PRESSURE COEFFICIENT. | | | 5.COMPONENTS AND CLADDING. THE DESIGN WIND | | | PRESSURES IN TERMS OF PSF (KN/M 2 ) TO BE USED FOR THE | | | SELECTION OF EXTERIOR COMPONENTS AND CLADDING MATERIALS | | | NOT SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN | | | PROFESSIONAL. | | | | | | 10)SUBMIT A WALL LEGEND WITH THE DIFFERENT TYPES OF | | | WALL TO BE INSTALLED AT THIS PROJECT. CONSTRUCTION | | | DOCUMENTS SHALL BE OF SUFFICIENT CLARITY TO INDICATE | | | THE LOCATION, NATURE AND EXTENT OF THE WORK PROPOSED | | | AND SHOW IN DETAIL THAT IT WILL CONFORM TO THE | | | PROVISIONS OF THE CODE. | | | | | | 11) A LIFE SAFETY PLAN SHALL BE SUBMITTED SHOWING ALL | | | MEANS OF EGRESS WHICH INCLUDE THE EXIT ACCESS, THE EXIT | | | AND THE EXIT DISCHARGE. PER CH. 10 | | | | | | MYRON JACOBS | | | BUILDING PLAN REVIEWER | | | (561)805-6726 | | | [email protected] | | | |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
4 |
Status |
P |
Date |
2008-05-28 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-05-28 |
Time |
14:49 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-05-28 |
Time |
14:49 |
Sent To |
|
|
| Notes |
| 2008-05-28 14:50:01 | MUST USE SE RATED TRANSFER SWITCH AS INDICATED. |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
3 |
Status |
F |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-03-26 |
Time |
12:39 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-03-26 |
Time |
12:39 |
Sent To |
|
|
| Notes |
| 2008-03-26 12:39:39 | ** DENIEDREVIEW** | | | | | | ** PLANS HAVE NOW BEEN COMPLETELY REVISED WHICH HAS | | | CREATE NEW COMMENTS. | | | | | | 1) NOTE: PLEASE PROVIDE INFORMATION ON THE EQUIPMENT | | | WHICH IS NOW BEING PROPOSED WHICH IS LISTED AS A | | | TRANSFER SWITCH AND BEING SERVICE ENTRANCE RATED. | | | PLEASE SEE THE STATUTES REQUIRES A TRANSFER SWITCH | | | WHICH IS ALSO DEFINED IN THE CODE. THIS MUST PROVIDE A | | | FAIL-SAFE OPERATION FOR THOSE TWO SIDES OF INCOMING | | | POWER FROM NORMAL AND EMERGENCY SO THAT IT IS NOT | | | POSSIBLE FOR POWER TO BE FED INTO SERVICE AT ANY | | | ONE-TIME. AS A*KEYED INTERLOCK*WHICH IS ONLY NOW | | | BEING SHOWN, THIS DOES NOT PROVIDE THIS OPERATION. | | | 702.6, 100, 110.3, 90.7 ETC. | | | | | | THIS IS A LIFE SAFETY, FIRE AND PROPERTY HAZARD. | | | | | | | | | | | | ** IMPORTANT** | | | ONCE ALL REVIEWS ARE DONE AND PLANS ARE PICKED UP FOR | | | CORRECTIONS, PLEASE BE SURE TO COMPLETELY REMOVE ALL | | | OLD/VOIDED SHEETS AND ONLY INSERT NEW REVISED SHEETS | | | INTO TWO COMPLETE SETS FOR REVIEW AND STAMPING. DO NOT | | | LEAVE ANY OLD/VOIDED SHEETS IN SETS. | | | PLEASE DO NOT ATTACH SUPPORTING DOCUMENTS TO PLANS. ANY | | | ADDITIONAL DOCUMENTATION SUCH AS PRODUCT APPROVALS, | | | SPEC/CUT SHEETS, CALCULATIONS ETC SHOULD BE PLACED INTO | | | TWO SETS/FOLDERS/BINDERS ETC. | | | PLEASE KNOW ONLY ONE SET OF THE OLD/VOIDED SHEETS | | | SHOULD BE SUBMITTED FOR REFERENCE. | | | THIS WILL HELP IN THE REVIEW PROCESS AND AVOID ANY | | | DELAYS. | | | | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
2 |
Status |
F |
Date |
2008-02-10 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2008-02-10 |
Time |
10:24 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2008-02-10 |
Time |
10:24 |
Sent To |
|
|
| Notes |
| 2008-02-11 10:25:22 | ** DENIED 2ND REVIEW ** | | | | | | ** PLEASE SEE NEW NOTES BASED ON CHANGES MADE TO | | | PLANS. | | | | | | 1) NOTE: PLEASE SEE THE CODE REFERENCES ON PLANS STILL | | | INDICATE THE 2002 NEC/ NFPA-70. | | | PLEASE SEE THIS WAS DONE ON ELECTRICAL SHEETS HOWEVER | | | PLEASE SEE SHEET COV -0. | | | PLEASE ALSO BE SURE TO ADD NFPA-110 2002 FOR NEW | | | GENERATOR. | | | FBC 106.1.2 FOR COORDINATION. | | | | | | 2) NOTE: PLEASE KNOW PLANS HAVE BEEN REVISED WITH NEW | | | GENERATOR AS REQUIRED HOWEVER PLEASE SEE COMMENTS FROM | | | OTHER TRADES WHICH WILL AFFECT PLANS. | | | PLEASE SUBMIT THE MANUFACTURES SPECS/CUT SHEETS FOR NEW | | | PROPOSED GENERATOR, TRANSFER SWITCH AND SUB BASE FUEL | | | TANK. | | | THE FUEL TANK WILL BE UNDER REVIEW OF FIRE MARSHAL AND | | | MECHANICAL REVIEW. | | | PLEASE INDICATE THE ELEVATION LEVEL OF ANY OF THE | | | REQUIRED EPSS SYSTEM EQUIPMENT INCLUDING GENERATOR PER | | | CHAPTER 7 OF NFPA 7.2.3 | | | 110.3, 90.7, NFPA-110 | | | | | | 3) NOTE: PLEASE SEE THE APPLIED VALUE FOR COMPLETE | | | SCOPE OF WORK NOW ON PLANS NEEDS TO BE UPDATED PER FBC | | | 108.3 | | | PLEASE KNOW AS THE PLANS INCLUDE THE GENERATOR ETC THE | | | COST INCLUDING LABOR, EQUIPMENT, MATERIALS, DESIGN COST | | | ETC IS REQUIRED WHETHER OR NOT ANY OF THESE ITEMS ARE | | | OWNER SUPPLIED. | | | | | | 4) NOTE: PLEASE SEE PREVIOUS REVIEW NOTES. AS MENTIONED | | | IF ANY NEW LIGHTING WILL BE PROPOSED AS STATED ON | | | ARCHITECTURAL PLANS. THESE MUST COMPLY WITH CHAPTER 13 | | | OF THE 2004 FBC W/2007 REVISIONS. | | | PLEASE SEE 13-415.2, 13-415.2.ABC.1.1 AND .1.2 FOR | | | REQUIRED LIGHTING PERFORMANCE CALCULATIONS. | | | | | | 5) NOTE: PLEASE VERIFY GROUNDING AT THE GENERATOR. 250 | | | THERE IS NO INFORMATION ON TRANSFER SWITCH WHICH IS | | | NEEDED. | | | IS THIS SERVICE ENTRANCE RATED AS REQUIRED? | | | IS THIS 3 OR 4-POLE? THIS WILL AFFECT THE GROUNDING AT | | | THE GENERATOR. | | | PLEASE SEE MANY QUESTIONS ARE OUTSTANDING WHICH MAY | | | AFFECT REVIEW NOTES ON THE FOLLOWING REVIEW. | | | 230.70, 230.71, 250.20,250.50 ETC | | | FBC 106.3.5.1.2 AND 106.1.2 FOR ADDITIONAL INFORMATION | | | AND COORDINATION. | | | | | | ** PLEASE SUBMIT THE ABOVE INFORMATION FOR REVIEW. IF | | | THERE ARE ANY QUESTIONS PLEASE DO NOT HESITATE IN | | | CONTACTING THIS OFFICE/REVIEWER. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPARTMENT | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
E |
ELECTRICAL |
| Rev No |
1 |
Status |
F |
Date |
2007-12-17 |
|
|
Cont ID |
|
| Sent By |
dpalmer |
Date |
2007-12-17 |
Time |
12:09 |
Rev Time |
0.00 |
| Received By |
dpalmer |
Date |
2007-12-13 |
Time |
11:21 |
Sent To |
|
|
| Notes |
| 2007-12-17 12:10:11 | ** DENIED ** | | | | | | | | | ** FIRST REVIEW UNDER NEW PERMIT APPLICATION. | | | PREVIOUS REVIEWS DONE UNDER EXPIRED PERMIT #06110708. | | | | | | | | | 1) NOTE: PLEASE SEE THE FOLLOWING CODES ARE AFFECTIVE | | | AS OF DECEMBER 8TH, 2006. | | | PLANS REFLECT PREVIOUS CODES. PLEASE LIST THE | | | FOLLOWING. | | | 2004 FBC W/2007 REVISIONS. | | | 2005 NFPA-70 | | | 2003 NFPA-101 | | | | | | 2) NOTE: PLEASE SEE PREVIOUS NOTES UNDER REVIEW OF | | | EXPIRED PERMIT MENTIONS THE HOUSE BILL 7121 WHICH | | | REQUIRES A LEGALLY REQUIRED STAND-BY GENERATOR SYSTEM. | | | PLEASE SEE THE PLANS ONLY INCLUDE A SYSTEM WHICH IS | | | PORTABLE. | | | WHEN PERMITTING OF SUBSTANTIALLY REMODELED OR NEW GAS | | | STATIONS REQUIRE AN ON-SITE SYSTEM WITH A MINIMUM OF 72 | | | HRS ON-SITE FUEL. | | | PLEASE ALSO SEE THAT IN ORDER TO USE A *KIRK-KEYED* | | | SYSTEM AS PROPOSED A LETTER FROM A CORPORATE | | | OFFICER/OWNER WOULD NEED TO ACCOMPANY PLANS THAT THE | | | CONNECTION AND DISCONNECT OF SYSTEM WOULD ONLY BE | | | PERFORMED BY QUALIFIED PERSONNEL. | | | PLEASE SEE *LEGALLY REQUIRED* IN NEC 701 AS THIS DOES | | | NOT PERMIT THIS KIRK KEY SYSTEM. | | | | | | 3) NOTE: PLEASE SEE MISSING PRINTED NAME AND PRINTED | | | LICENSE NUMBER FOR ENGINEER OF RECORD REQUIRED ON TITLE | | | BLOCKS. | | | FAC 61G15-23.002 | | | | | | 4) NOTE: PLEASE SEE THE RESPONSE FROM DESIGN TEAM | | | MENTIONED CLARIFICATION WAS NEEDED ON FBC AND CHAPTER | | | 13. DEPENDING ON THE SCOPE OF WORK, THIS IS WHAT WILL | | | DETERMINE WHAT PARTS OF CHAPTER 13 APPLY. | | | PLEASE SEE A-2 WHICH MENTIONS TO SEE ELECTRICAL PLANS | | | FOR NEW LIGHTING, HOWEVER COULD NOT LOCATE ANY LIGHTING | | | ON PLANS SUBMITTED. | | | ANY NEW LIGHTING BEING INSTALLED IS TO MEET 13-415.2. | | | NOTE ON A-2 MENTIONS NEWER LIGHTING TO REMAIN AND OLDER | | | LIGHTING TO BE REPLACE. THIS NEEDS TO BE CLARIFIED IN | | | SCOPE AT THIS TIME. | | | | | | ** AS THERE WILL BE SEVERAL CHANGES PLEASE KNOW THERE | | | MAY BE NEW COMMENTS WHICH CAN NOT BE MADE AT THIS | | | TIME. | | | | | | ** ON PREVIOUS REVIEW THE NOTES MENTIONED IF THERE ARE | | | ANY QUESTIONS OR COMMENTS TO PLEASE CONTACT THIS | | | REVIEWER OR OFFICE. | | | ** THIS OFFICE EXPRESSES THAT IF THERE ARE ANY | | | COMMENTS, QUESTIONS OR CLARIFICATION NEEDED TO PLEASE | | | DO NOT HESITATE IN CONTACTING THIS OFFICE. | | | PLEASE SEE BELOW FOR CONTACT INFORMATION. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW II | | | CONSTRUCTION SERVICES DEPT. | | | CITY OF WEST PALM BEACH | | | 561-805-6717 | | | [email protected] |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
3 |
Status |
P |
Date |
2008-04-15 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-04-15 |
Time |
15:49 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-04-15 |
Time |
15:01 |
Sent To |
|
|
| Notes |
| 2008-04-15 15:24:31 | *****APPROVED***** | | | | | | PLAN SHEETS A-1, A-2, LS-1, AND F-3 WERE STAMPED, | | | INITIALED, AND DATED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW / WPBFR | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
2 |
Status |
F |
Date |
2008-03-05 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-03-05 |
Time |
16:48 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-03-05 |
Time |
16:28 |
Sent To |
|
|
| Notes |
| 2008-03-05 16:47:34 | *****PROVISO***** | | | | | | THE PREVIOUS FIRE REVIEW COMMENTS HAVE BEEN ADDRESSED; | | | HOWEVER THE APPROPIATE PLAN SHEETS TO BE FIRE-STAMPED | | | WHEN THE OTHER REVIEWERS HAVE BEEN SATISFIED. | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW / WPBFR | | | 561-805-6722 |
|
|
| Review Stop |
FIRE |
FIRE DEPARTMENT |
| Rev No |
1 |
Status |
F |
Date |
2008-01-04 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-04 |
Time |
07:34 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2008-01-03 |
Time |
21:27 |
Sent To |
|
|
| Notes |
| 2008-01-03 22:30:44 | *****DENIED***** | | | | | | | | | 1.STRUCTURES UNDERGOING CONSTRUCTION, ALTERATION, OR | | | DEMOLITION OPERATIONS SHALL COMPLY WITH NFPA 241. | | | | | | 2.COMBUSTIBLE WASTE MATERIALS, DUST, AND DEBRIS SHALL | | | BE REMOVED FROM THE SITE AT THE END OF THE SHIFT OR | | | MORE FREQUENTLY AS NECESSARY FOR SAFE OPERATION. | | | | | | 3.WILL THE BUILDING OR PORTION OF THE BUILDING BE | | | OCCUPIED DURING THE SCOPE OF WORK?IF SO, HOW WILL THE | | | REQUIRED MEANS OF EGRESS BE MAINTAINED? | | | | | | 4.PROVIDE A LIFE SAFETY PLAN SHEET SHOWING TRAVEL | | | DISTANCE TO THE EXITS. | | | | | | 5AN ADDITIONAL DEVICE DIRECTING PERSONS TO THE REAR | | | EXIT MAY BE NEEDED IF THE EXIT/EMERGENCY LIGHT ABOVE | | | THE REAR DOOR IS NOT VISIBLE. | | | | | | 6INDICATE THE MINIMUM INTERIOR FINISH CLASSIFICATION | | | FOR THE NEW CEILING TILES IN TERMS OF CLASS A, B, OR | | | C. | | | | | | 7ON THE APPROPIATE PLAN SHEETS, RECTIFY THE | | | DISCREPANCY OF THE DOOR SWING IN THE FOOD PREP AREA | | | NEAR THE OVEN (FOR EXAMPLE SEE SHEET D-1, A-1, F-1 AS | | | COMPARED TO E-2, E-4, P-1, P-4 .THE REFERENCED DOOR | | | SHOULD NOT OPEN INTO THE PATH OF THE REAR EXIT ACCESS | | | CORRIDOR. | | | | | | 8PROVIDE DETAIL ON THE TYPES OF FOOD THAT WILL BE | | | PREPARED ON THE ROLLER GRILLS AND PLEASE EXPLAIN "HOT | | | SANDWICHES". | | | | | | | | | TO EXPEDITE THE PLAN REVIEW PROCESS WHEN RESUBMITTING, | | | INCLUDE A RESPONSE LETTER INDICATING HOW/WHERE EACH | | | ITEM WAS ADDRESSED | | | | | | | | | CAPT. MICHAEL A. WILLIAMS | | | FIRE PLAN REVIEW / WPBFR | | | 561-805-6722 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
4 |
Status |
N |
Date |
2008-05-15 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-05-15 |
Time |
08:54 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-05-15 |
Time |
08:54 |
Sent To |
|
|
| Notes |
| 2008-05-15 08:54:49 | TO "COMM" BD#12 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-25 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-03-25 |
Time |
14:37 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-03-25 |
Time |
14:37 |
Sent To |
|
|
| Notes |
| 2008-03-25 14:37:27 | TO "COMM" BD#47 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
2 |
Status |
N |
Date |
2008-02-08 |
|
|
Cont ID |
|
| Sent By |
adarroug |
Date |
2008-02-08 |
Time |
11:11 |
Rev Time |
0.00 |
| Received By |
adarroug |
Date |
2008-02-08 |
Time |
11:11 |
Sent To |
|
|
| Notes |
| 2008-02-08 11:13:59 | TO "COMM" BD#5 |
|
|
| Review Stop |
I |
INCOMING/PROCESSING |
| Rev No |
1 |
Status |
N |
Date |
2008-01-03 |
|
|
Cont ID |
|
| Sent By |
mawillia |
Date |
2008-01-03 |
Time |
22:33 |
Rev Time |
0.00 |
| Received By |
mawillia |
Date |
2007-12-10 |
Time |
09:49 |
Sent To |
|
|
| Notes |
| 2007-12-10 09:49:14 | TO "BOB"#18 |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
3 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-03-26 |
Time |
16:04 |
Rev Time |
0.25 |
| Received By |
tgordon |
Date |
2008-03-26 |
Time |
16:04 |
Sent To |
|
|
| Notes |
| 2008-03-26 16:07:58 | GENERATOR AND FUEL STORAGE TANK REMOVED FROM PLANS. | | | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
2 |
Status |
F |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2008-02-12 |
Time |
11:09 |
Rev Time |
1.30 |
| Received By |
tgordon |
Date |
2008-02-12 |
Time |
11:09 |
Sent To |
|
|
| Notes |
| 2008-02-12 11:20:04 | PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE & | | | REFERENCED CODES WITH 2007 REVISIONS, CITY OF WEST PALM | | | BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA | | | ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES | | | (F.S.). | | | | | | *** DENIED *** | | | 1) PLEASE SUBMIT A SITE PLAN SHOWING THE LOCATION OF | | | THE PURPOSED DIESEL GENERATOR AND 1,200 GALLON FUEL | | | STORAGE TANK, SEE 2004 FBC/M 1301.2. | | | | | | *** INFORMATIONAL *** | | | A 1,200 GAL. FUEL TANK MUST BE 15 FT. FROM PROPERTY | | | LINE THAT IS OR CAN BE BUILT UPON. ALSO 5 FT. FROM | | | NEAREST SIDE OF ANY PUBLIC WAY. SEE 2003 N.F.P.A. 30 | | | CHAPTER 4 TABLE 4.3.2.1.1(B). | | | | | | ALSO THE PLAN WILL NEED TO GO TO PALM BEACH COUNTY | | | DEPT. OF ENVIRONMENTAL RESOURCES MANAGEMENT (PHONE | | | #561-233-2400) BEFORE RETURNING FOR A MECHANICAL | | | REVIEW. | | | | | | MECHANICAL PLAN REVIEW BY; | | | TOM GORDON (561) 805-6729 | | | E-MAIL; [email protected] |
|
|
| Review Stop |
M |
MECHANICAL (A/C) |
| Rev No |
1 |
Status |
F |
Date |
2008-02-12 |
|
|
Cont ID |
|
| Sent By |
tgordon |
Date |
2007-12-11 |
Time |
09:08 |
Rev Time |
0.20 |
| Received By |
tgordon |
Date |
2007-12-11 |
Time |
09:08 |
Sent To |
|
|
| Notes |
| 2007-12-11 09:09:17 | SEE REVIEW NOTES FOR 02/12/08. | | | | | | NO MECHANICAL PLANS SUBMITTED, AND NO | | | MECHANICAL PERMIT NUMBER APPLIED FOR AT | | | THIS TIME. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
3 |
Status |
P |
Date |
2008-04-14 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-04-14 |
Time |
10:39 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-04-14 |
Time |
10:39 |
Sent To |
|
|
| Notes |
| 2008-04-14 11:03:12 | PER ENGINEER ONLY BOLD TYPE THIS PERMIT ON SHT P-2 | | | PLUMBING FIXTURE SCHEDULE. |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
2 |
Status |
F |
Date |
2008-03-15 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2008-03-15 |
Time |
10:33 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2008-03-15 |
Time |
10:33 |
Sent To |
|
|
| Notes |
| 2008-03-15 10:39:36 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | ****FROM PREVIOUS REVIEW: | | | | | | 1. ALL SHEETS WITH AN ARCHITECTURAL TITLE BLOCK | | | REQUIRES THE FIRM ADDRESS. THE ADDRESS ON THE TITLE | | | BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD ON THE | | | FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED SHEET). | | | PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE BLOCK | | | INFORMATION CORRELATE. FAC 61G1-16.004(1) & FS 481.219 | | | & 481.2055. | | | ****RESPONSE NOTED, BUT NOT ALL SHEETS HAVE BEEN | | | CHANGED. SEE SHEETS GR-1, A-1.1, A-2, F-1 & F-2. | | | | | | 2. OK | | | 3. OK | | | 4. OK | | | 5. OK | | | 6. SHT P-2 PLUMBING FIXTURE SCHEDULE INDICATES A P-10 | | | TRAP PRIMER. THIS IS NOT INDICATED ON THE FLOOR PLAN, | | | SANITARY RISER DIAGRAM NOR ON THE WATER RISER DIAGRAM. | | | PLEASE CLARIFY. SECTION 106.1.1. | | | ****RESPONSE NOTED, BUT THE TRAP PRIMER INFORMATION IS | | | STILL INDICATED. | | | | | | 7. OK | | | 8. OK | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | ****NO RESPONSE, ONE SET OF VOIDED SHEETS WAS NOT | | | SUBMITTED. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
P |
PLUMBING |
| Rev No |
1 |
Status |
F |
Date |
2007-12-18 |
|
|
Cont ID |
|
| Sent By |
kstevens |
Date |
2007-12-18 |
Time |
08:16 |
Rev Time |
0.00 |
| Received By |
kstevens |
Date |
2007-12-17 |
Time |
18:59 |
Sent To |
|
|
| Notes |
| 2007-12-18 08:51:06 | DENIED | | | REFERENCE: FBC-2004 PLUMBING | | | FBC-2004 CHAPTER 1 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | 1. ALL SHEETS WITH AN ARCHITECTURAL TITLE BLOCK | | | REQUIRES THE FIRM ADDRESS. THE ADDRESS ON THE TITLE | | | BLOCK DOES NOT REFLECT THE ADDRESS OF RECORD ON THE | | | FLORIDA STATE DBPR WEBSITE. (SEE ATTACHED SHEET). | | | PLEASE UPDATE THE DBPR WEBSITE OR THE TITLE BLOCK | | | INFORMATION CORRELATE. FAC 61G1-16.004(1) & FS 481.219 | | | & 481.2055. | | | | | | 2. PLUMBING SHEETS THE ENGINEER SHALL LEGIBLY INDICATE | | | THEIR NAME ON EACH SHEET. FAC 61G15-23.002(2) & FS | | | 471.025. | | | | | | 3. SHT P-1 KEY NOTES 20 & 21 NOT FOUND ON THE FLOOR | | | PLAN. PLEASE CORRELATE. SECTION 106.1.1. | | | | | | 4. SHT P-1 SHOWS A NEW 1-1/2" WATER SUPPLY CONNECTION | | | OUTSIDE THE BUILDING, BUT THE WATER SUPPLY TO THE | | | BUILDING IS SHOWN BY THE 3 COMPARTMENT SINK. PLEASE | | | CLARIFY.SECTION 106.1.2.WILL THERE BE ANOTHER METER | | | & BACKFLOW? | | | | | | 5. SHT P-2 SANITARY RISER DIAGRAM ITEM P-4 IF THE SINK | | | IS NOT INDIRECT WASTED, THEN IT SHALL BE VENTED. | | | SECTION 901.2.1. | | | | | | 6. SHT P-2 PLUMBING FIXTURE SCHEDULE INDICATES A P-10 | | | TRAP PRIMER. THIS IS NOT INDICATED ON THE FLOOR PLAN, | | | SANITARY RISER DIAGRAM NOR ON THE WATER RISER DIAGRAM. | | | PLEASE CLARIFY. SECTION 106.1.1. | | | | | | 7. SHT P-2 THE P-11 WATER FILTER SHALL MEET THE | | | REQUIREMENTS OF NSF-42. PLEASE SUBMIT THE MANUF | | | SPECIFICATIONS. SECTION 611.1. | | | | | | 8. SHT P-3 WATER MANIFOLD/FILTER DETAIL SHOWS A 1-1/2" | | | C.W. TO MEN'S REST ROOM. THIS IS NOT REFLECTED ON THE | | | WATER RISER DIAGRAM. PLEASE CORRELATE. SECTION | | | 106.1.1. | | | | | | WHEN RESUBMITTING PLANS PLEASE INDICATE | | | THE REVISION & REMOVE & REPLACE ANY | | | PAGES AS NECESSARY. A TRANSMITTAL LETTER | | | LISTING THE ORIGINAL REVIEW COMMENT NUMBER, | | | WITH A DESCRIPTION OF THE REVISION MADE, IDENTIFYING | | | THE SHEET OR SPECIFICATION | | | PAGE WHERE THE CHANGES CAN BE FOUND | | | WILL HELP TO EXPEDITE YOUR PERMIT. REMOVE | | | ALL VOID SHEETS FROM ALL PLANS AND PLACE | | | ONE SET OF THEM LOOSELY ON TOP OF THE | | | COLLATED PLANS TO BE REVIEWED. | | | THANK YOU FOR YOUR ANTICIPATED COOPERATION. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 805-6731 | | | E-MAIL [email protected] |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
3 |
Status |
N |
Date |
2008-03-26 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-03-26 |
Time |
14:04 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-03-26 |
Time |
14:04 |
Sent To |
|
|
| Notes |
| 2008-03-26 14:06:43 | ***N/R - RESUB #2*** | | | | | | *ZONING REVIEW NOT REQUIRED - GENERATOR HAS BEEN | | | REMOVED FROM PLANS. |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
2 |
Status |
F |
Date |
2008-02-19 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2008-02-19 |
Time |
16:05 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2008-02-19 |
Time |
16:05 |
Sent To |
|
|
| Notes |
| 2008-02-19 16:15:06 | ***FAILED - RESUB #1*** | | | | | | | | | 1)AS THE PLANS NOW SHOW A NEWLY PROPOSED DIESEL | | | GENERATOR, PRIOR TO THE ISSUANCE OF A BUILDING PERMIT, | | | A MINOR AMENDMENT TO THE NORTHPOINT COMMERCIAL PLANNED | | | DEVELOPMENT SHALL BE SUBMITTED TO AND APPROVED BY THE | | | PLANNING AND ZONING DEPARTMENT. | | | | | | NOTE:PROPOSED GENERATOR IS REQUIRED TO BE SCREENED | | | AND LANDSCAPED IN ACCORDANCE WITH SECTION 94-444(B) OF | | | THE CITY'S ZONING AND LAND DEVELOPMENT REGULATIONS | | | (ZLDRS). | | | | | | NOTE:AS PER SECTION 94-305(B)(4) OF THE ZLDRS: | | | MECHANICAL EQUIPMENT MAY NOT PROJECT MORE THAN 4 FEET | | | INTO A REQUIRED SETBACK. | | | | | | | | | QUESTIONS/COMMENTS, PLEASE CONTACT ERIC SCHNEIDER | | | PLANNING AND ZONING DEPARTMENT 822-1435 |
|
|
| Review Stop |
Z |
ZONING |
| Rev No |
1 |
Status |
N |
Date |
2007-12-11 |
|
|
Cont ID |
|
| Sent By |
choops |
Date |
2007-12-11 |
Time |
10:45 |
Rev Time |
0.00 |
| Received By |
choops |
Date |
2007-12-11 |
Time |
10:45 |
Sent To |
|
|
| Notes |
| 2007-12-11 10:45:48 | *ZONING REVIEW NOT REQUIRED - VALUE OF PROPOSED WORK | | | DOES NOT EXCEED 50% OF THE IMPROVEMENT VALUE. |
|
|